Vaillant auroMATIC VRS 560 Operating And Installation Manual

For the operator/expert technician
Operating and Installation Manual
auroMATIC 560
Solar Differential Controller
VRS 560
GB
For the operator/expert technician
Operating manual
auroMATIC 560
Solar Differential Controller
General information ...................................................3
Special product features ..........................................3
1 Notes on the documentation .........................3
1.1 Storage of documents ...........................................3
1.2 Symbols used ...........................................................3
1.3 Validity of manual ...................................................3
1.4 CE label ...................................................................... 3
2 Safety ...............................................................3
3 Information on installationand operation ....4
3.1 Vaillant warranty ..................................................4
3.2 Intended use .............................................................4
3.3 Requirements of the installation site ................4
3.4 Care ............................................................................4
3.5 Recycling and disposal ..........................................4
4 Functions ......................................................... 5
4.1 Solar yield .................................................................5
4.2 Reheating ..................................................................5
4.3 Reheating delay .......................................................5
4.4 Anti-legionella function .........................................5
4.5 Pump blocking protection .....................................5
4.6 Circulation .................................................................5
4.7 Calendar ....................................................................5
4.8 Activation duration controlling ...........................5
4.9 Special functions .....................................................6
4.9.1 Advance .....................................................................6
VRS 560
4.9.2 One-time reheating .................................................6
4.9.3 Holiday function ......................................................6
4.10 Cylinder priority ......................................................6
4.11 Frost protection function .....................................6
4.12 Solar circuit protection function .........................6
4.13 Solar pump kick (tube collector function) ........6
5 Operation .........................................................7
5.1 Operator guidance ..................................................7
5.2 Overview of controls .............................................. 7
5.3 Overview of display ................................................7
5.4 Display types ............................................................8
5.4.1 Display, main operating level ...............................8
5.4.2 Display, info level ....................................................8
5.4.3 Display, programming level ..................................8
5.4.4 Display, special functions ......................................8
5.4.5 Display, service/diagnostics level .......................9
5.4.6 Display, installer level ............................................9
5.5 Settings ......................................................................9
5.5.1 Calling up settings and operating values ..........9
5.5.2 Settings at main operating level .........................9
5.5.3 Setting the reheating function timer
program ................................................................... 10
5.5.4 Setting the timer program, circulation
pump ...........................................................................11
5.6 Activating the special functions ..........................11
6 Error messages ...............................................11
Notes on the documentation 1
Safety 2
General information
The auroMATIC 560 solar controller is a temperature­controlled differential controller set for solar hot water generation with a demand-oriented reheating function for Vaillant boilers. The control set is a fully-equipped system for control­ling solar systems with a collector field and a solar cylin­der. The controller can also be used in conjunction with vari­ous other components such as: – A swimming pool heating system or – A second solar cylinder As well as: – A second collector field – A circulation pump – A solid-fuel boiler
If a second collector field is connected, an additional collector sensor (available as an accessory) must be in­stalled. If a second solar cylinder or a swimming pool are added of the system, additional standard sensors (available as accessories) must be installed. It is possible to determine the solar yield by using an ad­ditional yield sensor (available as an accessory).
1.2 Symbols used
Please observe the safety instructions in this operating manual for the operation of the appliance!
Danger!
d
Immediate risk of serious injury or death!
Danger!
e
Risk of fatal electric shock!
Danger!
H
Danger of burning and scalding!
Caution!
a
Potentially dangerous situations for the pro­duct and environment!
Note
h
Useful information and tips.
• Symbol for a required task.
1.3 Validity of manual
This operating manual applies exclusively for units with the following article numbers: 306764, 306767. For the article number of your unit, refer to the identifi­cation plate.
Special product features
The vrDIALOG 810 diagnostic software enables the sim­ple display and query of specific parameters using a PC, and can be obtained from Vaillant as an accessory. For this purpose, the solar controller is equipped with an eBUS interface.
