Total capacity kW2,642,552,442,322,212,081,91
21ºC D
15ºC W
24ºC D
17ºC W
27ºC D
19ºC W
32ºC D
23ºC W
Sensitive capacity kW2,112,041,951,861,761,671,53
Input kW.0,530,540,540,550,560,570,66
Total capacity kW2,802,712,602,472,352,222,03
Sensitive capacity kW2,242,172,081,981,881,771,62
Input kW.0,580,590,600,610,610,620,73
Total capacity kW2,952,852,742,602,472,332,14
Sensitive capacity kW
Input kW.0,620,630,640,650,660,670,78
Total capacity kW3,313,203,062,912,772,612,39
Sensitive capacity kW2,642,562,452,332,212,091,91
Input kW.0,710,720,730,740,750,760,89
OUTDOOR TEMPERATURE DRY
2,362,282,192,081,981,871,71
HEATINGOUTDOOR CONDITIONS
Indoor Conditions
Capacity kW2,783,733,192,522,061,931,570,67
15ºC
Input kW.0,750,900,730,660,620,610,610,53
Capacity kW2,653,563,052,401,971,841,500,64
18ºC
Input kW.0,720,870,710,630,600,590,590,51
Capacity kW2,523,392,902,291,871,761,430,61
20ºC
Input kW.0,690,840,680,610,570,570,560,49
Capacity kW2,423,262,782,201,801,691,370,58
22ºC
Input kW.0,600,800,690,620,580,570,570,50
Capacity kW2,202,952,521,991,631,531,240,53
27ºC
Input kW.0,730,880,720,640,600,600,590,52
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W”
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W”
-15ºC D
-16ºC W”
ENG
5
Page 6
3- TEMPERATURE BY CAPACITIES
ENG
COOLING
Indoor Conditions21ºC25ºC30ºC35ºC40ºC45ºC50ºC
Total capacity kW3,553,433,293,132,972,812,57
21ºC D
15ºC W
24ºC D
17ºC W
27ºC D
19ºC W
32ºC D
23ºC W
Sensitive capacity kW2,842,752,632,502,382,252,06
Input kW.0,370,610,750,911,021,031,04
Total capacity kW3,773,653,503,333,162,992,73
Sensitive capacity kW3,022,922,802,662,532,392,19
Input kW.0,380,630,770,941,051,061,07
Total capacity kW3,973,843,683,503,333,142,88
Sensitive capacity kW
Input kW.0,390,650,790,971,091,101,11
Total capacity kW4,454,304,123,923,723,523,22
Sensitive capacity kW3,563,443,303,142,982,822,58
Input kW.0,440,720,881,071,201,211,22
OUTDOOR TEMPERATURE DRY
3,183,072,952,802,662,512,30
HEATINGOUTDOOR CONDITIONS
Indoor Conditions
Capacity kW3,864,324,183,453,242,932,651,25
15ºC
Input kW.0,350,741,071,080,960,780,730,55
Capacity kW3,684,123,993,293,092,792,531,20
18ºC
Input kW.0,340,711,031,040,930,750,700,53
Capacity kW3,513,933,803,132,942,662,411,14
20ºC
Input kW.0,330,680,991,000,890,730,680,51
Capacity kW3,373,773,653,012,832,552,321,09
22ºC
Input kW.0,330,691,001,010,900,730,680,51
Capacity kW3,053,423,312,732,562,312,100,99
27ºC
Input kW.0,330,701,011,020,910,740,690,52
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W”
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W”
-15ºC D
-16ºC W”
6
Page 7
3- TEMPERATURE BY CAPACITIES
3.3 VAI 2-050 WN
COOLING
Indoor Conditions21ºC25ºC30ºC35ºC40ºC45ºC50ºC
Total capacity kW5,074,904,704,474,244,013,67
21ºC D
15ºC W
24ºC D
17ºC W
27ºC D
19ºC W
32ºC D
23ºC W
Sensitive capacity kW4,053,923,763,573,393,212,94
Input kW.0,590,981,191,461,631,651,66
Total capacity kW5,395,225,004,754,514,273,90
Sensitive capacity kW4,314,174,003,803,613,413,12
Input kW.0,611,011,231,501,681,701,72
