Vaillant auroTHERM VTK 570/2, auroTHERM VTK 1140/2 Installation Manual

Page 1
For the expert technician
Installation manual
auroTHERM
On-roof/flat roof installation
VTK 570/2 VTK 1140/2
GB
Page 2
2
Contents
Contents
1 Notes on the documentation ......................... 3
1.1 Other applicable documents ................................3
1.2 Storage of the documents ....................................3
1.3 Symbols used ...........................................................3
1.4 Applicability of the manual ...................................3
2 Intended use .................................................... 3
2.1 Combination with other components ................3
2.2 Operational conditions ..........................................3
3 Safety instructions ........................................ 4
3.1 Technical Guidance .................................................4
3.2 Related documents .................................................4
3.3 Regulations for the prevention of accidents ...4
3.4 Lightning protection ...............................................5
3.5 Frost protection.......................................................5
4 Before installation ..........................................5
4.1 Safety instructions3 ...............................................5
4.2 Scope of delivery ....................................................6
4.2.1 On-roof mounting ...................................................6
4.2.2 Flat-roof mounting ..................................................7
4.3 Assembling the collector array ...........................8
4.3.1 On-roof mounting ...................................................8
4.3.1.1 Collector arrangement, 1-row ..............................8
4.3.1.2 Collector arrangement, 2-row ........................... 10
4.3.1.3 Collector arrangement, 3-row .............................11
4.3.2 Flat-roof mounting .................................................13
4.4 Interconnection scheme ...................................... 14
4.5 Preparing the hydraulic connection ................. 16
4.5.1 On-roof mounting ................................................. 16
4.5.2 Flat-roof mounting ................................................ 16
4.6 Required tools ........................................................ 16
5 On-roof mounting ...........................................16
5.1 Fitting the brackets ...............................................17
5.2.1 Bracket Type P (pantile) ..................................... 19
Fixing to the roof batten ................................................ 20
5.2.2 Bracket Type S (for high profile pantiles) .......21
5.2.3 Bracket Type S (Low profile for slate/ flat tiles) 21
5.2.3 Hanger bolt fixing kit ...........................................22
5.3 Fitting the collectors ............................................23
6 Flat-roof mounting ...................................... 28
6.2 Weighting and arrangement of the frames ... 28
6.3 Fitting the collectors ............................................32
7 Final operations ............................................37
8 Recycling and disposal ................................ 38
9 Vaillant Customer Service and warranty . 38
9.1 Vaillant warranty.................................................. 38
9.2 Vaillant service ..................................................... 38
10 Technical data ...............................................39
Page 3
1 Notes on the documentation
The instructions below are intended to help you throughout the entire documentation.
1.1 Other applicable documents
When assembling the tube collectors, pay attention to all the installation instructions for the components and assemblies within the solar installation. These instruc­tions are included with the individual components of the system and the additional components.We accept no li-
ability for any damage caused by failure to observe these instructions.
1.2 Storage of the documents
Please pass on this installation manual and all other ap­plicable documents and auxiliary equipment to the plant operator, whose responsibility it is to ensure the manu­als and auxiliary equipment are available whenever re­quired.
1.3 Symbols used
Please observe the safety instructions in this installation manual for the installation of the collector!
d
Danger!
Immediate risk of serious injury or death!
e
Danger!
Risk of death from electric shock!
H
Danger!
Danger of burning and scalding!
a
Caution!
Potentially dangerous situations for the prod­uct and the environment!
h
Note
Useful information and instructions.
• Symbol indicating the required action
1.4 Applicability of the manual
This installation manual applies exclusively to tube col­lectors with the following part numbers:
Collector type Part number
VTK 570/2 0010002227
VTK 1140/2 0010002228
Table 1.1 Collector types and article numbers
Please see the identification plate on the upper edge of the collector for the part number of the tube collector.
2 Intended use
Vaillant auroTHERM tube collectors are built according to the state of the art and recognised safety rules and regulations. Nevertheless, improper use may cause danger to life and limb of the user or third parties and could impair the operation of the unit and other objects. The unit is not intended for use by persons (including children) with reduced physical, sensory or mental capa­bilities, or lack of experience and/or knowledge, unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety. Children must be watched to ensure that they do not play with the unit. Vaillant auroTHERM tube collectors are used for solar assisted hot water generation and where specially de­signed can provide additional heating such as pool heat­ing. The collectors may only be operated with Vaillant ready­mixed solar fluid. Passing heating water or hot water di­rectly through the collectors is not permitted. Any other use or use exceeding the above-mentioned applications shall be considered as improper use. The manufacturer/supplier shall not be responsible for any damages resulting from such improper use. The user alone bears the risk. Intended use includes observance of the operating and installation manuals and all other applicable documents, as well as adherence to the maintenance and inspection conditions.
a
Caution!
Any improper use is forbidden!
2.1 Combination with other components
Vaillant tube collectors should be combined only with Vaillant components (fixing, connections) and system components. The use of other components or system components shall be considered as improper use. We accept no liabil­ity.
2.2 Operational conditions
a
Caution!
The roof may collapse! Mount the tube collectors only on roofs with an adequate load-bearing capacity. If necessary, call a technician.
3Installation manual auroTHERM 0020077994_00
Notes on the documentation 1
Intended use 2
GB
Page 4
On-roof mounting:
The tube collectors can be mounted at an angle of 15° – 75°. An installation angle of less than 15° is not permissible.
Flat roof installation:
The tube collectors can be installed on flat roof frames in the as-delivered condition with an angle of 30°, 45° or 60°. An installation angle of less than 15° is not permissible.
3 Safety instructions
The following safety instructions, technical rules and ac­cident prevention regulations must be observed when installing the flat collectors.
d
Danger!
Risk of death from falls and falling objects! Observe the national regulations for working at heights.
H
Danger!
Danger of burning and scalding! In case of solar irradiation inside the units, col­lectors can reach 300 °C. Remove the sun pro­tection film installed at the factory only after the solar energy system has been started up.
H
Danger!
Danger of burning and scalding! In case of solar irradiation inside the units, col­lectors can reach 300 °C. Do not perform maintenance work under direct sunlight.
a
Caution!
Collector damage! A qualified engineer is required to install tube collectors in accordance with this installation manual. The installation should thus be performed only if a qualified engineer is available.
3.1 Technical Guidance
The system must be installed in accordance with all rel­evant and applicable national regulations, and must be installed to suit site conditions. Observe all national regulations, including:
- Working at Heights Regulations 2005
- Health and Safety at Work Act 1974
- Electricity at Work Regulations 1989
- IEE Wiring Regulations BS 7671
- Lightning protection requirements
- Equipotential bonding of electrical installations.
