VEGA TOR631Ex User Manual

Operating Instruction
in
out
VEGATOR 631 Ex
Signal conditioning
instrument
s
conditioning
Signal
instruments

Contents

Contents
1 About this
1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Symbolism used. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 For your safety
2.1 Authorised personnel . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Appropriate use . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Warning about misuse . . . . . . . . . . . . . . . . . . . . . . .
2.4 General safety instructions . . . . . . . . . . . . . . . . . . . .
2.5 CE conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.6 Safety instructions for Ex areas . . . . . . . . . . . . . . . . .
2.7 Environmental instructions. . . . . . . . . . . . . . . . . . . . .
3 Product description
3.1 Conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Packaging, transport and storage . . . . . . . . . . . . . . .
4 Mounting
4.1 General instructions . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Mounting instructions . . . . . . . . . . . . . . . . . . . . . . . .
5 Connecting to power supply
5.1 Preparing the connection . . . . . . . . . . . . . . . . . . . . .
5.2 Connection procedure. . . . . . . . . . . . . . . . . . . . . . . .
5.3 Wiring plan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Set up
6.1 Adjustment system . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Adjustment elements . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Switching point adjustment . . . . . . . . . . . . . . . . . . . .
document
4 4 4
5 5 5 5 6 6 6
7 8 8 8
10 10
13 13 14
18 19 23
7 Maintenance and fault rectication
7.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Remove interferences. . . . . . . . . . . . . . . . . . . . . . . .
7.3 Instrument repair . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Dismounting
8.1 Dismounting steps . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 Supplement
9.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 VEGATOR 63
26 26 27
28 28
23440-EN-090130
29
1 Ex Signal conditioning instrument
Contents
23440-EN-090130
VEGATOR 631 Ex Signal conditi
Supplementary documentation
Information:
Suppleme with the delivery. You can nd them listed in chapter "Product
description".
ntary documents appropriate to the ordered version come
oning instrument 3

1 About this document

1 About this document

1.1 Function

is operating instructions manual provides all the information you
Th need for mounting, connection and setup as well as important instructions for maintenance and fault rectication. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2 Target group

This operating instructions manual is directed to trained qualied personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbolism used

Information, tip, note
This
symbol indicates helpful additional information.
Caution: If this result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.
applications
Ex
Th
symbol indicates special instructions for Ex applications.
is
l List
The dot set in front indicates a list with no implied sequence.
warning is ignored, faults or malfunctions can
à Action
This a
rrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
23440-EN-090130
4 VEGATOR 63
1 Ex Signal conditioning instrument

2 For your safety

2 For your safety
2.1 Auth
All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.
During work on and with the device the required personal protective equipment must always be worn.
orised personnel

2.2 Appropriate use

VEGATOR 631 Ex is a universal signal conditioning instrument for connection of a level switch.
You can nd detailed information on the application range in chapter
"Product description".
Operational reliability is ensured only if the instrument is properly used according to the specications in the operating instructions manual as well as possible supplementary instructions.
For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modications are explicitly forbidden.

2.3 Warning about misuse

Inappropriate or incorrect use of the instrument can give rise to application-specic hazards, e.g. vessel overll or damage to system components through incorrect mounting or adjustment.
23440-EN-090130
VEGATOR 631 Ex Signal conditi

2.4 General safety instructions

This is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country­specic installation standards as well as all prevailing safety regulations and accident prevention rules.
The instrument must only be operated in a technically awless and reliable condition. The operator is responsible for trouble-free operation of the instrument.
During the entire duration of use, the user is obliged to determine the compliance of the required occupational safety measures with the current valid rules and regulations and also take note of new regulations.
oning instrument 5
2 For your safety
2.5 CE conformi
This device fullls the legal requirements of the applicable EC guidelines. By attaching the CE mark, VEGA provides a conrmation of successful testing. You can nd the CE conformity declaration in the download area of
ty
www.vega.com.

2.6 Safety instructions for Ex areas

Please note the Ex-specic safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.