Total capacity kW5,685,495,265,004,754,494,11
Sensitive capacity kW
Input kW.0,631,041,271,551,741,751,77
Total capacity kW6,366,155,895,605,325,034,60
Sensitive capacity kW5,084,924,714,484,264,023,68
Input kW.0,701,151,401,711,921,931,95
OUTDOOR TEMPERATURE DRY
4,544,394,214,003,803,593,29
HEATINGOUTDOOR CONDITIONS
Indoor Conditions
Capacity kW5,185,805,614,634,353,933,561,68
15ºC
Input kW.0,501,051,521,541,371,121,040,78
Capacity kW4,945,535,364,424,153,753,401,61
18ºC
Input kW.0,481,011,461,481,321,071,000,75
Capacity kW4,705,275,104,213,953,573,241,53
20ºC
Input kW.0,470,971,411,421,271,030,960,72
Capacity kW4,525,064,904,043,793,433,111,47
22ºC
Input kW.0,470,981,421,441,281,040,970,73
Capacity kW4,094,584,443,663,443,112,821,33
27ºC
Input kW.0,481,001,441,461,301,060,990,74
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W”
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W”
-15ºC D
-16ºC W”
ENG
7
Page 8
3- TEMPERATURE BY CAPACITIES
3.3 VAI 2-065 WN
ENG
COOLING
Indoor Conditions21ºC25ºC30ºC35ºC40ºC45ºC50ºC
Total capacity kW6,796,576,295,985,685,374,92
21ºC D
15ºC W
24ºC D
17ºC W
27ºC D
19ºC W
32ºC D
23ºC W
Sensitive capacity kW5,435,265,044,794,554,303,93
Input kW.0,801,321,611,962,202,222,24
Total capacity kW7,226,996,706,376,055,725,23
Sensitive capacity kW5,785,595,365,094,844,574,19
Input kW.0,821,361,662,032,272,292,31
Total capacity kW7,607,367,056,706,376,025,51
Sensitive capacity kW
Input kW.0,851,401,712,092,342,362,39
Total capacity kW8,528,247,897,507,136,746,17
Sensitive capacity kW6,816,596,326,005,705,394,93
Input kW.0,941,551,892,312,582,612,63
OUTDOOR TEMPERATURE DRY
6,085,895,645,365,094,814,41
HEATINGOUTDOOR CONDITIONS
Indoor Conditions
Capacity kW7,448,338,066,656,255,645,122,42
15ºC
Input kW.0,721,512,192,211,971,611,501,12
Capacity kW7,107,957,706,355,965,394,892,31
18ºC
Input kW.0,701,452,112,131,901,551,441,08
Capacity kW6,767,577,356,055,685,134,652,20
20ºC
Input kW.0,671,402,032,051,831,491,391,04
Capacity kW6,497,277,045,805,454,934,472,11
22ºC
Input kW.0,681,422,052,071,851,501,401,05
Capacity kW5,886,596,385,264,944,464,051,91
27ºC
Input kW.0,691,432,082,101,871,521,421,07
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W”
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W”
-15ºC D
-16ºC W”
8
Page 9
4- WIRING DIAGRAMS
4.1 Indoor unit 025/035
4.2 Indoor unit 050
ENG
9
Page 10
4- WIRING DIAGRAMS
4.3 Indoor unit 065
4.4 Outdoor unit 025/035
ENG
10
Page 11
4- WIRING DIAGRAMS
4.5 Outdoor unit 050
4.6 Outdoor unit 065
ENG
11
Page 12
5- ERROR CODES
Indoor Unit Error Display 025/035 / 050
DisplayLED STATUS
E0EEPROM parameter error
E1Indoor / outdoor units communication protection
E2Zero-crossing signal error
E3Indoor fan speed out of control
E5Open or short circuit of outdoor ambient or condenser temperature sensor
E6Open or short circuit of indoor room or evaporator temperature sensor
P0Inverter module (IGBT) over-strong current protection
P1Over voltage or too low voltage protection
P2Temperature protection of compressor top.