3.2 Related documents
Designers and installers should refer to current informa­tion and standards. A useful reference would be the en­ergy saving trust document CE 131 (this is downloadable from their web site at www.est.org.uk/housingbuildings) which lists relevant standards and other documents that you might refer to. This includes but is not limited to the following; Solar Standards BS 7431, BS 6785: 1986, BS EN 12975 / 6 (Pt1-2), prEN 12977 (1-2-3) BS EN ISO 9488 The installation of the solar system must be in accord­ance with the relevant requirements of Health and Safe­ty Document No. 635 (The Electricity at Work Regula­tions 1989), BS7671 (IEE Wiring Regulations) and the Water Supply (Water Fitting) Regulations 1999, or The Water Bylaws 2000 (Scotland). It should also be in accordance with the relevant requirements of the Local Authority, Building Regulations, The Building Reg­ulations (Scotland), The Building Regulations (Northern Ireland) and the relevant recommendations of the following British Standards:
- BS EN 806: Specification for installations inside build­ings conveying water for human consumption
– BS 6700: Services supplying water for domestic use
within buildings and their curtilages.
- BS. 5449 Forced circulation hot water central heating systems for domestic premises. Note: only up to 45 kW.
- BS. 6880 Low temperature hot water heating systems of output greater than 45 kW. Part 1 Fundamental and design considerations. Part 2 Selection of equipment. Part 3 Installation, commissioning and maintenance.
– BS 6114: Expansion vessels using an internal dia-
phragm for unvented hot water supply systems
- BS. 4814 Specification for: Expansion vessels using an internal diaphragm, for sealed hot water heating sys­tems.
Unvented hot water systems must comply with building regulation G section 3.
3.3 Regulations for the prevention of accidents
When carrying out works such as solar installation work it is necessary to do so in a safe and workman like man­ner, taking due care of any aspects of the works that could result in injuries to person in or about the building as well as workers, passers by and the general public at large. To that end these works must conform, but not be limited to, the current regulations in force such as the following
- Health and Safety at Work act 1974
- Work at Height Regulations 2005.
- Electricity at Work Regulations 1989
- All necessary Building Regulations.
Work should be preceded by a risk assessment covering all aspects of health and safety risks, or training re­quirements that can reasonably be foreseen to be
Installation manual auroTHERM 0020077994_004
2 Intended use 3 Safety instructions
Page 5
associated with the work. All scaffolding in the UK, other than prefabricated (zip-up) scaffold towers, must be de­signed and constructed by a vetted contractor, and have suitable kick boards, hand rails and where appro­priate netting. Areas around the scaffolding should be zoned off and marked with suitable warning signs to a suitable distance to protect persons from falling objects. Workers should have available and use personal protec­tive equipment as necessary. This would include equip­ment such as fall protection systems, safety gloves, goggles, dust masks as well as any specialised equip­ment that may be in use such as lifting and handling equipment. The completed works shall comply with all necessary BS EN Standards and Codes of practice as well as Build­ing control or planning requirements and be confirmed where necessary by notification to building control or the appropriate competence based notification body.
3.4 Lightning protection
a
Caution!
Damage from lightning! If the installation height is more than 20 m or if the collectors are projected above the roof ridge, electro-conductive components must be connected to a lightning protection device!
3.5 Frost protection
a
Caution!
Damage due to frost! Never fill or flush the collector with water. Only fill and flush the collector with Vaillant ready­mixed solar fluid. Check the solar fluid regularly with an anti­freeze tester.
4 Before installation
4.1 Safety instructions3
Please note the following instructions before and during installation:
d
Danger!
Risk of death from falls and falling objects! Observe the national regulations for working at heights. Wear the Vaillant safety belt (article number
302066).
H
Danger!
Danger of burning and scalding! In case of solar irradiation inside the units, col­lectors can reach 300 °C. Remove the sun pro­tection film installed at the factory only after the solar energy system has been started up.
a
Caution!
Collectors may be damaged by incorrect stor­age! Always store the collectors in a dry place and protected from the elements.
Caution!
System error function due to air bubbles! To fill the system, use the fill trolley (article number 0020042548) to avoid air bubbles. Use the manual air vent installed on the collec­tor field. Alternatively, install the Vaillant Solar auto­matic air vent (article number 302019) in the highest point of the system or the automatic de-aerator (article number 302418) in the solar circuit. Observe the relevant installation and operating manual.
5Installation manual auroTHERM 0020077994_00
Safety instructions 3
Before installation 4
GB
Page 6
4.2 Scope of delivery
• Check the mounting kit for completeness based on the illustrations and bills of materials.
4.2.1 On-roof mounting
1
3
2
4
8
9
10
5
7
6
12
11
Fig. 4.1 On-roof mounting kit
Pos. Description Quantity Article number (kit)
1 Rail kit VTK 1140/2 2 0020076781
2 Rail kit VTK 570/2 2 0020076780
3 Tube collector VTK 570/2 1 0010002227
4 Tube collector VTK1140/2 1 0010002228
5
Connecting kit VTK (basic module)
- Compression fitting 15 mm x 3/4'' external thread DN16
- Insulation EPDM 13 x 28, 60 mm, split
1 0020076785
6
Connecting kit VTK (expansion module)
- Rail joining pieces
- Double nipple 15 x 15 mm
- Insulation Armeflex HT, 25 x 20 mm, 45lg
- Cover clip
1 0020076779
7 Valve, 2-way VTK for parallel interconnection 1 0020076784
8 Bracket type S 4
0020067275 (for mounting side-by-side) 0020067276 (for mounting on top of one another)
9 Bracket type S flat 4
0020080145 (for mounting side-by-side) 0020080147 (for mounting on top of one another)
10 Bracket type P (for pantile) 4
0020067273 (for mounting side-by-side)
0020067274 (for mounting on top of one another) 11 Long base (accessory, not available in every country) 4 0020080177 12 Stair bolt mounting kit 4 0020067277
Table 4.1 On-roof mounting bill of materials
Installation manual auroTHERM 0020077994_006
4 Before installation
Page 7
7Installation manual auroTHERM 0020077994_00
4.2.2 Flat-roof mounting
1
2
3
6
4
5
7
8
9
Fig. 4.2 Flat roof mounting kit
Pos. Description Quantity Article number (kit)
1 Rail kit VTK 1140/2 2 0020076781
2 Rail kit VTK 570/2 2 0020076780
3 Open air installation, VTK 1 0020076778
4 Gravel tray kit
230020059904 (2 pcs.)
0020059905 (3 pcs.) 5 Tube collector VTK 570/2 1 0010002227
6 Tube collector VTK1140/2 1 0010002228
7 Valve, 2-way VTK for parallel interconnection 1 0020076784
8 Connecting kit VTK (basic module) 1 0020076785
9 Connecting kit VTK (expansion module) 1 0020076779
Table 4.2 Flat roof installation bill of materials
Before installation 4
GB
Page 8
4.3 Assembling the collector array
The following tables list the required components ac­cording to the type of installation.
