vaillant Aurostor VIH S GB 210/2 S User guide

Page 1
Instructions for commissioning, maintenance
and troubleshooting
For the competent person
Instructions for commissioning, maintenance and troubleshooting
Solar heating system with auroSTOR
Solar hot water system
GB, IE
Page 2
Table of contents
1 Notes on the documentation ................................3
1.1 Other applicable documents ...................................3
1.2 Storing documents .....................................................3
1.3 Symbols used ...............................................................3
1.4 Applicability of the instructions .............................. 3
1.5 Cylinder identification plate .....................................4
1.6 CE label .........................................................................4
1.7 Benchmark ...................................................................4
2 Safety instructions and regulations ..................4
2.1 Safety and warning information .............................4
2.1.1 Classification of action-related warnings .............4
2.1.2 Structure of warnings ................................................4
2.2 Intended use ................................................................5
2.3 General safety instructions ......................................5
2.4 Overview of EU standards ........................................6
2.4.1 General information on solar heating system .....6
2.4.2 Cylinder and cylinder assembly .............................. 7
2.5 Regulations for Great Britain ...................................7
2.5.1 Technical Guidance .....................................................7
2.5.2 Related documents.....................................................7
2.5.3 Regulations for the prevention of accidents .......8
3 System description ..................................................8
3.1 Design and function of solar heating system ......8
3.2 Electrical wiring......................................................... 10
3.3 Hot water temperature regulation ....................... 10
3.4 Heating control .......................................................... 10
4 Description of the components ............................11
4.1 auroSTOR solar cylinder ...........................................11
4.1.1 Safety devices .............................................................12
4.1.2 Cylinder operating elements ...................................12
4.2 Solar fluid ....................................................................14
4.2.1 Properties of solar fluid ...........................................14
4.2.2 Solar circuit frost and corrosion protection
system ..........................................................................14
4.2.3 Cylinder frost protection ..........................................14
4.2.4 Safety data sheet for Vaillant solar fluid .............15
4.3 System configuration ................................................17
4.3.1 Vaillant controllers and their basic functions .....17
4.3.2 Control functions .......................................................18
4.3.3 Technical data of the auroSTOR solar cylinder 20
4.3.4 Dimensions .................................................................22
5 Assembly ...................................................................23
5.1 Scope of delivery ......................................................23
5.2 Transporting the cylinder .......................................23
5.3 Requirements for installation site ........................23
6 Installation ................................................................24
6.1 Installation sequence ...............................................24
6.2 Installation of solar circuit piping .........................24
6.2.1 Piping material in the solar circuit .......................24
6.2.2 Layout of piping in the solar circuit .....................24
6.2.3 Realisation of solar circuit piping .........................25
6.2.4 Venting the solar circuit..........................................27
6.3 Pipes for the primary heating circuit ..................29
6.4 Installing hot water pipes .......................................29
6.5 Hot water thermostat mixer ..................................29
6.5.1 Installing the hot water thermostat mixer
(without secondary circulation line) ................... 30
6.5.2 Installing the hot water thermostat mixer
(with secondary circulation line) .......................... 30
6.5.3 Setting the hot water thermostat mixer ............ 30
6.6 Installation of cold mains inlet ...............................31
6.6.1 Pressure in cold mains inlet ....................................31
6.6.2 Mounting the safety assembly ...............................31
6.6.3 Mounting the expansion vessel .............................32
6.6.4 Mounting the drain valve ........................................32
6.6.5 Laying the pipes to the tundish ............................32
6.7 Installation of discharge pipe ................................32
6.7.1 Design of discharge pipe .........................................32
6.7.2 High drain ...................................................................34
6.8 Electrical installation ...............................................34
6.8.1 Options for combining control components ......34
6.8.2 Electrical connection of control components ....36
6.8.3 Connecting up the electric immersion heater ... 37
6.8.4 Connection of the solar pump ...............................38
6.8.5 Connecting up the solar yield temperature
sensor ..........................................................................38
6.8.6 Installing the control components in accordance
with the connection wiring diagrams .......................40
7 Commissioning .........................................................52
7.1 Checking leak-tightness ..........................................52
7.2 Flushing the solar circuit with solar fluid ...........53
7.3 Filling the solar circuit with solar fluid ................53
7.4 Setting the flow rate in the solar circuit ............ 54
7.5 Flushing the primary heating circuit ...................55
7.6 Water treatment ........................................................55
7.7
7.8 Filling the central heating system ........................57
7
7.10 Setting the hot water thermostat mixer ............ 58
7.11 Filling in the commissioning report ....................58
7.12 Handover to the operator ...................................... 58
Filling the cylinder ................................................... 56
.9 Commissioning the gas-fired wall-hung boiler 58
2 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 3
8 Inspection and maintenance ...............................59
8.1 Checking the temperature/pressure
relief valve and expansion relief valve .................61
8.2 Checking the charge pressure
of the expansion vessel ............................................61
8.3 Draining the cylinder ................................................61
9 Fault finding ..............................................................62
10 Taking the cylinder out of service ................... 65
10.1 Temporarily taking the cylinder out of service 65
10.2 Permanently taking the cylinder
out of service ............................................................ 65
11 Recycling and disposal ......................................... 65
11.1 Cylinder disposal ...................................................... 65
11.2 Disposal of packaging ............................................. 65
12 Customer service and manufacturer's
guarantee .................................................................. 66
12.1 Vaillant service ......................................................... 66
12.2 Vaillant guarantee ................................................... 66
Notes on the documentation 1
1 Notes on the documentation
The following instructions are intended to guide you through the entire documentation. Other documents apply in addition to these installation instructions.
We do not accept liability for any claims or damages resulting from failure to observe these instructions.
1.1 Other applicable documents
> When installing and maintaining the solar heating system,
you must observe all of the installation and maintenance instructions for system components as well as those for other accessories which are used in the system.
These installation and maintenance instructions are pro­vided with the relevant system components and accesso­ries.
1.2 Storing documents
> Pass these installation instructions and all other appli-
cable documents and, if necessary, any required tools to the system operator.
The system operator will store these so that they are available when required.
1.3 Symbols used
The symbols used in the text are explained below.
Symbol that denotes useful tips and information
i
> Symbol for a required action
1.4 Applicability of the instructions
These instructions apply for the following only:
Unit type Cylinder volume Article number
VIH S GB 210/2 S 210 litres 0020115422
VIH S GB 260/2 S 260 litres 0020115425
VIH S GB 310/2 S 310 litres 0020115428
Table 1.1 Applicability of the instructions
> The article number of the unit is displayed
on the identification plate.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 3
Page 4
1 Notes on the documentation 2 Safety instructions and regulations
1.5 Cylinder identification plate
The identification plate is attached to the cylinder at the factory.
1.6 CE label
CE labelling shows that, based on the type overview, the units comply with the basic requirements of the applica­ble directives. The CE declarations of conformity can be viewed at the manufacturer's premises and can be supplied if neces­sary.
1.7 Benchmark
Vaillant Ltd. supports the Benchmark Initia-
tive. You will find the Benchmark Logbook on
i
the last page of this instruction manual. It is very important that this document be filled out properly when installing, commissioning and handing-over to the operator of the installation. Installers should point out also the service record section for completion fol­lowing service calls to this appliance. Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instruc­tions by competent persons approved at the time by the Health and Safety Executive and that it meets the requirements of the appro­priate Building Regulations. The Benchmark Checklist can be used to dem­onstrate compliance with Building Regulations and should be provided to the customer for future reference. Installers are required to carry out installa­tion, commissioning and servicing work in accordance with the Benchmark Code of Prac­tice which is available from the Heating and Hot water Industry Council who manage and promote the Scheme.
Visit "www.central heating.co.uk" for more
information
.
2 Safety instructions and regulations
2.1 Safety and warning information
When conducting installation and maintenance work, observe the general safety instructions and the warning notes which appear before each of the actions.
2.1.1 Classification of action-related warnings
The action-related warnings are classified in accordance with the severity of the possible danger using the follow­ing warning signs and signal words:
Warning sign Signal word Explanation
Danger!
a
Danger!
e
Warning!
a
Caution!
b
2.1.2 Structure of warnings
Warning signs are identified by an upper and lower sepa­rating line and are laid out according to the following basic principle:
Signal word!
Type and source of danger!
a
Explanation of the type and source of dan­ger.
> Measures for averting the danger
Imminent danger to life or risk of severe personal injury
Risk of death from electric shock
Risk of minor personal injury
Risk of material or environmental damage
4 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 5
Safety instructions and regulations 2
2.2 Intended use
The Vaillant solar heating system has been constructed using state-of-the-art technology in accordance with rec­ognised safety regulations. Nevertheless, there is still a risk of injury or danger of death to the operator or others or of damage to the unit and other property in the event of improper use or use for which the unit is not intended. These components of the Vaillant solar heating system are not intended to be used by persons (including chil­dren) with limited physical, sensory or mental capabili­ties or insufficient experience and/or knowledge, unless they are supervised by a person who is responsible for their safety or have been instructed by this person on how to use the unit. Children must be supervised to ensure that they do not play with the unit.
The purpose of the Vaillant solar heating system is to provide a solar-supported hot water supply. Vaillant auroSTOR VIH S GB 210/2 S, VIH S GB 260/2 S, and VIH S GB 310/2 S solar cylinders are unvented, indi­rectly heated domestic hot water cylinders for solar heating systems designed for use with gas-fired wall­hung boilers as per GB standards for hot water supply systems. The cylinders work with the pressure of the water supply line and do not need a cold water tank for their supply. They are used only to supply potable water heated up to 80 ºC by means of a solar collector array. They may only be used for this purpose. The cylinders can be used in combination with a downstream gas-fired wall-hung boiler for hot water production in accordance with GB standards. Any other use that is not specified in these instructions, or use beyond that specified in this document shall be considered improper use. Any direct commercial or industrial use is also deemed to be improper. The manufacturer/supplier is not liable for any claims or damage resulting from improper use. The user alone bears the risk. Intended use includes the following:
– observance of accompanying operating, installation and
servicing instructions for Vaillant products as well as for other parts and components of the system
– compliance with all inspection and maintenance condi-
tions listed in the instructions.
.
Improper use of any kind is prohibited!
At the end of these instructions there is a commission­ing report which you must fill in and hand over to the operator.
All installers should have a current ID card and registra­tion number. The cylinder must be installed by a compe­tent person approved at the time by the Health and Safety Executive to the prevailing standards, installation book and building regulations at the time of installation.
2.3 General safety instructions
Installation, commissioning, and maintenance
Installation and adjustment as well as service, mainte­nance and repair must be carried out by a competent person approved at the time by the Health and Safety Executive and be in accordance with the relevant requirements of the Local Authority, Building Regula­tions, Building Regulations (Scotland), Building Regula­tions (Northern Ireland), and the bye-laws of the local Water Undertaking.
All electrical wiring must be carried out by a competent electrician and be in accordance with the current I.E.E. Wiring Regulations.
> Make sure that the system has been planned in
accordance with technical regulations and all applicable planning standards.
Risk of death due to lack of safety devices
A lack of safety devices (e.g. expansion relief valve, expansion vessel) can lead to potentially fatal scalding and other injuries, e.g. due to explosions. The schematic drawings included in this document do not show all safety devices required for correct installa­tion.
> Install the necessary safety devices in the system. > Inform the operator about the function and position of
the safety devices.
> Observe the applicable national and international laws,
standards and guidelines.
Safety information on the solar heating system
> Mount and operate the entire solar heating system in
accordance with the recognised technical regulations.
> Make sure that all valid health and safety regulations are
observed, especially for work on the roof. Always use fall protection devices if there is a risk of falling. We recom­mend the use of a Vaillant safety belt. Observe the acci­dent prevention regulations of the professional associa­tions.
> Earth the solar circuit for potential equalisation and to
protect against overvoltage. Attach earthing pipe clamps to the solar circuit pipes and connect the clamps to a potential equalisation bar using 16 mm
2
Cu cable.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 5
Page 6
2 Safety instructions and regulations
Cylinder safety information
Following an inspection, it was ascertained that this product complies with the building regulations for closed hot water cylinder systems and must not be changed or rebuilt in any way.
> When replacing parts, only original replacement parts
from Vaillant Ltd. may be used.
The installation must be approved in accordance with the building regulations.
> Installation plans must be disclosed to the relevant
authorities.
Important:
As stipulated in the manual "Handling Operations Regu­lations 1992", the weight of the unit exceeds that which should be lifted by one person alone.
Electric potential equalisation
If you use an electric immersion heater in the cylinder, the external voltage may build up electrical potential in the water which can result in the electrochemical corro­sion of the electric immersion heater. If the solar cylinder is connected with pipes made of non-metallic materials and is not earthed, corrosion damage can occur.
> Make sure that both the hot water and cold mains inlets
are connected to the earth line by means of an earth cable directly on the cylinder.
> You must also make sure that the electric immersion
heater is connected to the earth line via the earthing ter­minal.
Risk of scalding and damage from escaping hot or cold water.
> If you use plastic pipes for the hot or cold water connec-
tion of the unit, you must only use pipes which are tem­perature-resistant up to 95 °C under a pressure of 1.0 MPa (10 bar).
If the solar heating system is in stagnation, hot steam can escape from the expansion relief valve of the solar pump unit, causing injury to persons. Escaping solar fluid is visible in the collection canister.
> Connect the expansion relief valve to a collecting
container via a metal pipe.
> Position an air vent or an air separator system in such a
way that persons are not endangered by escaping steam.
> Install a hot water thermostat mixer in the system
to protect against scalding.
Preventing frost damage
You should not turn the gas-fired wall-hung boiler off completely so that you can still use all of the safety functions for your heating system. If you want to take the unit out of operation for a relatively long period of time in an unheated room at risk from frost, you must completely drain the auroSTOR.
Avoiding damage caused by leaks
If there are leaks in the pipework, close off the cold water stop valve on the safety assembly and notify a competent person so that they can rectify the leaks.
Preventing damage due to unauthorised changes to the unit
Changes to the supply lines, relief valve termination, and expansion relief valve may only be carried out by a competent person!
2.4 Overview of EU standards
2.4.1 General information on solar heating system
EN ISO 9488
Solar heating system and components, terminology (ISO/DIS 9488; 1995)
Improper use and/or the use of unsuitable tools may result in damage (e.g. water leaks).
> Always use a suitable open-end wrench (spanner) to tigh-
ten or undo threaded connections. Do not use pipe wren­ches, extensions, etc.
If the water does not satisfy the standards for water quality in the UK with a maximum chloride content of
EN 12975-1
Solar heating systems and components; Collectors, Part 1: General requirements
EN 12975-2
Solar heating systems and components; Collectors;
Part 2: Testing methods 250 mg/l, this may result in corrosion damage to the cylinder.
> Only use the cylinder to heat potable water.
EN 1991-2-3
Eurocode 1 – Basis of design and actions on structures,
Part 2–3: Actions on structures - Snow loads
Avoiding burns and scalds
> Install and replace collectors or collector parts on very
cloudy days. Only carry out installation work in the early morning or in the evening on sunny days or cover the collector.
> Fill and flush the solar heating system when the collec-
tors are cold. Cover the collectors while doing so.
EN 12976-1
Solar heating systems and components;
Factory made systems - Part 1: General requirements
EN 12976-2
Solar heating systems and components;
Factory made systems - Part 2: Testing methods
6 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 7
Safety instructions and regulations 2
ENV 12977-1
Solar heating systems and components; Custom built systems, Part 1: General requirements
ENV 12977-2
Solar heating systems and components; Factory made systems, Part 2: Testing methods
ISO 9459-1: 1993
Solar heating – Domestic water heating systems – Part 1: System rating procedures using indoor test methods
ISO/TR 10217
Solar energy; Water heating system; Guideline for mate­rial selection with reference to internal corrosion
2.4.2 Cylinder and cylinder assembly
Pressure equipment directive 97/23/EC
Directive of the European Parliament and Council of 29th May 1997 for the approximation of the laws on pressure equipment of the Member States
EN 12977-3
Solar heating systems and components; Custom built systems, Part 3: Performance characterisation of domestic hot water cylinders
EN 12897:2006
Water supply - specification for indirectly heated unvented (closed) domestic hot water cylinders
2.5 Regulations for Great Britain
2.5.1 Technical Guidance
The system must be installed in accordance with all rele-
vant and applicable national regulations, and must be
installed to suit site conditions.
Observe all national regulations, including:
– Working at Heights Regulations 2005 – Health and Safety at Work Act 1974 – Electricity at Work Regulations 1989 – IEE Wiring Regulations BS 7671 – Lightning protection requirements – Equipotential bonding of electrical installations.
2.5.2 Related documents
The installation of the solar system must be in accord-
ance with the relevant requirements of Health and
Safety Document No. 635 (The Electricity at Work Regu-
lations 1989), BS7671 (IEE Wiring Regulations) and the
Water Supply (Water Fitting) Regulations 1999, or The
Water Bylaws 2000 (Scotland). It should also be in
accordance with the relevant requirements of the Local
Authority, Building Regulations, The Building Regulations
(Scotland), The Building Regulations (Northern Ireland)
and the relevant recommendations of the following
British Standards:
BS EN 806: Specification for installations inside build-
ings conveying water for human consumption
BS 6700: Services supplying water for domestic use
within buildings and their curtilages.
EN 806-1
Specifications for installations inside buildings conveying water for human consumption - Part 1: General
EN 1717
Protection against pollution of potable water installa­tions and general requirements of devices to prevent pollution by backflow
EN 60335-2-21
Safety of household and similar electrical appliances; Part 2: Particular requirements for storage water heat­ers (domestic hot water cylinders and hot water boilers) (IEC 335-2-21: 1989 and supplements 1; 1990 and 2; 1990, modified)
Lightning protection
ENV 61024-1
Protection of structures against lightning – Part 1: General principles (IEC 1024-1: 1990; modified) BS 6651: Code of practice for protection of structures against lightning
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 7
BS. 5449 Forced circulation hot water central heating
systems for domestic premises. Note: only up to 45 kW.
BS. 6880 Low temperature hot water heating systems
of output greater than 45 kW.
Part 1 Fundamental and design considerations.
Part 2 Selection of equipment.
Part 3 Installation, commissioning and maintenance.
BS 6114: Expansion vessels using an internal diaphragm
for unvented hot water supply systems
BS. 4814 Specification for: Expansion vessels using an
internal diaphragm, for sealed hot water heating sys-
tems.
Unvented hot water systems must comply with building
regulation G section 3.
Page 8
2 Safety instructions and regulations 3 System description
2.5.3 Regulations for the prevention of accidents
When carrying out works such as solar installation work it is necessary to do so in a safe and workman like man­ner, taking due care of any aspects of the works that could result in injuries to person in or about the building as well as workers, passers by and the general public at large. To that end these works must conform, but not be limited to, the current regulations in force such as the following Health and Safety at Work act 1974 Work at Height Regulations 2005. Electricity at Work Regulations 1989 All necessary Building Regulations.
