Tyco BFV-N User Manual

Page 1
Model BFV-N Butterfly Valve Wafer Style
Worldwide
Contacts
www.tyco-fire.com
General Description
For applications requiring supervision of the open position of the valve, the Gear Operators for the Model BFV-N Butterfly Valves are provided with two sets of factory installed internal switches each having SPDT contacts. The supervisory switches transfer their electrical contacts when there is move­ment from the valve’s normal open posi­tion during the rst two revolutions of the handwheel.
NOTICE
The TYCO Model BFV-N Wafer Style Butterfly Valves described herein must be installed and maintained in compli­ance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authori­ties having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Con­tact the installing contractor or product manufacturer with any questions.
Technical Data
Model
BFV-N
Sizes: ANSI Inches (DN)
2 (DN50), 2-1/2 (DN65), 3 (DN80), 4 (DN100), 5 (DN125), 6 (DN150), 8 (DN200), 10 (DN250), 12 (DN300)
Approvals
UL and C-UL Listed FM Approved
California State Fire Marshall under Listing No. 7770-1670:101
Maximum Working Pressure
250 psi (17,2) bar
Materials of Construction: Body
Ductile iron conforming to ASTM A536
Disc
Ductile iron conforming to ASTM A395, Nickel Plated
Seat Material
Grade EPDM “E” rubber conforming to ASTM D2000
Upper Stem
Type 416 Stainless Steel conforming to ASTM 582
Operator
Gear operator with iron housing
Friction Loss
The approximate friction loss, based on the Hazen Williams formula and expressed in equivalent length of pipe with C= 120, is as follows. Unless oth­erwise indicated, the data is based on friction loss information collected at a typical ow rate of 15 feet per second.
4.4 feet of 2 inch Sch. 40 pipe for the 2 inch valve.
6.2 feet of 2-1/2 inch Sch. 40 pipe for the 2-1/2 inch valve.
7.6 feet of 3 inch Sch. 40 pipe for the 3 inch valve.
9.2 feet of 4 inch Sch. 40 pipe for the 4 inch valve.
9.0 feet* of 5 inch Sch. 40 pipe for the 5 inch valve.
8.2 feet of 6 inch Sch. 40 pipe for the 6 inch valve.
12.7 feet* of 8 inch Sch. 30 pipe for the 8 inch valve.
20.1 feet* of 10 inch Sch. 30 pipe for the 10 inch valve.
22.3 feet* of 12 inch Sch. 30 pipe for the 12 inch valve.
*NFPA 13
Page 1 of 4 MARCH 2015 TFP1515
Page 2
TFP1515
B
INDICATOR
OPERATOR
CONNECTION
Page 2 of 4
Nominal
Valve Sizes
Inches
(DN)
2
(50)
2-1/ 2
(65)
3
(80)
4
(100)
5
(125)
6
(150 )
8
(200)
10
(250)
12
(300)
Nominal Installation Dimensions
A B C D E F G H J K
2.53
(64,0)
2.90
(74, 0 )
3.17
(81, 0)
4.17
(106 ,0)
5.17
(131,0)
6.17
(1 57,0)
8.17
(208,0)
10 .17
(258,0)
12.17
(309,0)
1.68
(43,0)
1.81
(46,0)
1.81
(46,0)
2.06
(52,0)
2.19
(56,0)
2.19
(56,0)
2.38
(60,0)
2.68
(69,0)
3.00
(76,0)
H
12.6 2
(320,5)
13.51
(34 3 ,1)
13,88
(352,6)
15.24
(387,0 )
16.49
(418,8)
17. 6 5
(448,3)
20 .11
(510,8)
23.35
(593,1)
26 .10
(663,0)
2.88
(73,0)
3.25
(83,0)
3.38
(86,0)
4.00
(160,3)
4.75
(121,0)
5.25
(133 ,0)
6.50
(165,0)
8.00
(203,0)
9.25
(235,0)
G HANDWHEEL
Inches (mm)
6.48
(164,6)
6.98
(177,3)
7. 2 2
(183 ,4)
7.98
(202,7)
8.48
(215,4)
9.1 0