2.7 Environmental instructions

Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection.
The environment management system is certied according to DIN EN ISO 14001.
Please help us full this obligation by observing the environmental
instructions in this manual:
l Chapter "Packaging, transport and storage" l Chapter "Disposal"
6 VEGATOR 63
23440-EN-090130
1 Ex Signal conditioning instrument

3 Product description

3
1
2
1 2 3 4
5 6 7 8
9 10 11 12 13 14
631Ex
on
0 10
5
!
3 Product description
Scope of delivery
Components
3.1 Congurat
ion
The scope of delivery encompasses:
l VEGATOR 631 Ex signal conditioning instrument l Transparent cover (lead-sealable) l Terminal socket l Bridges (4 pieces) l Coded pins (2 pieces) l Ex label l Ex separating chamber l Documentation
- this operating instructions manual
- Ex-specic "Safety instructions" (with Ex-versions)
- if necessary, further certicates
VEGATOR 631 Ex consists of:
l VEGATOR 631 Ex signal conditioning instrument
Type label
23440-EN-090130
VEGATOR 631 Ex Signal conditi
Fig. 1: VEGATOR 631 Ex
1 Ex separating 2 Terminal socket 3 Transparent cover
The type label contains the most important data for identication and use of the instrument:
chamber with Ex version
l Article number l Serial number l Technical data l Article numbers documentation
oning instrument 7
3 Product description
Application area
Functional principle
Power supply
The serial number allows you to access the delivery data of the instrument
search".
via
www.vega.com, "VEGA Tools" and "serial number

3.2 Principle of operation

VEGATOR 631 Ex is a single signal conditioning instrument for processing the signals of conductive probes.
The VEGATOR 631 Ex signal conditioning instrument powers connected sensors and simultaneously processes their measuring signals.
When the medium reaches the switching point of the sensor, the voltage between sensor and VEGATOR 631 Ex drops. The output relays then switch according to the set mode.
Detailed information about the power supply can be found in chapter
"Technical data".

3.3 Operation

The integration time and the mode (A/B) can be preset via a DIL switch block on the signal conditioning instrument.
A potentiometer for adjustment the switching point is located on the front panel of VEGATOR 631 Ex.

3.4 Packaging, transport and storage

Packaging
Transport
Transport inspection
Storage
8 VEGATOR 63
Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test according to DIN EN 24180.
The packaging of standard instruments consists of environment­friendly, recyclable cardboard. For special versions, PE f oam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
Transport must be carried out under consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.
The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with.
Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.
23440-EN-090130
1 Ex Signal conditioning instrument
3 Product description
Storage and transport temperature
Unless otherwise indicated, the p
ackages must be stored only under
the following conditions:
l Not in the open l Dry and dust free l Not exposed to corrosive media l Protected against solar radiation l Avoiding mechanical shock and vibration
l Storage and transport temperature see chapter "Supplement -
Technical data - Ambient conditions"
l Relative humidity 20 85 %
23440-EN-090130
VEGATOR 631 Ex Signal conditi
oning instrument 9

4 Mounting

4 Mounting
Installation location
Transparent cover
4.1 General ins
VEGATOR 631 Ex signal conditioning instrument with plug-in socket for mounting on carrier rail according to EN 50022.
The front plate of VEGATOR 631 Ex can be provided with a lead­sealable transparent cover to protect the instrument against unau­thorised or inadvertent adjustment. See the following gure on how to remove the transparent cover.
tructions
cover
Housing IP 65
Fig. 2: Removing the transparent
For moisture-protected mounting outside the switching cabinet, we oer an insulated protective housing with transparent cover (IP 65) for surface mounting.
In this housing you can mount a maximum of 3 instruments of 36 mm width.