P4Inverter compressor drive error
Indoor Unit Error Display 065
DisplayLED STATUS
E0EEPROM parameter error
E1Indoor / outdoor units communication protection
E5
E6Open or short circuit of indoor room or evaporator temperature sensor
P0Inverter module (IGBT) over-strong current protection
P1Over voltage or too low voltage protection
P2
P4
Open or short circuit of outdoor ambient or condenser temperature sensor
Temperature protection of compressor top.
Inverter compressor drive error
ENG
12
Page 13
6- FLOW CHART OF DIAGNOSIS AND SOLUTIONS
E0 (EEPROM parameter error) error diagnosis and solution
E1 (indoor / outdoor units communication protection) error diagnosis and solution
E2 (zero-crossing signal error) diagnosis and solution
13
ENG
Page 14
6- FLOW CHART OF DIAGNOSIS AND SOLUTIONS
E3 (indoor fan speed out of control) diagnosis and solution
E5 (Open or short circuit of outdoor ambient or condenser temperature sensor) diagnosis and solu-
E6 (open or short circuit of indoor room or evaporator temperature sensor) diagnosis and solu-
ENG
P0 (IGBT over-strong current protection) diagnosis and solution.
14
Page 15
6- FLOW CHART OF DIAGNOSIS AND SOLUTIONS
P1 (over voltage or too low voltage protection) diagnosis and solution.
P2 (temperature protection of compressor top) diagnosis and solution.
P4 (inverter compressor drive error) diagnosis and solution.
15
ENG
Page 16
ENG
7- PCB EXPLANATION
7.1 ABBREVIATION
T1 Indoor ambient temperature
T2 Pipe temperature of indoor heat exchanger
T3 Pipe temperature of outdoor heat exchanger
T4 Outdoor ambient temperature
7.2 DISPLAY FUNCTION
Timer indicator
This indicator illuminates when TIMER is set ON/
OFF.
DEF. Indicator
This indicator illuminates when the air conditioner
starts defrosting automatically or when the warm
air control feature is activated in heating mode.
Temperature indicator
Usually it displays the temperature settings. When
Run indicator
Flash at 0.5Hz when the unit is standby. Illuminate
when the unit is turned on.
Auto indicator
This indicator illuminates when the air conditioner
is in AUTO operation.
Ion indicator
Illuminate when Ionizer/Plasma function is activated.
LED display control function.
Pressing “LED display” button on remote controller will turn off all displays on indoor unit, while pressing
once again, all displays will resume.
change the setting temperature, this indicator
begins to flash, and stops 20 seconds later. It
displays the room temperature when the air conditioner is in FAN only operation, and the range of
that is 0~50℃. When the unit stops operation, it
returns to original factory settings. It will also display the error codes when malfunction or protection happen.
Frequency indicator
This indicator appears only when the compressor
is in operation and indicates the current operating
frequency.
7.3 PROTECTION
Protection of compressor top temperature.
When the Over-load Protector is cut due to too high temperature of compressor top, the unit will stop.
When the Over-load Protector is closed again due to decreasing of compressor top temperature, the unit
will restart( in this case the compressor is restricted by Three Minutes Delay protection).
16
Page 17
7- PCB EXPLANATION
Protection of discharge temperature (Td).
1) Compressor will stop immediately if Td>115 for 5s.
2) If 90 ≤ Td ≤ 115 , compressor will run with restricted frequency.
3) If Td<90, compressor will restart or run without restricted frequency
Three Minutes Delay at restart for compressor.
It will take 3 minutes every time when compressor starts.
It will take only 1 minute when the unit is powered on at first time.
Temperature sensor protection at open circuit or short circuit.
Protection of indoor fan speed.