(23 1,1)
10.35
(262,9)
12.27
(311, 7 )
13.77
(349,8)
6.00
(152,4)
6.00
(152,4)
6.00
(152,4)
6.00
(152,4)
6.00
(152,4)
6.00
(152,4)
10.0 0
(254,0)
11. 8 0
(300,0)
11. 8 0
(300,0)
5.80
(1 47, 3 )
5.80
(1 47, 3 )
5.80
(1 47, 3 )
5.80
(1 47, 3 )
7.8 0
(198,1)
7.8 0
(198,1)
7.9 0
(200,7)
9.50
(241,3)
9.50
(241,3)
2.12
(53,8)
2.12
(53,8)
2.12
(53,8)
2.12
(53,8)
2.12
(53,8)
2.12
(53,8)
2.12
(53,8)
3.03
( 77,0)
3.03
( 77,0)
FLAG
1.3 8
(35 ,1)
2.00
(50,8)
2.55
(64,8)
2.58
(65,5)
4.64
(117, 9)
5.75
(146 ,1)
7.7 7
(1 97,4)
9.77
(248,2)
11.75
(298,5)
1/2" NPT
CONDUIT
5/8
(15,9)
5/8
(15,9)
5/8
(15,9)
5/8
(15,9)
3/4
(19,1)
3/4
(19,1)
3/4
(19,1)
7/8
(22,2)
7/8
(22,2)
Weight
Lbs.
(kg)
21
(10,0)
24
(11,0 )
24
(11,0 )
27
(12,0)
31
(14,1)
34
(15,0)
49
(22,0)
78
(35,0)
103
(4 7, 0 )
GEAR
BODY
K
BOLT
DIAMETER
MODEL BF V-N WAFER STYLE BUTTERFLY VALVE
Installation
The TYCO Model BFV-N Wafer Style Buttery Valves may be installed with flow in either direction and can be positioned either horizontally or verti­cally. They are designed for installation between the faces of ANSI Class 125 and 150 anges. The Series BFV-N are self-sealing between mating anges; therefore, they do not require the use of additional gaskets.
The Model BFV-N may be installed with any pressure class or schedule of pipe or tubing no greater than schedule 40 that is listed or approved for re protec­tion service and installed in accordance with the manufacturer’s instructions.
F
E
D
C
J
FIGURE 1
NOMINAL DIMENSIONS
The wafer bodies have locating lugs to ensure proper centering of the valve body when ange bolts are installed. Refer to Figure 1 for bolt diameter. Bolts and studs must meet the minimum strength requirements of ASTM A307 (Grade B), and the nuts must meet the minimum strength requirements of ASTM A563 (Grade A).
Prior to installation, close the valve. Spread the anges apart to allow the valve to slip easily between the anges. Make sure the pipe ange faces are clean of any foreign material such as scale, metal shavings, or welding slag. Insert the valve between the anges (without ange gaskets). Do not apply lubricant to the seat faces as this may
DISC
A
Nominal
Flange Size
ANSI Inches
(DN)
2 - 4
(50 - 100)
5 - 8
(125 - 200)
10
(250)
12
(300)
Recommended
Minimum Torque
Ft.-Lbs
(Nm)
20 - 30
(27,1 - 40,7)
33 - 50
(44,7 - 67,8)
53 - 75
(71,8 - 101,7)
80 - 110
(108,4 - 149,1)
TABL E A
RECOMMENDED TORQUES
Page 3
TFP1515
SWITCH SHOWN
SHUT
Page 3 of 4
CONTACT RATING:
1/2A @ 125 VDC 1/4A @ 250 VDC
15.1A/12HP @ 125, 250 VAC 5A @ 125 VAC "L"
YELLOW
END OF LINE
RESISTOR
INTERNAL SWITCH WIRING DIAGRAM WITH VALVE IN OPEN POSITION
damage the seat material. Be sure to center the valve and do not damage the liner. Relax the separation of the anges, install, and hand-tighten all ange bolts. Slowly open the valve, checking for free movement of the disc. If valve opens freely, leave the valve in the open position, and using a cross­draw sequence, tighten all ange bolts until the valve is metal-to-metal with both mating anges. Recommended tightening torques are listed in Table A.