1 Notes on the documentation
The following information is intended to help you throughout the entire documentation. Further documents apply in combination with this oper­ating and installation manual.
We accept no liability for any damage caused by fail­ure to observe these instructions.
Other applicable documents
When operating the auroMATIC 560 solar differential controller, please observe all operating manuals for the components in the system. These operating manuals are enclosed with the relevant system parts and additional components.
1.1 Storage of documents
Please store this operating and installation manual and all other applicable documents in a safe place in case they are needed for future reference. If you move out or sell the appliance, please give the documents to the new owner.
1.4 CE label
CE label indicates that the auroMATIC 560 solar differ­ential controller complies with the basic requirements of the applicable directives in accordance with the type summary.
2 Safety
The controller must be installed by a qualified engineer, who is responsible for adhering to the existing stand­ards and regulations.
Alterations
For alterations to the appliance or to its environment, you must refer to the recognised handicraft business which is responsible for it.
Caution!
a
Risk of damage due to improper alterations! Under no circumstances should you ever at­tempt to make alterations to the control set or other parts of the system.
3Operating manual – auroMATIC 560 0020008427_01
3 Information on installation and operation
3 Information on installation
and operation
3.1 Vaillant warranty
We only grant a Vaillant manufacturers warranty if a suitably qualified engineer has installed the system in accordance with Vaillant instructions. The system owner will be granted a warranty in accordance with the Vaillant terms and conditions. All requests for work during the guarantee period must be made to Vaillant Service Solutions (0870 6060 777).
3.2 Intended use
The auroMATIC 560 solar controller is a state-of-the-art appliance which has been constructed in accordance with recognised safety regulations. Nevertheless, im­proper use can cause serious or fatal injury to the user or others, and the appliance or other property can be damaged. The unit is a control system for domestic hot water cyl­inders with solar heating, and includes a reheating op­tion via a boiler or electrical heating rod. Any other use or extended use is considered to be im­proper. The manufacturer or supplier is not liable for any resulting damage. The user alone bears any risk. Intended use includes the observance of the operating manual and all other applicable documents.
3.3 Requirements of the installation site
The controller must be installed in a dry room.
3.4 Care
You can clean the casing of the controller with a damp cloth and a little soap.
Note
h
Do not use abrasive cleaners or detergents that could cause damage, especially to the display.
3.5 Recycling and disposal
Neither the controller or any of its accessories belong in the household waste. Make sure the old appliance and any existing accessories are disposed of properly.
Caution!
a
Any improper use is forbidden.
Operating manual – auroMATIC 560 0020008427_014
Functions 4
4 Functions
4.1 Solar yield
The solar controller works on the principle of differen­tial temperature control system. The controller always switches on the collector pump when the difference in temperature (collector temperature - cylinder tempera­ture) is greater than the programmed activation differ­ence. The controller switches off the collector pump when the difference in temperature (collector temperature - cylin­der temperature) is less than the programmed deactiva­tion difference. The expert technician sets the parameters to the install­er level when the solar controller is installed.
The solar yield is determined from: – The difference in temperature between the collector‘s
forward flow and return flow
– The flow value specified (during installation) at the
control valve of the flow rate limiter – The running time of the collector pump During installation the expert technician sets the flow rate limiter and enters the flow rate into the solar con­troller at the installer level. The solar yield is calculated by the solar controller. The total yield can be called up and reset in the installer level.
4.2 Reheating
The reheating function allows the cylinder to heat up to the required temperature during a set time window, even if the solar yield is insufficient. In this case the water can be reheated using an external heater or an electrical heating rod. You can set up time windows for reheating the solar cylinder (see Section 5.5.3 for de­tails).
4.3 Reheating delay
The controller is equipped with a reheating delay func­tion to prevent unnecessary reheating by an external heater or an electrical heating rod. This function delays reheating by up to 30 min. in case the collector pump is running and the solar yield becomes available. If the col­lector pump remains off and/or the desired cylinder temperature is not reached after the delay period, the cylinder is reheated using the external heater or electri­cal heating rod. The reheating delay function is activated in the installer level.
