Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model B-1 — 3.0 K-factor
Upright and Pendent
Foam-Water Sprinklers
tection Association, in addition to the
General
Description
The Model B-1 Upright and Pendent
Foam-Water Sprinklers are air-aspirating foam discharge outlets designed for use in foam-water deluge
systems. They are designed for flammable liquidrisks where it is desired to
apply foam from overhead sprinklers
(either upright or pendent) and where
follow-upwith plain waterina standard
spraysprinkler patternis necessaryas
in the case of NFPA 16, “Standard for
the Installation of Foam-Water Sprinkler and Foam-WaterSpray Systems”.
Itis recommended thattheend user be
consultedwith respecttothe suitability
of thematerials of construction for any
given corrosive environment. The effects of ambient temperature, concentration of chemicals,and gas/chemical
velocity, should be considered, at a
minimum, along with the corrosive nature to which the sprinklers may be
exposed.
The Model B-1 Foam-Water Sprinkler
is a redesignation for the Gem Issue
B-1 and Star Model B-1.
WARNINGS
TheModel B-1Foam-WaterSprinklers
describedherein mustbeinstalled and
maintained in compliance with this
document, as well as with the applicable standards of the National Fire Pro-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage
a sprinkler system or its components and cause thesprinkler to fail
tooperate ina fire situationor cause
it to operate prematurely.
standardsof anyother authoritieshaving jurisdiction. Failure to do so may
impair the performance of thesedevices.
The owneris responsible formaintaining theirfire protectionsystem and devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Approvals
The M odel B-1 Upright and Pendent
Foam-Water Sprinklers are UL and
ULC Listed. (Discharge outlets and
foam concentrates are Listed for use
together. Refer to the individual foam
concentrate Listing for operating limitations and compatibility with the B-1
Foam-Water Sprinklers as providedin
the UL Fire Protection Equipment Directory.)
The M odel B-1 Upright and Pendent
Foam-Water Sprinklers meet the requirements of MIL-S-901C for lightweight Grade A shock proof equipment.
The Model B-1 Pendent Foam-Water
Sprinklers meet the requirements of
MIL-H-24146.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=3.0GPM/psi
Thread Connection
1/2 inch NPT
Finishes
Natural Bronze
Physical Characteristics
Body . . . . . . . . . . . . . . Bronze
Deflector............ Brass
Agitator ............ Brass
1/2
(43,2 LPG/bar
1/2
Operation
TheModel B-1 Foam-WaterSprinklers
are designed with a unique venturi
style body. As foam solution (water
and foam concentrate mixture) flows
through the inlet of the body, air is
drawn into thebody through the openings adjacent to the wrenching area.
The foam solution and air mix is then
agitated to create an air-aspirated
foam.
The B-1 Foam-Water Sprinklers are
designed to discharge foam in a predetermined discharge pattern, as well
as to discharge water similar to standard spray sprinklers. To meet the intent of NFPA 16, foam-water sprinklers must be able to sufficiently
)
distribute water after depletion of the
foam concentrate.
Page 1 of 4 TFP840
MARCH, 2006
Page2of4
TFP840
1/2"
NPT
(11,1 mm)
NOMINAL
MAKE-IN
WRENCHING
AREA
2-1/8" DIA.
(54,0 mm)
5-13/16"
(147,6 mm)
7/16"
UPRIGHT
AGITATOR
BODY
3/8" DIA.
(9,5 mm)
1" (25,4 mm)
ACROSS
WRENCH
FLATS
DEFLECTOR
1/2"
NPT
WRENCHING
AREA
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
5-15/16"
(150,8 mm)
2-1/8" DIA.
(54,0 mm)
PENDENT
FIGURE 1
MODEL B-1 UPRIGHT AND PENDENT FOAM-WATER SPRINKLERS
NOMINAL DIMENSIONS
1" (25,4 mm)
ACROSS
WRENCH
FLATS
3/8" DIA.
(9,5 mm)
BODY
AGITATOR
DEFLECTOR
Design
Criteria
The M odel B-1 Upright and Pendent
Foam-Water Sprinklers are intended
for fire protection systems designed in
accordance with the standard installation rules for foam-water sprinklers
systems recognized by the applicable
Listing agency (e.g., UL Listing is
basedon the requirementsofNFPA13
and 16).
Figure 2 provides the nominal discharge patterns for reference use.
NOTE
The discharge patterns shown in Figure 2 are not to be used for design
purposes or to disregard standard installation rules.
Not l ess tha n two foam-wat er spri nklers are to be installed in any area,
regardless of size, in order to obtain
pattern overlap.
The applied density (flow per unit of
area) of foam solution must meet the
requirements of the Authority Having
Jurisdiction for the type flammable liquidand occupancy.Per NFPA 16,coverage density must not be less than
0.16 GPM/ft2(6,52 mm/min) of floor
area with a resulting minimu m dischargepressure ofnot less than30 psi
(2,1 bar).
Foam-water sprinkler spacing must
not exceed the requirements of NFPA
13 for extra hazard occupancies and
the system must be hydraulically calculated to obtain the required density
and discharge pressure.
NOTE
Discharge outlets and foam concentrates are Listed for use together. Refer to the individual foam concentrate
Listing for operating limitations and
compatibility withthe B-1 Foam-Water
Sprinklers as provided in the UL Fire
Protection Equipment Directory.
Installation
TheModel B-1 Foam-WaterSprinklers
must be installed in accordance with
the following instructions:
NOTE
A leak tight1/2 inchNPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maximum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. Higher levels of
torque may distort the sprinkler inlet
and causeimpairment of the sprinkler.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklersare to be installedin
the upright position.
Step 2. With pipe thread sealant applied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using an 8 or 10 inch
adjustable Crescent wrench. With reference to Figures 1 and 3, the adjustable Crescent wrench is only to be
applied to the wrench flats of the
wrenching area.