Work should be preceded by a risk assessment covering all aspects of health and safety risks, or training require­ments that can reasonably be foreseen to be associated with the work. All scaffolding in the UK, other than prefabricated (zip-up) scaffold towers, must be designed and constructed by a vetted contractor, and have suitable kick boards, hand rails and where appro­priate netting. Areas around the scaffolding should be zoned off and marked with suitable warning signs to a suitable distance to protect persons from falling objects. Workers should have available and use personal protec­tive equipment as necessary. This would include equip­ment such as fall protection systems, safety gloves, goggles, dust masks as well as any specialised equip­ment that may be in use such as lifting and handling equipment. The completed works shall comply with all necessary BS EN Standards and Codes of practice as well as Build­ing control or planning requirements and be confirmed where necessary by notification to building control or the appropriate competence based notification body.
3 System description
3.1 Design and function of solar heating system
The solar heating system consists of four main compo-
nents:
– The collectors, which absorb the solar radiation and
make it useful
– The solar controller, which monitors, displays, and cont-
rols all system functions
– The solar pump unit, which is responsible for trans-
porting the solar heat
– The solar cylinder
The Vaillant solar heating system is a closed hydraulic
system in which heat is transferred to the cylinder via
the heat exchanger with the help of the system's special
heat transfer fluid.
On days when the solar radiation is not sufficient to heat
the hot water in the cylinder, the cylinder water must be
reheated using a heating system. This can take place
using a gas-fired wall-hung boiler or an electric immer-
sion heater.
8 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 9
System description 3
6
7
8
9
C
M
3
10
D
DHW
12
2
5
M
5
M
Fig. 3.1 System for solar hot water production
Key
1 Gas-fired wall-hung boiler 2 Cylinder 3 Two port motorised valve (230 V, supplied with cylinder) 4 Electric immersion heater 5 Two port motorised valve (230 V) 6 Collector (tube collector with top connections (example) or flat
collector with top and bottom connections) 7 Solar pump unit 8 Solar protection and expansion vessel (Combined unit) 9 Collection canister for solar fluid
4
1
BA
10 Automatic air separator system 11 Hot water expansion vessel 12 Thermostat mixer A Primary heater flow B Primary heater return C Solar flow D Solar return DHW Hot water
11
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 9
Page 10
3 System description
The collection canister for solar fluid collects
escaping solar fluid. The solar fluid must not
i i
i
The collector(6) converts solar energy into heat and transfers the heat energy to a frost-protected solar fluid. Using the pipe system, the solar pump of the solar pump unit (7) conveys the heat from the collector to the biva­lent cylinder (2). The solar pump unit is controlled by the solar controller.
The solar controller switches the solar pump on and off as soon as the temperature difference between the col­lector and cylinder exceeds or falls below the preset value. If the solar energy is not sufficient for require­ments, the controller activates the gas-fired wall-hung boiler (1) to reheat the top third of the cylinder to the set hot water temperature value. The water in the cylin­der can also be reheated using the electric immersion heater installed at the factory.
A solar expansion vessel compensates for pressure fluctuations in the solar circuit. A solar protection vessel protects the expansion vessel from excessive temperatures in the solar circuit. We rec­ommend installing a protection vessel. All Vaillant solar sets contain a combined solar protec­tion and solar expansion vessel (8).
reach the drainage system.
For the supply and return lines in the solar cir-
cuit, use insulated stainless steel pipes, e.g. the Vaillant Solar flexible pipe that is included in the scope of delivery of a Vaillant Solar set. Alterna­tively, you can also use copper pipes with press fittings and suitable insulation. Soft solder con­nections are not suitable for solar piping.
If a cylinder is fitted very high up in the building,
negative pressure may form in the cylinder. Under such circumstances, the competent per­son must decide whether an anti-vacuum valve is required in order to prevent damage to the cylinder. If, as a result of draining or thermal contraction of the drinking water, the negative pressure in the cylinder is too high, an anti-vac­uum valve ensures pressure compensation as a result of air flowing into the cylinder.
3.2 Electrical wiring
If you use an eBUS-compatible Vaillant gas-fired wall­hung boiler, you can use a Vaillant Control Centre for the wiring. If you are using a non-eBUS-compatible Vaillant gas­fired wall-hung boiler or a third-party boiler, you can use a standard cabling box. Section 6.8 of these instructions describes the electrical wiring of the system in detail.
3.3 Hot water temperature regulation
You can control the hot water temperature in the top third of the cylinder using an auroMATIC VRS 560/2 or a calorMATIC VRC470 with VR68/2 and VR61/2 or with a separate hot water controller.
Danger!
Risk of burns and scalds!
a
3.4 Heating control
If you are using an eBUS-compatible Vaillant gas-fired wall-hung boiler, you can control the heating using a programmable Vaillant VRT room thermostat or a VRC weather compensator. If you are using a non-eBUS-compatible Vaillant gas­fired wall-hung boiler or a third-party boiler, you can use a Vaillant VRT30 room thermostat or one of the room thermostats commonly available on the market.
Water at a temperature of more than 60 ºC could be delivered to the hot water draw-off points.
> Install a hot water thermostat mixer in
the hot water pipe to provide effective scald protection.
> Set the hot water thermostat mixer to
less than 60 ºC and check the tempera­ture at a hot water draw-off point.
10 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 11
4 Description of the components
4.1 auroSTOR solar cylinder
26
25
Description of the components 4
1
2 3
21
22
24
23
20
3
4
2
5
1
18
19
3
17
16
15
14
13
12
11
Fig. 4.1 auroSTOR solar cylinder function elements
10
4
67
5
9
8
Key
1 Hot water draw off 2 Expansion relief valve (6.0 bar) 3 Pressure reducing valve (3.5 bar) with line strainer 4 Cold water inlet 5 Pressure-controlled cold water inlet 6 Connection for hot water expansion vessel 7 Cylinder connection 8 Hot water expansion vessel 9 Tundish 10 Cylinder drain valve 11 Solar return 12 Solar yield temperature sensor (Ertrag) 13 Cold water inlet 14 Solar circuit thermal cut-out (TCO), set to 80ºC, to be con-
nected with the solar pump in order to isolate this heat source
if there is a fault in the solar control.
15 Solar circuit cylinder dry pocket (SP2) 16 Solar flow 17 2-pole isolating switch for electric immersion heater 18 Electric immersion heater with thermostat and thermal cut-out 19 Return (gas-fired wall-hung boiler) 20 Primary heating circuit cylinder dry pocket (SP1) 21 Primary heating circuit thermal cut-out, set to 80ºC, to be con-
nected to the two port motorised valve in order to isolate the
primary heat source if a fault occurs. 22 Cylinder thermostat (20 °C to 65 °C) 23 Two port motorised valve 24 Flow line (gas-fired wall-hung boiler) 25 Secondary return 26 Temperature and pressure relief valve (90 °C, 7 bar)
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 11
Page 12
4 Description of the components
The auroSTOR solar cylinder is available in three sizes: 210, 260, and 310 litres. The cylinder is made from stain­less steel and is insulated with EPS with heat radiation absorbers. The cylinder is supplied along with all required cold and hot water control devices and a two port motorised valve. The cylinder works with the pressure of the water supply line and does not need a cold water tank for its supply. The cylinder has hot and cold water inlets with a diame­ter of 22 mm. To enable the cylinder to work as well as possible, a cold water supply with a dynamic pressure and flow rate that are appropriate for the system is required (¬ section 6.6.1).
4.1.1 Safety devices
The cylinder is delivered with all safety and control devices for the operation of the unvented domestic hot water supply system:
– Temperature and pressure relief valve (90 °C, 7 bar) – Pressure reducing valve (3.5 bar) with line strainer – Expansion relief valve (one-way valve, 6.0 bar) – Solar circuit thermal cut-out, set to 80 ºC, to be connec-
ted with the solar pump in order to isolate this heat
source if there is a fault in the solar control. – Thermal cut-out for electric immersion heater – Primary heating circuit thermal cut-out, set to 80 ºC, to
be connected to the two port motorised valve in order to
isolate the primary heat source if a cylinder thermostat
fault occurs.
The thermal cut-out and other safety devices must always be used.
4.1.2 Cylinder operating elements
8
3
4
5
6
5
Fig. 4.2 Cylinder operating elements
Key
1 Cover cap for reset button for primary heating circuit TCO 2 Primary heating circuit temperature controller 3 Electric immersion heater cover 4 Cover cap for reset button for solar circuit TCO 5 Solar circuit thermal cut-out (TCO) 6 Electric immersion heater 7 Cylinder thermostat 8 Primary heating circuit thermal cut-out
7
2
1
1
2
3
4
The following are pre-mounted at the factory for the auroSTOR solar cylinder:
– Cylinder thermostat (7) and primary heating circuit ther-
mal cut-out (8)
– Electric immersion heater(6) with thermal cut-out and
cylinder thermostat
– Solar circuit thermal cut-out (5)
The cylinder must be properly wired in order to comply with G3 building regulations.
12 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 13
Description of the components 4
Electric immersion heater
1
1
3
2
3
2
3
4
3
Fig. 4.4 Electric immersion heater operating elements
3
4
5
2
3
1
Fig. 4.3 Connection diagram for solar pump
Key
1 Solar controller or solar module 2 Terminal strip for series circuit to solar pump via TCO solar
circuit
3 Solar pump 4 Solar circuit thermal cut-out
You must connect the solar pump to the solar
controller via the solar circuit thermal cut-out
i
(5) (¬section 6.8). The thermostat switches the solar pump off if the hot water temperature in the cylinder exceeds 80 ºC. Set the maximum cylinder temperature (MAXT 1) to 75 °C (factory setting) on the auroMATIC VRS 560 solar controller.
Key
1 Electric immersion heater temperature controller 2 Electric immersion heater TCO reset button 3 Electric immersion heater
The cylinder is equipped with an additional electric immersion heater (3) with a heating output of 3 kW. The electric immersion heater is located behind the top front cladding. The electric immersion heater is designed for use in unvented cylinders and has a thermostat with a temperature controller (1) and a thermal cut-out (TCO) with a reset button (2).
If you need to make a replacement, you must
use the correct electric immersion heater with a
i
thermal cut-out for overheating protection. The seal of the electric immersion heater must also always be replaced. Use only original replace­ment parts from VaillantLtd.
Setting the hot water temperature
You can set the hot water temperature by pointing the arrow on the temperature controller (1) of the electric immersion heater to a number between 1 and 5. The fol­lowing table contains the approximate hot water temper­ature for each of the five settings.
Setting Hot water temperature
1 20 °C 2 35 °C 3 45 °C 4 60 °C 5 68 °C
Table 4.1 Setting the hot water temperature
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 13
Page 14
4 Description of the components
4.2 Solar fluid
4.2.1 Properties of solar fluid
This information applies to Vaillant solar fluid (20l canister: article number 302498 and 10l canister: article number 302363). Vaillant solar fluid is a ready-mixed frost and corrosion protection agent, consisting of approximately 45% propylene glycol with anti-corrosion inhibitors and 55% water.
Vaillant solar fluid is extremely temperature-resistant and can be used in conjunction with Vaillant tube collec­tors and Vaillant flat collectors. The solar fluid also has a high heat capacity. The inhibitors provide reliable corrosion protection when different types of metal are used (mixed installations).
Caution!
Risk of damaging the collectors and
b
i
other system parts if unsuitable solar fluid is used.
If you mix the solar fluid with water or another liquid, frost and corrosion protec­tion cannot be ensured.
> Never mix the solar fluid with water
or another liquid.
Do not use any other frost protection agents or
inhibitors for the Vaillant solar heating system. Only Vaillant's solar fluid is permitted for use with the system.
4.2.2 Solar circuit frost and corrosion protection system
In order to reliably protect the solar heating system from frost in winter, you must fill the entire system with undiluted Vaillant solar fluid.
Filling the solar heating system with Vaillant
solar fluid provides frost protection up to
i
We recommend the Vaillant refractometer for quick and simple checking. A classic Vaillant frost protection tester can be used for this. See the enclosed operating instructions.
4.2.3 Cylinder frost protection
If you want to put a cylinder out of operation where it may be at risk from frost, you must drain it completely. It is drained at the cold water inlet with a T-piece with tap to be provided by the installer. Any heat exchangers not filled with solar fluid in rooms which are at risk of frost must also be completely drained.
approx. -28 ºC. Even at outside temperatures of lower than
-28 ºC, frost damage does not occur straight away since the explosive effect of the water is distributed. Check the frost protection effect after filling the system and then once every year.
Vaillant solar fluid is infinitely durable in hermetically sealed containers. It is not dangerous if it comes into contact with the skin. Eye contact only causes minor irritations, you should nevertheless immediately wash your eyes. Pay attention to the safety data sheet (¬section 4.2.4).
14 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 15
Description of the components 4
4.2.4 Safety data sheet for Vaillant solar fluid
1) Name of substance/preparation and company details:
1a) Trade name:
Vaillant ready-mixed solar fluid
1b) Use:
Heat transfer fluid for solar heating systems
1c) Company:
Vaillant GmbH Berghauser Str. 40 42859 Remscheid, Germany Tel. 0049 (0) 2191 18-0, Fax 0049 (0) 2191 18-2810
1d) Emergency information:
your local poison information centre (see directory assistance or telephone directory).
2) Possible dangers:
2a) Special danger indications for people and the
environment: Not required!
3) Composition/information on ingredients:
3a) Chemical nature:
Aqueous solution of 1.2-propylene glycol (CAS no.: 57-55-6) with corrosion inhibitors.
3b) Hazardous ingredients:
1,1’-iminodipropan-2-ol content (w/w): > 1 % - < 3 %, CAS no.: 110-97-4 EC no.: 203-820-9, hazard symbol: Xi INDEX no: 603-083-00-7, R phrases: 36
If hazardous ingredients are named, the wording for
the hazard symbols and R phrases will be provided in Point 16.
4) First aid measures:
4a) General information:
Remove dirty clothes.
4b) After inhalation:
Discomfort after inhaling fumes/aerosol: fresh air, help from a doctor.
4c) After skin contact:
Wash off with water and soap.
4d) After contact with the eyes:
Thoroughly rinse out with running water for at least 15 minutes with the eyes open.
4e) After swallowing:
Rinse mouth and drink lots of water.
4f) Information for the doctor:
Treatment of symptoms (decontamination, vital function), no specific antidote known.
5) Firefighting measures:
5a) The product is not flammable. Surrounding fire can be
combated with sprayed water, dry extinguishers, alco­hol-resistant foam, and carbon dioxide (CO
5b) Special dangers: Fumes which are detrimental to
health. Formation of smoke/mist. The specified subs­tances/substance groups may be released in the event of a fire.
5c) Special protection equipment: Wear a breathing appa-
ratus which is independent of the circulating air in the event of a fire.
5d) Further information: The dangers depend on the bur-
ning substances and the fire conditions. Polluted fire water must be disposed of according to local official regulations.
6) Measures in the case of accidental release:
6a) Precautions to protect persons:
No particular measures required.
6b) Measures to protect the environment:
Contaminated water/fire water must be withheld. It must not be discharged into bodies of water without being pre-treated first (in a biological waste water treatment plant).
6c) Cleaning/collection procedure:
Contain any escaped material and cover with large quantities of sand, soil, or another absorbing material; then sweep enthusiastically to promote absorption. Fill the mixture into containers or plastic bags and take away for disposal.
Wash away small amounts (splashes) with large quan-
tities of water. For large quantities, pump out the pro­duct, collect it up and take it away for disposal. If lar­ger quantities may have entered the drainage system or water bodies, contact the responsible water autho­rities.
7) Handling and storage:
7a) Handling:
No particular measures required.
7b) Fire and explosion protection:
No particular measures required.
7c) Storage:
Containers must be closed so that they are airtight and stored in a dry location. Galvanised storage containers must not be used.
).
2
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 15
Page 16
4 Description of the components
8) Exposure prevention and personal protective equip­ment:
8a) Personal protective equipment:
Breathing protection: Breathing protection if vapours/aerosols are released. Hand protection: chemical-resistant protective gloves (EN 374). Recommended: Nitrile rubber (NBR), protection class
6. Owing to the large variety of types, observe the manufacturers' operating instructions. Eye protection: Safety glasses with lateral protection (framed glasses) (EN 166)
8b) General protection and hygiene measures:
The usual precautions for working with chemicals must be observed.
9) Physical and chemical properties:
Form: Liquid. Colour: Fluorescent red. Smell: Product-specific. Freezing point: Approx. -25 ºC (ASTM D 1177) Solidification point: Approx. -31 ºC (DIN 51583) Boiling point: >100 ºC (ASTM D 1120) Flashpoint: N/A Lower explosion limit: 2.6 vol% (propylene glycol) Upper explosion limit: 12.6 vol% (propylene glycol) Ignition temperature: N/A Vapour pressure (20° C): 20 mbar Density (20 ºC): Approx. 1,030 g/cm
3
(DIN 51757) Solubility in water: Completely soluble Solubility in other solvents: Soluble in polar
solvents
pH value (20 ºC): 9.0 - 10.5 (ASTM D 1287)
2
Viscosity (kinematic at 20 ºC): Approx. 5.0 mm
/s (DIN
51562)
10) Stability and reactivity:
10a) Substances to be avoided:
Strong oxidants
10b) Hazardous reactions:
No dangerous reactions if the storage and handling regulations/notes are observed
10c) Hazardous decomposition products:
No dangerous decomposition products if the storage and handling regulations/notes are observed.
11) Toxicology information:
LD50/oral/rat: > 2000 mg/kg
Primary skin irritation (rabbits): Non-irritant (OECD Directive 404). Primary mucous membrane irritation (rabbits): Non-irritant (OECD Directive 405).
11a) Additional information:
The product has not been checked. The statements are derived from the properties of the individual com­ponents.
12) Ecology information:
12a) Ecotoxicity:
Fish toxicity: Leuciscus idus/LC50 (96 h): > 100 mg/l Aquatic invertebrates: EC50 (48 h): > 100 mg/l Aquatic plants: EC50 (72 h): > 100 mg/l Micro-organisms/effect on activated sludge: DEV-L2 > 1000 mg/l. If low concentrations are pro­perly introduced into adapted biological waste water treatment plants, no disturbances of the degradation activity of activated sludge are to be expected.
12b) Assessment of aquatic toxicity:
The product has not been checked. The statements are derived from the properties of the individual com­ponents.
12c) Persistence and degradability:
Details regarding elimination: OECD 301A test method (new version) Analysis method: DOC acceptance Degree of elimination: > 70 % Assessment: easily biodegradable.
13) Information on disposal:
13a) Disposal:
When disposing of the fluid, you must observe all local regulations, e.g. take the waste to a suitable dump or incinerator. For quantities of less than 100 l, contact the local city cleaning department or mobile environmental service.
13b) Contaminated packaging:
Uncontaminated packaging can be reused. Packaging that cannot be cleaned must be disposed of in the same way as the material.
14) Information on transport:
Not dangerous goods in terms of the transport
regulations. (ADR RID ADNR IMDG/GGV, see ICAO/IATA)
15) Legislation:
15a) European Union legislation (labelling)/national
regulations: EU Directive 1999/45/EC (Dangerous Preparations Directive): No labelling obligation
15b) Other legislation:
Water hazard class 1: Low hazard to water (Germany, VwVwS of 17.05.1999).