4.3.1 On-roof mounting
When mounted on the roof, Vaillant tube collectors can be arranged above one another in up to 3 rows.
4.3.1.1 Collector arrangement, 1-row
Fig. 4.3 Installation kit for single row on-roof mounting
(here: VTK 570/2)
Number of collectors 1 2 3 4 5 6 7 8 9 10 11 12 13 14
VTK 570/2
Connecting kit VTK (basic module) Part No. 0020076785
Required quantity
1
1)
Connecting kit VTK (expansion module) Part No. 0020076779
- 1 2 3 4 5 6 7 8 9 10 11 12 13
Bracket kit Type P (pantile) Part No. 0020067273
12)22)32)42)52)62)72)82)92)102)112)122)132)14
2)
Bracket kit Type S (shingle) Part No. 0020067275
Bracket kit Type S flat Part No. 0020080145
Bracket kit (hanger bolt) Part No. 0020067277
Rail kit (2), VTK 570/2 Part No. 0020076780
1234567891011121314
1) 1 each per row
2) applies up to 700 m above sea level
Table 4.3 Components for single row on-roof mounting
Installation manual auroTHERM 0020077994_008
4 Before installation
Page 9
Number of collectors
1234567
VTK 1140/2
Connecting kit VTK (basic module) Part No. 0020076785
Required quantity
1
1)
Connecting kit VTK (expansion module) Part No. 0020076779
-123456
Bracket kit Type P (pantile) Part No. 0020067273
1
2)
2
2)
3
2)
4
2)
5
2)
6
2)
7
2)
Bracket kit Type S Part No. 0020067275
Bracket kit Type S flat Part No. 0020080145
Bracket kit (hanger bolt) Part No. 0020067277
Rail kit (2), VTK 1140/2 Part No. 0020076781
1234567
VTK 1140/2 + VTK 570/2
Number of collectors VTK 1140/2
123456
Number of collectors VTK 570/2
111111
Connecting kit VTK (basic module) Part No. 0020076785
Required quantity
1
1)
Connecting kit VTK (expansion module) Part No. 0020076779
123456
Bracket kit Type P (pantile) Part No. 0020067273
2
2)
3
2)
4
2)
5
2)
6
2)
7
2)
Bracket kit Type S Part No. 0020067275
Bracket kit Type S flat Part No. 0020080145
Bracket kit (hanger bolt) Part No. 0020067277
Rail kit (2), VTK 1140/2 Part No. 0020076781
123456
Rail kit (2), VTK 570/2 Part No. 0020076780
1
1) 1 each per row
2) applies up to 700 m above sea level
Table 4.3 Components for single row on-roof mounting (contin-
ued)
9Installation manual auroTHERM 0020077994_00
Before installation 4
GB
Page 10
4.3.1.2 Collector arrangement, 2-row
A
B
A
Fig. 4.4 Installation kit for 2-row on-roof mounting (here: VTK 570/2)
Number of collectors per row 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Number of rows 2
VTK 570/2
Connecting kit VTK (basic module) Part No. 0020076785
Required quantity
2
1)
Connecting kit VTK (expansion module) Part No. 0020076779
-2468101214161820222426
Bracket kit Type P (pantile) Part No. 0020067273
a
12)22)32)42)52)62)72)82)92)102)112)122)132)14
2)
Bracket kit Type S Part No. 0020067275
Bracket kit Type S flat Part No. 0020080145
Bracket kit Type P (pantile) Part No. 0020067274
B
1
2)22)32)42)52)62)72)82)92)102)112)122)132)142)
Bracket kit Type S Part No. 0020067276
Bracket kit Type S flat Part No. 0020080147
Rail kit (2), VTK 570/2 Part No. 0020076780
2 4 6 8 10 12 14 16 18 20 22 24 26 28
1) when the connection between the rows is also flat-sealing
2) applies up to 700 m above sea level
Table 4.4 Components for 2-row on-roof mounting
Installation manual auroTHERM 0020077994_0010
4 Before installation
Page 11
11Installation manual auroTHERM 0020077994_00
Number of collectors per row 1 2 3 4 5 6 7
Number of rows 2
VTK 1140/2
Connecting kit VTK (basic module) Part No. 0020076785
Required quantity
2
1)
Connecting kit VTK (expansion module) Part No. 0020076779
-24681012
Bracket kit Type P (pantile) Part No. 0020067273
a 1
2)
2
2)
3
2)
4
2)
5
2)
6
2)
7
2)
Bracket kit Type S Part No. 0020067275
Bracket kit Type S flat Part No. 0020080145
Bracket kit, Type P (pantile) Part No. 0020067274
B 1
2)
2
2)
3
2)
4
2)
5
2)
6
2)
7
2)
Bracket kit Type S Part No. 0020067276
Bracket kit Type S flat Part No. 0020080147
Rail kit (2), VTK 1140/2, Part No. 0020076781
2 4 6 8 10 12 14
1) when the connection between the rows is also flat-sealing
2) applies up to 700 m above sea level
Table 4.4 Components for 2-row on-roof mounting (continued)
4.3.1.3 Collector arrangement, 3-row
A
B
B
A
Fig. 4.5 Installation kit for 3-row on-roof mounting
(here: VTK 570/2)
Before installation 4
GB
Page 12
Number of collectors per row 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Number of rows 3
VTK 570/2
Connecting kit VTK (basic module) Part No. 0020076785
Required quantity
3
1)
Connecting kit VTK (expansion module) Part No. 0020076779
- 3 6 9 12 15 18 21 24 27 30 33 36 39
Bracket kit Type P (pantile) Part No. 0020067273
a 12)22)32)42)52)62)72)82)92)102)112)122)132)14
2)
Bracket kit Type S Part No. 0020067275
Bracket kit Type S flat Part No. 0020080145
Bracket kit Type P (pantile) Part No. 0020067274
B 22)42)62)82)102)122)142)162)182)202)222)242)262)28
2)
Bracket kit Type S Part No. 0020067276
Bracket kit Type S flat Part No. 0020080147
Rail kit (2), VTK 570/2 Part No. 0020076780
3691215182124273033363942
Number of collectors per row 1 2 3 4 5 6 7
Number of rows 3
VTK 1140/2
Connecting kit VTK (basic module) Part No. 0020076785
Required quantity
3
1)
Connecting kit VTK (expansion module) Part No. 0020076779
- 3 6 9 12 15 18
Bracket kit Type P (pantile) Part No. 0020067273
a 12)22)32)42)52)62)7
2)
Bracket kit Type S Part No. 0020067275
Bracket kit Type S flat Part No. 0020080145
Bracket kit, Type P (pantile) Part No. 0020067274
B 22)42)62)82)102)122)14
2)
Bracket kit Type S Part No. 0020067276
Bracket kit Type S flat Part No. 0020080147
Rail kit (2), VTK 1140/2 Part No. 0020076781
36912151821
1) when the connections between the rows are made by flat seal connection.