When indoor fan speed is too low (lower than 300rpm for 50 seconds), the unit will stop and LED display
error code and can’t return to normal operation automatically.
Cross Zero signal error warning.
If there are no Cross Zero signal or the alternation of Cross Zero signal is not correct, the unit will stop
and LED display error code .
Inverter module Protection.
Inverter module has a protection function against current, voltage and temperature. If these protections
happened, the unit will stop and LED display error code .
Indoor fan delayed open function.
When the unit is turned on at all modes, the indoor fan will operate 10 seconds later than the action of
louver.
Compressor preheating function.
1) Preheating permitting condition:
If T4(outdoor ambient temperature) <3ºC and the machine connects to power supply newly or if T4 <
3ºC and compressor has stopped for over 3 hours, the compressor heating cable will work.
2) Preheating mode:
A weak current flows through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
3) Preheating release condition:
If T4 > 5 ºC or user turns on the machine and compressor runs, preheating function will stop.
7.4 FAN-ONLY MODE
-Temperature setting function is disabled, and no
setting temperature display.
-In this mode, the action of louver is the same as
in cooling mode.
-The action of auto fan in fan-only mode is the
same as auto fan in cooling mode with 24℃ setting
temperature.
ENG
17
Page 18
7- PCB EXPLANATION
7.5 COOLING MODE
After starting, the operation frequency of compressor submits to following rule.
When the machine is running and ΔT(=room
temp. – setting temp.) changes, the frequency of
compressor will rise or descend a grade (7 minutes after starting).
After starting, if ΔT stays in a zone for 3 minutes,
the frequency will change as follow:
Zone A: Current frequency rise a grade till the
maximum grade F8.
Zone B:
Keep the current frequency of compressor.
Zone C:
Descend the current frequency of compressor
until F1.
Zone D: Compressor stops after running as the
minimum frequency F1 for 60 minutes or
ΔT is less than -2ºC.
Indoor heat exchanger anti-freezing function.
If T2 is lower than 0ºC, the compressor stops and
resumes when T2>5ºC.
ENG
Outdoor unit current control in cooling mode(refer
to the parameter table)
Rating capacity test function
1) Set the indoor unit with remote controller as: high fan, 17ºC in cooling mode, then press “TURBO”
button on controller 6 times or more within 10 seconds(make sure indoor unit receives these signals),
the machine will turn into rating capacity test mode, the buzzer will make a “di” sound for 2 seconds
continuously. Also, indoor fan will change to rating speed, the frequency of compressor will be fixed
as rating value. Any condition of above is not satisfied, the machine can not be turned into rating
capacity test mode.
2) The machine will quit from the rating capacity test mode if running for 5 hours or changing fan speed
or setting temperature.
Turbo function(press the “TURBO” button on remote controller)
1) Elevate current frequency to a higher grade.
2) Indoor fan turns to turbo speed.
3) After running for 30 minutes the machine will turn back to previous setting mode.
Indoor fan operation rule.
1) In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low
and auto.
2) Auto fan in cooling mode acts as follow:
18
Page 19
7- PCB EXPLANATION
Condenser high temperature protection function(in cooling and drying mode)
If T3>60ºC for 5 seconds, compressor will stop immediately, and the machine will not resume until
T3<52ºC.
7.6 DRYING MODE
Indoor fan speed is fixed at breeze grade and can’t be changed. The horizontal angle is the same as in
cooling mode.
Overlow room temperature protection: In drying mode, if room temperature is lower than 10℃, compressor will stop and not resume until room temperature climbs up to 12ºC.
Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit frequency
limit are valid, and they are the same as that in cooling mode.
Horizontal louver action is the same as that in cooling mode.
7.7 HEATING MODE
Indoor fan action:
1) Anti-cold-wind function.
2) If the compressor stops caused by room temperature rising, indoor fan will be forced to run
127 seconds with breeze. During this period,
anti-cold-wind is disabled. After this, anti-cold
–wind function is available.
3) If the machine runs in rating capacity test
mode, indoor fan runs with rating speed, and
anti-cold-wind is disabled.