16 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 17
Description of the components 4
16) Other information
Complete wording for hazard symbols and R phrases
if stated in "Hazardous ingredients" in section 3: Xi: Irritant. R36: Irritates the eyes. All information which has been changed since the last edition is identified by means of a vertical slash on the left-hand side of the passage in question. In such cases, the information shown in older editions loses its validity. The safety data sheet is intended to communicate the most important physical, safety-related, toxicological, and ecological information to be observed when wor­king with chemicals and preparations and to provide recommendations for safe use and/or storage, hand­ling, and transport. No liability is assumed for damage in connection with the usage of this information or the usage, application, adaptation or processing of the products described here. This does not apply as long as we, our statutory agents or assistants are liable in the event of intention or gross negligence. No liability is assu­med for indirect damage.
This information has been compiled to the best of our
knowledge and conscience according to our current state of knowledge. No guarantee can be made for product properties.
17) Valid as of: 01.01.2009 Created by: Vaillant GmbH.
4.3.1 Vaillant controllers and their basic functions
VRS560/2 solar controller
The auroMATIC 560/2 solar controller is a differential temperature-controlled control set for solar-aided hot water production with demand-controlled primary heat­ing for Vaillant gas-fired wall-hung boilers. The control set is a fully equipped system for solar heat­ing systems with a collector array and cylinder. If a solar yield temperature sensor (VR 10, supplied with controller) is connected, the solar yield can be recorded.
Control Centre
A Vaillant Control Centre provides a system solution which allows the Vaillant dual-channel eBUS controller (low-voltage) to be used in the English market with valves and domestic hot water cylinders with conven­tional 230 V cylinder thermostats. The Control Centre sends the information on the heat requirement of the cylinder to the Vaillant ecoTEC gas­fired wall-hung boiler. The gas-fired wall-hung boiler decides whether a hot water requirement needs to be met and sends a signal to control the 230 V valves via the Control Centre. The gas-fired wall-hung boiler can thus hold different set temperature values for heating mode and for hot water handling. A Control Centre can be used to integrate commonly available 230 V S plan or Y plan components into the Vaillant eBUS system.
4.3 System configuration
The Vaillant solar heating system enables various sys­tem configurations and control types in accordance with the connection wiring diagrams 1 to 6 (¬section 6.8).
Single-channel eBUS controllers are not suitable
for this system configuration.
i
Wiring
If you use an eBUS-compatible Vaillant gas-fired wall­hung boiler, you can use one of the Vaillant Control Cen­tres to wire the system. For all other gas-fired wall-hung boilers, you can use a standard cabling box.
VRC weather compensator (VRC430, VRC430f, VRC470, VRC470f)
A VRC controller controls the solar heating system in a weather-compensated and time-dependent manner with or without hot water production/a circulation pump in conjunction with a Vaillant gas-fired wall-hung boiler with an eBUS interface and the Vaillant VR68/2 solar module.
Solar module VR 68/2
The VR68/2 solar module integrates a solar heating sys­tem into the control concept of a VRC controller. In con­junction with a VRC controller , various solar heating system configurations can be implemented and the solar yield recorded. You can combine the VR68/2 solar mod­ule with a VR61/2 mixer module in a solar heating sys­tem.
VR 61/2 mixer module
The VR61/2 mixer module is a system component which controls a cylinder charging circuit or circulation pump in conjunction with a VRC controller. You can use the VR 61/2 mixer module to control a solar heating system for the heating of potable water in conjunc­tion with a VRC controller and the VR68/2 solar module.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 17
Page 18
4 Description of the components
4.3.2 Control functions
Hot water temperature control
The hot water temperature in the top half of the cylinder can be controlled in one of the following ways:
– Vaillant auroMATIC VRS 560/2 solar controller or – using one of the Vaillant Control Centre‘s with the Vail-
lant dual-channel eBUS controller
– Vaillant VRC weather compensator with VR 61/2 mixer
module and VR68/2 solar module or
– using the cylinder thermostat in conjunction with a timer.
If you are using a controller by a third-party manufac­turer, you use this controller to adjust the hot water temperature. In this case, the Vaillant controller (e.g. auroMATIC 560/2) acts only as a solar controller and only controls the temperatures for solar water heating.
Solar circuit control system
The solar circuit can be controlled in one of the follow­ing ways:
VRS560/2 (connection wiring diagrams 1, 2, 3, 4, and 6, ¬section6.8)
The lower cylinder sensor (SP 2) and the solar yield temperature sensor are connected up to the VRS 560/2. The solar pump is controlled via the VRS560/2.
VRC with VR 68/2 (connection wiring diagram 5, ¬ section 6.8)
The lower cylinder sensor (SP 2) and the solar yield temperature sensor are connected up to the VR68/2. The solar pump is controlled via a VRC.
Kol 1
230 V~
7
6
C
D
Fig. 4.5 Temperature differential control of solar pump
Key
1 Solar controller or solar module 2 Gas-fired wall-hung boiler 3 Solar cylinder 4 Solar circuit thermal cut-out 5 Solar yield temperature sensor 6 Solar pump 7 Solar pump unit Kol 1 Collector sensor for flow line collector temperature SP1 Cylinder sensor for upper cylinder temperature
(primary heating circuit/standby section) SP2 Cylinder sensor for lower cylinder temperature (solar circuit) A Primary heater flow B Primary heater return C Solar flow D Solar return
5
3
SP 1
4
SP 2
A
1
2
B
Temperature differences, not absolute temperature val­ues, are important for the operation of solar heating systems. For this reason, solar heating systems are con­trolled via temperature differential controllers. Integrated temperature sensors record the temperature difference between the collector and the cylinder. If the temperature difference (Kol 1–SP2) is larger than 7K, the solar heating system's solar pump is switched on. If the temperature difference (Kol 1–SP2) is smaller than 3K, the solar heating system's solar pump is switched off.
18 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 19
Description of the components 4
Primary heating circuit control system
The primary heating circuit can be controlled in one of the following ways:
Vaillant dual-channel eBUS controller with Vaillant Control Centre (connection wiring diagrams 1 and 2, ¬section 6.8)
Important:
Terminals NTC and CYL. of the Vaillant Control Centre may not be connected at the same time.
– Option 1: The upper cylinder sensor NTC is connected to
terminal NTC of the Vaillant Control Centre.
The recharging of the cylinder is controlled via the eBUS controller. Here, the cylinder temperature is measured using the cylinder sensor NTC. The temperature is com­pared with the target value programmed in the eBUS controller and the cylinder is reheated if necessary.
– Option 2: The cylinder thermostat is connected
up to terminal CYL. of the Vaillant Control Centre.
The recharging of the cylinder is triggered via the cylin­der thermostat. If the actual value falls below the target temperature set on the cylinder thermostat, the cylinder thermostat is shut. The closing of the cylinder thermo­stat is registered by the Vaillant Control Centre and passed onto the eBUS controller. The eBUS controller releases the recharging of the cylinder for the programmed primary heating times: The primary heating device activates and the Vaillant Control Centre switches the zone valves into the correct position for the recharging of the cylinder. The required zone valve position differs depending on whether the S plan is being used:
– S plan: Valve CH closed, valve DHW open.
VRS560/2 (connection wiring diagrams 3 and 4, ¬section6.8)
The upper cylinder sensor is connected to the terminal SP1 of the VRS560/2. The output EP of the VRS 560/2 is connected to the input CYL. of the Vaillant Control Centre. The recharging of the cylinder is controlled via the VRS 560/2. Here, the sensor SP1 measures the cylinder temperature. The temperature is compared with the pro­grammed target value in the VRS560/2. Within the primary heating times programmed in the VRS560/2, the contact EP is closed if the actual value falls below the target temperature for the cylinder. The closing of the contact EP is registered by the Vaillant Control Centre and the recharging of the cylin­der is triggered: The primary heating device activates and the Vaillant Control Centre switches the zone valves into the correct position for the recharging of the cylin­der. The required zone valve position differs depending on whether the S plan is being used:
– S plan: Valve CH closed, valve DHW open.
Vaillant dual-channel eBUS controller with VR68/2 (connection wiring diagram 5, ¬section 6.8)
The upper cylinder sensor is connected to the terminal SP1 of the VR68/2. The recharging of the cylinder is controlled via the eBUS controller, which is connected with the VR68/2 and VR61/2 via eBUS. The zone valves are switched via the VR61/2 (valve DHW open, heating circuit valve closed).
VRS560/2 in conjunction with non-eBUS-compatible controllers (connection wiring diagram 6, ¬section6.8)
The upper cylinder sensor is connected to the terminal SP1 of the VRS560/2. The output EP of the VRS560/2 is connected to the wiring of the S plan via the cylinder thermostat. Important: The target temperature on the cylinder thermostat must be set to the maximum temperature!
The recharging of the cylinder is controlled via the VRS 560/2. Here, the sensor SP1 measures the cylinder temperature. The temperature is compared with the pro­grammed target value in the VRS560/2. Within the primary heating times programmed in the VRS560/2, the contact EP is closed if the actual value falls below the target temperature for the cylinder. The switching signal is coupled into an S plan and the recharging of the cylinder is triggered.
Room heating control
The room heating can be controlled in one of the follow­ing ways:
Vaillant dual-channel eBUS controller with Vaillant Control Centre (connection wiring diagrams 1, 2, 3, and 4, ¬section 6.8)
The room heating is controlled by the Vaillant eBUS controller. The actuation of the valves (S plan plan) is controlled by the Vaillant Control Centre.
Vaillant dual-channel eBUS controller with VR61/2 (connection wiring diagram 5, ¬section 6.8)
The room heating is controlled by the Vaillant eBUS controller. The actuation of the valves (S plan plan) is controlled by the VR61/2.
Programmable timer and room thermostat (connection wiring diagram 6, ¬section6.8)
The room heating is controlled using a programmable timer and a room thermostat. The actuation of the valves (S plan) is realised via the programmable timer and DHW timer.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 19
Page 20
4 Description of the components
4.3.3 Technical data of the auroSTOR solar cylinder
Unit VIH S GB 210/2 S VIH S GB 260/2 S VIH S GB 310/2 S
Total capacity litres 210 260 310 Actual capacity litres 209,4 254,4 297,2 Hot water capacity (upper coil) litres 104,8 142,0 144,2 Hot water capacity (solar coil) litres 203,3 246,1 271,1 Dedicated solar volume litres 104,6 112,4 153,0 Maximum supply pressure to pressure reducing valve MPA (bar) 1,2 (12) Rated pressure of cylinder MPA (bar) 0,7 (7) Maximum operating pressure of heating coil MPA (bar) 0,35 (3,5) Maximum operating pressure of solar coil MPA (bar) 0,6 (6) Operating pressure MPA (bar) 0,35 (3,5) Pressure limiting valve MPA (bar) 0,35 (3,5) Expansion relief valve MPA (bar) 0,6 (6) Temperature and pressure relief valve °C,
Charge pressure of hot water expansion vessel MPA (bar) 0,4 (4) Maximum temperature of heating circuit °C 85 Maximum temperature of potable hot water °C 85 Maximum temperature of solar fluid °C 85 Standing heat loss kW/24 h 1,98 2,15 2,35 Heat up time according to EN 12897 mins 20 27 28 Recovery time (70% capacity) mins 15 20 21 Primary heat exchanger performance kW 16,7 16,5 16,0 Flow rate for primary heat exchanger performance l/min 23,3 Primary heat exchanger pressure drop mbar 79 78 79 Primary heat exchanger volume Liter 2,37 Primary heat exchanger surface area m Heat up time according to EN 12897 (solar) min 32 40 49 Solar heat exchanger performance kW 19,7 19,5 17,2 Flow rate for solar heat exchanger output l/min 23,3 Solar heat exchanger pressure drop mbar 97 95 98 Solar heat exchanger volume Liter 2,94 Solar heat exchanger surface area m
Dimensions
Height mm 1593 1843 2153 Height with hot water draw off mm 1625 1875 2185 Topple measure mm 1680 1918 2217 Diameter mm 554,5 Depth mm 633 Net weight kg 40 43 50 Weight (full) kg 249 298 347
Connections
Cold water inlet 22 mm unprofiled pipe (crimp joints) Hot water draw off 22 mm unprofiled pipe (crimp joints) Balanced pressure cold water outlet 22 mm unprofiled pipe (crimp joints) Secondary return 15 mm unprofiled pipe (crimp joints) Primary heater flow 22 mm unprofiled pipe (crimp joints) Primary heater return 22 mm unprofiled pipe (crimp joints) Solar flow 22 mm unprofiled pipe (crimp joints) Solar return 22 mm unprofiled pipe (crimp joints) Primary heating circuit cylinder dry pocket size mm 8 Solar circuit cylinder dry pocket size mm 8
MPA (bar)
2
2
90,
0,7 (7)
0,5
0,62
Tab. 4.2 Technical data for auroSTOR solar cylinder
20 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 21
Description of the components 4
Unit VIH S GB 210/2 S VIH S GB 260/2 S VIH S GB 310/2 S
Electrical connections
Immersion heater (according to EN BS 60335) 2.7 kW, 230 V, 50 Hz Length of immersion heater inch 14 Two port motorised valve 230/240 V, 50 Hz Cylinder thermostat 230/240 V, 50 Hz Thermal cut-out solar 230/240 V, 50 Hz
Material data
Cylinder body material Stainless steel (1.4521) Cylinder jacket material Polypropylene Insulation material EPS with infrared absorber Insulation thickness mm 50 Corrosion protection Stainless steel Blowing agent for insulation material Pentane (GWP < 5) ODP 0
Tab. 4.2 Technical data for auroSTOR solar cylinder (continued)
The heat up time is based on a flow rate
of 1400l/h at 80 ºC.
i
Temperature rise from 15 ºC to 60 ºC.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 21
Page 22
4 Description of the components
4.3.4 Dimensions
a
b
c
d
1
2
3
4
5
6
7
8
9
10
11
e
f
g
h
633
Ø 554,5
i
j
k
l
Fig. 4.6 Dimensions of the auroSTOR solar cylinder
Key
1 Hot water draw off 2 Temperature and pressure relief valve connection 3 Secondary return 4 Primary heater flow 5 Primary heating circuit cylinder dry pocket (SP 1)
Unit type a b c d e f g h i j k l
VIH S GB 210/2 S 1625 1593 1341 1158 1052 912 822 802 534 506 259 51 VIH S GB 260/2 S 1875 1843 1591 1346 1102 962 872 852 534 506 259 51 VIH S GB 310/2 S 2185 2153 1901 1578 1377 1237 1147 1127 534 506 259 51
Tab. 4.3 Dimensions
6 Primary heater return 7 Electric immersion heater 8 Solar flow 9 Solar circuit cylinder dry pocket (SP 2) 10 Cold mains inlet connection 11 Solar return
25°
45°
22 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 23
Assembly 5
5 Assembly
5.1 Scope of delivery
8
7
6
5
4
3
Fig. 5.1 Scope of delivery
Item Quantity Component
11
22
In separate packaging:
31
4 1 Two port motorised valve 5 1 15mm compression cap for secondary return 6 1 Tundish 7 1 Assembly set for hot water expansion vessel
81
Table 5.1 Scope of delivery
Domestic hot water cylinder with insulation in separate packaging
Instructions on commissioning, maintenance, and troubleshooting and operating instruc­tions (packaged with the cylinder)
Safety assembly (pressure reducing valve, expansion relief valve, connections for pres­sure-controlled cold water inlet and hot water expansion vessel)
Hot water expansion vessel: 12 l for VIH GB 120/2 S and VIH GB 155/2 S 18 l for VIH GB 180/2 S and VIH GB 210/2 S 25 l for VIH GB 260/2 S and VIH GB 310/2 S
5.2 Transporting the cylinder
Danger!
Risk of injury due to heavy load!
a
Heavy load can cause injuries.
> At least two people should lift the cylin-
der to prevent injuries.
> Use a suitable transportation aid
(sack truck or similar).
1
> Transport the packaged cylinder to the installation site. > Only remove the cylinder from its packaging once
it reaches the installation site.
5.3 Requirements for installation site
Position the domestic hot water cylinder as near as possible to the heater to prevent unnecessary heat loss.
2
Place the cylinder in a suitable location in the building, paying attention to the following:
– The tundish discharge pipe must be installed with a mini-
mum slope of 1:200 and must end in a safe and visible
place (¬section6.7).
– The installation surface must be flat and capable
of bearing the weight of the entire cylinder
(¬section5.3).
– The installation site must not be at risk of frost.
If necessary, install a frost protection thermostat.
– The control system for the installed cylinder thermostat
beneath the front plate must be easily accessible to the
operator.
– There must be sufficient space for the assembly, check,
and pressure build-up of the expansion vessel.
– There must be sufficient space for mounting, maintai-
ning and replacing the electric immersion heater.
– The floor must be even.
> Choose a cylinder installation site that allows the potable
water and heating lines to be laid in an appropriate man-
ner.
> To prevent energy losses in accordance with the Heating
Equipment Ordinance, provide all system pipes with ther-
mal insulation.
> Check the scope of delivery for completeness. > Make sure the cylinder is stored in an upright position in
a dry environment prior to its installation.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 23
Page 24
6 Installation
6 Installation
6.1 Installation sequence
Install the solar heating system in the following order:
– Solar collectors and solar pump unit – Cylinder – Solar circuit piping – Primary heating circuit piping – Hot water piping, with secondary circulation line if requi-
red – Cold water piping – Discharge pipes – Electrical installation
> Assemble the collectors in accordance with the assembly
instructions supplied with the collector assembly set.
> Install the solar pump unit in accordance with the instal-
lation instructions supplied with the solar pump unit.
> For the rest of the installation process, proceed
as described in the sections below.
6.2 Installation of solar circuit piping
6.2.1 Piping material in the solar circuit
All Vaillant solar sets are supplied with pipes made from stainless steel with DN fittings.
Caution!
Risk of damage to the system if the
b
wrong piping material is used in the solar circuit!
The solar fluid can reach high temperatures and leaks can occur if the wrong piping material is used (e.g. PE pipes and Teflon band).
> You should preferably use copper pipes
in the solar circuit.
> Use brazing solder to solder the piping
in the solar circuit.
> Only use press fittings if the manufactu-
rer has stated that they can be used up to a temperature of 200 ºC.
6.2.2 Layout of piping in the solar circuit
The correct choice of pipe diameter is vital to ensure the optimum efficiency of the solar heating system. To keep the pressure loss in the solar circuit as low as possible, the flow velocity in the pipe must not be more than 1.5m/s. At the same time, the flow velocity must be at least
0.4 m/s to transport air bubbles from the collectors downwards to the air vents (¬ section 6.2.4). A nominal flow rate of 0.66 l/min is required for the flat collectors and a nominal flow rate of 0.4 l/min per m net collector area is required for the vacuum tube collec­tors in order to achieve optimum heat transfer (¬ table
6.1 and 6.2). A further decisive factor to ensure that your solar heat­ing system works as well as possible is the correct solar pump design. It must be possible for the solar pump to convey more than the nominal flow rate at the specified operating pressure. The selection of the required pump speed depends on the installed system. For a reference value for the selection of a solar pump, see section 7.4.
2
of
24 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 25
6.2.3 Realisation of solar circuit piping
Danger!
Risk of death from electric shock!
a
b
Incorrect installation or a faulty power cable can result in a supply voltage on the pipes, which can cause personal injury.
> Attach earthing pipe clamps to the pipes
and connect the earthing pipe clamps to a potential equalisation bar using 16 mm cable.