4.2 Mounting instructions

Mounting
10 VEGATOR 63
The plug-in socket is constructed for carrier rail mounting according to EN 50022. Power supply is connected to terminals 9 and 10. For
neighbouring signal conditioning instruments, it is possible to continue connection L1 and N directly via the supplied bridges.
23440-EN-090130
1 Ex Signal conditioning instrument
1 2 43
4 Mounting
Danger:
bridges must never be used with single instruments or at the end
The of a row of instruments. If this rule is not heeded, there is a danger of coming into contact with the operating voltage or causing a short circuit.
Ex separating chamber
A VEGATOR 631 Ex in E
x version is an auxiliary, intrinsically safe
instrument and must not be installed in explosion-endangered areas.
Before setup, the Ex separating chamber must be attached (as shown below) with Ex versions. Safe operation can be only ensured if the operating instructions manual and the EG type approval certicate are observed. VEGATOR 631 Ex must not be opened.
Close the upper terminals according to the following illustration.
Fig. 3: Mounting the separating
chamber
Instrument coding
23440-EN-090130
VEGATOR 631 Ex Signal conditi
All signal conditioning instruments are provided with dierent gaps
dependent on type and version (mechanical coding).
The plug-in socket is provided with coded pins that can be inserted to prevent accidental interchanging of the various instrument types.
With a VEGATO
R 631 Ex in Ex version, the supplied coded pins (type
coded pin and Ex coded pin) must be inserted by the user according to the below chart.
oning instrument 11
5 6 7 8
14131211109
4321
A B C 1 2 3
7 8 9
N L
1
-
+
1
4
2
3
4 Mounting
Fig. 4: Plug-in socket VEGATOR 631 Ex
1 Ex
separating chamber
2 Ex coding with Ex version (A) 3 Type coding for VEGATOR 631 Ex (3) 4 Bridges for looping the operating voltage
12 VEGATOR 63
23440-EN-090130
1 Ex Signal conditioning instrument

5 Connecting to power supply

5 Connecting to power supply
Note safety instructions
Take note of
safety instruc­tions for Ex ap­plications
Select power supply
Selecting connection
cable
Cable screening and grounding
5.1 Preparin
Always keep in mind the following safety instructions:
l Connect only in the complete absence of line voltage l If overvoltage surges are expected, overvoltage arresters should
be installed
Tip:
We recomm VEGATOR 631 Ex) and B62-36G (sensor supply).
In hazardous areas you should take note of the appropriate
regulations, con and power supply units.
The power supply can be 20 … 253 V AC, 50/60 Hz or 20 … 72 V DC.
Power supply of VEGATOR 631 Ex is connected with standard cable
according to the national installation standards.
The sensors are connected with standard two-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas, screened cable should be used.
From a cable length of 50 m use one cable for each signal conditioning instrument.
If you are using a common cable, the min. and max. cables must be screened. The screen must be connected the ground on both sides.
g the connection
end VEGA overvoltage arresters B61-300 (power supply
formity and type approval certicates of the sensors
Select connec­tion cable for Ex applications
23440-EN-090130
VEGATOR 631 Ex Signal conditi
Take note of the corresponding installation regulations for Ex
ications.
appl

5.2 Connection procedure

Move on to electrical connection and proceed as follows:
1 Snap the socket without VEGATOR 631 Ex onto the carrier rail 2 Connect the sensor cable to terminal 1 and 3 (see the following
wiring plans)
3 Connect power supply (switched off) to terminal 9 and 10 4 Insert VEGATOR 631 Ex into the plug-in socket and screw it down
tightly
The electrical connection is nished.
oning instrument 13
1 2
5
4
1 32 4
5 6
9 1310 1412
7 8
L
(+)
N
(–)
1 2 3
6
5 Connecting to power supply
Limit level measurement
Before setting up Ex
versions, make sure the Ex separating chamber is plugged (above the sensor terminals). The pins for type and Ex coding must also be inserted correctly.