4.4 Anti-legionella function
The anti-Legionnaire‘s disease protection function is de­signed to kill germs in the cylinder and pipelines. When the function is activated, the cylinder, the corre­sponding hot water pipes and circulation pump (if in­stalled) are brought to a temperature of at least 60 °C once a week at a specific time on a specific day, or every day.
In doing so, the cylinder temperature is raised to 71 °C and the corresponding circulation pump is switched on (if installed). The anti-legionella function is implemented either via an external heater or electrical heating rod if this is used for reheating. The anti-Legionnaire’s disease protection function will stop once a temperature of at least 68 °C has been maintained for a period of 30 minutes. The anti-legionella function is activated by the expert technician at installer level.
4.5 Pump blocking protection
If no pumping has occurred for 23 hours, all installed pumps are switched on for roughly 3 seconds to prevent the pumps from seizing.
4.6 Circulation
If you only have one collector field connected, a circula­tion pump can be connected to the controller. You can specify up to three heating windows for the circulation pump in the timer program (see Sec. 5.5.4). Set up the time program so that the circulation pump only oper­ates at times when you expect a supply of hot water de­mand will be needed. Otherwise the circulation pump operates unnecessarily and inadvertently cools down the cylinder.
4.7 Calendar
The controller is equipped with a calendar so that it can automatically adjust for daylight-savings time. To acti­vate it, simply enter the current date in the installer level.
Note
h
Please observe that in the event of a power failure the controller only has a power reserve of 30 minutes. After 30 minutes, the internal clock stops and the calender will not automati­cally resume function once power has been re­stored. In this case the time and date will need to be reset.
4.8 Activation duration controlling
Activation duration controlling serves to keep the solar circuit at the activation value, and thus in operation, for as long as possible. The pump is switched on and off in periodical bursts depending on the difference between the collector temperature and lower cylinder sensor. When the activation difference is reached, the function is started (if activated) with an activation duration of 30 % – i.e. the pump is switched on for 18 seconds and then switched off for 42 seconds. If the difference in temperature increases, the activation duration is pro­longed (e.g. 45 seconds on, 15 seconds off). If the differ­ence in temperature falls, the activation duration is re­duced (e.g. 20 seconds on, 40 seconds off). The period length is always a minute. Activation duration control is activated in the installer level.
5Operating manual – auroMATIC 560 0020008427_01
4 Functions
4.9 Special functions
Please refer to Sec. 5.6 for information on how to acti­vate the following special functions.
4.9.1 Advance
When the advance is activated, the reheating function is enabled. This means that the set target value for the cylinder will be maintained by reheating if necessary.
4.9.2 One-time reheating
When this function is activated, the cylinder tempera­ture is reheated to the set level one time.
4.9.3 Holiday function
When this function is activated, the operating mode is switched to "OFF" for the set holiday period (1 to 99 days). This deactivates both the solar yield and the reheating function.
4.10 Cylinder priority
Two solar-charged cylinders can be connected to the heating installation. You can use the PRIO cylinder pri­ority function to define which cylinder should be charged as the highest priority. This is normally the drinking water cylinder. The cylin­ders can only be clearly identified via the cylinder sen­sors (cylinder 1 = Sp 2; cylinder 2 = SP 3). You can only change this setting at the installer level. The cylinder that has been assigned the highest priority will always be charged if the collector temperature is greater than the sum of the actual temperature in the cylinder and the activation difference specified. The heating of the cylinder will stop once the maximum tem­perature for the cylinder is reached, or if the collector temperature is less than the actual cylinder tempera­ture plus the set deactivation difference. The second cylinder can only be heated when the first cylinder is not being heated. The charging of the second cylinder is interrupted for at least 5 minutes every 15 minutes to check whether the cylinder can be charged with the highest priority. The same activation and deactivation conditions apply here as well.