2) applies up to 700 m above sea level
Table 4.5 Components for 3-row on-roof mounting
Installation manual auroTHERM 0020077994_0012
4 Before installation
Page 13
13Installation manual auroTHERM 0020077994_00
4.3.2 Flat-roof mounting
Number of collectors 1 2 3 4 5 6 7 8 9 10 11 12 13 14
VTK 570/2
Connecting kit VTK (basic module) Part No. 0020076785
Required quantity
1
1)
Connecting kit VTK (expansion module) Part No. 0020076779
- 1 2 3 4 5 6 7 8 9 10 11 12 13
Mounting kit for open-air installation on a flat roof Part No. 0020076778
2 3 4 5 6 7 8 9 10 11 12 13 14 15
Gravel trays required 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Gravel tray kit (2 pcs.) Part No. 0020059904
2-12-12-12- 12-
Gravel tray kit (3 pcs.) Part No. 0020059905
-22244466688810
Rail kit (2), VTK 570/2 Part No. 0020076780
1234567891011121314
VTK 1140/2
Connecting kit VTK (basic module) Part No. 0020076785
1
1)
Connecting kit VTK (expansion module) Part No. 0020076779
-123456
Mounting kit for open-air installation on a flat roof Part No. 0020076778
2345678
Gravel trays required 8 12 16 20 24 28 32
Gravel tray (2 pcs.) Part No. 0020059904
1-21-21
Gravel tray (3 pcs.) Part No. 0020059905
24468810
Rail kit (2) aluminium, VTK 1140/2 Part No. 0020076781
1234567
VTK 1140/2 + VTK 570/2
Number of collectors VTK 1140/2 - 1 2 3 4 5 6
Number of collectors VTK 570/2 - 111111
Connecting kit VTK (basic module) Part No. 0020076785
Required quantity
-1
1)
Connecting kit VTK (expansion module) Part No. 0020076779
-123456
Mounting kit for open-air installation on a flat roof Part No. 0020076778
-345678
Gravel trays required - 8 12 16 20 24 28
Gravel tray kit (2 pcs.) Part No. 0020059904
-1-21-2
Gravel tray kit (3 pcs.) Part No. 0020059905
- 244688
Rail kit (2), VTK 1140/2 Part No. 0020076781
-123456
Rail kit (2), VTK 570/2 Part No. 0020076780
-1
1) 1 each per collector array
Table 4.6 Flat roof installation components
Before installation 4
GB
Page 14
Installation manual auroTHERM 0020077994_0014
4.4 Interconnection scheme
h
Note
Observe the planning information when dimen­sioning the array volume flow.
Furthermore, observe the following rules:
max. 14
Fig. 4.6 Series connection VTK 570/2
• Connect a maximum of 14x VTK 570/2 (corresponding to an aperture area of 14 m
2
) in series.
max. 7
Fig. 4.7 Series connection VTK 1140/2
• Connect a maximum of 7x VTK 1140/2 (corresponding to an aperture area of 14 m
2
) in series.
Fig. 4.8 Parallel connection (here VTK 570/2)
• For aperture areas greater than 14 m2, you must configure several collector arrays in parallel and connect them hydraulically in parallel.
• Always connect as many collectors as pos­sible in series.
h
Note
You should only connect the collec­tor arrays in parallel if the aperture area is greater than 7 m
2
(correspon­ding to 7x VTK 570/2 or 3x 1140/2 + 1x VTK 570/2).
4 Before installation
Page 15
15Installation manual auroTHERM 0020077994_00
Fig. 4.9 Sizes of the individual arrays
When collector arrays are connected in par­allel, each individual array must have the same aperture area.
Fig. 4.10 Stop valve in the collector supply line
a
Caution!
Danger of air locks! If 3 or more collector arrays are con­nected in parallel, a stop valve must be fitted in the collector supply line (hot side) of each individual array. These will be used for venting the in­dividual arrays during commissio­ning. Only use the Vaillant stop valve, Part No. 0020076784
a
Caution!
Danger of damage to the material as a result of incorrect assembly! With the valve closed or wrong valve positioning, damaging of the collector due to excessive pressure will be possible. Never mount the stop valve in the collector return. The stop valve must be open during system operation.
Before installation 4
GB
Page 16
Installation manual auroTHERM 0020077994_0016
4.5 Preparing the hydraulic connection
4.5.1 On-roof mounting
Fig 4.11 Passing the pipe through the sarking membrane
If there is a sarking membrane, proceed as follows:
• Make a v-shaped cut in the sarking membrane.
• Fold the upper, wider flap on to the roof batten above, and the lower, narrower flap on to the roof batten below.
• Fix the sarking membrane tight to the roof batten. This ensures that the dampness flows away to the side.
• With board-clad roofs, cut out a hole with a padsaw.
• Work the roofing felt as described for the sarking membrane.
4.5.2 Flat-roof mounting
a
Caution!
The roof skin can break and cause leaks! When installing the roof sealing surfaces, make sure the roof skin is adequately protected.
• Place large protection mats under the system.
• If the frame is screwed directly, check the sealing of the building shell.
4.6 Required tools
• Have the following tools ready for assembling the tube collectors.
Fig. 4.12 Assembly tools: spirit level, cordless screwdriver,
Torx bit (TX30, supplied), allen key 5mm, socket/combination wrench (13 mm), hammer, measuring tape / folding rule
5 On-roof mounting
With on-roof mounting, the tube collectors are fastened to horizontal mounting rails quickly and reliably with at­tachment clips. To ensure a good adaptation to the dif­ferent roofings, four different brackets are available:
- Type P for standard concrete tiles (e.g. pantile),
- Type S for extremely high protruding tiles (e.g. Medi­terranean clay tiles)
- Type S flat (low profile) for flat tiles or slate roofs.
- Stair bolt mounting kit for universal fixing (e.g. corru­gated slabs, sheet with trapezoidal corrugations, shin­gles).
a
Caution!
Risk of corrosion! On roofs made of metals more noble than alu­minium (e.g. on copper roofs) galvanic corrosion can occur at the anchor points, whereby the at­tachment of the collectors is no longer guaran­teed. Ensure that the metals are separated by suitable underlays.
When mounted on the roof, the Vaillant tube collectors in the collector array can be arranged side-by-side or above each other.
In general, the installation steps and instructions de­scribed in this manual are applicable to all collector arrangements.
Any different installation steps are clearly pointed out:
For collectors arranged side-by-side
For collectors arranged above each other
When arranging the collectors, take note in each case of the possible interconnection schemes in Section 4.4.
4 Before installation 5 On-roof mounting
Page 17
17Installation manual auroTHERM 0020077994_00
5.1 Fitting the brackets
For collectors arranged side-by-side
• Mount the anchors for the mounting rails at the fol­lowing distances:
h
Note
During final fixing the pre-assembly dimension A is reduced by approx. 20 - 25 mm. Take care that there is adequate clearance on the an­chors, therefore.