Caution!
Risk of damage to electronics resulting from lightning strikes!
Without potential equalisation, lightning can destroy the electronics in the solar heating system, heating system, or building.
> Earth the solar circuit in accordance with
the requirements of "BS7671 IEE Wiring Regulations". Attach earthing pipe clamps to the solar circuit pipes, for instance, and connect the earthing pipe clamps to a potential equalisation bar using 16 mm
> Connect the collectors to an existing buil-
ding lightning protection system.
2
cable.
Installation 6
2
Caution!
Risk of damage to the collectors due
b
Observe the following points to ensure perfect operation with maximum energy utilisation:
> Ensure that the piping diameter is not too large, since
this could result in low flow velocities in the solar hea-
ting system; this makes the system less efficient.
> Design all system components to ensure an even flow
rate with the required nominal flow rate.
> Ensure sufficient heat protection for the pipes so that
not too much heat energy is lost before it reaches the
consumers. For pipes laid outside, choose weather- and
UV-resistant insulation and insulation which is resistant
to the pecking of birds.
> Vent the system completely for commissioning and main-
tenance, since air in the system significantly impairs its
efficiency.
to excessive pressure.
The safety devices in the solar circuit can be knocked out of operation if you install a two port motorised valve in the pipes of the solar heating system.
> Never install a two port motorised valve
in the pipes of the solar heating system.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 25
Page 26
6 Installation
Nominal flow rate and pipe diameter in the solar circuit
Flat collectors auroTHERM plus VFK 150 H/V, auroTHERMVFK 145 H/V
Quan­tity Qty. in m
Net area Configuration
2
Row x collector quantity for connection: On one side Opposite sides l/h l/min
1 2,35 1 x 1 1 x 1 180 3 15 x 1 15 x 1 2 4,7 1 x 2 1 x 2 180 3 15 x 1 15 x 1 3 7,05 1 x 3 1 x 3 180 3 15 x 1 15 x 1 4 9,4 1 x 4 1 x 4 / 2 x 2 180 3 15 x 1 18 x 1 5 11,75 1 x 5 1 x 5 180 3 18 x 1 18 x 1 6 14,1 3 x 2 * / 2 x 3 * 1 x 6 / 3 x 2 * / 2 x 3 * 212 3,6 18 x 1 18 x 1 7 16,45 1 x 7 247 4,2 18 x 1 18 x 1 8 18,8 2 x 4 * / 4 x 2 * 2 x 4 / 4 x 2 / 1 x 8 282 4,7 18 x 1 22 x 1 9 21,15 1 x 9 318 5,3 22 x 1 22 x 1 10 23,5 2 x 5 * / 5 x 2 * 1 x 10 / 2 x 5 / 5 x 2 353 5,9 22 x 1 22 x 1 11 25,8 1 x 11 387 6,5 22 x 1 22 x 1 12 28,2 1 x 12 / 2 x 6 / 3 x 4 / 4 x 3 423 7,1 22 x 1 22 x 1 20 47 4 x 5 / 5 x 4 705 11,8 22 x 1 28 x 1.5 24 56,4 2 x 12 / 4 x 6 / 6 x 4 etc. 846 14,1 28 x 1.5 28 x 1.5 32 75,2 4 x 8 etc. 1128 18,8 28 x 1.5 28 x 1.5 * Only with parallel array connection
** At least 15l/m
2
h in collector array or 3l/min. in the solar circuit; in the case of larger systems,
the flow rate in the collector array must be below 30 l/m2 h.
Tab. 6.1 Nominal flow rate in relation to collector quantity,
pipe diameter, and pipe length
Nominal flow rate ** Recommended diameter for
copper piping and a total pipe length of: 20 m 50 m
Nominal flow rate and pipe diameter in the solar circuit
Parallel collector arrays
Tube collectors Net area VTK 570/2 VTK 1140/2
in m
2
Qty. in l/h in l/min 20 m 50 m
VTK 1140/2 or 570/2 and 1140/2 in series
Recommended nominal flow rate
Minimum diameter for copper piping and a total pipe length of:
1 collector array 2 - 2 2 x 1 180 3 12 x 1 15 x 1
2 - 2 3 x 1 180 3 12 x 1 15 x 1
- 2 4 1 x 2 180 3 12 x 1 15 x 1 1 2 5 1x (1 + 2) 180 3 12 x 1 15 x 1
- 3 6 1 x 3 180 3 12 x 1 15 x 1 1 3 7 1 x (1 + 3) 210 3,5 15 x 1 15 x 1
- 4 8 1 x 4 210 3,5 15 x 1 15 x 1 1 4 9 1 x (1 + 4) 210 3,5 15 x 1 15 x 1
- 5 10 1 x 5 210 3,5 15 x 1 15 x 1 1 5 11 1 x (1 + 5) 240 4 18 x 1 18 x 1
- 6 12 1 x 6 240 4 18 x 1 18 x 1 1 6 13 1 x (1 + 6) 240 4 18 x 1 18 x 1
- 7 14 1 x 7 240 4 18 x 1 18 x 1
2 parallel collec­tor arrays
2 6 14 2 x (1 + 3) 300 5 18 x 1 18 x 1
- 8 16 2 x 4 300 5 18 x 1 18 x 1 2 8 18 2 x (1 + 4) 360 6 18 x 1 18 x 1
- 10 20 2 x 5 360 6 18 x 1 18 x 1 2 10 22 2 x (1 + 5) 420 7 18 x 1 22 x 1
- 12 24 2 x 6 480 8 22 x 1 22 x 1 2 12 26 2 x (1 + 6) 480 8 22 x 1 22 x 1
- 14 28 2 x 7 480 8 22 x 1 22 x 1
Tab. 6.2 Design of pipe diameter and recommended nominal
flow rate in relation to collector configuration for auroTHERM exclusive VTK 570/2 tube collectors
26 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 27
6.2.4 Venting the solar circuit
Danger!
Risk of burns and scalds resulting from
a
b
escaping hot steam!
Hot steam can discharge from automatic air vents which are not shut off if the sys­tem is in stagnation.
> Use automatic air vents with a
manufacturer's release to at least 150 ºC.
> Shut off the automatic air vents when
operating the system.
Caution!
Malfunction due to air vents that are not shut off!
Vapourous solar fluid can escape from automatic air vents which are not shut off whilst the system is in stagnation. The loss of solar fluid results in functional problems.
> Close all automatic air vents once ven-
ting is complete.
Installation 6
Caution!
Malfunction due to unsuitable air vents!
b
Solar circuit filling with
Hand pump
Motorised filling pump (maximum flow rate of < 10 l/min)
Motorised filling pump (maximum flow rate of > 10 l/min)
Tab. 6.3 Selection of venting method in accordance
Unsuitable air vents can be destroyed in solar mode.
> Only use Vaillant automatic air vents
with a manufacturer's release to at least 150 ºC.
Vent opening
for flat collectors
with filling type
Venting via
or
Absolutely vital
Not necessary Recommended
Automatic air vent
with stop cock
Automatic
air separator system
Alternative
Recommended
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 27
Page 28
6 Installation
Air in the system impairs the efficiency of the solar heating system considerably. For this reason, there must be sufficient venting points in every solar circuit.
> Select one of the following venting methods in relation
to the filling type of the solar circuit as per
Tab. 6.3:
– Only for flat collectors: Venting via the vent opening
(¬Fig.6.1)
– Venting via an air separator system (¬Fig.6.2)
Vent opening (only for flat collectors)
1
2
Fig. 6.1 Plug with vent opening for flat collectors
Key
1 Plug 2 Vent opening
Automatic air separator system
The vent opening enables the venting of the solar circuit during filling and flushing, i.e. during commissioning or maintenance.
> For flat collectors, install a plug with a vent opening at
the highest point.
Whilst the solar heating system is being oper-
ated, the vent opening must be closed to pre-
i
vent the loss of fluid at times of stagnation.
Fig. 6.2 Automatic air separator system
You can use the Vaillant automatic air separator system instead of an automatic air vent. An air separator system vents the solar circuit com­pletely automatically, both during filling and flushing and continuously whilst the solar heating system is being operated.
You must install an air separator system in
an area where no steam will escape, preferably
i
in the return line between the solar pump unit and the solar cylinder.
> Install the Vaillant automatic air separator system in
accordance with the corresponding assembly instruc­tions.
28 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 29
Installation 6
6.3 Pipes for the primary heating circuit
Make sure that the pipes in the primary heating circuit between the gas-fired wall-hung boiler and cylinder are as short as possible. Use copper piping with a minimum diameter of 22mm. A heating pump is installed in all Vaillant gas-fired wall­hung boilers (apart from the ecoMAX pro with open ven­tilation). If you are using the cylinder with another gas­fired wall-hung boiler as per GB standards, you may have to install a suitable heating pump in the primary heating circuit.
Installing the two port motorised valve
1
6.4 Installing hot water pipes
> Connect the hot water piping to the 22 mm hot water
draw off of the cylinder.
> Lay the 22 mm piping up to the first T-piece.
The required diameter of subsequent pipes depends on the system design.
Connecting up the secondary circulation line
The cylinder has a connection with a 15 mm diameter for a secondary circulation line.
> Connect a WRAS-approved circulation pump which has a
non-return valve with the secondary return.
> Establish the connection to the secondary circulation
line.
If a secondary circulation line is used, an addi-
tional expansion vessel may be required in
i i
6.5 Hot water thermostat mixer
some circumstances.
If you are not using the secondary return,
this must be properly closed off with the cap included in delivery.
Fig. 6.3 Two port motorised valve
The two port motorised valve prevents the cylinder from overheating.
> Install the two port motorised valve (1) supplied with the
cylinder in the flow line (A¬Fig.3.1) of the gas-fired
wall-hung boiler.
> Note the direction of flow, which is marked with arrows.
You can install the 2-way motorised valve verti-
cally or horizontally. If you install the 2-way
i
motorised valve horizontally, you must install the valve with the valve head facing upwards (¬ fig. 6.3).
1
A
B
Fig. 6.4 Hot water thermostat mixer
Key
1 Thermostat mixer 2 Non Return Valve A Hot water B Cold water AB Mixed water
In a solar heating system, a hot water thermostat mixer must be installed as scald protection. The hot water thermostat mixer mixes the hot water from the cylinder with cold water to produce water with a maximum tem­perature of between 30 and 60 ºC as required. The hot water thermostat mixer must be provided by the customer.
AB
2
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 29
Page 30
6 Installation
6.5.1 Installing the hot water thermostat mixer (without secondary circulation line)
2
3
1
5
6
Fig. 6.5 Installing the hot water thermostat mixer
(system without secondary circulation line)
Key
1 Non-return valve 2 Hot water thermostat mixer 3 Hot water pipe 4 Cold mains inlet 5 Expansion relief valve 6 Bivalenter solar cylinder
> Install a hot water thermostat mixer (2) in the hot water
pipe (3).
6.5.2 Installing the hot water thermostat mixer (with secondary circulation line)
2
230
1
7
165
4
Fig. 6.6 Installing the hot water thermostat mixer
Key
1 Non-return valve 2 Hot water thermostat mixer 3 Solar controller 4 Hot water pipe 5 Secondary circulation line 6 Circulation pump 7 Contact thermostat 8 Expansion relief valve 9 Cold mains inlet 10 Bivalent solar cylinder
10
(system with secondary circulation line)
3
4
8
9
Where possible, avoid installing a secondary circulation line, since a secondary circulation line results in higher energy consumption. If the installation of a secondary circulation line is required, keep circulation operations to a minimum by only using circulation mode when required for demand and temperature reasons.
> Connect the secondary circulation line(5) to the hot
water pipe(4) via a hot water thermostat mixer(2).
6.5.3 Setting the hot water thermostat mixer
Danger!
Risk of burns and scalds!
a
Water at a temperature of more than 60 ºC can escape from the water draw-off point.
> Set the hot water thermostat mixer to
less than 60 ºC and check the tempera­ture at a hot water draw-off point.
> When commissioning the solar heating system for the
first time, set the hot water thermostat mixer to the required maximum temperature.
This maximum temperature is observed at the hot water draw-off points.
30 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 31
Installation 6
6.6 Installation of cold mains inlet
6.6.1 Pressure in cold mains inlet
The efficiency of an unvented cylinder depends on the available pressure in the cold mains inlet and the flow rate. To obtain optimum cylinder output, there must be a suitable cold mains inlet, i.e. the measured static line pressure must be at least 2.0 bar. A corresponding flow rate of at least 20-25 l/min must be available.
The pressure in the cold mains inlet will be
reduced at times of high consumption. Thus,
i
The cylinder still works satisfactorily with a pressure below 2 bar but the flow rate is reduced. If the pressure is below 1 bar, you should not install an unvented cylin­der. Vaillant Ltd. can provide information on alternative hot water supply systems.
measurements should be taken at such times.
80
60
6.6.2 Mounting the safety assembly
Caution!
Risk of damage to the cylinder as a
b
7
6
5
4
result of excess pressure!
Excess pressure can cause the cylinder to burst.
> Make sure that there is no stop valve ins-
talled between the safety assembly and the cylinder.
1
2
40
Flow rate (l/min)
20
0
1
Fig. 6.7 Maximum flow rate of the cold water assembly based
on the supply pressure
The displayed flow rates apply to installations in which the cold water supply has a dynamic pressure and flow rate appropriate for the system. If the static water pressure is less than 1 bar, contact Vaillant Ltd.
2
Inlet pressure (bar)
3
45
Fig. 6.8 Safety assembly
Key
1 Pressure reducing valve with line strainer 2 Cold water inlet 3 Pressure-controlled cold water inlet 4 Cylinder connection 5 Hot water expansion vessel connection 6 15 mm expansion relief valve connection 7 Expansion relief valve
> During the installation process, position the valves so
that you are able to connect the 15 mm connection (6) of the expansion relief valve (7) with the tundish. Note the direction of flow, which is marked on the safety assembly with arrows.
The safety assembly must be installed horizon-
tally with the expansion relief valve facing
i
b
upwards (¬ Fig. 6.8) in order to prevent the build-up of dirt.
Caution!
Risk of damage to the cylinder as a result of excess pressure!
Excess pressure can cause the cylinder to burst.
> Make sure that the expansion relief valve
outlet is not covered or closed.
3
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 31
Page 32
6 Installation
> Mount the discharge pipe of the expansion relief valve
with a constant slope to the outside. The discharge pipe must finish at a safe and visible point where there is no danger of it freezing up and where it poses no risk of injury to persons.
> Actuate the expansion relief valve regularly to prevent
calcification.
> Connect the cylinder to the cylinder connection (4). > For the pipe from the main stop valve of the building to
the cylinder, use copper piping with a diameter of at least 22 mm to ensure that the cylinder is as efficient as possible. This is particularly important for installations with a pressure-controlled cold water inlet (3).
> Mount the safety assembly in the cold mains inlet
on the cylinder.
> If necessary, establish the connection to the cold water
inlet (3) with pressure compensation of the safety assembly.
> Depending on the fittings used and the type of the draw-
off points, it may be necessary to install a backflow pre­venter in the pressure-controlled cold water inlet.
If you mount the safety assembly above the cyl-
inder, you do not need to drain the cylinder in
i
When the discharge pipes are connected, the expansion relief valve may not be more than 600 mm away from the temperature and pressure relief valve (¬ fig. 6.9).
6.6.3 Mounting the expansion vessel
The Vaillant solar cylinder is delivered with an external expansion vessel (ADG). Connect this expansion vessel to the installed safety assembly as follows:
> Screw the expansion vessel directly to the safety assem-
bly via the provided connection (5) or
> Connect the expansion vessel with the safety assembly
via a copper pipe or suitable hose line. Make sure the expansion vessel is supported sufficiently.
> Use the supplied wall bracket if you want to mount the
expansion vessel to a wall.
order to maintain the safety assembly. Make sure there is sufficient space for maintenance and connection of the discharge pipe of the expansion relief valve.
6.6.4 Mounting the drain valve
> Mount a drain valve as low as possible between the cylin-
der and the safety assembly in the cold mains inlet (10 ¬ Fig. 4.1).
The drain valve must be provided by the customer. We recommend mounting a hose which reaches about 1 m under the base of the cylinder to the outlet of the drain valve.
6.6.5 Laying the pipes to the tundish
> Connect the temperature and pressure relief valve and
the expansion relief valve to the tundish using 15 mm piping.
> Lay the tundish discharge pipe (¬section 6.7).
The tundish discharge pipes must be laid at a
sufficient distance from electrical components in
i
6.7 Installation of discharge pipe
6.7.1 Design of discharge pipe
a
accordance with valid building regulations.
Danger!
Risk of burns and scalds resulting from escaping hot water!
In the event of a fault, hot water can escape suddenly from the discharge pipe of the expansion relief valve.
> Lay the discharge pipe so that it ends at
an easily visible point inside or outside the building where escaping hot water does not pose a risk to persons.
In regions with high water pressure (4 bar or
more), you can also connect the mixer tap for a
i
32 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
bath or shower to the cold water inlet with pres­sure compensation (3) of the safety assembly. This ensures that the hot and cold water supply to the mixer tap have the same pressure. You should install the cold water supply for all other connections using a T-piece before the safety assembly in the cold mains inlet to the cylinder.
Page 33
Installation 6
Safety valve (e.g. Temperature and pressure relief valve)
600 mm
At least 300 mm
Metal discharge pipe (D2) from tundish with constant incline
Fig. 6.9 Typical drainage installation
Metal discharge pipe (D1) from temperature and pressure relief valve to tundish
Max.
Thundish
Discharge point beneath grille
Fixed grille
Gully with siphon
The discharge connections of the temperature and pres­sure relief valve and the expansion relief valve must be connected to the supplied tundish via 15 mm copper pip­ing. The tundish should be mounted vertically, as close to the cylinder as possible and not more than 600 mm from the connection of the temperature and pressure relief valve. It must be mounted in the same room as the cylinder at a sufficient distance from the electrical com­ponents. The discharge pipes from the temperature and pressure relief valve and from the expansion relief valve can be joined above the tundish using a T-piece (¬ fig. 4.1). The discharge pipe from the 22 mm connection of the tundish must be laid using copper piping with a diameter of at least 22 mm to a safe and visible discharge point. There must be a vertical section of pipe at least 300 mm long beneath the tundish before any bends or elbows in the pipework. If the total resistance of the discharge pipe exceeds the values specified in Tab. 6.4 below, you must increase the diameter of the piping. When install­ing the discharge piping, you must observe Directive G3 (¬section 2.2).
Minimum diameter of discharge pipe (D2) from tundish
22 mm up to 9 m 0.8 m 28 mm up to 18 m 1.0 m 35 mm up to 27 m 1.4 m
Tab. 6.4 Sizing of copper discharge pipe "D2" for G1/2
temperature and pressure relief valve outlet size
Maximum permis­sible total resist­ance, expressed as straight pipe length (without elbows or bends)
Resistance due to each elbow or bend
Worked example
The example below is for a G1/2 temperature relief valve with a discharge pipe (D2) having 4 No. 22 mm elbows and length of 7 m from the tundish to the point of dis­charge.
