Tyco CIM800 Installation Instructions Manual

CIM800 Contact Input Module – Installation Instructions MZX CIM800
Installation Instructions Doc. version 4.0 1/8
CIM800 Contact Input Module – Installation Instructions
Technical specification
Electromagnetic Compatibility
The CIM800 complies with the following:
respect of Conducted Disturbances, Radiated Immunity, Electrostatic Discharge, Fast Tran­sients and Slow High Energy
EN 61000-6-3 for emissions
Introduction
The CIM800 Contact Input Module is designed to monitor fire contacts such as extinguishing system control, ventilation control, fire door con­trol etc. The CIM800 can be configured as:
Two spur circuits (Class B) monitoring multi-
ple normally open contacts, with short circuit giving a fault output.
Fig. 1: CIM800 Contact Input Module
Parameter Value
Type Identification Value:
145
System Compatibility: Use only with MX
Fire Alarm Control­lers
Environment: Indoor Application
only
Operating Temperature: -25 °C to +70 °C
Storage Temperature: -40 °C to +80 °C
Operating Humidity: Up to 95 % non-
condensing
Dimensions (HWD): 87 x 148 x 14 mm
Weight: 100 g
Mounting Require­ments:
One MK backbox surface mount or an ANC-8 ancillary housing
Table 1: Technical Specifications
Battery Requirements: 
Standby current: Alarm current:
0.505mA
4.5mA
Wire Size:
Min 1.5 mm
2
Max 2.5 mm
2
Maximum Wiring Resistance Monitored Circuit:
10 ohm
Addressable Device Conditions:
NormalActiveShort Circuit wir-
ing fault
Open Circuit
wiring fault
Device Type
Invalid
Device No
Response
Parameter Value
Table 1: Technical Specifications
2/8 Installation Instructions Doc. version 4.0
MZX CIM800 MZX Fire detection system
Two spur circuits (Class B) monitoring single
normally closed contacts, with short circuit giving a fault output.
Single loop circuit (Class A) monitoring a nor-
mally open contact, with short circuit giving a fault output.
Single loop circuit (Class A) monitoring a nor-
mally closed contact, with short circuit giving a fault output.
Two spur circuits (Class B) monitoring multi-
ple normally open contacts, with short circuit giving an alarm.
Single loop circuit (Class A) monitoring multi-
ple normally open contacts, with short circuit giving an alarm.
Features
The CIM800 monitoring features include the fol­lowing configurable items:
Identifies all monitored contacts and signals to
the Fire Controller, the status of monitored contacts and wiring to the contacts.
Can monitor a single normally closed contact.Can monitor two Class B spur circuits, or a sin-
gle class Class A loop circuit.
When two Class B spur circuits are con-
nected, each must be of the same style. A monitored contact going to the active state, on either spur circuit, will cause the CIM800 to report the Active State back to the MX control­ler.
An LED reports the CIM800 status to the user. The LED lights when the contact monitored by
the CIM800 has switched to the active (off normal) state.
The LED when normally off, will pulse when
the CIM800 is polled by the controller.
Wiring notes
Mounting
Installation of modules into an ANC­8 ancillary housing
The housing can accommodate up to eight ancil­lary PCBs. A stacking kit is available if a second layer of PCBs is required.
How to install MX800 modules into an ANC-8 ancillary housing
1 Assemble the required ancillary PCBs onto the
chassis plate as required, fixing as shown in Fig. 3.
2 Assemble the chassis plate into the housing and
secure using fixing screw, see Fig. 2.
NOTICE
There are no user- circuit required set-
tings (such as switches or headers) on the CIM800.
All wiring must conform to the current
edition of IEE Wiring Regulations and BS5839 part 1.
All conductors to be free of earths.Fit the PCB to the M520 cover/ANC-8
ancillary housing.
Connect wiring to the monitored con-
tact. For CIM800 typical wiring config­urations (see Figures 6 to 11).
Verify the correct polarity of wiring
before connecting the CIM800 to the addressable loop
Mounting MZX CIM800
Installation Instructions Doc. version 4.0 3/8
3 Connect the chassis plate earth lead to the hous-
ing, see Fig. 2.
Installation to M520 double gang cover
How to install MX800 modules to an M520 double gang cover
1 Assemble the CIM800 to the M520 Double Gang
cover, using the four screws and washers pro­vided,
2 Fit cover onto MK backbox. 3
If an IP22 rating is required additional sealing must be applied. Apply Loctite S1595
silicone
sealant around the LED, as shown in Fig. 5. Note how the sealant fills the small gap between the LED and its hole in the cover.
Fig. 2: A
NC-8 - Chassis Plate 1 – Chassis plate fixing screw 2 – Chassis plate 3 – Cover earth 4 – Chassis plate earth 5 – Transit screw 6 – Typical positions of 800 modules (4 per row)
CAUTION
Ensure only nylon stand-offs and washers are used.
1
2
3
4
5
6
Fig. 3: ANC-8 - PCB Fixing Detail
1 – Housing 2 – Plate 3 – Nylon spacer 4 – Ancillary PCB. 5 – Plain washer 6 – Nylon nut
Fig. 4: CIM800 Fitted to Cover
2
3
4
5
6
1
TB1
TB2
A+ A- B+ B-
L+ L- L+ L-
PROGRAMMING
PORT
Loading...
+ 5 hidden pages