Number of collectors
A* B C D
VTK 570/2
1
1663 / 1638
50 - 100
507 - 607
707
2 1414
3 2121
4 2828
5 3535
6 4242
7 4949
8 5656
9 6363
10 7070
11 7777
12 8484
13 9191
14 9898
VTK 1140/2
1
100 - 200
997 - 1197
1397
2 2794
3 4191
4 5588
5 6985
6 8382
7 9779
* Pre-assembly dimension / Finished dimension During final fixing of the collectors, the pre-assembly dimension is reduced by approx. 20 - 25 mm.
Table 5.1 Spacings when arranging collectors side-by-side
[in mm]
B
B
B
C
B
A
D
A
A
Fig. 5.1 Spacings when arranging collectors side-by-side
On-roof mounting 5
GB
Page 18
Installation manual auroTHERM 0020077994_0018
For collectors arranged on top of each other
• Mount the anchors for the mounting rails at the fol­lowing distances:
h
Note
During final fixing the pre-assembly dimension A is reduced by approx. 20 - 25 mm. Take care that there is adequate clearance on the an­chors, therefore.
Number of collectors
A* B C D E
2 rowsE3 rows
VTK 570/2
1
1663 / 1638
50 - 100
507 - 607
707
3322 5006
2
1414
3
2121
4
2828
5
3535
6
4242
7
4949
8
5656
9
6363
10
7070
11
7777
12
8484
13
9191
14
9898
VTK 1140/2
1
1663 / 1638
100 - 200
997 - 1197
1397
3322 5006
2
2794
3
4191
4
5588
5
6985
6
8382
7
9779
* Pre-assembly dimension / Finished dimension During final fixing of the collectors, the pre-assembly dimension is reduced by approx. 20 - 25 mm.
Table 5.2 Spacings when arranging collectors on top of each
other [in mm]
A
E
B
B
B
C
B
D
A
A
E
E
Fig. 5.2 Spacings when arranging collectors on top of each other
5 On-roof mounting
Page 19
19Installation manual auroTHERM 0020077994_00
5.2.1 Bracket Type P (pantile)
A
B
1
2
1
2
5 mm
3
Fig. 5.3 Bracket type P
Key
1 Lower bracket 2 Upper bracket 3 Central bracket
The bracket type P can be fixed to the rafters (Pos. A) or by use of the long rear plate set 0020080177 can be offset to suit tile profile.
Fixing to rafters
5
3
4
6
1
2
A
B
Fig. 5.4 Fixing to rafters
1. Uncover the rafters where needed. For distances please see Tab. 5.1 and 5.2.
2. Position the bracket. Take note of the correct posi­tions of the upper, central and lower brackets (see Fig. 5.3).
3. Loosen the upper bolt with the socket/combination wrench (13 mm) until the height of the bracket can be adjusted.
4. Position the bracket at the same height of the pan­tiles, so that the upper part of the anchor is on the roofing, and tighten the bolt with the socket/combina­tion wrench (13 mm).
5. Screw the bracket to the rafters with the 3 supplied bolts.
6. Slide the pantiles back to the original position. If necessary, adapt the water gutter on the lower (A) or upper side (B) of the pantile with a hammer, or suitable disk cutter, until the pantiles are tight.
d
Danger!
Risk of injury! Always wear suitable eye protection and all necessary personal protective equipment and ensure the area of work is safe with regard to other persons.
On-roof mounting 5
GB
Page 20
Installation manual auroTHERM 0020077994_0020
h
Note
With some roof covering it may be necessary to offset the roof bracket to the left or right of the rafter, to do this use the accessory: Part No. 0020080177 (not available in every country). Observe the appropriate installation manual.
Fixing to the roof batten
a
Caution!
Only acceptable if roof and battens have been inspected by a competent roofing contractor / designer. Before installation on the roof batten, check the load capacity of the roof batten! If necessary, replace the roof batten or provide additional timber bearers. Also ensure battens are fixed securely (screw to rafter each side of brackets).
1
3
2
5
6
4
Fig. 5.5 Fixing to the roof batten
1. Slide upward one or two pantiles above the roof bat­ten. For distances please see Tab. 5.1 and 5.2.
2. Loosen the upper bolt with the socket/combination wrench (13 mm) until the height of the bracket can be adjusted.
3. Hook the bracket to the roof batten. Take note of the correct positions of the upper, central and lower brackets when doing this (see Fig. 5.3).
4. Position the bracket at the same height of the pan­tiles. The upper part is on the roofing, the lower part is pressed tight against the roof batten from the bot­tom.
Take care anchor is tightly fixed and pre-tensioned on
the roof batten (toothing engaged).
5. Tighten the bolt with the socket/combination wrench (13 mm).
6. Slide the pantiles back to the original position. If nec­essary, adapt the water gutter on the lower side of the pantile with a hammer, until the pantiles are tight
5 On-roof mounting
Page 21
21Installation manual auroTHERM 0020077994_00
5.2.2 Bracket Type S (for high profile pantiles)
a
Caution!
Before installation on the roof batten, check the load capacity of the roof batten! If necessary, replace the roof batten.
4
2
1
3
Fig. 5.6 Fixing the bracket type S
1. Uncover the rafters or the roof batten where needed. For distances please see Tab. 5.1 and 5.2.
2. Position the bracket. Take note of the correct posi­tions of the upper, central and lower brackets (see Fig. 5.3).
5.2.3 Bracket Type S (Low profile for slate/ flat
tiles)
a
Caution!
Only acceptable if roof and battens have been inspected by a competent roofing contractor / designer. Before installation on the roof batten, check the load capacity of the roof batten! If necessary, replace the roof batten or provide additional timber bearers. Also ensure battens are fixed securely (screw to rafter each side of brackets).
4
2
1
3
Fig. 5.7 Fixing the bracket type S flat
1. Uncover the rafters or the roof batten where needed. For distances please see Tab. 5.1 and 5.2.
2. Position the bracket. Take note of the correct posi­tions of the upper, central and lower brackets (see Fig. 5.3).
3. Screw the bracket to the rafters/roof batten with the 3 supplied bolts.
4. Slide the pantiles back to the original position.
3. Screw the bracket to the rafters/roof batten with the 3 supplied bolts.
4. Slide the pantiles back to the original position.
On-roof mounting 5
GB
Page 22
Installation manual auroTHERM 0020077994_0022
5.2.3 Hanger bolt fixing kit
a
Caution!
Before installation check the load-bearing ca­pacity of the wooden substructure! If necessary, strengthen it. Only for use on roof structures with timbers large enough to accept stair bolt.