From Table 6.4: Maximum resistance allowed for a straight length of 22 mm copper discharge pipe (D2) from a G1/2 tempera­ture relief valve is: 9.0 m. Subtract the resistance for 4 No. 22 mm elbows at 0.8 m each = 3.2 m Therefore the maximum permitted length equates to:
5.8 m, which is less than the actual length of 7 m there-
fore calcu late the next largest size.
Maximum resistance allowed for a straight length of 28 mm pipe (D2) from a G1/2 temperature relief valve is: 18 m.
Subtract the resistance of 4 No. 28 mm elbows at 1.0 m each = 4.0 m.
Therefore the maximum permitted length equates to: 14 m. As the actual length is 7 m, a 28 mm (D2) copper pipe will be satisfactory.
A suitable place for the end of the discharge pipe is, for example, beneath a fixed grille above the odour seal in a gully with a siphon. Low discharge pipes, for example up to 100mm above external surfaces such as car and other parking spaces, grasslands, etc. can be used pro­vided that they are secured by a wire fence or some­thing similar to prevent children from coming into con­tact with the waste water and provided that the system is not visible. You must not install any valves or stop cocks in the discharge pipe.
> Make sure that the discharge pipe from the tundish to
the drain has a constant downward incline of at least 1:200.
The discharge pipe from the pressure relief valve of the Vaillant gas-fired wall-hung boiler can be connected to the horizontal discharge pipe of the cylinder behind the tundish using a T-piece.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 33
Page 34
6 Installation
6.7.2 High drain
tundish
At least 300 mm
Fig. 6.10 High drain connection
The method illustrated in Fig. 6.10 is allowed provided that no-one inside or outside the building is endangered by the discharge point.
Examples of points to consider when deciding whether a location is suitable for the high drain:
– The possibility (taking into account the effect of the
wind) that a person might be located in the area where the water escapes, and, if this is the case, whether the water is sufficiently cooled by that point to pose no dan­ger. Thermal conductivity of the structure's surface, cli­matic conditions and location and orientation of the discharge pipe may or may not have an effect on redu-
cing the temperature of the discharge water. – The position of windows and other openings. – The probability of prams being parked under the drain. – The resistance of the surface to hot water. – The possibility of ice forming if the water is discharged
onto paths.
Discharge pipe
Metal funnel
6.8 Electrical installation
Danger!
Risk of death from electric shock!
e
e
Wiring should be installed by a qualified competent per­son in accordance with the building regulations, Part P of the current IEE regulations, and all other applicable regulations and directives. You can use standard commercial cables (H05RR-F 3G1.5 or H05VV-F 3G1.5) for the wiring:
– Cross-section of conductors: 1.5mm – Torque for strain relief: 1.5 Nm – Maximum length of bus cables: 300 m
230 V supply lines and bus cables must be laid sepa­rately above lengths of 10 m.
i
Improperly executed electrical connections can impair the operational safety of the unit.
> The electrical installation may only be
performed by a competent person appro­ved at the time by the Health and Safety Exe­cutive.
Danger!
Risk of death from electric shock!
Without potential equalisation, life-threat­ening voltage can reach the piping and water draw-off points.
> Earth the heating system.
2
The discharge pipes of the tundish, drain valves
and motorised valves, etc. must be laid at a dis­tance from electrical components.
6.8.1 Options for combining control components
> For the installation, use the connection wiring diagram
specified in Tab. 6.5 for the gas-fired wall-hung boiler and control components used.
Gas-fired wall-hung boiler used
eBUS-compatible gas-fired wall-hung boiler such as the Vaillant ecoTEC or non-eBUS-compatible gas-fired wall­hung boiler from Vaillant or a third-party manufacturer.
Wiring
Wiring via the Vaillant VR61/2 mixer module or Vaillant Control Centre as a system solution which enables Vail­lant dual-channel eBUS controllers (low-voltage) to be used with valves and domestic hot water cylinders in the traditional 230 V range in the English market. Alterna­tively, using a standard cabling box.
34 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 35
Solar circuit control system
Solar circuit control via one of the following means:
– The auroMATIC 560/2 differential temperature-cont-
rolled control set for solar-aided hot water production – The VRC weather compensator with VR 68/2.
The temperature sensors VR 10 (cylinder sensor)
and VR 11 (collector sensor) are supplied with the
i
VRS 560/2 solar controller or VR68/2 solar module.
Control system of the heating circuits
The heating circuits can be controlled via Vaillant pro­grammable room thermostats or weather compensators in conjunction with the Vaillant range of eBUS-compati­ble gas-fired wall-hung boilers. You can also use tested standard operating elements (see above). For an overview of the combination options for these control components, see Tab.6.5.
All wiring must be carried out in accordance
with BS7671: "Requirements for electrical instal-
i
lations" (IEE wiring regulations, current edition).
Installation 6
For the wiring of the solar pump, solar
controller, and solar pump thermal cut-outs on
i
the cylinder (see connection wiring diagrams 1 to 6, ¬section 6.8.6), an additional terminal strip is required.
Hot water reheating control
Hot water primary heating control via the auroMATIC 560/2 differential temperature-controlled control set for solar-aided hot water production with demand-control­led primary heating for Vaillant gas-fired wall-hung boil­ers. Alternatively, via a Vaillant dual-circuit eBUS con­troller or a timer (from a third-party manufacturer).
Gas-fired wall-hung boiler
Vaillant ecoTEC, eBUS-compatible
Vaillant ecoTEC, eBUS-compatible
Vaillant ecoTEC, eBUS-compatible
Vaillant ecoTEC, eBUS-compatible
Vaillant ecoTEC, eBUS-compatible
Non-eBUS-compati­ble boiler from a third-party manufac­turer
Tab. 6.5 Options for combining control components
Wiring via
Vaillant Control Centre
Vaillant Control Centre
Vaillant Control Centre
Vaillant Control Centre
VR61/2 and VR68/2
Standard cabling box
Solar circuit control sys­tem
VRS 560/2
VRS 560/2
VRS 560/2
VRS 560/2
VRC with VR 68/2
VRS 560/2
Control system of the heating circuits
Vaillant dual-channel eBUS controller
Vaillant dual-channel eBUS controller
Vaillant dual-channel eBUS controller
Vaillant dual-channel eBUS controller
Vaillant dual-channel eBUS controller
Programmable timer and room thermostat
Solar cylinder primary heating control sys­tem
Vaillant dual-channel eBUS controller with Vaillant Control Centre Vaillant dual-channel eBUS controller with Vaillant Control Centre
VRS 560/2 with Vaillant Control Centre
VRS 560/2 with Vaillant Control Centre
Vaillant dual-channel eBUS controller and VR68/2
VRS 560/2 S or Y plan 6 ¬ Fig. 6.22
Hydraulic plan
S plan 1 ¬ Fig. 6.17
Y plan 2 ¬ Fig. 6.18
S plan 3 ¬ Fig. 6.19
Y plan 4 ¬ Fig. 6.20
S plan 5 ¬ Fig. 6.21
Connection wiring dia­gram
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 35
Page 36
6 Installation
6.8.2 Electrical connection of control components
7
12
11
3
3
4
5
10
6
9
13
2
1
8
1
2
3
4
5
6
7
6
5 4
Fig. 6.12 Cylinder thermostat and thermal cut-out (TCO)
for primary heating circuit
Key
1 Cylinder thermostat 2 Cylinder thermostat protective earth terminal 3 Cylinder thermostat terminal 1 4 Primary heating circuit TCO protective earth terminal 5 Primary heating circuit TCO C terminal 6 Primary heating circuit TCO reset button 7 Primary heating circuit thermal cut-out (TCO)
1
2
3
Fig. 6.11 Cylinder temperature control
Key
1 Cover cap for reset button for primary heating circuit TCO 2 Primary heating circuit temperature controller 3 Primary heating circuit cylinder dry pocket (SP1) 4 Electric immersion heater cover 5 Casing 6 Solar circuit cylinder dry pocket (SP2) 7 Cover cap for reset button for solar circuit TCO 8 Upper cylinder dry pocket 9 Solar circuit thermal cut-out (TCO) 10 Electric immersion heater 11 Lower cylinder dry pocket 12 Primary heating circuit thermal cut-out 13 Cylinder thermostat
The cylinder has a suitable thermal cut-out for the pri­mary heating circuit (12) and solar circuit(9) and a cyl- inder thermostat (13).
Before wiring the control components, dismantle
the casing(5) to facilitate work on
i
the components. When reinstalling the casing, use the cutouts in the casings for routing the cables.
1
2
3
4
5
Fig. 6.13 Solar circuit thermal cut-out (TCO)
Key
1 Solar circuit thermal cut-out (TCO) 2 Solar circuit TCO reset button 3 Solar circuit TCO terminal C 4 Solar circuit TCO protective earth terminal 5 Solar circuit TCO terminal 2
You must connect the solar pump’s outer con-
ductor from the solar control via terminals "3"
i
and "5" of the TCO solar circuit in series circuit to the solar pump.
36 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 37
Installation 6
6.8.3 Connecting up the electric immersion heater
The Vaillant auroSTOR VIH S GB 210/2 S, VIHSGB260/2S, and VIH S GB 310/2 S solar cylinders are fitted with an electric immersion heater at the fac­tory.
1
2
3
4
5
Fig. 6.14 Electrical connection of electric immersion heater
2
1
3
4
5
Caution!
Corrosion and short circuits may occur
a
> Mount the cover for the electric immersion heater.
due to incorrect earthing.
If you insert a electric immersion heater into the cylinder, the external voltage may build up electrical potential in the water which may result in the electrochemical corrosion of the electric immersion heater.
> Ensure that both the hot water and cold
water pipes are connected to the earth line by means of an earth cable directly on the cylinder.
> You must also make sure that the elec-
tric immersion heater is connected to the earth line via the earthing terminal.
Only switch the immersion heater on once
the cylinder is completely full.
i
With the isolating switch, the electric immersion heater can be switched on if the primary heating device has malfunctioned.
Key
1 Protective earth terminal (PE) 2 Cable grip 3 Electric immersion heater 4 Neutral conductor terminal (N) 5 Outer conductor terminal (L)
Danger!
Risk of death from electric shock!
e
> Remove the front cladding of the casing (5¬fig. 6.11)
from the cylinder.
> Dismantle the casing to facilitate work on the compo-
nents.
> Dismantle the electric immersion heater cover. > Install a separate electrical power supply for the electric
immersion heater in accordance with current IEE regula-
tions (BS 7671).
– Use heat-resistant cables (H05BN4-F 1.5 mm
– Use the cable grip(2) to firmly secure the supply
– Connect the electric immersion heater to the power
– Protect the circuit using a 16 A fuse.
Without potential equalisation, life-threat­ening voltage can reach the piping and water draw-off points.
> Earth the electric immersion heater.
2
, 3-wire HOFR-coated) for the cabling of the electric immer­sion heater.
cable of the immersion heater.
mains via a double pole isolating switch with a contact separation of at least 3 mm in both poles.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 37
Page 38
6 Installation
6.8.4 Connection of the solar pump
3
4
Fig. 6.15 Connection diagram for solar pump
Connection wiring diagrams 1, 2, 3, 4, and 6 (VRS560/2):
> Connect the terminal strip with the terminal Kol1-P of
1
the VRS560/2(1).
Connection wiring diagram 5 (VR68/2):
> Connect the terminal strip with the terminal Kol1-P of
the VR68/2(1).
3
6.8.5 Connecting up the solar yield temperature
2
3
3
sensor
1
2
Key
1 VRS560/2 or VR68/2 2 Terminal strip for series circuit to solar pump via TCO solar
circuit 3 Solar pump 4 Solar circuit thermal cut-out (TCO)
Connection wiring diagrams 1, 2, 3, 4, and 6:
> Next to the cylinder, install the VRS 560/2 solar control-
ler (1).
Connection wiring diagram 5:
> Next to the cylinder, install the VR68/2 solar module (1).
> Dismantle the cover of the VRS 560/2 solar controller or
the VR68/2 solar module.
> Dismantle the cover of the solar circuit thermal
cut-out(4).
> Connect the solar pump (3) in series with the provided
solar circuit thermal cut-out. To do so, use a protected
terminal strip (2) and 3-core cable provided by the cus-
tomer.
The solar pump and solar circuit thermal cut-out must be earthed using a protective earth.
> You must carry out a protective earth test.
Fig. 6.16 Solar yield temperature sensor
Key
1 Solar yield temperature sensor 2 Solar return
> Mount the solar yield temperature sensor (1) on the
return line (2) of the solar circuit.
Connection wiring diagrams 1, 2, 3, 4, and 6 (VRS560/2):
> Connect the solar yield temperature sensor to the yield
("Ertrag") terminal of the VRS560/2 solar controller.
Connection wiring diagram 5 (VR68/2):
> Connect the solar yield temperature sensor to the yield
("Ertrag") terminal of the VR68/2 solar module.
38 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 39
Installation 6
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 39
Page 40
6 Installation
6.8.6 Installing the control components in accordance
with the connection wiring diagrams
Connection wiring diagram 1 (S plan hydraulics)
12
Kol 2
Ertrag
SP 3
SP 2
SP 1
Kol 1
C1 C2
12
12
12
12
12 12
2
2
2
Solar yield
Yield
Kol 1
LP/UV 1
LEG / Byp
KOL 2-P / ZP
KOL 1-P
230 V grid
NPE LNPE L
12
EP
NPE L
NPE L
NPE L
VRS 560
NTC
21+-NPE onNPE L offonNPE on
BUS
DHW
DHW
CH
CYL.
230 V grid
Vaillant Control Centre
Fig. 6.17 Connection wiring diagram 1
USE
DO NOT
3A
PE
PE 3A
L
N
Cylinder
2 2
L
N
NTC
C2
Cylinder thermostat and TCO
Brown
Blue
PE
M
Blue
PE
CH
DHW
M
Brown
SP2
1
PE
1
2
TCO solar circuit
2
-
+
Vaillant
ecoTEC
BUS
LNPE
-
Vaillant
BUS
dual-channel
eBUS controller
Solar pump
+
40 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 41
Installation 6
– eBUS-compatible Vaillant gas-fired wall-hung boiler – Wiring via Vaillant Control Centre – Solar circuit control via VRS560/2 solar controller – Primary heating circuit control via Vaillant dual-channel
eBUS controller
– Room heating control via Vaillant dual-channel
eBUS controller
– S plan hydraulics
> Next to the solar cylinder, install the Vaillant Control Cen-
tre.
> Dismantle the cover of the Vaillant Control Centre.
> Insert a VR10 temperature sensor into the bottom cylin-
der dry pocket for SP2 (6¬fig. 6.11).
> Connect this lower cylinder sensor (SP 2) to the terminal
SP 2 of the VRS560/2.
> Mount the VR11 collector sensor (Kol1) in the provided
sensor sleeve on the collector array.
> Connect the VR11 collector sensor to the terminal Kol1
of the VRS560/2.
The terminals NTC and CYL. of the Vaillant Con-
trol Centre may not be connected at the same
i
time.
The electrical installation of the eBUS connection is described in the installation instructions for the Vaillant dual-channel eBUS controller.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the Vaillant Control Centre.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the Vaillant dual-channel eBUS controller.
> Connect the zone valves for the heating circuit and hot
water circuit in accordance with connection diagram 1 (S plan hydraulics).
> Connect the gas-fired wall-hung boiler, Vaillant Control
Centre, and VRS 560/2 to the power mains.
> Mount the covers for the Vaillant Control Centre and the
VRS560/2.
> Adjust the Vaillant dual-channel eBUS controller and the
VRS 560/2 solar controller in accordance with their ope­rating and installation instructions.
> Set the maximum cylinder temperature (MAXT 1) to 75 °C
(factory setting) on the auroMATIC VRS 560/2 solar con­troller (see operating instructions for the VRS 560/2).
Option 1: Upper cylinder sensor (NTC) to Vaillant Control Centre:
> Insert a VR10 temperature sensor into the cylinder dry
pocket for SP1 (3¬fig. 6.11).
> Connect the upper cylinder sensor (NTC) to the
terminal NTC of the Vaillant Control Centre.
Option 2: Cylinder thermostat to Vaillant Control Centre:
> Dismantle the cover of the cylinder thermostat (13¬fig.
6.11).
> Connect the terminals 1 (cylinder thermostat)
(3¬fig. 6.12) and C (primary heating circuit TCO)
(5¬fig. 6.12) to the terminal CYL. of the Vaillant Control
Centre.
> Mount the cover for the cylinder thermostat. > Mount the casing(5 ¬ fig. 6.11) on the cylinder and use
the cutouts in the casings for routing the cables.
> Mount the front claddings of the casing.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 41
Page 42
6 Installation
Connection wiring diagram 2 (Y plan hydraulics only with an
eBUS-compatible Vaillant wall-hung boiler.)
12
Kol 2
Ertrag
SP 3
SP 2
SP 1
Kol 1
C1 C2
12
12
12
12
12 12
2
2
2
Solar yield
Yield
Kol 1
LP/UV 1
LEG / Byp
KOL 2-P / ZP
KOL 1-P
230 V grid
VRS 560
NTC
BUS
NPE LNPE L
12
EP
NPE L
NPE L
NPE L
DO NOT
21+-NPE onNPE L offonNPE on
USE
3A
PE
L
N
Cylinder
2 2
NTC
C2
Cylinder thermostat and TCO
SP2
1
PE
1
2
TCO solar circuit
LNPE
Solar pump
DHW
-
+
ecoTEC
BUS
2
-
+
Vaillant
BUS
dual-channel
eBUS controller
DHW
CH
CYL.
230 V grid
Vaillant Control Centre
Orange
Grey
Brown or white
Blue
PE
M
PE 3A
L
N
Vaillant
Fig. 6.18 Connection wiring diagram 2
42 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 43
Installation 6
– eBUS-compatible Vaillant gas-fired wall-hung boiler – Wiring via Vaillant Control Centre – Solar circuit control via VRS560/2 solar controller – Primary heating circuit control via Vaillant dual-channel
eBUS controller
– Room heating control via Vaillant dual-channel
eBUS controller
– Y plan hydraulics
> Next to the solar cylinder, install the Vaillant Control Cen-
tre.
> Dismantle the cover of the Vaillant Control Centre.
> Insert a VR10 temperature sensor into the bottom cylin-
der dry pocket for SP2 (6¬fig. 6.11).
> Connect this lower cylinder sensor (SP 2) to the terminal
SP 2 of the VRS560/2.
> Mount the VR11 collector sensor (Kol1) in the provided
sensor sleeve on the collector array.
> Connect the VR11 collector sensor to the terminal Kol1
of the VRS560/2.
The terminals NTC and CYL. of the Vaillant Con-
trol Centre may not be connected at the same
i
time.
The electrical installation of the eBUS connection is described in the installation instructions for the Vaillant dual-channel eBUS controller.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the Vaillant Control Centre.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the Vaillant dual-channel eBUS controller.
> Connect the 3-way valve for the heating circuit and hot
water circuit in accordance with connection diagram 2 (Y plan hydraulics).
> Connect the gas-fired wall-hung boiler, Vaillant Control
Centre, and VRS 560/2 to the power mains.
> Mount the covers for the Vaillant Control Centre and the
VRS560/2.
> Adjust the Vaillant dual-channel eBUS controller and the
VRS 560/2 solar controller in accordance with their ope­rating and installation instructions.