5.3 Wiring plan

Fig. 5: Limit
1 Relay 2 Power supply 3 Transistor output 4 Mass 5 max. 6 Probe, e.g. EL1
level
output
measurement
14 VEGATOR 63
23440-EN-090130
1 Ex Signal conditioning instrument
1 3
2
5
6
4
1 32 4
5 6
9 1310 1412
7 8
L
(+)
N
(–)
1 2 3
7
1
2
3
Two-point control (min./ max. control)
Fig. 6: Two-point control
1 Relay output 2 Power
supply
3 Transistor output 4 Mass 5 Max. 6 Min. 7 Probe, e.g. EL3
5 Connecting to power supply
23440-EN-090130
VEGATOR 631 Ex Signal conditi
Note:
Mutiplerod
probes connected to several signal conditioning instru-
ments or to a multiple channel instrument need a ground rod to keep the signal conditioning instruments from inuencing each other.
oning instrument 15
1 32 4
5 6
9 10 131412
7 8
1
2
3
4
1 32 4
5 6
9 10 131412
7 8
L
(+)
N
(–)
L
(+)
N
(–)
1
4
2
3
5
6
7
8
A B
4
1 2 3
5 Connecting to power supply
Two-point control (min./ max.) with overll pro­tection
Fig. 7: Two-point control with
overll protection
1 Relay output 2 Power supply 3 Transistor output 4 Max. overll protection 5 Min. 6 Max. 7 Mass 8 Probe, e.g. EL3
A Overll protection B Min./max. control
16 VEGATOR 63
23440-EN-090130
1 Ex Signal conditioning instrument
+
-
+
+
+
-
-
1
2
3
R
S
R
S
U
CE
U
CE
Circuit of the transistor outputs
5 Connecting to power supply
Fig. 8: Circuit of the
1 VEGATOR 631 Ex 2 VEGATOR 631 Ex 3 PLC
The resistor R
R
S
47 Ω 0.25 W
150 Ω 0.75 W
330 Ω 1.5 W
560 Ω 2.2 W
transistor outputs
serves as short-circuit protection.
S
P
23440-EN-090130
VEGATOR 631 Ex Signal conditi
oning instrument 17
Typ 600-1
on
5 6 7 8
9 10 12 13 14
5 6 7 8
141312109
4321
TEST
EEx ia
+
-
L
1
N
DISBUS
0...10V
9
8
7
3
2
1
C
B
A
12
Plug-in socket
6
5
10
7
7
8
9
1
2
3
4

6 Set up

6 Set up
6.1 Adjustm
Fig. 9: Indicating
ent system
and
adjustment
1 Control lamp - Fault signal (LED red) 2 Potentiometer for switching point adjustment 3 Control lamp - Output (LED yellow) 4 Control lamp - Power supply (LED green) 5 Bridge for adjusting the fault signal 6 Terminals for probe 7 Function coding Ex version 8 Instrument coding 9 Sockets for bridges 10 Transistor output 11 Relay output 12 Power supply
18 VEGATOR 63
elements
23440-EN-090130
1 Ex Signal conditioning instrument
maximum
3 4
IP 30
60mA
-
+
max: 36V
5 6
R
nsp. I
a
: -20É+60¡C
power supply
20É72VDC
1...8 VA
20É250 VAC
L
N
Sensor
1 2
Terminal
12 13
out
14
2A
125VA
max.250VAC
9 10
+
-
CE
VEGA TOR 631 EX
minimum
1 2 3 4
12
6 2 A
B
off
sec t
1
32
6 Set up
Control lamps
23440-EN-090130
VEGATOR 631 Ex Signal conditi
Fig. 10: Indicating
and
adjustment
elements
1 DIL switch block 2 Type label 3 Transparent cover