1
2
3
5
4
6
Fig. 5.8 Fixing with stair bolt
1. Bore a hole in the roof covering in the corresponding position. For distances please see Tab. 5.1 and 5.2.
2. Tighten the stair bolt to the rafters through the pan­tile.
3. Screw the lower nut against the roof covering, and tighten it until the seal sufficiently seals the opening.
4. Position the central nut so that after inserting the an­chor upper part the front contact area is on the roof­ing. Take note of the correct positions of the upper, central and lower brackets when doing this (see Fig. 5.3).
5. Screw the second nut and tighten it (17 mm).
6. Cut off the threaded bolt directly above the nut.
Deburr the interface.
5 On-roof mounting
Page 23
23Installation manual auroTHERM 0020077994_00
5.3 Fitting the collectors
Fig. 5.9 Fixing the mounting rails
• Fix the horizontal mounting rails with the frame clamping elements on the brackets.
h
Note
For the vertical spacing between the brackets please see Tables 5.1 and
5.2.
h
Note
For a better visual appearance, posi­tion the lower rail as low as possible on the bracket.
Fig. 5.10 Joining the mounting rails
• Insert the connecting elements into the mounting rails by the side, until they lock into place.
• Join the mounting rails and fix them with the clamping elements on the brackets (see Fig. 5.8).
1
2
Fig. 5.11 Balancing the mounting rails
• Make sure that the mounting rails are fixed in horizontal position.
• Compensate any difference in height by moving the clamping elements.
• Pull the clamping element upward, now it can be moved and it engages again when released.
On-roof mounting 5
GB
Page 24
Installation manual auroTHERM 0020077994_0024
1
Fig. 5.12 Hooking the collector
• Place the collector with the lower edge on the mounting rail and hook it to the clam­ping elements.
• Make sure that the upper part (1) of the clamping element is above the collector rail.
• Tighten the clamping elements of the lower mounting rail with the socket/combination wrench (13 mm).
a
Caution!
After tightening the clamping ele­ments, make sure the tension is cor­rect by shaking the upper part of the clamping element. If it can be moved, retighten the nut.
1
Fig. 5.13 Peeling the film from the edges of the collector
• Lift the film at the edges of the collector. This will facilitate pulling off the film later, after commissioning.
H
Danger!
Danger of burning! In case of solar irradiation inside the units, collectors can reach 300 °C. Remove the sun protection film installed at the factory only after the solar energy system has been started up.
Fig. 5.14 Removing the carrying straps
• Remove the carrying straps.
5 On-roof mounting
Page 25
25Installation manual auroTHERM 0020077994_00
1
Fig. 5.15 Mounting other collectors
• Place the next collector on the lower mounting rail.
• Make sure that the upper part (1) of the clamping element is above the collector rail.
• Tighten the lower clamping elements on the collector.
• Slide the upper mounting rails and clam­ping elements little by little from the top against the collector.
1
2
A
B
Fig. 5.16 Joining the collectors
• Couple the double nipple (A) (from the VTK expansion module connecting kit, Part No.
0020076779) to the union nut (B) on the first collector.
• Push the collectors together.
Fig. 5.17 Tightening the compression fitting
a
Caution!
Danger of damage to the collector as a result of incorrect assembly! To prevent damage when tightening the compression fitting, always use a second spanner to provide a counter force.
• Tighten the two union nuts on the double nipple.
1
Fig. 5.18 Positioning the upper mounting rail
• Slide the upper mounting rails towards the collector.
• Take care that the upper parts of the clam­ping elements are over the rails on the collectors.
On-roof mounting 5
GB
Page 26
Installation manual auroTHERM 0020077994_0026
1
2
3
Fig. 5.19 Central mounting rail for 2 or 3 rows of collectors
For collectors arranged on top of
each other
• Slide the central mounting rail flush with the lower collector (1).
• Make sure that the hook of the clamping element (3) is above the edge of the colle­ctor.
• Fix the mounting rail (2) for the next row of collectors to the clamping element.
2
1
3
Fig. 5.20 Central mounting rail for 2 or 3 rows of collectors
For collectors arranged on top of
each other
• Place the upper collector (1) in the central mounting rail (2).
• Screw the clamping elements (3) on the central rail tight.
• Fit the second row of collectors as descri­bed above.
5 On-roof mounting
Page 27
27Installation manual auroTHERM 0020077994_00
Fig. 5.21 Fitting the hydraulic connections
For systems with collector sensors: Plug the collector sensor into the opening provi­ded on the flow side of the collector (hot side).
With several rows of collectors:
• Connect the rows of collectors in accor­dance with the interconnection schemes (cf. Section 4.4).
h
Note
In general it is possible to attach the collector sensor to the left or the right side of the collector array, as the collectors have a corresponding opening on each side. Ensure VR11 sensors are fitted to the hot side of the collector array.
a
Caution!
Danger of damage to the collector as a result of incorrect assembly! To prevent damage when tightening the compression fitting, always use a second spanner to provide a counter force.
• Connect the collector supply and return to the system with the connection pipes.
• To do this, connect the compression fitting (from the VTK basic module connecting kit, Part No. 0020076785) to the collector and connect this to the connecting pipe.
• If necessary check all connections for leaks.
1
3
2
Fig. 5.22 Insulating the hydraulic connections
After commissioning:
• Insulate the hydraulic connections with the Armeflex insulation (1) (from the VTK ex­pansion module connecting kit, Part No.
0020076779).
• Cover the insulation with the cover clip (2) (from the VTK expansion module connec­ting kit, Part No. 0020076779).
• Insulate the hydraulic system connections with the EPDM insulation (3) (from the VTK expansion module connecting kit, Part No.
0020076779).
On-roof mounting 5
GB
Page 28
Installation manual auroTHERM 0020077994_0028
6 Flat-roof mounting
6 Flat-roof mounting
With flat roof installation, the tube collectors are fas­tened to frames. The flat roof frames allow for a flexible installation with an angle of 30 °, 45 ° or 60 °. Also note that the height of the mounting rails is varia­ble, in order to compensate for small floor irregularities.
6.2 Weighting and arrangement of the frames
First of all, define the necessary load of the frames based on Tab. 6.1.
Load [kg/collector]
Height above ground
Angle of attack 0-10 m 10-18 m 18-25 m
30° 159 178 197
45° 225 252 279
60° 276 309 342
Table 6.1
Flat roof installation load
a
Caution!
The roof may collapse! Before installation, check the maximum roof load! If necessary, contact a specialist roofing de­signer/contractor before proceeding. Consider if the frame can be bolted to the structure as opposed to weighting.
a
Caution!
For determining the installation location, keep a distance of 1 m from the roof edge! A differ­ent distance causes high wind loads.
Page 29
29Installation manual auroTHERM 0020077994_00
For the required space and the distances between frames please see Tables 6.2 to 6.4.