> Set the maximum cylinder temperature (MAXT 1) to 75 °C
(factory setting) on the auroMATIC VRS 560/2 solar con­troller (see operating instructions for the VRS 560/2).
Option 1: Upper cylinder sensor (NTC) to Vaillant Control Centre:
> Insert a VR10 temperature sensor into the cylinder dry
pocket for SP1 (3¬fig. 6.11).
> Connect the upper cylinder sensor (NTC) to the terminal
NTC of the Vaillant Control Centre.
Option 2: Cylinder thermostat to Vaillant Control Centre:
> Dismantle the cover of the cylinder thermostat (13¬fig.
6.11).
> Connect the terminals 1 (cylinder thermostat)
(3¬fig. 6.12) and C (primary heating circuit TCO)
(5¬fig. 6.12) to the terminal CYL. of the Vaillant Control
Centre.
> Mount the cover for the cylinder thermostat. > Mount the casing(5¬fig. 6.11) on the cylinder and use
the cutouts in the casings for routing the cables.
> Mount the front claddings of the casing.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 43
Page 44
6 Installation
Connection wiring diagram 3 (S plan hydraulics)
12
Kol 2
Ertrag
SP 3
SP 2
SP 1
Kol 1
C1 C2
12
12
12
12
12 12
22
2
Solar yield
Yield
Kol 1
LP/UV 1
LEG / Byp
KOL 2-P / ZP
KOL 1-P
230 V grid
VRS 560
NTC
BUS
NPE LNPE L
12
EP
NPE L
NPE L
NPE L
USE
DO NOT
21+-NPE onNPE L offonNPE on
2 2
3A
PE
L
N
Cylinder
SP1
SP2
PE
1
2
TCO solar circuit
LNPE
Solar pump
Brown
DHW
DHW
CH
CYL.
230 V grid
Vaillant Control Centre
Brown
Blue
CH
PE 3A
L
N
Blue
PE
M
DHW
PE
M
Vaillant
-
+
ecoTEC
BUS
2
-
+
Vaillant
BUS
dual-channel
eBUS controller
Fig. 6.19 Connection wiring diagram 3
44 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 45
Installation 6
– eBUS-compatible Vaillant gas-fired wall-hung boiler – Wiring via Vaillant Control Centre – Solar circuit control via VRS560/2 solar controller – Primary heating circuit control via VRS560/2 solar cont-
roller
– Room heating control via Vaillant dual-channel
eBUS controller
– S plan hydraulics
> Next to the solar cylinder, install the Vaillant Control Cen-
tre.
> Dismantle the cover of the Vaillant Control Centre.
> Insert a VR10 temperature sensor into the cylinder dry
pocket for SP2 (6¬fig. 6.11).
> Connect this lower cylinder sensor (SP 2) to the terminal
SP 2 of the VRS560/2.
> Insert a VR10 temperature sensor into the bottom cylin-
der dry pocket for SP1 (3¬fig. 6.11).
> Connect this upper cylinder sensor (SP 1) to the terminal
SP 1 of the VRS560/2.
> Mount the VR11 collector sensor (Kol1) in the provided
sensor sleeve on the collector array.
> Connect the VR11 collector sensor (Kol 1) to the terminal
Kol1 of the VRS560/2.
> Connect the terminal EP of the VRS560/2 with the ter-
minal CYL. of the Vaillant Control Centre.
The electrical installation of the eBUS connection is described in the installation instructions for the Vaillant dual-channel eBUS controller.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the Vaillant Control Centre.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the Vaillant dual-channel eBUS controller.
> Connect the zone valves for the heating circuit and hot
water circuit in accordance with connection diagram 3 (S plan hydraulics).
> Connect the gas-fired wall-hung boiler, Vaillant Control
Centre, and VRS 560/2 to the power mains.
> Mount the covers for the Vaillant Control Centre and the
VRS560/2.
> Adjust the Vaillant dual-channel eBUS controller and the
VRS 560/2 solar controller in accordance with their ope­rating and installation instructions.
> Set the maximum cylinder temperature (MAXT 1) to 75 °C
(factory setting) on the auroMATIC VRS 560/2 solar con­troller (see operating instructions for the VRS 560/2).
The terminals NTC and CYL. of the Vaillant Con-
trol Centre may not be connected at the same
i
> Mount the casing(5¬fig. 6.11) on the cylinder and use
the cutouts in the casings for routing the cables.
> Mount the front claddings of the casing.
time.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 45
Page 46
6 Installation
Connection wiring diagram 4 (Y plan hydraulics)
12
Kol 2
Ertrag
SP 3
SP 2
SP 1
Kol 1
C1 C2
12
12
12
12
12 12
2
2
2
Solar yield
Yield
Kol 1
LP/UV 1
LEG / Byp
KOL 2-P / ZP
KOL 1-P
230 V grid
VRS 560
NTC
BUS
NPE LNPE L
12
EP
NPE L
NPE L
NPE L
USE
DO NOT
21+-NPE onNPE L offonNPE on
2 2
3A
PE
L
N
Cylinder
SP1
SP2
PE
1
2
TCO solar circuit
LNPE
Solar pump
DHW
-
+
ecoTEC
BUS
2
-
+
Vaillant
BUS
dual-channel
eBUS controller
DHW
CH
CYL.
230 V grid
Vaillant Control Centre
Orange
Grey
Brown or white
Blue
PE
M
PE 3A
L
N
Vaillant
Fig. 6.20 Connection wiring diagram 4
46 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 47
Installation 6
– eBUS-compatible Vaillant gas-fired wall-hung boiler – Wiring via Vaillant Control Centre – Solar circuit control via VRS560/2 solar controller – Primary heating circuit control via VRS560/2 solar cont-
roller
– Room heating control via Vaillant dual-channel
eBUS controller
– Y plan hydraulics
> Next to the solar cylinder, install the Vaillant Control Cen-
tre.
> Dismantle the cover of the Vaillant Control Centre.
> Insert a VR10 temperature sensor into the cylinder dry
pocket for SP2 (6¬fig. 6.11).
> Connect this lower cylinder sensor (SP 2) to the terminal
SP 2 of the VRS560/2.
> Insert a VR10 temperature sensor into the bottom cylin-
der dry pocket for SP1 (3¬fig. 6.11).
> Connect this upper cylinder sensor (SP 1) to the terminal
SP 1 of the VRS560/2.
> Mount the VR11 collector sensor (Kol1) in the provided
sensor sleeve on the collector array.
> Connect the VR11 collector sensor (Kol 1) to the terminal
Kol1 of the VRS560/2.
> Connect the terminal EP of the VRS560/2 with the ter-
minal CYL. of the Vaillant Control Centre.
The electrical installation of the eBUS connection is described in the installation instructions for the Vaillant dual-channel eBUS controller.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the Vaillant Control Centre.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the Vaillant dual-channel eBUS controller.
> Connect the 3-way valve for the heating circuit and hot
water circuit in accordance with connection diagram 4 (Y plan hydraulics).
> Connect the gas-fired wall-hung boiler, Vaillant Control
Centre, and VRS 560/2 to the power mains.
> Mount the covers for the Vaillant Control Centre and the
VRS560/2.
> Adjust the Vaillant dual-channel eBUS controller and the
VRS 560/2 solar controller in accordance with their ope­rating and installation instructions.
> Set the maximum cylinder temperature (MAXT 1) to 75 °C
(factory setting) on the auroMATIC VRS 560/2 solar con­troller (see operating instructions for the VRS 560/2).
The terminals NTC and CYL. of the Vaillant Con-
trol Centre may not be connected at the same
i
> Mount the casing(5¬fig. 6.11) on the cylinder and use
the cutouts in the casings for routing the cables.
> Mount the front claddings of the casing.
time.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 47
Page 48
6 Installation
Connection wiring diagram 5 (S plan hydraulics)
12
TD 2
12
TD 1
Ertrag
SP 2
SP 1
Kol 1
BUS
LEG-P
12
12
12
12 12
NPE LNPE L
2
2
2
2
2
Solar yield
Yield
Kol 1
KOL 1-P
230 V grid
VR 68/2
HK2 / P
HK1 / P
ZP / LP
230 V grid
VR 61/2
MA
VF2
BUS
HK2
NPE L
NPE L
21+-NPE L NPE L NPE L
NPE L
NPE on off
3A
PE
PE 3A
L
N
Cylinder
Brown
Blue
PE
HW
L
N
SP1
PE
1
2
Blue
PE
HZ2
M
Vaillant
TCO solar circuit
-
+
ecoTEC
BUS
SP2
Brown
Brown
Blue
PE
M
HZ1
M
LNPE
2
Vaillant
dual-channel
Solar pump
-
+
VR 81
BUS
eBUS controller
-
+
BUS
Fig. 6.21 Connection wiring diagram 5
48 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 49
Installation 6
– eBUS-compatible Vaillant gas-fired wall-hung boiler – Wiring via VR68/2 solar module and VR61/2 mixer
module
– Control of the solar circuit via a VRC weather compensa-
tor and the VR 68/2 solar module
– Control of the primary heating circuit via a VRC control-
ler
– Control of the room heating via a VRC controller – S plan hydraulics with VR81 for 2nd zone
> Next to the solar cylinder, install the VR61/2 mixer
module.
> Install a VRC weather compensator next to the solar
cylinder.
> Dismantle the covers of the VR 61/2 and the VRC cont-
roller.
> Insert a VR10 temperature sensor into the cylinder dry
pocket for SP2 (6¬fig. 6.11).
> Connect this lower cylinder sensor (SP 2) to the terminal
SP 2 of the VR68/2.
> Insert a VR10 temperature sensor into the bottom cylin-
der dry pocket for SP1 (3¬fig. 6.11).
> Connect this upper cylinder sensor (SP 1) to the terminal
SP 1 of the VR68/2.
> Mount the VR11 collector sensor (Kol1) in the provided
sensor sleeve on the collector array.
> Connect the VR11 collector sensor (Kol 1) to the terminal
Kol1 of the VR68/2.
The electrical installation of the eBUS connection is described in the installation instructions for the Vaillant dual-channel eBUS controller.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the VR61/2.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the VR68/2.
> Install the eBUS connection from the gas-fired wall-hung
boiler to the VRC controller.
> Optional: Install the eBUS connection from the gas-fired
wall-hung boiler to the VR81.
> Connect the zone valves for the heating circuit and hot
water circuit in accordance with connection diagram 5 (S plan hydraulics).
> Connect the gas-fired wall-hung boiler, VR61/2, and
VR68/2 to the power mains.
> Mount the covers of the VR 61/2, the VR 68/2 and the
VRC controller.
> Adjust the Vaillant dual-channel eBUS controller in
accordance with its operating and installation instruc­tions.
> Set the maximum cylinder temperature (MAXT 1) to 75 °C
(factory setting) on the VRC weather compensator (see operating instructions for the VR 68/2).
> Mount the casing(5¬fig. 6.11) on the cylinder and use
the cutouts in the casings for routing the cables.
> Mount the front claddings of the casing.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 49
Page 50
6 Installation
Connection wiring diagram 6 (S plan or Y plan hydraulics)
12
Kol 2
Ertrag
SP 3
SP 2
SP 1
Kol 1
C1 C2
12
12
12
12
12 12
2
2
2
2
Solar yield
Yield
Kol 1
LP/UV 1
LEG / Byp
KOL 2-P / ZP
KOL 1-P
230 V grid
VRS 560
NPE LNPE L
12
EP
NPE L
NPE L
NPE L
3A
N
PE
Cylinder
SP1
LNPE
L
PE
1
2
SP2
TCO solar circuit
Solar pump
PE
C2
Cylinder thermostat
PE
1
and TCO
Standard cabling box
S-plan or Y-plan
Fig. 6.22 Connection wiring diagram 6
50 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 51
Installation 6
– Third-party boiler, non-eBUS-compatible – Wiring via standard cabling box – Solar circuit control via VRS560/2 solar controller – Primary heating circuit control via VRS560/2 solar cont-
roller
– Room heating control via programmable timer and room
thermostat
– S or Y plan hydraulics
> Next to the solar cylinder, install a standard cabling box. > Dismantle the cover for the standard cabling box. > Dismantle the cover of the cylinder thermostat (13¬fig.
6.11).
> Insert a VR10 temperature sensor into the cylinder dry
pocket for SP2 (6¬fig. 6.11).
> Connect this lower cylinder sensor (SP 2) to the terminal
SP 2 of the VRS560/2.
> Insert a VR10 temperature sensor into the cylinder dry
pocket for SP1 (3¬fig. 6.11).
> Connect this upper cylinder sensor (SP 1) to the terminal
SP 1 of the VRS560/2.
> Mount the VR11 collector sensor (Kol1) in the provided
sensor sleeve on the collector array.
> Connect the VR11 collector sensor (Kol 1) to the terminal
Kol1 of the VRS560/2.
> Install a bridge between the protective earth terminal
(2¬fig. 6.12) of the cylinder thermostat and the protec­tive earth terminal (4¬fig. 6.12) of the primary heating circuit TCO.
> Mount the cover for the cylinder thermostat. > Mount the casing(5¬fig. 6.11) on the cylinder and use
the cutouts in the casings for routing the cables.
> Mount the front claddings of the casing.
C
2
Fig. 6.23 Connections of the cylinder thermostat and the
thermal cut-out
1
For S plan hydraulics:
> Install standard S plan wiring between the boiler,
two port valves, terminal C of the cylinder thermostat,
and the standard cabling box.
For Y plan hydraulics:
> Install standard Y plan wiring between the boiler, 3-way
zone valve, terminal C of the cylinder thermostat, and
the standard cabling box.
> In the VRS 560/2 solar controller, install a bridge from
terminal 230V~, connection L to terminal EP, connec-
tion 2.
Connect the VRS 560/2 and the cylinder thermostat using a 2-core cable (phase conductor and protective earth):
> Connect the connection 1 of the terminal EP of the VRS
560/2 with the terminal 1 (3¬fig. 6.12) of the cylinder
thermostat.
> Connect the protective earth connection of the VRS 560
with the protective earth terminal (2¬fig. 6.12) of the
cylinder thermostat.
Connect the standard cabling box with the thermal cut­out (TCO) for the primary heating circuit using a 2-core cable (phase conductor and protective earth):
> Connect the standard cabling box with the terminal C
(5¬fig. 6.12) of the primary heating circuit TCO.
> Connect the protective earth connection of the standard
cabling box with the protective earth terminal (4¬fig.
6.12) of the primary heating circuit TCO.
> Connect the boiler, VRS560/2, and standard cabling box
to the power mains.
> Mount the covers for the VRS 560/2 and the standard
cabling box.
> Adjust the Vaillant VRS 560/2 solar controller in
accordance with its operating and installation instruc­tions.
> Set the maximum cylinder temperature (MAXT 1) to 75 °C
(factory setting) on the auroMATIC VRS 560/2 solar con­troller (see operating instructions for the VRS 560/2).
The switching signal for the primary heating of
the hot water is forwarded to the S plan/Y plan
i
wiring via terminal EP of the VRS560/2, the cyl­inder thermostat, and the primary heating cir­cuit TCO.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 51
Page 52
7 Commissioning
7 Commissioning
4
6a 6b
8
11
Fig. 7.1 Checking, flushing, and filling the solar circuit
Key
1 Combined filling and draining tap 2 6 bar expansion relief valve 4 Air vent 5 Solar protection vessel 6a Flow line thermometer 6b Return line thermometer 7 Pressure gauge 8 Flow line ball valve with non-return valve 9 Filter 10 Solar fluid container 11 Combined filling and draining tap 12 Flow rate limiter 13 Solar pump 14 Return line non-return valve 15 3-way ball valve with non-return valve 16 Combined filling and draining tap 17 Return hose 19 Filling pump 21 Vaillant automatic air separator system
15
14
13
12
21
7
16
9
2
1
17
10
You must adhere to the following procedure for the commissioning of the total system:
> Check for leak-tightness. > Flush the solar circuit with solar fluid. > Fill the solar circuit with solar fluid. > Set the solar pump. > Set the flow rate limiter. > Check the controller. > Set the hot water thermostat mixer.
Only use Vaillant solar fluid for pressure tests,
flushing, and filling.
i
7.1 Checking leak-tightness
For the pressure test, first fill the solar circuit with
5
Vaillant solar fluid (ready mixed). A self-priming filling pump with a pressure of 2 to 3 bar is required to fill the solar circuit.
> Connect the pressure hose of the filling pump (19) to the
20
19
upper combined filling and draining tap (1) of the solar circuit.
> Connect the return hose (17) to the lower combined fil-
ling and draining tap (16) of the solar circuit. > Close the 3-way ball valve (15). > Open the air vent (4). > Switch the filling pump on.
The solar fluid now flows into the solar circuit.
> Place enough solar fluid into the container (10) to ensure
that the filling pump cannot run dry. > Allow the system to pump the solar fluid (ready mixed)
out of the container (10) via the combined filling and
draining tap (1) until solar fluid runs back out of the
return hose (17) and into the container (10). > Close the combined filling and draining tap (16). > Let the pressure build to around 4.5 bar. > Close the combined filling and draining tap (1) and imme-
diately switch the filling pump off. > Carry out a visual inspection of the pipes and connec-
tions. > Rectify any leaks and then check again.
Only flush the solar circuit following
a successful pressure test.
i
52 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 53
Commissioning 7
7.2 Flushing the solar circuit with solar fluid
Flushing is performed from the solar pump unit to the cylinder via the collector.
> Connect the pressure hose of the filling pump (19) to the
upper combined filling and draining tap (1) of the solar circuit.
> Connect the return hose (17) to the lower combined fil-
ling and draining tap (16) of the solar circuit. > Close the 3-way ball valve (15). > Open the air vent (4). > Switch the filling pump on. > Place enough solar fluid into the container (10) to ensure
that the filling pump cannot run dry. > Allow the system to pump the solar fluid out of the con-
tainer via the combined filling and draining tap (1) until
solar fluid runs back out of the return hose (17) and into
the container (10). > Allow the solar fluid to circulate in the circuit for at least
15 minutes to flush the solar circuit and filter the solar
fluid.
7.3 Filling the solar circuit with solar fluid
> First, carry out a pressure test and flush the system with
Vaillant solar fluid (ready mixed). > Connect the pressure hose of the filling pump (19) to the
upper combined filling and draining tap (1) of the solar
circuit. > Connect the return hose (17) to the lower combined fil-
ling and draining tap (16) of the solar circuit. > Completely open the combined filling and draining taps
(1) and (16) on the solar pump unit to ensure a maximum
flow rate. > Open the ball valve (8) on the solar pump unit. > Close the 3-way ball valve (15) on the solar pump unit. > Switch the filling pump on. > Place enough solar fluid into the container (10) to ensure
that the filling pump cannot run dry. > Check to see whether the solar fluid is running out of the
return hose (17) and back into the container (10). > Allow the filling pump to run for at least 15 minutes to
sufficiently vent the solar circuit.
The vent operation was successful if the fluid in the solar fluid container is clear and no more bubbles rise to the surface.
> Use the screw cap opening on the solar fluid container to
carry out the visual check.
> Set the 3-way ball valve (15) on the solar pump unit to
45° (non-return valve out of operation).
> Allow the filling pump to run for a further 5 minutes to
vent the pipeline between the combined filling and drai­ning taps (1) and (16).