6.2 Adjustment elements

Control lamps (LED) in the front plate indicate operation, switching status and fault signal.
l Green
- Operating control lamp
- Mains voltage on, instrument is
l Red
- Failure lamp
- Fault on the sensor circuit due to sensor failure or line break
- The relay deenergises in case of failure
l Yellow
- Relay
control lamp
- The yellow relay control lamp reacts depending on the set mode (A/B)
oning instrument 19
operating
1 2 3 4
12
62A
B
off
sec t
6 Set up
Potentiometer for switching point adjust­ment
DIL switch block
- Generally the relay control lamp shows the activated gized) condition of the relay
(ener
- A dark relay control lamp means that the relay is deenergised
(transistor
A potentiometer for switching point adaptation is located on the front plate of the signal conditioning instrument. With this potentiometer you can adapt the measuring system to the conductivity of the product.
On top to the side (covered when mounted) there is a DIL switch block with four switches. The individual switches are assigned as follows:
l 1 - A/B mode
- A - Max. detection or overow protection
- B - Min. det
l 2 - Integration time 2 s l 3 - Integration time 6 s l 4 - Integration time 12 s
With switch 1 you can adjust the mode (A - overll protection or B - dry run protection).
Fig. 11: DIL switch
blocks)
ection or dr
block
y run detection
In
example (see previous illustration), mode A (max. detection or
the
overll protection) is selected (switch 1). The integration time is set to 8 seconds (switch 2, 3 and 4).
You can adjust the integration time accordingly with switch 2, 3 and 4. The time periods of the activated time switches add up. The set time
applies to the switch on as well as the switch odelay.
Switch 1 2 3 4
Time 2 s 6 s 12 s
0.2 s A/B o o o
2 s A/B on o o
6 s A/B o on o
8 s A/B on on o
12 s A/B o o on
14 s A/B on o on
18 s A/B o on on
20 s A/B on on on
20 VEGATOR 63
23440-EN-090130
1 Ex Signal conditioning instrument
2
3
1
2
3
1
1 2 3 4
1
2
3
1
2
31
1 2 3 4
1
6 Set up
Fault signal adjustment, bridge
To implement line monitoring, you ha
ve to mount a resistor of 220 kΩ
between terminals 1 and 2 in the connection housing of the probe. This means that with single point control, the measuring and ground electrode are monitored and with two-point control, the max. and ground electrode.
When a fault message is generated, the switching output is simultaneously activated.
Fig. 12: Measuring system with line monitoring
1 Resistor (220 kΩ)
If
a fault message is not wanted, a bridge must be provided on the
signal conditioning instrument instead of the resistor in the connection housing of the probe.
Note:
Theline
monitoring and the fault signal are inactive with this bridge.
Fig. 13: Measuring system without line monitoring
1 Bridge
between terminal 3 and 4
23440-EN-090130
VEGATOR 631 Ex Signal conditi
If a measuring system is used as part of an overll prote
the bridge on the signal conditioning instrument must not be closed. With Ex probes, the resistor in the probe housing is already present.
oning instrument 21
ction system,
1
2
3
6 Set up
Mode switch
You can nd the
electrical connection of VEGATOR 631 Ex in the
operating instructions manual of the corresponding signal conditioning instrument.
Line monitoring
With Ex versions, this 220 kresistor is already integrated ex factory in the connection housing of the probe. The Ex measuring system (max. and ground connection cable of the probe to the signal conditioning instrument) is generally monitored for line break.
You can set mode A or B by means of the selection switch.
Mode A
Preferrably as overow protection, compulsory as overll protection.
Fig. 14: Mode A - Overll
protection
Mean
with covered max. electrode:
s
l Relay deenergises, connection 12 - 13 is connected through relay l Transistor output blocks l Control lamp - Output extinguishes
Means with uncovered max. electrode (level detection) or min. electrode (two-point control):
l Relay energises, connection 12 - 14 is connected through relay l Transistor output is conductive l Control lamp - Output lights
22 VEGATOR 63
23440-EN-090130
1 Ex Signal conditioning instrument
1
2
3
6 Set up
Mode B
Preferrably
Fig. 15: Mode B - Dry run protection
Mean
l Relay energises, connection 12 - 14 is connected through relay l Transistor output is conductive l Control lamp - Output lights
as dry run protection system.
s with covered max. electrode:
Means with uncovered max. electrode (level detection) or min. electrode (two-point control):
l Relay deenergises, connection 12 - 13 is connected through relay l Transistor output blocks l Control lamp - Output extinguishes
Line monitoring
Level detection for max.
signal
23440-EN-090130
VEGATOR 631 Ex Signal conditi