VTK 570/2 [distances in mm]
B
E
D
A
C
F
α
1)
C
α
1)
Number of collectors
A
3)
30° (28.5°)
45° (42.5°)
60° (59.5°)
CD
±30
A
BFB F BF
1 560
4)
1072
2950
2)
1432
3940
2)
1757
4830
2)
2460
-
-
2 1168
584
707
3 1875
4 2582
5 3289
6 3996
7 4703
8 5410
9 6117
10 6824
11 7531
12 8238
13 8945
14 9652
1) Installation angle 30°, 45° oder 60°
2) Solar altitude of 20° (winter sun)
3) Dimension A may vary in conjunction with dimensions D and E by r30 mm
4) r5 mm
Table 6.2 Dimensions for VTK 570/2 [in mm]
Flat-roof mounting 6
GB
Page 30
Installation manual auroTHERM 0020077994_0030
VTK 1140/2 [distances in mm]
E
D
A
B
C
F
α
1)
C
α
1)
Number of collectors
A
3)
30° 45° 60°
C
D
±30
A
BFBFBF
1 1170
4)
1072 2950
2)
1432 3940
2)
1757 4830
2)
2460
--
2 2548
1274 1397
3 3945
4 5342
5 6739
6 8136
7 9533
1) Angle of attack 30°, 45° or 60°
2) Solar altitude of 20° (winter sun)
3) Dimension A may vary in conjunction with dimensions D and E by ±30 mm
4) ±5 mm
Table 6.3 Dimensions for VTK 1140/2 [in mm]
6 Flat-roof mounting
Page 31
31Installation manual auroTHERM 0020077994_00
VTK 1140/2 and VTK 570/2 in combination [distances in mm]
E
D
A
B
G
C
F
α
1)
C
α
1)
VTK 570/2
VTK 1140/2
Number of collectors
A
3)
30° 45° 60°
C
D
±30
AG
BFBFBF
VTK 570/2
VTK 1140/2
1 1 1170
4)
1072 2950
2)
1432 3940
2)
1757 4830
2)
2460 584 1397 1274
1 2 2548
1 3 3945
1 4 5342
1 5 6739
1 6 8136
1) Angle of attack 30°, 45° or 60°
2) Solar altitude of 20° (winter sun)
3) Dimension A may vary in conjunction with dimensions D and E by ±30 mm
4) ±5 mm
Table 6.4 Dimensions for VTK 1140/2 and VTK 570/2 in com-
bination [in mm]
Flat-roof mounting 6
GB
Page 32
Installation manual auroTHERM 0020077994_0032
6.3 Fitting the collectors
1
2
3
Fig. 6.1 Preparing the frame
• Open the frames.
a
Caution!
Follow Tables 6.1 to 6.4 without ex­ception to determine the required weights!
With screwed connection on the roof:
• Fasten the rear section to the base section with a retaining pin and locking clip.
1
VTK 570/2
VTK 1140/2
1
Fig. 6.2 Mounting the gravel trays
If gravel trays are used:
• Slide the gravel tray (1) on the base section.
• Fasten the rear section to the base section with a retaining pin and locking clip.
60°
45°
30°
1
2
Fig. 6.3 Frame assembly
• Insert the telescopic sections into each other, until the holes of the desired angular position are placed one above the other.
h
Note
You can choose settings of 30°, 45° or 60°.
• Insert the retaining pin into the correspon­ding hole (1).
• Fix the retaining pin with the safety clip (2).
6 Flat-roof mounting
Page 33
33Installation manual auroTHERM 0020077994_00
VTK 570/2
VTK 1140/2
1
1
Fig. 6.4 Frames with gravel trays
If gravel trays are used:
• Place large protection mats under the sys­tem.
• Set up the frames (1) according to the num­ber of collectors to be mounted.
h
Note
The weights and distances can be found in Table 6.1.
a
Caution!
Before mounting the collectors, fill the gravel trays on the first frame with gravel or other suitable weighting material, to give the sys­tem stability.
Fig. 6.5 Direct screwed connection
With screwed connection on the roof:
• Assembly frames based on the number of collectors to be installed.
h
Note
The weights and distances can be found in Table 6.1.
• Fix the frames on the roof.
a
Caution!
The roof skin can break and cause lack of tightness! When installing the roof sealing sur­faces, make sure the roof skin is ade­quately protected.
1
2
Fig. 6.6 Fixing and blocking the mounting rail
• Fasten the horizontal mounting rails (1) to the clamping elements(2) on the frames.
• Compensate for any difference in height by moving the clamping elements (2).
• Pull the lower part of the clamping element (2) upwards; now it can be moved and it engages again when released.
Flat-roof mounting 6
GB
Page 34
34
20
A B
1
1
2
Fig. 6.7 Positioning the mounting rails
• If multiple collectors are mounted, have the mounting rails (1) meet in the centre of the frames (2) (A).
• On the first and last frame, the mounting rails (1) should project by 20 mm over the edge (B).
1
Fig. 6.8 Joining the mounting rails
• Insert the connecting elements (1) into the ends of the mounting rails.
• Join the mounting rails and fix them to the frame clamping elements.
• Compensate any difference in height by moving the clamping elements.
1
Fig. 6.9 Hooking the collector
• Place the collector with the lower edge in the section of the mounting rail.
• Position the upper part (1) of the clamping element over the rail on the collector.
• Tighten the clamping elements of the lower mounting rail with the socket/combination wrench (13 mm AF).
a
Caution!
After tightening the clamping ele­ments, make sure the tension is cor­rect by shaking the upper part of the clamping element. If it can be moved, retighten the nut.
1
Fig. 6.10 Peeling the film from the edges of the collector
• Lift the film at the edges of the collector. This will facilitate pulling off the film later, after commissioning.
H
Danger!
Danger of burning! In case of solar irradiation inside the units, collectors can reach 300 °C. Remove the sun protection film installed at the factory only after the solar energy system has been started up.
Installation manual auroTHERM 0020077994_00
6 Flat-roof mounting
Page 35
35Installation manual auroTHERM 0020077994_00
Fig. 6.11 Removing the carrying straps
• Remove the carrying straps.
1
Fig. 6.12 Mounting other collectors
• Place the next collector on the lower moun­ting rail at a distance of approx. 10 cm from the first collector.
1
2
A
B
Fig. 6.13 Joining the collectors
• Couple the double nipple (A) (from the VTK expansion module connecting kit, Part No.
0020076779) to the union nut (B) on the first collector.
• Push the collectors together.
Fig. 6.14 Tightening the compression fitting
a
Caution!
Danger of damage to the collector as a result of incorrect assembly! To prevent damage when tightening the compression fitting, always use a second spanner to provide a counter force.
• Tighten the two union nuts on the double nipple.
Flat-roof mounting 6
GB
Page 36
Installation manual auroTHERM 0020077994_0036
1
Fig. 6.15 Positioning the upper mounting rail
• Slide the upper mounting rails towards the collectors.
• Take care that the upper parts (1) of the clamping elements are over the rails on the collectors.
• Tighten the clamping element with the socket/combination wrench (13 mm AF).
a
Caution!