> After 5 minutes, close the 3-way ball valve (15) again
(horizontal position).
> Close the combined filling and draining taps (1) and (16)
and then immediately switch off the filling pump.
> Place the 3-way ball valve (15) into the vertical position
again (flow and non-return valve working).
> Remove the pressure hose and return hose of the solar
circuit combined filling and draining taps.
The system is now filled and vented.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 53
Page 54
0,5
1
2
3
0,5
1
2
3
4
5
6
4
5
6
L/min
L/min
7 Commissioning
7.4 Setting the flow rate in the solar circuit
In addition to factors such as the temperature, pipe diameter, number of collectors and so on, the flow rate is important for ensuring optimum heat transfer. A flow rate above the nominal flow rate is not as unfavourable as a flow rate below the nominal flow rate.
Never allow the flow rate to fall below the nomi-
nal flow rate. Doing so can cause the efficiency
i
of the collectors to drop significantly, resulting in a solar yield of up to 10% less and unneces­sarily high power consumption by the solar pump.
The solar pump unit has a three-stage solar pump and a flow rate limiter to enable it to optimally modify the flow rate in line with the collector performance.
– In conjunction with central air vents, the flow rate in the
solar circuit should be at least 3 l/min so that the resi-
dual air in the system is pulled along with the solar fluid
and conveyed to the air vents.
– You must maintain a flow rate of at least
0.25l/m
– In the case of small systems with a net area of up to
10 m
0.67l/m
– In the case of larger systems, the flow rate in the collec-
tor array must be lower than 0.50l/m
2
min in the collector array.
2
, a flow rate of 0.50 to
2
min is recommended in the collector array.
2
min.
For a suitable nominal flow rate for the collectors, pipe diameter, and pipe length used, see Tab. 6.1 and 6.2.
> Determine the nominal flow rate to be set from Tab.
6.1/6.2.
> Completely open the flow rate limiter with the control
valve (1).
> Allow the solar pump to run on the lowest pump speed. > Check the flow rate on the indicator (2) of the flow rate
limiter.
> Choose a pump speed that sets the flow rate to equal to
or more than the nominal flow rate.
– If the actual flow rate is lower than the nominal flow
rate, switch to the next higher pump speed.
– If the nominal flow rate cannot be reached even at the
highest pump speed, check to see whether it is possi­ble to connect less collectors in series and to switch to a combination of series and parallel connections. Check out other ways of reducing the pressure loss. Observe here the Vaillant solar planning information.
> Use the control valve (1) of the flow rate limiter to set
the flow rate so that it is slightly higher than the nominal flow rate.
If you are using the auroMATIC 620 controller, you can use the set flow rate to calculate the yield.
> Enter the set flow rate on the controller; the controller
then calculates the yield.
For more information, see the operating and installation instructions for the controller.
Set the flow rate in the solar circuit as specified
in ¬tab.6.1 or ¬tab.6.2.
i
1
1,1l/min
2
Fig. 7.2 Flow rate limiter
54 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 55
Commissioning 7
7.5 Flushing the primary heating circuit
Detailed recommendations for the water circuit can be found in BS 6798 and BS 5449: Part 1 (for central heat­ing systems with both small and the smallest pipe width). Pipes which do not form part of the usable heating sur­face must be insulated in order to prevent heat losses and possible freezing. Pipe insulation is particularly important if you are installing pipes under the roof or in open areas under the floor. Discharge valves must be mounted in easily accessible locations, so that the entire system, including the boiler and hot water system, can be discharged. Discharge valves must have a nominal size of 1/2 inch BSP and comply with BS 2879. Copper pipes which comply with BS 2871: Part 1 for water-carrying pipes must be used. All soldered connec­tions in the private hot water pipe system must be made with lead-free soldering material.
Caution!
Risk of material damage as a result
b
of deposits in the unit or system!
Cleaning agents can result in deposits and follow-on damages.
> Use a suitable cleaning agent in
accordance with this instruction manual.
> Never leave cleaning agents in the sys-
tem for longer than 24 hours.
> Completely remove the cleaning agents
from the system by flushing it tho­roughly.
7.6 Water treatment
Caution!
The use of unsuitable heating water can
b
b
Mixing additives with the heating water can result in material damage. However no incompatibility with Vail­lant units has been detected with proper use of the fol­lowing products over a long period.
> When using additives, follow the manufacturer's instruc-
tions without exception.
cause aluminium corrosion resulting in leaks!
In contrast to steel, grey cast iron, and cop­per, for example, aluminium reacts with alkaline heating water (pH value > 8.5) to produce substantial corrosion.
> When using aluminium, make sure that
the pH value of the heating water is bet­ween 6.5 and a maximum of 8.5.
Caution!
Risk of material damage as a result of enriching the heating water with unsuita­ble frost or corrosion protection agents!
Frost and corrosion protection agents can cause changes to the seals, noises during heating mode and possibly subsequent dam­age.
> Do not use any unsuitable frost and cor-
rosion protection agents.
All cleaning must be performed before installing the new boiler and must comply with BS 7593. Information on the use of cleaning agents for the system can be obtained from Sentinel, Betz Dearborn Ltd. Widnes, Cheshire, WA8 8UD. Tel: 0151 420 9595, or Fernox, Alpha Fry Technologies, Tandem House, Marlow Way, Croydon, CR0 4XS. Tel: 0870 8700362.
Vaillant does not accept any liability relating to the com­patibility or efficiency of any additives throughout the heating system
Additives for cleaning measures (subsequent flushing required)
– Fernox F3 – Sentinel X 300 – Sentinel X 400
Additives intended to remain permanently in the system
– Fernox F1 – Fernox F2 – Sentinel X 100 – Sentinel X 200
Additives for frost protection intended to remain permanently in the system
– Fernox Antifreeze Alphi 11 – Sentinel X 500
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 55
Page 56
7 Commissioning
> Inform the operator of the necessary measures if you
have used these additives. > Inform the operator about the required measures for
frost protection.
> Observe all valid national and technical regulations when
treating the filling and supplementary water.
Provided the national regulations and technical stand­ards do not stipulate more stringent requirements, the following applies:
> You must treat the heating water in the following cases:
– If the entire filling and supplementary water quantity
during the operating life of the system exceeds three times the nominal volume of the heating system or
– If the limit values shown in the tables are not obser-
ved.
Total heating output
kW mol/m
< 50
> 50 to £ 200 > 200 to £ 600 > 600
1) For systems with circulation water heaters and for systems with electric heating elements
2) Of specific system volume (nominal content in litres/heating output; in the case of multi-boiler systems, the smallest single heating output is to be used). These values only apply up to 3 times the system volume for filling and supplementary water. Once this triple system vol­ume is exceeded, the water will have to be treated exactly the same as in case of exceeding the limit values given in this table (softening, desalination, hardness stabilisation and desludging).
Overall hardness at smallest boiler heating
2)
surface
20 l/kW
3
No requirement
1)
or < 3 2 1,5 0,02 1,5 0,02 0,02 0,02 0,02 0,02
> 20 l/kW < 50 l/kW
3
mol/m
20,02
> 50 l/kW
3
mol/m
7.7 Filling the cylinder
Caution!
Risk of material damage due to unsuita-
b
ble water!
Unsuitable water can lead to deposits and corrosion damage in the cylinder and in the hot water circuit.
> Use only potable water with a chloride
content of below 250 mg/l in the hot water circuit.
Use the draw-off points to vent the cylinder and
water pipes. Do not use the combined tempera-
i
> Make sure that the drain valve is closed. > Open all of the draw-off points in the cold and hot water
pipes.
> Open the water supply inlet to the cylinder and allow the
water to run until bubble-free water runs from all of the
draw-off points and the air is removed from the system. > Close all of the draw-off points. > Check the system for leaks.
In particular, check the installed electric immersion hea-
ter for leaks. > Open two hot water draw-off points, one at the lowest
point and one at the highest point of the pipe system,
and allow water to run for at least 5 minutes. > Close both of the hot water draw-off points.
ture/pressure relief valve of the cylinder or the pressure relief valve of the cold water safety assembly for venting, since foreign bodies can contaminate or damage the valves.
Table 7.3 Guidelines for the heating water: Water hardness
Heating water charac­teristics
Electrical conductivity at 25 ºC
Appearance Free from sedimentary materials
pH value at 25 ºC 8,2 - 10,0 8,2 - 10,0 Oxygen mg/l < 0.1 < 0.02
Table 7.4 Guidelines for the heating water: Salt content
Unit Low-salt Saline
mS/cm
< 100 100 - 1500
56 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 57
7.8 Filling the central heating system
Commissioning 7
The system can be filled using the built-in filling loop (ecoTEC plus combi boiler only) or via a separate filling connection that is fitted at an easily accessible location in the heating circuit. The filling loop must be removed once filling is complete. If a temporary connection is not possible due to legal regulations, a closed system filling pump with a buffer tank must be used. The heating system is not automatically supplied from the hot water side of the central heating. Alternative procedures for filling closed systems can be found in BS 5449.
Do not use the pressure relief valve of the gas-
fired wall-hung boiler for venting.
i
1
Fig. 7.3 Two port motorised valve
> Place the lever (1) on the two port motorised valve
to "MAN OPEN" and lock it into this position.
> Flush the entire primary central heating system including
the primary heating circuit with cold and hot water.
> Flush, fill, and vent the central heating system in
accordance with the installation instructions of the gas­fired wall-hung boiler.
> Release the lever on the two port motorised valve
by placing it in the "AUTO" position.
3
3
4
5
Fig. 7.4 Setting thermostats
2
2
1
> Remove the upper front cladding (1) from the cylinder. > Dismantle the electric immersion heater cover. > Set the cylinder thermostat (3) and the electric immer-
sion heater thermostat (2) to a maximum of 60 °C for
commissioning and to achieve maximum energy effici-
ency. > Commission the gas-fired wall-hung boiler (¬section
7. 9) until the cylinder reaches the operating temperature
and all radiators in the system are hot. > Then drain the entire central heating system again to
remove any residue from the pipes. > Fill and vent the entire central heating system again as
described in the installation instructions for the gas-fired
wall-hung boiler.
1
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 57
Page 58
7 Commissioning
7.9 Commissioning the gas-fired wall-hung boiler
> Make sure that the control device and thermostats are
set so that heating is required.
> Carry out the commissioning and testing measures for
the gas-fired wall-hung boiler in accordance with the ins­tallation instructions.
> Check whether the gas-fired wall-hung boiler starts ope-
rating and the water in the cylinder and radiators heats up in accordance with the hot water and room thermostat settings.
> After completing the commissioning measures, set the
hot water temperature on the controller (e.g. auroMATIC 560/2 solar controller) to a maximum of 60 °C to achieve optimum energy efficiency in your solar heating system. If you are controlling the hot water temperature via the cylinder thermostat installed in the cylinder, switch the cylinder thermostat (2) on as follows. Set the electric immersion heater thermostat (1) to the required tempe­rature.
> Reattach the cover for the electric immersion heater and
the upper front cladding of the cylinder.
7.10 Setting the hot water thermostat mixer
7.11 Filling in the commissioning report
> Fill in the benchmark cylinder commissioning checklist
located on the last few pages of these instructions.
7.12 Handover to the operator
> Hand over the appropriate instructions and cylinder
papers to the operator. > Make the operator aware that the instructions must be
kept near to the unit. > Draw special attention to the safety instructions which
the operator must follow. > Explain to the operator how to safely use the gas-fired
wall-hung boiler, cylinder, and control devices. > Explain to the operator how to use the solar controller,
hot water control system, and heating control system.
Inform the operator that he can improve the solar yield
by limiting the cylinder heating by lowering the target
cylinder temperature.
In regions with hard water, the set hot water
temperature must not exceed 60 ºC to avoid
i
scaling.
Danger!
Risk of burns and scalds!
a
Water at a temperature of more than 60 ºC can escape from the water draw-off point.
> Install a hot water thermostat mixer in
the hot water pipe to provide effective scald protection.
> Set the hot water thermostat mixer to
less than 60 ºC and check the tempera­ture at a hot water draw-off point.
You can set the hot water from the cylinder to a desired maximum temperature of between 30 and 70 ºC by mix­ing hot and cold water.
> Regulate the hot water thermostat mixer via the adjus-
ting knob to maintain the required temperature on the hot water taps.
> Go through the operating instructions with the operator
and answer any questions. > Inform the operator of the required precautionary mea-
sures to prevent damage to the system and building if
the system is not kept in operation during frost. > In addition, inform the operator that the electric immer-
sion heater is intended as a reserve appliance for water
heating and must not be used to heat water in the cylin-
der at the same time as the gas-fired wall-hung boiler. > In addition, inform the operator that the settings you
have made on the solar heating system must not be
changed. > Inform the operator that the gas-fired wall-hung boiler
and the cylinder must be serviced at least once a year by
a qualified competent person. Recommend a mainte-
nance agreement with a specialist workshop to ensure
the regular maintenance of the gas-fired wall-hung boiler
and cylinder.
For more information, contact Vaillant customer service.
58 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 59
8 Inspection and maintenance
Vaillant solar heating systems are designed for a long and stable working life. In order to guarantee this, the solar heating system should be maintained annually by a competent person approved at the time by the Health and Safety Executive. This can be performed at the same time as boiler and cylinder maintenance and consists primarily of visual inspections. Inspection access to the cylinder is available through the immersion heater boss.
The essential maintenance work on the solar heating system and corresponding maintenance intervals are specified in the following table.
Servicing
After servicing, the servicing engineer must complete the relevant Service Interval Record section of the Benchmark Checklist located on the inside back pages of this document.
Inspection and maintenance 8
Procuring spare parts
If you require spare parts for maintenance or repair work, you must use only Vaillant genuine spare parts. The original components of the unit were also certified as part of the CE declaration of conformity. If you do not use certified Vaillant genuine spare parts, this voids the CE conformity of the unit. We therefore strongly recom­mend that you fit Vaillant genuine spare parts.
Replacement parts
An overview of the available genuine Vaillant spare parts can be obtained:
– From your parts wholesaler. – Alternatively contact Spares Technical Enquiries on
01773 596615 or via email: technicalspares@groupservice.co.uk
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 59
Page 60
8 Inspection and maintenance
Maintenance work Maintenance interval
Solar circuit
Check the system pressure at the gauge on the solar pump station. Annually Visually check pipe work and connections for solar fluid leaks. Annually Check the solar fluid discharge pipe is secure and canister is empty. Annually If necessary following above checks arrange for corrective work to be carried out.
Ensure system cannot go into stagnation. Avoid middle of day (cover collectors if possible). Depressurise the system. NOTE: Drain fluid into suitable canisters. Carry out any repairs to correct any leaks found. Check the pH value of the solar fluid (with litmus paper, pH > 7.5). Annually
Check the frost protection of the solar fluid (use the Vaillant solar fluid tester). Annually Check the operation of the solar pump. Annually Check the flow rate in the solar circuit is set correctly for the system. Annually
Collector Array Visual inspection of the collector, collector fastenings and connections.
Visual inspection only from suitable safe location. Check the pipe insulation for damage and arrange repair if necessary. Annually
Solar controller
Check and record solar gains. Reset as necessary. Annually Check the sensors are secure and temperatures correctly displayed (KOL1, SP1 and SP2). Annually Check settings are correct (see controller manual for details). Annually Check the time programme and temperature settings for auxiliary reheat are correct. Annually
Annually
Cylinder Check all connections to ensure that there are no leaks. Annually Check the temperature and pressure relief valve. Annually Check the expansion relief valve. Annually Check the charge pressure of the hot water expansion vessel. Annually Check water flow rates are correct (check and clean filters as necessary). Annually Ensure set temperatures are correct Annually Check the charge pressure of the expansion vessel, re-pressurise as necessary. Annually Check the function of the hot water thermostat mixer. Annually Fill in the service section of the Benchmark cylinder commissioning checklist. Annually
Tab. 8.1 Maintenance checklist
60 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 61
8.1 Checking the temperature/pressure relief valve and expansion relief valve
> Open each valve manually by turning the valve cap and
check whether water is able to flow to the drain via the tundish without obstruction. Make sure that both valves sit correctly in their idle position.
8.2 Checking the charge pressure of the expansion vessel
> Shut off the water supply pipe and open the nearest hot
water draw-off point to discharge the pressure from the secondary water system.
> Use a pressure gauge to check the expansion vessel
pressure at the measuring point. If the pressure is below
3.0 bar, increase it using a suitable air pump.
> Fill in the maintenance section of the commissioning
report.
Inspection and maintenance 8
8.3 Draining the cylinder
> Close the cold water supply pipe. > Secure a hose to the drain valve. > Place the free end of the hose in a suitable discharge
position. The opening should be around 1 m beneath the cylinder.
> Open the highest hot water draw-off point to reduce the
pressure and vent the water pipes, thus draining them completely.
> Open the cylinder drain valve and leave open until no
more water escapes and the cylinder is completely empty.
> Once the water has drained out, close the hot water
draw-off point and the drain valve.
> Remove the hose from the drain valve.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 61
Page 62
9 Fault finding
9 Fault finding
The tables below provide information on possible faults when the solar heating system is being operated, infor­mation on their causes and how to rectify them. All work on the Vaillant solar heating system (installa­tion, maintenance, repairs etc.) may be performed only by approved competent persons.
Danger!
Risk of death from electric shock!
a
b
Improperly executed work on the solar heating system can result in risk to life and limb.
> Faults may only be eliminated by a com-
petent person approved at the time by the Health and Safety Executive.
Caution!
Risk of damage due to overheating!
Not all electric immersion heaters have a thermal cut-out.
> Use only Vaillant Ltd. electric immersion
heaters with a thermal cut-out as repla­cement parts.
When replacing parts, use only original replace-
ment parts from Vaillant Ltd.
i
We recommend entering into a maintenance agreement.
Fault Cause Remedy
Solar pump
The solar pump doesn't work even though the collector is warmer than the cylinder. (neither motor noises can be heard nor vibrations felt).
The solar pump is running but no solar fluid is flowing from the collector (the solar pump is getting hot). Forward- and return flow temperatures are the same or the cylinder temperature is not increasing at all or only slowly.
The solar pump kicks in late and stops early.
Table 9.1 Troubleshooting
1. No current available. Check the power cable and fuses.
2. Temperature difference set too high or controller is not switching.
3. Maximum temperature reached.
4. The solar pump shaft is blocked by deposits on the bearings.
5. The solar pump is dirty. Dismantle and clean the solar pump. Close the
6. Solar pump is faulty. Replace the solar pump.
7. The flow rate is not set correctly. Check the setting and adjust if necessary.
Air is in the pipe system. Check the system pressure. Operate the solar
1. The temperature difference between
the collector and cylinder has been set too high.
2. Collector connection pieces not insulated (tube collector).
Check the controller. Check the temperature sensors. Reduce the temperature difference.
Switch temporarily to max. speed or unblock the rotor, insert a screwdriver in the notch and turn it by hand.
flow rate limiter and pump ball valve.
pump intermittently at maximum output. Open the air vent on the solar pump and open and vent the cylinder. Vent the backflow preventer. If there is no improvement, check whether there is a "u pocket" anywhere in the piping (e. g. at beam projections or at the bend of water pipes). Change the pipe routing or install additional air vents. if the system has already been commis­sioned and is refilled again, check the automatic air vent: Unscrew the protective cap and check the float using a blunt pin to make sure that it can move freely. If the floater is jammed, change the air vent.
