TYCO B-1 User Manual

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model B-1 — 3.0 K-factor Upright and Pendent Foam-Water Sprinklers
tection Association, in addition to the
General Description
The Model B-1 Upright and Pendent Foam-Water Sprinklers are air-aspi­rating foam discharge outlets de­signed for use in foam-water deluge systems. They are designed for flam­mable liquidrisks where it is desired to apply foam from overhead sprinklers (either upright or pendent) and where follow-upwith plain waterina standard spraysprinkler patternis necessaryas in the case of NFPA 16, “Standard for the Installation of Foam-Water Sprin­kler and Foam-WaterSpray Systems”.
Itis recommended thattheend user be consultedwith respecttothe suitability of thematerials of construction for any given corrosive environment. The ef­fects of ambient temperature, concen­tration of chemicals,and gas/chemical velocity, should be considered, at a minimum, along with the corrosive na­ture to which the sprinklers may be exposed.
The Model B-1 Foam-Water Sprinkler is a redesignation for the Gem Issue B-1 and Star Model B-1.
WARNINGS
TheModel B-1Foam-WaterSprinklers describedherein mustbeinstalled and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro-
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and in­stallation can permanently damage a sprinkler system or its compo­nents and cause thesprinkler to fail tooperate ina fire situationor cause it to operate prematurely.
standardsof anyother authoritieshav­ing jurisdiction. Failure to do so may
impair the performance of thesede­vices.
The owneris responsible formaintain­ing theirfire protectionsystem and de­vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.
Technical Data
Approvals
The M odel B-1 Upright and Pendent Foam-Water Sprinklers are UL and ULC Listed. (Discharge outlets and foam concentrates are Listed for use together. Refer to the individual foam concentrate Listing for operating limi­tations and compatibility with the B-1 Foam-Water Sprinklers as providedin the UL Fire Protection Equipment Di­rectory.)
The M odel B-1 Upright and Pendent Foam-Water Sprinklers meet the re­quirements of MIL-S-901C for light­weight Grade A shock proof equip­ment.
The Model B-1 Pendent Foam-Water Sprinklers meet the requirements of MIL-H-24146.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=3.0GPM/psi
Thread Connection
1/2 inch NPT
Finishes
Natural Bronze
Physical Characteristics
Body . . . . . . . . . . . . . . Bronze
Deflector............ Brass
Agitator ............ Brass
1/2
(43,2 LPG/bar
1/2
Operation
TheModel B-1 Foam-WaterSprinklers are designed with a unique venturi style body. As foam solution (water and foam concentrate mixture) flows through the inlet of the body, air is drawn into thebody through the open­ings adjacent to the wrenching area. The foam solution and air mix is then agitated to create an air-aspirated foam.
The B-1 Foam-Water Sprinklers are designed to discharge foam in a pre­determined discharge pattern, as well as to discharge water similar to stand­ard spray sprinklers. To meet the in­tent of NFPA 16, foam-water sprin­klers must be able to sufficiently
)
distribute water after depletion of the foam concentrate.
Page 1 of 4 TFP840
MARCH, 2006
Page2of4
TFP840
1/2"
NPT
(11,1 mm) NOMINAL
MAKE-IN
WRENCHING
AREA
2-1/8" DIA.
(54,0 mm)
5-13/16"
(147,6 mm)
7/16"
UPRIGHT
AGITATOR
BODY
3/8" DIA. (9,5 mm)
1" (25,4 mm)
ACROSS
WRENCH
FLATS
DEFLECTOR
1/2"
NPT
WRENCHING
AREA
7/16" (11,1 mm) NOMINAL
MAKE-IN
5-15/16"
(150,8 mm)
2-1/8" DIA.
(54,0 mm)
PENDENT
FIGURE 1
MODEL B-1 UPRIGHT AND PENDENT FOAM-WATER SPRINKLERS
NOMINAL DIMENSIONS
1" (25,4 mm)
ACROSS
WRENCH
FLATS
3/8" DIA. (9,5 mm)
BODY
AGITATOR
DEFLECTOR
Design Criteria
The M odel B-1 Upright and Pendent Foam-Water Sprinklers are intended for fire protection systems designed in accordance with the standard installa­tion rules for foam-water sprinklers systems recognized by the applicable Listing agency (e.g., UL Listing is basedon the requirementsofNFPA13 and 16).
Figure 2 provides the nominal dis­charge patterns for reference use.
NOTE
The discharge patterns shown in Fig­ure 2 are not to be used for design purposes or to disregard standard in­stallation rules.
Not l ess tha n two foam-wat er spri n­klers are to be installed in any area, regardless of size, in order to obtain pattern overlap.
The applied density (flow per unit of area) of foam solution must meet the requirements of the Authority Having Jurisdiction for the type flammable liq­uidand occupancy.Per NFPA 16,cov­erage density must not be less than
0.16 GPM/ft2(6,52 mm/min) of floor
area with a resulting minimu m dis­chargepressure ofnot less than30 psi (2,1 bar).
Foam-water sprinkler spacing must not exceed the requirements of NFPA 13 for extra hazard occupancies and the system must be hydraulically cal­culated to obtain the required density and discharge pressure.