4.12 Solar circuit protection function
If the solar heat exceeds the current heat demand (e.g. all cylinders fully charged), the temperature may occur in the collector field may increase rapidly. If the safety temperature at the collector sensor is ex­ceeded, the collector pump is switched off to protect the solar circuit (solar pump, valves, etc.) from over­heating, or restarting is prevented if a solar reheating requirement exists. The solar pump is switched back on once the system has cooled down. This function is exe­cuted independently for each collector field.
4.13 Solar pump kick (tube collector function)
Depending on the design of the tube collectors, the measured value obtained for the purposes of tempera­ture recording may be subject to a time delay. This can be reduced via the tube collector function. Measured value of collector temperature with active tube collector function: The solar pump is switched on for 15 s (solar pump kick) once the temperature at the collector sensor has risen by 2 °C. The heated solar fluid is thereby transported more quickly to the measuring point. If the temperature difference between the collector and cylinder temperature is at least 10 °C) the solar pump runs for as long as is necessary to heat the cylinder up (differential control). If two solar circuits are connected, the tube collector function is activated for both solar circuits. The function is implemented separately in each case for all collector fields.
4.11 Frost protection function
The frost protection function is relevant to Spain only due to statutory regulations and is deactivated in the as-delivered condition (standard setting: OFF).
Note
h
This function should not be activated to pre­vent undesired cooling of the cylinder.
Operating manual – auroMATIC 560 0020008427_016
Operation 5
5 Operation
5.1 Operator guidance
The controller has a display which consists of symbols, and is designed according to the Vaillant "turn and click" operating concept. You can call up and set values by turning the dial. You can also click the dial in order to call up values within an operating level. You can access the operating and display levels with the three selection buttons. To prevent operating errors, the programming button must be held down for roughly three seconds to reach the installer level.
5.2 Overview of controls
1
2
Fig. 5.1 Controls
Key
1 Display 2 Dial (turn and click) i Information button F Special functions button P Programming button
5.3 Overview of display
13
12
11
10
9 8
Fig. 5.2 Display
Key
1 Programming level 2 Service/diagnostics level 3 Reheating 4 Info level 5 Programming of timer programs 6 Solar yield (flashes if solar yield is available) 7 Units 8 Cursor 9 Multi-function display 10 Weekdays 11 Target/actual value 12 Operating modes 13 Special functions
Display symbols
Timer programs:
Timer program for reheating function
1 2 3
4
5
6
7
Programming of timer program for connected cir­culation pump
Operating modes:
Reheating function with timer program
Reheating function in constant standby mode
No reheating
No actuation of solar pump(s), no reheating
Special functions:
Party
One-time reheating
Holiday function
7Operating manual – auroMATIC 560 0020008427_01
5 Operation
5.4 Display types
5.4.1 Display, main operating level
The main operating level appears when the appliance is switched on. Please refer to Sec. 5.5.2 for information on how to set and change the values.
6
5 4 3
Fig. 5.3 Display, main operating level
Key
1 Display, solar yield present 2 Actual collector temperature 3 Actual time or LEG for anti-legionella function (if active);
FROS for frost protection function;
PROT for solar circuit protection function 4 Current day of the week 5 Current temperature of cylinder (the target temperature can be called up and adjusted by turning the dial) 6 Current operating mode
1 2
5.4.2 Display, info level
You can access the info level by pressing the info but­ton. The display initially appears as seen in the diagram below. You can call up additional information by press­ing the info button again (see Sec. 5.5.1). The informa­tion called up appears on the display for roughly five seconds, then the display returns to the main operating level.
1
5.4.3 Display, programming level
You can access the level for programming the control­ler‘s operating times by pressing the "P" programming button. You can set timer programs here for reheating the solar cylinder and for a connected circulation pump (see Section 5.5.3 or 5.5.4). The display returns to the main operating level if you press the programming button.