Reduce the temperature difference.
Insulate the collector connection pieces.
62 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 63
Fault finding 9
Fault Cause Remedy
The solar pump starts up and switches off again shortly afterwards. This is repeated several times until the system runs its course. The same occurs in the evening.
The solar pump is making noises. 1. There is air in the solar pump. Vent the solar pump.
Solar heating system
Clocking of the system. Incorrect position of the collector sensor Position the collector sensor in the flow.
The pressure gauge indicates a drop in pres­sure.
The water pressure and amount of discharged water decreases at hot water draw-off points.
The system is making noises. Normal for the first few days after filling the system. If it occurs later, there are two possible causes:
The solar yield is unusually low. The pipe insulation is too thin or incorrect.
Solar controller
auroMATIC 560/2: display example "KOL 1 Err" or similar
The controller temperature difference is too small or the pump speed has been set too high. The solar radiation is not yet sufficient to heat up the entire pipework.
2. Insufficient system pressure. Increase the system pressure.
Pressure loss is normal shortly after filling the system, since air still escapes from the system. If a drop in pressure occurs again later on, it might be caused by an air bubble which was released later. Furthermore, there are fluctuations to the pressure in normal operation mode between 0.2 to 0.3 bar, depending on the system temperature. If the pressure drops continuously, there is a leak in the solar circuit, probably in the collector array. Pressure in the main cold water supply too low. Line strainer in the pressure reducing valve dirty. Pressure reducing valve faulty. Replace the pressure reducing valve. Blockage in the system. Unblock the blockage and replace any
1. System pressure is too low. The solar pump is pulling in air via the air vent.
2. Pump output set too high. Switch to a lower speed.
The system may have been designed incor­rectly.
Faulty sensor (short circuit or interruption). 1. Test the cable connection.
Check whether the entire pipework is fully insulated. Increase the temperature differ­ence of the controller.
Insulate the collector sensor.
First check all screw connections, stuffing boxes at gate valves and threaded connec­tions, then the soldering points. Check the collector array and replace a tube or the collector if necessary.
Tell the operator to notify the water supplier.
Clean the line strainer in the pressure reduc­ing valve and replace it if necessary.
blocked parts. Check the system to see if air is escaping from the expansion relief valve and tempera­ture/pressure relief valve.
Increase the system pressure.
Check the insulation. Check the design of the system (collector size, shading, pipe length) and modify the system if necessary.
2. Measure the resistance values of the dis­connected sensor at known temperatures, and compare these with the manufactur­er's details.
3. Inspect the piping for damage.
Cylinder
The cylinder cools down at night. After the solar pump is switched off, the supply and return lines have different tem­peratures. The collector temperature is higher than the air temperature at night.
Tab. 9.1 Troubleshooting (continued)
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 63
1. The non-return valve is blocked. 1. Check the position of the blue handle.
2. One-pipe circulation in the case of short tube networks with low pressure loss.
2. Check the non-return valve for tightness (jammed cuttings, particles of dirt in the sealing face).
3. Do not connect the solar heat exchanger directly; instead, first pull the supply lines downwards and then upwards to the col­lector (the siphon supports the non-return valve) or mount a two port valve which is switched at the same time as the solar pump.
Install a non-return valve (as close as possi­ble to the cylinder).
Page 64
9 Fault finding
Fault Cause Remedy
Primary heating is not working. The gas­fired wall-hung boiler runs for a short time, goes off, and then comes back on again. This is repeated until the cylinder is at its target temperature.
Only cold or lukewarm water comes out of the draw-off points.
1. Air in the primary heating heat exchanger.
2. Heat exchanger surface area too
small.
1. The cold and hot water draw offs on the cylinder have been mixed up.
2. Hot water thermostat mixer set too
low.
3. Solar heating insufficient; gas-fired
wall-hung boiler does not reheat. External control device faulty.
Air in the primary heating heat exchanger.
Vent the primary heating heat exchanger.
Compare the specifications of the boiler manufac­turer with those of the cylinder manufacturer. It may be possible to solve the problem by setting a higher flow temperature on the gas-fired wall-hung boiler. Turn off the cold water supply, then let water flow out via the hot water draw off. Only a few litres of water flow out if the connection is set up correctly. The hot water withdrawal pipe intake is then in the air space and further draining is not possible. If it is possible to empty the entire cylinder via the hot water draw off, the connections have been laid incorrectly. Change the connections! Increase the setting.
Check whether the gas-fired wall-hung boiler is work­ing.
Check whether the external control device is working. Check that the two port valve is in the DHW position. Replace the two port valve.
Vent the primary heating heat exchanger.
Water flows out of the expansion relief valve (only when heating up).
Water flows out of the temperature and pressure relief valve (only when heating up).
Only connection wiring diagram 6: The thermal cut-out for the primary heating circuit actuated at 80 ºC, thus causing the two port motorised valve to close the flow line to the cylinder.
Table 9.1 Troubleshooting (continued)
Cylinder sensor faulty.
Dirt on the valve seat of the expansion relief valve.
Pressure reducing valve faulty. If water only escapes during heating, switch off the
Expansion vessel faulty. Check the pressure in the expansion vessel. If the
Expansion relief valve faulty. If the pressure is normal, replace the expansion relief
Dirt on the valve seat of the tempera­ture and pressure relief valve.
The temperature control system for the gas-fired wall-hung boiler is faulty.
Cylinder sensor faulty. Check the cylinder sensor and corresponding thermal
Two port valve faulty. Check the function of the two port valve and replace
Temperature and pressure relief valve faulty.
Electric immersion heater faulty. Check the temperature sensor of the electric immer-
The cylinder has been overheated by the solar circuit.
Check the thermal cut-out and repair the fault. Replace the cylinder thermostat. Check the seat of the expansion relief valve and repair the fault.
gas-fired wall-hung boiler and electric immersion heater and check whether the pressure behind the pressure reducing valve is lower than 3.0 bar. If so, replace the pressure reducing valve.
pressure is insufficient, re-establish the pressure and check whether the expansion vessel maintains it.
valve. Check the seat of the temperature and pressure relief
valve and repair the fault. If water is only escaping when being heated up by
the gas-fired wall-hung boiler, check the temperature control system of the gas-fired wall-hung boiler. Check whether the two port valve switches to the heating position when the cylinder temperature is reached.
cut-out, replace the cylinder sensor if necessary, and repair the thermal cut-out fault.
if necessary. If water is only escaping when being heated up by the
electric immersion heater, replace the temperature and pressure relief valve.
sion heater and the corresponding thermal cut-out and replace the electric immersion heater if necessary. Set the maximum cylinder temperature (MAXT 1) on the VRS 560/2 solar controller to a maximum of 75ºC. Use the fuses to deenergise the cylinder thermostat. Unscrew the cover cap of the reset button for the thermal cut-out (TCO) for the primary heating circuit. Press the primary heating circuit TCO button to repair the TCO fault. Mount the cover cap. Switch on the cylinder thermostat using the fuses.
64 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 65
Taking the cylinder out of service 10
Recycling and disposal 11
10 Taking the cylinder out of service
10.1 Temporarily taking the cylinder out of service
Caution!
Risk of damage as a result of the cylin-
b
> Temporarily take the cylinder out of service
by switching the boiler off.
10.2 Permanently taking the cylinder
e
der freezing!
Frost protection and monitoring devices are only active while the boiler is connected up to the power supply.
> Make sure that the cylinder cannot be
damaged if there is a frost.
out of service
Danger!
Risk of death from electric shock from live connections!
There is continuous voltage present on the mains connection terminals of the boiler.
> Interrupt the power supply. > Prevent the power supply from being
switched on again.
> Ensure that any electrical work is carried
out by a qualified competent person.
11 Recycling and disposal
Both the cylinder and its transport packaging are made primarily of recyclable raw materials.
11.1 Cylinder disposal
You must not dispose of the cylinder or any of its acces­sories in normal domestic rubbish.
> Dispose of the old unit and any accessories properly and
in accordance with national regulations.
11.2 Disposal of packaging
The heating specialist company which installs the unit is responsible for disposing of the transport packaging.
> Observe national regulations.
> Switch the boiler off. > Drain the cylinder (¬section 8.3). > Dismantle the hydraulic connections. > Dismantle the temperature sensor. > Remove the wiring for the temperature sensor
from the boiler or external controller.
Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02 65
Page 66
12 Customer service and manufacturer’s guarantee
12 Customer service and
manufacturer's guarantee
12.1 Vaillant service
To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agree­ment. Please contact Vaillant Service Solutions (0870 6060 777) for further details.
12.2 Vaillant guarantee
Vaillant provides a full parts and labour guarantee for this appliance. The appliance and all associated pipe work and controls must be installed by suitably competent persons in accordance with all current and relevant safety, building control and planning regulations and in full compliance with the manufacturer’s instructions. All unvented domestic hot water cylinders must be installed by a competent person to the prevailing build­ing regulations at the time of installation (G3). Terms and conditions apply to the guarantee, details of which can be found on the guarantee registration card included with this appliance. Failure to install and commission this appliance in com­pliance with the manufacturer’s instructions will invali­date the guarantee (this does not affect the customer’s statutory rights).
66 Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
Page 67
Commissioning checklist
and service record
Page 68
MAINS PRESSURE HOT WATER STORAGE SYSTEM COMMISSIONING CHECKLIST
This Commissioning Checklist is to be completed in full by the competent person who commissioned the storage system as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission this equipment to the manufacturer’s instructions will invalidate the warranty but does not affect statutory rights.
Customer Name Telephone Number
Address
Cylinder Make and Model
Cylinder Serial Number
Commissioned by (print name) Registered Operative ID Number
Company Name Telephone Number
Company Address
Commissioning Date
To be completed by the customer on rHFHLSWRID%XLOGLQJ5HJXODWLRQV&RPSOLDQFH&HUWL¿FDWH
Building Regulations 1RWL¿FDWLRQ Number (if applicable)
ALL SYSTEMS PRIMARY SETTINGS (indirect heating only)
Is the primary circuit a sealed or open vented system? Sealed
What is the maximum primary ÀRZ temperature?
ALL SYSTEMS
What is the incoming static cold water pressure at the inlet to the system?
Has a strainer been cleaned of installation debris (if ¿WWHG" Ye s
Is the installation in a hard water area (above 200ppm)? Ye s
If yes, has a water scale reducer been ¿WWHG" Ye s
What type of scale reducer has been ¿WWHG"
What is the hot water thermostat set temperature?
What is the maximum hot water ÀRZ rate at set thermostat temperature (measured at high ÀRZ outlet)?
Time and temperature controls have been ¿WWHG in compliance with Part L of the Building Regulations? Yes
Type of control system (if applicable) Y Plan
Is the cylinder solar (or other renewable) compatible? Ye s
What is the hot water temperature at the nearest outlet?
All appropriate pipes have been insulated up to 1 metre or the point where they become concealed Yes
:
*
Open
No
No
No
S Plan
Other
No
bar
l/min
°C
°C
°C
UNVENTED SYSTEMS ONLY
Where is the pressure reducing valve situated (if ¿WWHG"
What is the pressure reducing valve setting?
Has a combined temperature and pressure relief valve and expansion valve been ¿WWHG and discharge tested? Yes
The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes
Are all energy sources ¿WWHG with a cut out device? Ye s
Has the expansion vessel or internal air space been checked? Ye s
No
No
No
THERMAL STORES ONLY
What store temperature is achievable?
What is the maximum hot water temperature?
ALL INSTALLATIONS
The hot water system complies with the appropriate Building Regulations Ye s
The system has been installed and commissioned in accordance with the manufacturer’s instructions Yes
The system controls have been demonstrated to and understood by the customer Ye s
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Ye s
Commissioning Engineer’s Signature
Customer’s Signature
(TRFRn¿rm satisfactory demonstration and receipt of manufacturer’s literature)
bar
°C
°C
llA installations in England and Wales must be QRWL¿HG to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme.
*
A Building Regulations Compliance &HUWL¿FDWH will then be issued to the customer.
©Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
Page 69
SERVICE RECORD
It is recommended that your hot water system is serviced regularly and that the appropriate Service Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
SERVICE 1 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 3 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 2 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 4 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 5 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 7 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 6 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 8 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 9 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 10 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
Page 70
SOLAR THERMAL COMMISSIONING CHECKLIST
7KLV&RPPLVVLRQLQJ&KHFNOLVWLVWREHFRPSOHWHGLQIXOOE\WKHFRPSHWHQWSHUVRQZKRFRPPLVVLRQHGWKH6RODU7KHUPDO6\VWHPDQGDVVRFLDWHGHTXLSPHQW DVDPHDQVRIGHPRQVWUDWLQJFRPSOLDQFHZLWKWKHDSSropriate Building Regulations and then handed to the customer to keep for future reference.
FailurHWRLQVWDOODQGFRPPLVVLRQWKLVHTXLSPHQWWRWKHPDQXIDFWXrer’VLQVWUXFWLRQVZLOOLQYDOLGDWHWKHZDUUDQW\EXWGRHVQRWDffect statutory rights.
Customer Name Telephone Number
Address
Commissioned by
Company Name Telephone Number
Company Address
Commissioning Date
To be completed by the customer on receLpt oI D %uLldLnJ ReJulDtLons ComplLDnce CertL¿cDte
%XLOGLQJ5HJXODWLRQV1RWL¿FDWLRQ1XPEHU (if applicable)
&RQ¿UPDWLRQWKDWrHTXLred arHDVRIWKHLQVWDOODWLRQKDYHEHHQQRWL¿HGWR/RFDO$XWKRULW\%XLOGLQJ&RQWrol (LABC)
D,QLWLDOVRIFRPPLVVLRQLQJHQJLQHHU
b). Competent Persons Scheme (CPS) details or details of LABC dirHFWQRWLL¿FDWLRQ
&RQ¿UPDWLRQWKDWSDQHOVKDYHEHHQLQVWDOOHGZLWKRXWOHVVHQLQJWKHVWUXFWXrHZHDWKHULQJDQG¿re resistance of the roof in accorGDQFHZLWKWKH rHOHYDQW%XLOGLQJ5HJXODWLRQVDQGVWDQGDrGV,QLWLDOVRIFRPPLVVLRQLQJHQJLQHHU
COLLECTOR DETAILS
Make of collector Model of collector
Serial number of each collector:
i. ii. iii.
,Y. Y. YL
(print name)
(if more than 6 collectors please append additional sheet)
INSTALLATION DETAILS
Solar System Operating Pressure bar (cold) ([SDQVLRQYHVVHODLUQLWrogen charge bar (cold)
([SDQVLRQRUGUDLQEDFNYHVVHOVL]HOLWres
Operating correctly: Yes TrHDWHGIRUOHDNVDQGÀXVKHGYes Filled and purged for air: Yes
System heDt trDnsIer ÀuLd detDLls
:KDWW\SHPDNHRIKHDWWUDQVIHUÀXLGXVHG" 6\VWHPYROXPHOLWres
:KDWLVWKHÀXLGPL[Water % Glycol %
Frost protection prRYLGHGWR&
,VWKHLQVWDOODWLRQLQDKDrGZDWHUDrHDDERYHSSP" Yes No
,I\HVKDVDZDWHUVFDOHrHGXFHUEHHQ¿WWHGRUKDV7PD[EHHQOLPLWHGWRÛ&" Yes No
What type of scale rHGXFHUKDVEHHQ¿WWHG"
Air purged from solar primary circuit: Yes Primary cirFXLWYDOYHVDQGDLUYHQWVVHWWR¿QDORSHUDWLQJSRVLWLRQV Ye s
Pump speed setting recorGHG6SHHGVHWWLQJ0D[ÀRZUDWHOLWrHVPLQ
Solar primary circuit pressure rHOLHIYDOYHVWHVWHGIRUFRUrect operation: Yes Location
'HYLFHIRUOLPLWLQJKRWZDWHUWHPSHUDWXrHRXWOHWVKDVEHHQ¿WWHG Yes No
Type Location
$OOH[SRVHGSLSHZRUNODJJHGLQDFFRrGDQFHZLWKregulations using suitably temperature rated materials Yes
)RUXQYHQWHGKRWZDWHUVWRUDJHF\OLQGHrZLOOFRQWrROVVWRSVRODUÀXLGFLrFXODWLRQLQWKHHYHQWRIF\OLQGHURYHUKHDWLQJ" Ye s
SOLAR SYSTEM CONTROLS
Make and model of DTC
Temperature sensors checked and operating correctly Yes
Differential Temperature ContrROOHU'7&VHWWLQJV7RQ&7RfI&
T ma[&2WKHU'7&6HWWLQJV
7KHUPRVWDWORFDWHGLQEDFNXSKHDWLQJ]RQHRIF\OLQGHU Ye s N o
+DYHRSWLPXPVHWWLQJVIRU+:FRQWrROVEHHQH[SODLQHGWRWKHFXVWRPHU" Yes N o
Does this include Legionella Bacteria prRWHFWLRQVHWWLQJVZLWKEDFNXSKHDWLQJV\VWHPWREULQJERLOHUYROXPHWR&IRUDQKRXURQFHDGD\" Ye s N o
Electrical installation is accorGDQFHZLWK%6 Ye s
/RFDWLRQRIHOHFWULFDOLVRODWLRQVZLWFKWRVRODUFRQWrROSXPSXQLW
ALL INSTALLATIONS
7KHKHDWLQJDQGKRWZDWHUV\VWHPFRPSOLHVZLWKWKHDSSropriate Building Regulations Yes
The system and associated prRGXFWVKDYHEHHQLQVWDOOHGDQGFRPPLVVLRQHGLQDFFRrGDQFHZLWKWKHPDQXIDFWXrer’s instructions Yes
7KHHI¿FLHQWRSHUDWLRQRIV\VWHPDQGLWVFRQWrROVKDYHEHHQGHPRQVWUDWHGWRDQGXQGHUVWRRGE\WKHFXVWRPHU Ye s
The manufacturer’s literaturHLQFOXGLQJ%HQFKPDUN&KHFNOLVWDQG6HUYLFH5HFRrGKDVEHHQH[SODLQHGDQGOHIWZLWKWKHFXVWRPHU Ye s
Commissioning Engineer’s Signature
Customer’s Signature
To con¿rm satisfactory demonstration and receipt of manufacturer’s literature)
$%XLOGLQJ5HJXODWLRQV&RPSOLDQFH&HUWL¿FDWHZLOOWKHQEHLVVXHGWRWKHFXVWRPHr.
+HDWLQJDQG+RWZDWHU,QGXVWU\&RXQFLO++,&
.emehcS snosreP tnetepmoC a hguorht ro yltcerid rehtie )CBAL( lortnoC gnidliuB ytirohtuA lacoL ot de¿iton eb tsum selaW dna dnalgnE ni snoitallatsni llA *
ZZZ.centralheating.co.uk
Page 71
SERVICE RECORD
It is recommended that your hot water system is serviced regularly and that the appropriate Service Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
SERVICE 1 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 3 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 2 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 4 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 5 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 7 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 6 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 8 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 9 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 10 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
Page 72
Supplier
Manufacturer
0020111119_02 GBIE 022012 – Subject to change
Loading...