NOTE
Discharge outlets and foam concen­trates are Listed for use together. Re­fer to the individual foam concentrate Listing for operating limitations and compatibility withthe B-1 Foam-Water Sprinklers as provided in the UL Fire Protection Equipment Directory.
Installation
TheModel B-1 Foam-WaterSprinklers must be installed in accordance with the following instructions:
NOTE
A leak tight1/2 inchNPT sprinklerjoint should be obtained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi­mum of 21 ft. lbs. (28,5 Nm) of torque may be used to install sprinklers with 1/2 NPT connections. Higher levels of torque may distort the sprinkler inlet and causeimpairment of the sprinkler.
Step 1. Pendent sprinklers are to be installed in the pendent position, and upright sprinklersare to be installedin the upright position.
Step 2. With pipe thread sealant ap­plied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the sprinkler fitting using an 8 or 10 inch adjustable Crescent wrench. With ref­erence to Figures 1 and 3, the adjust­able Crescent wrench is only to be applied to the wrench flats of the wrenching area.
TFP840
Page 3 of 4
CEILING, METRES
DISTANCEBELOW
CEILING, METRES
DISTANCEBELOW
0 0,5 1,0 1,5 2,0 2,5
0 0,5 1,0 1,5 2,0 2,5
RADIUS, METRES
RADIUS, METRES
3,0 2,0
DATAKEY
FOAM DISCHARGEWATER DISCHARGE
RADIUS, FEET
024868
UPRIGHT
RADIUS, FEET
01,0 246810
PENDENT
8 OR 10 INCH
101,02,03,0
0
2
4
6
CEILING, FEET
DISTANCEBELOW
ADJUSTABLE
WRENCH
APPLYTO
WRENCH
FLATS
ONLY
FIGURE 3
WRENCH FLATS
0
2
4
6
CEILING, FEET
DISTANCEBELOW
8
FIGURE 2
NOMINAL DISCHARGE PATTERNS
(Shown for reference only — Not suitable for design purposes)
Frequent visual inspections are rec-
Care and
ommendedtobeinitiallyperformedfor sprinklersinstalled inpotentially corro-
Maintenance
siveatmospheres toverify the integrity ofthe materialsof constructionas they
TheModel B-1 Foam-WaterSprinklers must be maintained and serviced in accordance with the following instruc­tions:
NOTE
Before closinga fire protection system main control valve for maintenance work on thefire protection system that itcontrols, permission toshutdownthe affectedfire protection systemmustbe obtained from the proper authorities and all personnel who may be affected by this action must be notified.
Model B-1 Foam-Water Sprinklers must never be painted, plated, coated or altered in any way after leaving the factory; otherwise, the spray perform­ance may be impaired.
Care must be exercised to avoid dam­age to the sprinklers - before, during, and after installation. Sprinklers dam­aged by droppin g, s triking, wrench
may be affected by the corrosive con­ditions present for a given installation. Thereafter, annual inspections per NFPA 25 are required.
The owner is responsible for the in­spection, testing, and maintenance of their fire p rotection system and de­vices in compliance with this docu­ment, as well as with the applicable standards of the National Fire Protec­tion Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The in­stalling contractor or sprinkler manu­facturer should be contacted relative to any questions.
It is rec ommen ded that foam-water sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.
twist/slippage, or the like, must be re­placed.
Page4of4
TFP840
Limited Warranty
Products manufactured byTyco Fire& Building Products ( TFBP) ar e war­ranted solely to the original Buyer for ten (10) years againstdefects inmate­rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com­ponents manufactured by companies not affiliated by ownership with TFBP or forproducts and componentswhich havebeen subject tomisuse,improper installation, corrosion, or which have not been installed, maintained, modi­fied orrepaired in accordance with ap­plicable Standards of theNational Fire Protection Ass ociation, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to bedefective shall be either repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizesany persontoassumefor it, any otherobligation inconnection with the sale of products or parts of prod­ucts.TFBP shallnot be responsiblefor sprinkler systemdesign errorsor inac­curate or incomplete information sup­plied by Buye r or Buy er’s repre­sentatives.
In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect,special or consequentialdam­ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price.
Theforegoingwarrantyismadeinlieu of any and all other warranties, ex­press or implied, including warranties ofmerchantabilityand fitnessfor a par­ticular purpose.
This limited warranty sets forth theex­clusive remedy for claims based on failure of or defect in products, materi­als or components, whether the claim is made in contract, tort, strict liability or any other legal theory.
This warranty will apply to the full ex­tent permittedby law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder.
Ordering Procedure
Whenplacing an order,indicatethefull product name. Refer to the Price List for complete listing of Part Numbers.
Contact your local distributor for avail­ability.
Upright Foam-Water Sprinklers:
Specify: Model B-1 Upright Foam­Water Sprinkler, P /N 49-210-1-001 .
Pendent Foam-Water Sprinklers:
Specify: Model B-1 Pendent Foam­Water Sprinkler, P /N 49-211-1-001 .
TYCO FIRE & BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Loading...