1
7
2 6 5
4
Fig. 5.5 Display, programming level
Key
1 Programming level 2 Timer program for solar cylinder reheating
(water tap symbol) or circulation pump
(pump symbol) 3 End time 4 Start time 5 Day of the week or block of days 6 Cursor (marks the value to be changed) 7 Time window
3
5.4.4 Display, special functions
By pressing the "F" button, you can access the special functions: party, one-time reheating, and holiday func­tion. After roughly ten seconds, the selected function is activated and the display returns to the main operating level. Please refer to Sec. 5.6 for information on how to acti­vate the individual special functions.
4
Fig. 5.4 Display, info level
Key
1 Info level 2 Display, solar yield 3 Yield in kWh 4 Set target temperature of cylinder
3
2
2 3
1
Fig. 5.6 Display, special functions
Key
1 Special function activated 2 Cursor (marks the special function selected) 3 Symbol for the special function selected
Operating manual – auroMATIC 560 0020008427_018
Operation 5
5.4.5 Display, service/diagnostics level
The actuators and sensors should be checked by the technician expert. You can access the service/diagnostics level by simulta­neously pressing the programming button "P" and the dial for roughly 3 seconds. All actuators and sensors can be controlled and checked in this level (see Chapter 7 in the installation instructions). The display returns to the main operating level if you press the programming button.
5.4.6 Display, installer level
The parameters at installer level should only be adjust­ed by an expert technician. You can access the installer level by pressing the pro­gramming button "P" for at least 3 seconds. Press the programming button briefly to return to the basic display.
5.5 Settings
5.5.1 Calling up settings and operating values
You can call up the values set at the info level succes­sively by pressing the info button repeatedly. Once called up, the information remains in the display for roughly five seconds then the display returns to the main operating level.
Display Settings
Cylinder temperature target value Yield
Display Settings
Collector sensor 1 temperature
Collector sensor 2 temperature (if connected)
Operating hours, solar pump 1
Operating hours, solar pump 2
The current date is only displayed in the following cases
- a valid date is entered during start-up and
- the calendar has been activated.
Timer program for heating window
Cylinder sensor 1 temperature
Cylinder sensor 2 temperature
Cylinder sensor 3 temperature (if connected)
Table 5.1 Values for settings
Table 5.1 Values for settings (continued)
Further displays will be shown here depending on how many timer programs you have set (see Sections 5.5.3 and 5.5.4).
5.5.2 Settings at main operating level
You can adjust the following settings in the main oper­ating level: – Cylinder temperature target value, – Operating mode, – Current day of the week, – Current time
When you call up a setting, it can be viewed and/or changed for roughly five seconds before the basic dis­play at the main operating level reappears automatical­ly. Click the dial within the five second period to display the next setting.
9Operating manual – auroMATIC 560 0020008427_01
5 Operation
Operating modes:
Reheating function with timer program
Reheating function in constant standby mode
No reheating
No actuation of solar pump(s), no reheating
Reheating function in automatic mode – the
corresponding symbol for the time window status is displayed next to the clock symbol. Time window active
Reheating function in automatic mode
Display Required steps
Time window not active
Turn the dial, after 3 seconds the cursor marks the temperature display, which will be flashing.
Turn the dial to adjust the target value for the cylinder temperature.
Click the dial - The cursor will mark the operating modes. The selected operating mode flashes.
Select an operating mode by turning the dial.
Click the dial - The cursor will mark the day of the week. The selected day of the week flashes.
Turn the dial to select the current day of the week.
Click the dial - The cursor will mark the hours and/or the minutes.
Turn the dial to adjust the current time.
Time window Weekday/
Block of days
H 1 M0 - S0 5:30 22:00 H 2 — — — H 3———
Table 5.3 Default reheating program
Start time End time
There are four steps to setting the times you want:
1. Select the time window,
2. Select a weekday or block of days,
3. Specify the start time,
4. Specify the end time. You can specify up to three time windows, as long as none of the time windows overlap another. For clarification, the individual steps are shown in the following table:
Display Required steps
Press the programming key P Turn the dial until you see the tap sym­bol.
