TYCO B-1 User Manual

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model B-1 — 3.0 K-factor Upright and Pendent Foam-Water Sprinklers
tection Association, in addition to the
General Description
The Model B-1 Upright and Pendent Foam-Water Sprinklers are air-aspi­rating foam discharge outlets de­signed for use in foam-water deluge systems. They are designed for flam­mable liquidrisks where it is desired to apply foam from overhead sprinklers (either upright or pendent) and where follow-upwith plain waterina standard spraysprinkler patternis necessaryas in the case of NFPA 16, “Standard for the Installation of Foam-Water Sprin­kler and Foam-WaterSpray Systems”.
Itis recommended thattheend user be consultedwith respecttothe suitability of thematerials of construction for any given corrosive environment. The ef­fects of ambient temperature, concen­tration of chemicals,and gas/chemical velocity, should be considered, at a minimum, along with the corrosive na­ture to which the sprinklers may be exposed.
The Model B-1 Foam-Water Sprinkler is a redesignation for the Gem Issue B-1 and Star Model B-1.
WARNINGS
TheModel B-1Foam-WaterSprinklers describedherein mustbeinstalled and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro-
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and in­stallation can permanently damage a sprinkler system or its compo­nents and cause thesprinkler to fail tooperate ina fire situationor cause it to operate prematurely.
standardsof anyother authoritieshav­ing jurisdiction. Failure to do so may
impair the performance of thesede­vices.
The owneris responsible formaintain­ing theirfire protectionsystem and de­vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.
Technical Data
Approvals
The M odel B-1 Upright and Pendent Foam-Water Sprinklers are UL and ULC Listed. (Discharge outlets and foam concentrates are Listed for use together. Refer to the individual foam concentrate Listing for operating limi­tations and compatibility with the B-1 Foam-Water Sprinklers as providedin the UL Fire Protection Equipment Di­rectory.)
The M odel B-1 Upright and Pendent Foam-Water Sprinklers meet the re­quirements of MIL-S-901C for light­weight Grade A shock proof equip­ment.
The Model B-1 Pendent Foam-Water Sprinklers meet the requirements of MIL-H-24146.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=3.0GPM/psi
Thread Connection
1/2 inch NPT
Finishes
Natural Bronze
Physical Characteristics
Body . . . . . . . . . . . . . . Bronze
Deflector............ Brass
Agitator ............ Brass
1/2
(43,2 LPG/bar
1/2
Operation
TheModel B-1 Foam-WaterSprinklers are designed with a unique venturi style body. As foam solution (water and foam concentrate mixture) flows through the inlet of the body, air is drawn into thebody through the open­ings adjacent to the wrenching area. The foam solution and air mix is then agitated to create an air-aspirated foam.
The B-1 Foam-Water Sprinklers are designed to discharge foam in a pre­determined discharge pattern, as well as to discharge water similar to stand­ard spray sprinklers. To meet the in­tent of NFPA 16, foam-water sprin­klers must be able to sufficiently
)
distribute water after depletion of the foam concentrate.
Page 1 of 4 TFP840
MARCH, 2006
Page2of4
TFP840
1/2"
NPT
(11,1 mm) NOMINAL
MAKE-IN
WRENCHING
AREA
2-1/8" DIA.
(54,0 mm)
5-13/16"
(147,6 mm)
7/16"
UPRIGHT
AGITATOR
BODY
3/8" DIA. (9,5 mm)
1" (25,4 mm)
ACROSS
WRENCH
FLATS
DEFLECTOR
1/2"
NPT
WRENCHING
AREA
7/16" (11,1 mm) NOMINAL
MAKE-IN
5-15/16"
(150,8 mm)
2-1/8" DIA.
(54,0 mm)
PENDENT
FIGURE 1
MODEL B-1 UPRIGHT AND PENDENT FOAM-WATER SPRINKLERS
NOMINAL DIMENSIONS
1" (25,4 mm)
ACROSS
WRENCH
FLATS
3/8" DIA. (9,5 mm)
BODY
AGITATOR
DEFLECTOR
Design Criteria
The M odel B-1 Upright and Pendent Foam-Water Sprinklers are intended for fire protection systems designed in accordance with the standard installa­tion rules for foam-water sprinklers systems recognized by the applicable Listing agency (e.g., UL Listing is basedon the requirementsofNFPA13 and 16).
Figure 2 provides the nominal dis­charge patterns for reference use.
NOTE
The discharge patterns shown in Fig­ure 2 are not to be used for design purposes or to disregard standard in­stallation rules.
Not l ess tha n two foam-wat er spri n­klers are to be installed in any area, regardless of size, in order to obtain pattern overlap.
The applied density (flow per unit of area) of foam solution must meet the requirements of the Authority Having Jurisdiction for the type flammable liq­uidand occupancy.Per NFPA 16,cov­erage density must not be less than
0.16 GPM/ft2(6,52 mm/min) of floor
area with a resulting minimu m dis­chargepressure ofnot less than30 psi (2,1 bar).
Foam-water sprinkler spacing must not exceed the requirements of NFPA 13 for extra hazard occupancies and the system must be hydraulically cal­culated to obtain the required density and discharge pressure.
NOTE
Discharge outlets and foam concen­trates are Listed for use together. Re­fer to the individual foam concentrate Listing for operating limitations and compatibility withthe B-1 Foam-Water Sprinklers as provided in the UL Fire Protection Equipment Directory.
Installation
TheModel B-1 Foam-WaterSprinklers must be installed in accordance with the following instructions:
NOTE
A leak tight1/2 inchNPT sprinklerjoint should be obtained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi­mum of 21 ft. lbs. (28,5 Nm) of torque may be used to install sprinklers with 1/2 NPT connections. Higher levels of torque may distort the sprinkler inlet and causeimpairment of the sprinkler.
Step 1. Pendent sprinklers are to be installed in the pendent position, and upright sprinklersare to be installedin the upright position.
Step 2. With pipe thread sealant ap­plied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the sprinkler fitting using an 8 or 10 inch adjustable Crescent wrench. With ref­erence to Figures 1 and 3, the adjust­able Crescent wrench is only to be applied to the wrench flats of the wrenching area.
Loading...
+ 2 hidden pages