Job __________________________
Item No ______________________
FireMax200x2TM Modular Water Heater
` Model:FM200x2N
• Woven Fiber Power Burners
• Radial solid copper fin-tube heat
exchanger for 3600 heat transfer
• Cleanable intake air filters
• Burners activated by water flow and
temperature
• Advanced microprocessor controls
• Natural Gas or Liquid Propane 199,900
BTUH per burner
• Stainless Steel Seismic Legs are
standard
ACCESSORIES AND OPTIONS
(available at additional cost)
□ EZ-Vent Kit for Venting through
FEATURES AND BENEFITS
• Single point water, gas and electrical
connections
• Factory-provided pressure and
temperature relief valve
• All waterways constructed of stainless
steel, copper and brass for corrosion
protection and clean operation
• Simple, easy maintenance through
front panel
• All stainless steel cabinet and frame
• Circulates to hot water storage tank
• All pumps, sensors and controls
included
Printed in USA R06/15
dishwasher ventilation system (Each
burner must be vented separately)
□ Factory Authorized StartUp
□ Water Hammer Arrester
□ Water Pressure Gauge
□ Water Temperature Gauge
□ Water Pressure/Temperature Gauge
□ Water pressure reducing valve (if water
supply pressure exceeds 80psi)
□ Low Pressure water pressure reducing
valve (for dishwasher rinse; installed
after booster & before D/W rinse)
□ Auxiliary PowerVent required for
extended flue lengths. Call factory
□ EZ Install Kit
□ Expansion Tank
TM
or FM200x2L
TM
FireMax200x2TM – Modular Water Heater
Model: FM200x2NTM or FM200x2L
TM
BtuH per burner
Model Number
FM200x2
Natural Gas
Pressure
WC @ Inlet
Min M ax Min Max Nat LP Min Max 1" Side Top Rear
7” 10.5” 10” 14”
FireMax200x2TM/120 1 hour 840 gal 735 gal 660 gal 600 gal 552 gal 515 gal
BTU/Storage 2 hour 1560 gal 1350 gal 1200 gal 1080 gal 984 gal 910 gal
Firemax200x2TM/240 1 hour 960 gal 858 gal 780 gal 720 gal 672 gal 635 gal
BTU/Storage 2 hour 1680 gal 1470 gal 1320 gal 1200 gal 1104 gal 1030 gal
TM
Natural or Propane
2 @ 199,900 1" NPT 1" NPT
LP Gas
Pressure
WC @ Inlet
Temp Rise 600F 700F 800F 900F 1000F 1100F
Output Temp 1100F 1200F 1300F 1400F 1500F 1600F
Manifold
Pressure
WC
2.75”
-
3.5”
Gas
Connection
6.5”
-
8”
Water
Pressure
(Flow)
40
80
psi
psi
Water
Supply
Re-circulating
Loop
To Storage Tank
Electrical
Connection
120V 1ph
12.4 amps
Clearance From
6” L
1” R
Gas Pressure
Regulators
Two Supplied 836 lbs
Combustible
Surface
Auxiliary Power
1”
6” *
Shipping
Weight
Vent Per
Local Code
Vent
Required for
extended flue
lengths Call
factory
*1” from back of exhaust vent
Note: May be vented through the dishwasher canopy or pant-leg exhaust system per 1991
Uniform Mechanical Code Sec 916. & 917. Check with local authority
Printed in USA R 07/15