ENG
19
Page 20
7- PCB EXPLANATION
Indoor fan speed can be set as high, medium, low
or auto grade, but anti-cold-wind function is preferential.
Auto fan action in heating mode.
After start the operation frequency of compressor
submits to following rule:
When the machine runs, if ΔTh stays in a zone for
3 minutes, action of frequency is as follow:
Zone A: Elevate the current frequency one grade,
and not stop until the maximum grade.
Zone B: Keep the current frequency.
Zone C: Descend the current frequency one grade.
Zone D: Compressor stops after running with F1 for
60 minutes or when ΔTh>61ºC.
Outdoor unit current control in heating mode.
ENG
Indoor heat exchanger high temperature protection.
If T2>60ºC, the compressor will stop and not resume until T2<48ºC.
Defrosting mode.
1) Condition of defrosting.
Condition 1: If T4>0ºC, When the units are running, if the following two items are satisfied the units start
defrosting:
a) The units runs with T3<3ºC for 40 minutes and T3 keeps lower than -6ºC for more than 3 minutes.
b) The units runs with T3<3ºC for 80 minutes and T3 keeps lower than -4ºC for more than 3 minutes.
Condition 2: If T4<0ºC,
The program judges according to the condition 1, if the two items are satisfied, then judges if T2 has
descended for more than 5ºC, if it has the machine starts defrosting, or continues to judge T2 and will
not defrost until T2 drops more than 5ºC.
Condition 3: No matter what value T4 is, if the machine runs with T3<3ºC for more than 120 minutes and
T3 keeps lower than -2ºC for more than 3 minutes, the machine will defrost, no matter if T2 drops for
more than 5ºC or not.
20
Page 21
7- PCB EXPLANATION
2) Condition of ending defrosting.
If any one of following items is satisfied, defrosting will finish and the machine will turn to normal
heating mode.
a) T3 rises to be higher than 12ºC.
b) T3 rises to be higher than 8ºC and remains for 80 seconds.
c) The machine has run for 10 minutes in defrosting.
Defrosting action.
Rating capacity test function.
1) Set the indoor unit with remote controller as: high fan, 30ºC in heating mode, then press “TURBO”
button on controller 6 times or more within 10 seconds(make sure indoor unit receives these signals),
the machine will turn into rating capacity test mode, the buzzer will make a “di” sound for 2 seconds
continuously. Also, indoor fan will change to rating speed, the frequency of compressor will be fixed
as rating value. Any condition of above is not satisfied, the machine cannot be turned into rating
capacity test mode.
2) The machine will quit from the rating capacity test mode if running for 5 hours or changing fan speed
or setting temperature.
Turbo function in heating mode. (press the “TURBO” button on remote controller)
1) Elevate current frequency (excluding F8) to a higher grade. If indoor fan is in low speed or pause
caused by defrosting or anti-cold-wind function, frequency of compressor will not be elevated one
grade until these limit has been released.
2) Indoor fan changes to turbo speed and anti-cold-wind function is valid.
21
ENG
Page 22
7- PCB EXPLANATION
7.8 AUTO MODE FUNCTION
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30ºC.
In auto mode, the machine will choose cooling, heating or fan-only mode according to ∆T(ΔT =T1-Ts).
ΔT=T1-TsRunning mode
ΔT > 1ºCCooling
-1≤ΔT≤1ºCFan-only
ΔT<-1ºCHeating
Indoor fan will choose auto speed of relevant mode.
If the machine switches mode between heating and cooling, compressor will keep stopping for 15 minutes and then rechoose mode according to ΔT.
If the setting temperature is modified, the machine will rechoose running function.
7.9 FORCED OPERATION FUNCTION
Forced cooling and auto function can carry out with a touch button. In these two modes, the machine can
be changed by remote controller to any other mode at any moment.
When the machine is off, pressing the touch button once, the unit will enter forced auto mode. When the
machine is off, pressing the touch button twice within 5s, the unit will enter forced cooling mode. When
the unit is running at forced auto or forced cooling mode, pressing the touch button continuously, the
unit will be turned off.