After tightening the clamping ele­ments, make sure the tension is cor­rect by shaking the upper part of the clamping element. If it can be moved, retighten the nut.
Fig. 6.16 Fitting the hydraulic connections
For systems with collector sensors: Plug the collector sensor into the opening provi­ded on the flow side of the collector (hot side).
h
Note
It is possible to attach the collector sensor to the left or the right side of the collector array, as the collectors have a corresponding opening on each side. Always ensure the VR11 sensor is fit­ted to the hot side of the collector array.
a
Caution!
Danger of damage to the collector as a result of incorrect assembly! To prevent damage when tightening the compression fitting, always use a second spanner to provide a counter force.
• Connect the collector supply and return to the system with the connection pipes.
• To do this, connect the compression fitting (from the VTK basic module connecting kit, Part No. 0020076785) to the collector and connect this to the connecting pipe.
• If necessary check the connections for leaks.
6 Flat-roof mounting
Page 37
37Installation manual auroTHERM 0020077994_00
1
3
2
Fig. 6.17 Insulating the hydraulic connections
After commissioning:
• Insulate the hydraulic connections with the Armeflex insulation (1) (from the VTK ex­pansion module connecting kit, Part No.
0020076779).
• Cover the insulation with the cover clip (2) (from the VTK expansion module connec­ting kit, Part No. 0020076779).
• Insulate the hydraulic system connections with the EPDM insulation (3) (from the VTK expansion module connecting kit, Part No.
0020076779).
7 Final operations
Based on the following table, make sure all work steps have been performed.
Step
1 For flat roof installation: frames fixed with retaining pin and safety clip
2 For flat roof installation: gravel trays filled/frames anchored
3 All hydraulic connections tightened
4 Hydraulic connections laid correctly
5 VR 11 collector sensors connected (for systems with collector sensors)
6 All clamping elements tightened
7 Collectors connected to lightning protection device (optional with lightning protection device)
8 Pressure test (ideally with air pressure) carried out, all connections tight
Table 7.1 Final operations
Flat-roof mounting 6
Final operations 7
GB
Page 38
Installation manual auroTHERM 0020077994_0038
8 Recycling and disposal
The development of all Vaillant products takes into ac­count the future with regard to use of materials that can be easily recycled with the least detrimental affects upon our environment. The packaging makes maximum use of recycled materials and the appliance itself con­sists mainly of metals that are readily separated into re­cyclable raw materials. After many years of reliable op­eration our appliance can be disposed via recognised re­cycling and reclamation facilities in a way that will cause least harm to our environment.
9 Vaillant Customer Service
and warranty
9.1 Vaillant warranty
Vaillant provides a full parts and labour warranty for this appliance. The appliance and all associated pipe work and controls must be installed by suitably competent persons in ac­cordance with all current and relevant safety, building control and planning regulations and in full compliance with the manufacturer’s instructions. All unvented domestic hot water cylinders must be in­stalled by a competent person to the prevailing building regulations at the time of installation (G3). Terms and conditions apply to the warranty, details of which can be found on the warranty registration card in­cluded with this appliance. Failure to install and commission this appliance in com­pliance with the manufacturer’s instructions may invali­date the warranty (this does not affect the customer’s statutory rights).
9.2 Vaillant service
To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agree­ment. Please contact Vaillant Service Solutions (0870 6060 777) for further details.
8 Disposal 9 Vaillant Customer Service and warranty
Page 39
39Installation manual auroTHERM 0020077994_00
10 Technical data
Units VTK 570/2 VTK 1140/2
Number of vacuum tubes 6 12
η
0
(aperture), DIN4757-4 or EN12975
% 64.2
c
1
with wind, relative to aperture W/(m2k) 0.885
c
2
with wind, relative to aperture W/(m2k2) 0.001
K
θ,trans
(50°), relative to aperture
1
K
θ,long
(50°), relative to aperture
0.9
Predicted energy gain (location Würzburg, 5m
2
aperture, 300l cylinder, 4 persons)
kWh/m2a 586
Peak output per collector module W
peak
w 642 1278
Area-related heat capacity c kJ/(m
2
k) 8.3
Volume flow (per m
2
of collector surface) l/(m2h) 24
Minimum volume flow in solar circuit l/h 180
Absolute pressure in hard vacuum bar 10
-5
mbar (= 10-8 bar)
Absorber absorption alpha > 93.5% (see also ITW test report)
Absorber emission epsilon < 6% (see also ITW test report)
Modular dimensions (length x height x depth) m 0.7 x 1.65 x 0.11 1.39 x 1.65 x 0.11
Gross area m
2
1.16 2.30
Aperture surface area m
2
1.0 2.0
Absorber surface area m
2
1.0 2.0
Collector capacity l 0.9 1.8
Weight kg 19 37
Operating overpressure, max. permissible bar 10 10
Standstill temperature, max. °C 295
Connection diameter, supply/return mm 15
Collector material Al / Cu / Glass / Silicon / PBT / EPDM / TE
Glass tubing material Borosilicate 3.3
Selective absorber coating material Aluminium nitrite
Glass tubing (outer dia./inner dia./wall thickness/tube length)
47 / 37 / 1.6 / 1500
Colour (plastic parts) Black
Thermal shock test ITW test number 02COL282
Hail impact test per DIN EN 12975-2 TÜV test number 435/142448
Type approval number 01-228-770
Table 10.1 Technical data
Technical data 10
GB
Page 40
Installation manual auroTHERM 0020077994_0040
VTK 570/2
1652
111
702
Fig. 10.1 Dimensional drawing VTK 570/2
10 Technical data
Page 41
41Installation manual auroTHERM 0020077994_00
VTK 1140/2
1652
111
1392
Fig. 10.2 Dimensional drawing VTK 1140/2
0
0%
10%
20%
30%
40%
50%
60%
70%
80%
5101520253035404550556065707580
ΔT
η
Fig. 10.3 Efficiency of the VTK 570/2 and the 1140/2 at an ir-
radiance Eg of 300 W/m
2
Key
K Efficiency [%] 'T = T
Collector
- T
Ambient air
[K]
Technical data 10
GB
Page 42
Installation manual auroTHERM 0020077994_0042
0
0%
10%
20%
30%
40%
50%
60%
70%
80%
5101520253035404550556065707580
ΔT
η
Fig. 10.4 Efficiency of the VTK 570/2 and the 1140/2 at an ir-
radiance Eg of 800 W/m
2
Key
K Efficiency [%] 'T = T
Collector
- T
Ambient air
[K]
160
140
120
100
90
60
40
20
0
Q [l/h]
Δp [mbar]
0 50 100 150 200 250 300 350 400 450 500
VTK 1140/2
VTK 570/2
Fig. 10.5 Pressure loss graph
Key
Q Mass flow [l/h] 'p Pressure loss [mbar]
10 Technical data
Page 43
Page 44