6.3 Switching point adjustment

Note:
Keep in mind momenet when the switching point is reached and the momenet when the switching function is triggered, there is an integration time of
0.5 sec. The potentionmeter must therefore be turned slowly.
A possible additional integration time should only be switched on after
the adjustment.
In all following applications in conjunction with an integrated resistor of 220 kΩ, line monitoring of the ground and max. electrode is ensured.
l Set the mode selection switch to mode A l Connect the signal conditioning instrument to power supply
l Turn the potentiometer to position 0 l Fill the vessel until the max. electrode is covered approx. 1 cm by
the product
l Turn the potentiometer slowly clockwise until the yellow signal
lamp extinguishes
oning instrument 23
for all switching point adjustments that, between the
6 Set up
Level detection for min. signal
Two-point control (min./ max.), mode A (overll protection)
The max. electrode
is now adapted to the conductivity of the medium i.
e. the relay deenergises at max. level and the transistor blocks.
l Set the mode selection switch to mode B l Connect the signal conditioning instrument to power supply
l Turn the potentiometer to position 10 l Empty the vessel until the min. electrode is covered approx. 1 cm
by the product
l Turn the potentiometer slowly anticlockwise until the yellow signal
lamp extinguishes
The min. electrode is now adapted to the conductivity of the medium, i. e. the relay deenergises at min. level and the transistor blocks.
l At rst, connect only ground and max. electrode to the signal
conditioning instrument (terminals 1 and 3)
l Set the mode selection switch to mode A l Connect the signal conditioning instrument to power supply l Turn the potentiometer to position 0 l Fill the vessel until the max. electrode is covered approx. 1 cm by
the product
l Turn the potentiometer slowly clockwise until the yellow signal
lamp extinguishes
l Connect the min. electrode to terminal 2 of the signal conditioning
instrument
The two-point control is now adapted to the conductivity of the medium, i.e. the relay deenergises at max. level and the transistor blocks.
This switching condition remains until the level falls below the position of the min. electrode, i.e. the relay energizes at min. level and the transistor conducts.
The relay deenergises again at max. level and the transistor blocks.
Two-point control (min./ max.), mode B (dry run protection)
l At rst, connect only ground and max. electrode to the signal
conditioning instrument (terminals 1 and 3)
l Set the mode selection switch to mode B l Connect the signal conditioning instrument to power supply l Turn the potentiometer to position 10 l Fill the vessel until the max. electrode is covered approx. 1 cm by
the product
l Turn the potentiometer slowly clockwise until the yellow signal
lamp extinguishes
l Connect the min. electrode to terminal 2 of the signal conditioning
instrument
The two-point control is now adapted to the conductivity of the medium, i.e. the relay deenergises at max. level and the transistor blocks.
This switching condition remains until the level falls below the position of the min. electrode, i.e. the relay energizes at min. level and the transistor conducts.
24 VEGATOR 63
23440-EN-090130
1 Ex Signal conditioning instrument
6 Set up
The relay deenergises again at max. level
and the transistor blocks.
23440-EN-090130
VEGATOR 631 Ex Signal conditi
oning instrument 25
7 Maintenance and fault recticati
7 Maintenance and fault rectication
on
Causes of malfunction
Fault rectication
24 hour service hotline
Failure
7.1 Maintena
When used in the correct way, no special maintenance is required in normal operation.
nce

7.2 Remove interferences

A maximum of reliability is ensured. Nevertheless, faults can occur during operation. These may be caused by the following, e.g.:
l Measured value from sensor not correct l Power supply l Interference on the cables
The rst measure to be taken is to check the input and output signals. The procedure is described as follows. In many cases the causes can
be determined this way and faults can be easily rectied.
However, should these measures not be successful, call the VEGA service hotline in urgent cases under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since we oer this service world-wide, the support is only available in the English language. The service is free of charge, only the standard telephone costs will be charged.
? The red failure control lamp (LED) of the signal conditioning
instrument lights
l Sensor not connected correctly
à Check the electrical connection by means of the wiring plans
l Line break
à Check the electrical connection cables from the probe to the
signal conditioning instrument
l Resistance for line monitoring missing
à Check if a 220 kresistor is mounted in the sensor housing
between terminals 1 and 2 or if the respective bridge to the fault message adjustment on the signal conditioning instru­ment is present.
à You can nd further information in chapter "Set up - Failure
adjustment, bridge".
In Ex systems, make measuring instruments used.
sure that the Ex protection is not inuenced by the
23440-EN-090130
26 VEGATOR 63
1 Ex Signal conditioning instrument
7 Maintenance and fault recticati
on
? The signal conditioning instrument does not switch when the
respective
l Conductivity of the product too low
à Check if the conductivity value of your product is at least
probe is covered or uncovered
7.5 µS/cm

7.3 Instrument repair

If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our Internet homepage
www.vega.com under: "Dow form".
By doing this you help us carry out the repair quickly and without having to call back for needed information.
l Print and ll out one form per instrument l Clean the instrument and pack it damage-proof l Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
l Please ask the agency serving you for the address of your return
shipment. You can nd the respective agency on our website www.vega.com under: "Compa
nloads - Forms and certicates - Repair
ny - VEGA worldwide"
23440-EN-090130
VEGATOR 631 Ex Signal conditi
oning instrument 27