Be certain to keep ange faces as paral­lel as possible during and after tighten­ing bolts or studs. After nal tightening, again check the valve for full opening and closing.
As applicable, refer to Figure 2 for the internal switch wiring diagram.
Conduit and electrical connections are to be made in accordance with the authority having jurisdiction and/or the National Electrical Code. With reference to Figure 2, the supervisory switch is intended for connection to the supervi­sory circuit of a re alarm control panel in accordance with NFPA 72. The auxil­iary switch is intended for the unsuper­vised connection to auxiliary equipment in accordance with NFPA 70, National Electric Code.
NOTE: For outdoor applications with internal supervisory switches, it is rec­ommended that wiring connections be made at a temperature above 15°F (-9°C), in order to insure sufficient flex­ibility of the wire lead insulation.
Stop Adjustment Procedure
The gear operator’s OPEN and SHUT position have been factory set. The following procedure should be used if slight adjustments are needed. Refer to Figure 3.
SUPERVISORY
SWITCH
SWITCH SHOWN
WITH VALVE FULL OPEN
YELLOW
ORANGE
ORANGE
PANEL
POWER
FIGURE 2
MODEL BF V-N BUTTERFLY VALVE
Step 1. Turn the Handwheel until the valve is fully closed.
Step 2. Remove the two Lock Screws (A) from the gear operator body.
Step 3. Turn the Shut Stop Screw (B) clockwise until snug.
Step 4. Turn the Handwheel until the valve is fully open.
Step 5. Turn the Open Stop Screw (C) clockwise until snug.
Step 6. Close the valve by turning the Handwheel until the valve is fully in the closed position. Ensure the disc has returned to the fully closed posi­tion and the disc is centered in the seat area. Readjust the Shut Stop Screw if necessary.
Step 7. Replace the two Lock Screws (A) into the gear operator body, locking the stops into position.
Care and Maintenance
The TYCO Model BFV-N Wafer Style Buttery Valves must be maintained and serviced in accordance with this section.
Before closing a re protection system control valve for maintenance or inspec­tion work on either the valve or re protection system which it controls, per­mission to shut down the affected re protection systems must be obtained from the proper authorities and all per­sonnel who may be affected by this decision must be notied.
The owner is responsible for the inspection, testing, and maintenance of their re protection system and devices in accordance with the applicable stan­dards of the National Fire Protection
AUXILIARY
GND
RED
VIOLET
GREEN
+
- -
A
OPEN
BLUE
C
B
A
SWITCH
WITH VALVE FULL OPEN
BELL
+
FIGURE 3
MODEL BF V-N WAFER STYLE
BUTTERFLY VALVE
OPERATOR ADJUSTMENT
Association (e.g., NFPA 25), in addi­tion to the standards of any authority having jurisdiction. Contact the install­ing contractor or product manufacturer with any questions. Any impairment must be immediately corrected.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualied inspec­tion service.
Page 4
TFP1515
Page 4 of 4
Limited Warranty
For warranty terms and conditions, visit www.tyco-re.com.
Ordering Procedure
Wafer Style Butterfly Valves
Specify: (specify inch size) Model BFV-N Wafer Style Buttery Valve with internal supervisory switches, P/N (specify)
Valve Size Valve Part Number
2 . . . . . . . . . . . . . . . . . . . . . . . . . 59-8 01-1-0 20N
2-1/ 2 . . . . . . . . . . . . . . . . . . . . . . .59 -801-1-025N
3 . . . . . . . . . . . . . . . . . . . . . . . . . 59-801-1-030 N
4 . . . . . . . . . . . . . . . . . . . . . . . . . 59-8 01-1-0 40N
5 . . . . . . . . . . . . . . . . . . . . . . . . . 59-801-1-050 N
6 . . . . . . . . . . . . . . . . . . . . . . . . . 59 -8 01-1-0 60 N
8 . . . . . . . . . . . . . . . . . . . . . . . . . 59 -801-1-080 N
10 . . . . . . . . . . . . . . . . . . . . . . . . .59 -801-1-10 0N
12 . . . . . . . . . . . . . . . . . . . . . . . . . 59 -80 1-1-12 0N
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
Copyright © 2015 Tyco Fire Products, LP. All rights reserved.