Click the dial - The cursor marks the changeable value (H1), which also flash­es. Select the time window by turning the dial. Settings: H 1, H 2, H 3
Click the dial - The cursor marks the block of days display, which also flashes. Select a block of days or a single day of the week by turning the dial. Settings: (MO-SU); (MO - FR); (SA-SU); (MO); (TU); (WE); (TH); (FR); (SA); (SU)
Click the dial – The cursor marks the start time and the hour display flashes. Select the start time by turning the dial. Click the dial again to set the minutes.
Click the dial – The cursor marks the end time and the hour display flashes. Select an end time by turning the dial. To adjust the minutes, click the dial again.
Table 5.2. Settings in the main operating level
5.5.3 Setting the reheating function timer program
You can create a timer program with up to three time windows for reheating the solar cylinder. The controller is equipped with a default program which can be customised to meet your individual needs.
Table 5.4 Setting time windows
Operating manual – auroMATIC 560 0020008427_0110
Operation 5
Error messages 6
5.5.4 Setting the timer program, circulation pump
You can create a customised timer program for a con­nected circulation pump (only possible for hydraulic plan 1), just as you can for the reheating function. The controller is equipped with a default program for this as well:
Time window Weekday/
Block of days
H 1 M0 - S0 6:00 22:00 H 2 — H 3
Table 5.5 Default circulation pump program
Start time End time
You can access the timer program for the circulation pump by pressing programming button "P" and turning the dial until the pump symbol appears in the display in­stead of the water tap symbol. The setting of the de­sired heating times is done in the same manner as the setting of the heating times for the reheating function (see Sec. 5.5.3). Set up the timer program so that the circulation pump only operates at times when you ex­pect a supply of hot water will be needed. Otherwise the circulation pump operates unnecessarily and inadvert­ently cools down the cylinder.
5.6 Activating the special functions
6 Error messages
The auroMATIC 560 solar controller shows error mes­sages in the main operating level if there is a problem with the temperature sensor. The sensor configuration will always be displayed when the controller is switched on for the first time, or if the power supply has been switched off and on again. De­pending on the set hydraulic plan, the controller recog­nises whether there is an error, or if the sensor is not necessary for operation.
Caution!
a
Never try to repair or carry out maintenance work on the controller yourself. Call in an ap­proved technician. We recommend concluding a maintenance contract for your solar system with a recognised handicraft business.
The following table explains the error messages.
Display Message/Description
Error cylinder sensor 1
This error occurs if the there is a prob­lem with the connected sensor.
Display Required steps
Advance
Press the special function button once­the party symbol flashes for approx. ten seconds in the display, then the function is activated. The function is deactivated automatically when the next reheating window begins. If you want to deactivate the function before, simply reselect the function. The function can only be activated in the reheating operation mode .
One-time reheating
Press the special function button twice ­The one-time reheating symbol flashes in the display for approx. ten seconds, then the function is activated. If you want to deactivate the function before, simply reselect the function.
Holiday function
Press the special function button three times - the holiday function symbol flash­es in the display for approx. ten seconds, and you can use the dial to set the number of holidays. Finally, the function is activated for the set time. If you want to deactivate the function before, simply reselect the function. If the anti-Legionnaire’s disease function is activated, the protection will be car­ried out on the last holiday.
Error cylinder sensor 2
This error occurs if the there is a prob­lem with the sensor, or if it is not con­nected.
Error cylinder sensor 3
This error occurs if the there is a prob­lem with the connected sensor.
Table 6.1 Error messages
No error messages are output for collector sensors Kol 1 and Kol 2. A plausibility check is still possible, e.g. by comparing the collector temperature with the outside temperature.
Table 5.6 Activating the special functions
11Operating manual – auroMATIC 560 0020008427_01