ENG
In forced operation mode, all general protections is available.
In forced cooling mode, the unit will run with fixed frequency F2 at low speed. 30 minutes later, the unit
will turn to normal auto mode with setting temperature 24ºC.
In forced auto mode, the unit will run with setting temperature 24ºC.
7.10 ACTION OF 4-WAY VALVE
In cooling, drying, fan-only, or turning off mode, 4-way valve is off, while in heating mode 4-way valve
is on. If the machine changes operation mode from heating mode to some other mode, 4-way valve will
be delayed off 2 minutes after compressor stop. For defrosting, please refer to the passage “defrosting
mode”.
22
Page 23
7- PCB EXPLANATION
7.11 TWO SPEEDS OUTDOOR FAN FUNCTION
Outdoor fan starts at the same time with compressor, but stops 30 seconds later than compressor ‘s stop.
Outdoor fan action in heating mode(including heating in auto mode).
Outdoor fan action in cooling & drying mode(including cooling in auto & forced mode). Please refer to
the pic. above.
7.12 TIMER FUNCTION
-Timing range is 24 hours, and the minimum resolution is 15 minutes.
-Timer on. After turning off, the machine will turn on automatically when reaching the setting time.
-Timer off. After turning on, the machine will turn off automatically when reaching the setting time.
-Timer on/off. After turning off, the machine will turn on automatically when reaching the setting “on”
time, and then turn off automatically when reaching the setting “off” time.
-Timer off/on. After turning on, the machine will turn off automatically when reaching the setting “off”
time, and then turn on automatically when reaching the setting “on” time.
-The tolerance of Timer is 1 minute per hour.
7.13 SLEEP FUNCTION MODE
Operation time in sleep mode is 7 hours. After 7 hours the machine quits this mode and turns off.
Sleep function is available in cooling, heating and auto mode .
Operation process in sleep mode is as follow:
1) After pressing ECONOMIC or SLEEP button on controller, the machine will turn into sleep mode.
2) When cooling, the setting temperature rises 1ºC (be lower than 30ºC) every one hour, 2 hour later
the rising stops and indoor fan is fixed as low speed.
3) When heating, the setting temperature descends 1ºC(be lower than 30ºC) every one hour, 2 hour
later the descending stops and indoor fan is fixed as low speed, and anti-cold-wind is available.
23
ENG
Page 24
7- PCB EXPLANATION
7.14 MODE CONFLICT
The indoor units can not work cooling mode and heating at same time. Heating mode has a priority.
Definition
Cooling modeHeating ModeFanOff
Cooling modeNoYesNoNo
Heating ModeYesNoYesNo
FanNoYesNoNo
OffNoNoNoNo
No: No mode conflict;
Yes: Mode conflict
7.15 AUTO-RESTART FUNCTION
The indoor unit is equipped with auto-restart function. In case of a sudden power failure, the setting
conditions before the power failure will be restored. The unit will resume the previous operation setting
automatically after 3 minutes when power returns.
7.16 IONIZER/PLASMA DUST COLLECTOR FUNCTION (OPTIONAL)
The indoor unit is equipped with Ionizer/Plasma, which is controlled by the CLEAN AIR button on the
remote controller. Press the CLEAN AIR button to activate the function while the unit is turned on, press
it again to stop the function. Ionizer/Plasma will be turned off automatically if indoor fan stops running
due to malfunctions or anti-cold-wind. When indoor fan restarts after malfunctions being eliminated and
anti-cold-wind being released, Ionizer/Plasma will be available again.
ENG
7.17 OUTDOOR CHASSIS HEATING CABLE (OPTIONAL)
Heating cable is fixed on outdoor chassis to help deicing and to avoid freezing. The heating cable’s
power is 85W, rated voltage is 220V-240V, and is controlled by the program. If outdoor temperature is
lower than 5ºC, the heating cable will begin to work. If outdoor temperature is higher than 15ºC, the
heating cable will stop working.