8 Dismounting

8 Dismounting
8.1 Dism
Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order.
ounting steps

8.2 Disposal

The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable.
WEEE directive 2002/96/EG
This instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.
Correct disposal avoids negative eects to persons and environment and ensures recycling of useful raw materials.
Materials: see chapter "Technical data"
If you have no possibility to dispose of the old instrument
professionally, please contact us concerning return and disposal.
28 VEGATOR 63
23440-EN-090130
1 Ex Signal conditioning instrument

9 Supplement

9 Supplement
9.1 Technical
General data
Series Module unit with plug-in socket for mounting on
Weight 170 g (6 oz) Housing material Noryl SE100, Lexan 920A Socket material Noryl SE100, Noryl SE1 GFN3
Power supply
Operating voltage 20 … 253 V AC, 50/60 Hz, 20 72 V DC Max. power consumption 1.5 W (1 9 VA)
Fuse
- Supply area T 315 mA, 253 V
- Switching opossibility min. 35 A at 253 V AC or 125 V DC
Sensor input
Quantity 1 x level detection or 1 x pump control (min./max.) Response resistor 1 … 200 kΩ adjustable Parallel resistor for fault monitoring 220 Measuring circuit max. 5 V e., max. 1 mA Permissible line capacitance 1 x 100 nF or 2 x 70 nF with min./max. control Switching hysteresis 15 %
Adjustment elements
DIL switch block for preadjustment of the integration time and mode
Potentiometer for switching point adjustment
Control lamps in the front plate
- Status indication operating voltage Signal lamp green (LED)
- Status indication fault signal Signal lamp red (LED)
- Status indication switching point control Signal lamp yellow (LED)
data
carrier rail 35 x 7.5 or 35 x 5 according to EN 50022
Relay output
Quantity 1
Mode A/B switch (A - max. detection or overll protection,
Integration time 500 ms Contact 1 spdt for each output
Contact material AgNi, hard gold-plated
23440-EN-090130
VEGATOR 631 Ex Signal conditi
oning instrument 29
B - min. detection or dry run protection)
9 Supplement
Turn-on voltage 10 mV
DC, 253 V AC/DC Switching current 10 µA DC, 3 A AC, 1 A DC Breaking capacity 750 VA, 54 W DC
Transistor output
Number, function 1 output, synchronously switching with the relay
Galvanic separation Floating
Maximum values
- U
- I
B
B
36 V DC 60 mA
Transistor voltage loss (UCE) approx. 1.5 V at IB60 mA
Inverse current (I0) 10 µA
Ambient conditions
Ambient temperature -20 +60 °C (-4 +140 °F) Storage and transport temperature -40 +70 °C (-40 +158 °F)
Electromechanical data
Screw terminals for wire cross-section up to 1.5 mm² (AWG 16)
Electrical protective measures
Protection class
- Signal conditioning instrument IP 30
- Terminal socket IP 20
Overvoltage category II
Protection class II Electrical separating measures reliable separation (VDE 0106, part 1) between
power supply, sensor input, level relay and tran­sistor output
Approvals
1)
ATEX ATEX II (1) G [EEx ia] IIC
Others WHG
Ship approval
1)
Deviating data in Ex applications: see separate safety instructions.
30 VEGATOR 63
1 Ex Signal conditioning instrument
23440-EN-090130

9.2 Dimensions

118,5 mm (4.67")
134 mm (5.28")
36 mm (1.42")
54,5 mm (2.15")
5 6 7 8
9 10 12 13 14
1
2
on
3
9 Supplement
Fig. 16: Dimensions VEGATOR 631 Ex
1 Transparent 2 Carrier 3 Ex separating chamber
cover
rail 35 x 7.5 or 35 x 15 according
23440-EN-090130
VEGATOR 631 Ex Signal conditi
to EN 50022
oning instrument 31
VEGA Grieshaber KG
ISO 9001
Am Hohenstein 113 77761 Schiltach
Germany Phone +49 7836 50-0 Fax +49 7836 50-201 E-mail: info@de.vega.com
www.vega.com
Printing date:
All statements concerning scope of delivery, application,
practical use
and operating conditions of the sensors and
processing systems correspond to the information avail-
able at the time of printing.
© VEGA Grieshaber KG, Schiltach/Germany 2009
Subject to change without prior notice 23440-EN-090130
Loading...