Tyco AV-1-300 Specification

Worldwide
Contacts
www.tyco-fire.com
Model AV-1-300 Alarm Check Valve, 300 psi (20,7 bar) 2-1/2, 4, 6 & 8 Inch (DN65, DN100, DN150 & DN200) Vertical or Horizontal* Installation
General Description
The TYCO Model AV-1-300 Alarm Check Valves are divided seat ring, rubber-faced clapper, waterow alarm check valves that are intended for use in wet pipe (automatic sprinkler) re protection systems. They may be installed vertically or horizontally*, and they are designed to automati­cally actuate electric and/or hydraulic alarms when there is a steady ow of water into the system that is equivalent to the discharge rate of one or more sprinklers.
A separately ordered Model RC-1 Retard Chamber (Ref. Technical Data Sheet TFP920) is required for installa­tions subject to variable pressures. It is used to help prevent false alarms asso­ciated with pressure variations in public water supplies.
The AV-1-300 Alarm Check Valve Trim includes pressure gauges to monitor system pressure conditions, a bypass check valve, a main drain valve, and an alarm test valve. The bypass check valve reduces the possibility of false alarms by permitting slow as well as small transient increases in water sup­ply pressure to be passed through to the system without opening the water­way cla p p e r.
NOTICE
The TYCO Model AV-1-300 Alarm Check Valves described herein must be installed and maintained in com­pliance with this document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition to the standards of any authorities having jurisdiction. Fail­ure to do so may impair the integrity of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating condition. Contact the installing con­tractor or product manufacturer with any questions.
Technical Data
Approvals
UL and C-UL Listed FM Approved
Working Water Pressure Range
20 to 300 psi (1,4 to 20,7 bar)
Friction Loss
Refer to Graph A.
End Connections
Groove x Groove Flange x Groove Flange x Flange Refer to Table A for size applicability
Weights
Refer to Table A.
Physical Characteristics
The body is ductile iron, the hand-hole cover is ductile iron, and the seat ring is bronze. The clapper for the 2-1/2 inch (DN65) valve size is stainless steel. The clapper for the larger valve sizes is ductile iron. All valve sizes utilize an EPDM clapper facing.
Flanged connections are available drilled per ANSI, ISO, AS, and JIS specications as detailed in Table B.
Threaded port connections for the AV-1-300 Valves are available NPT threaded or threaded per ISO 7-1 as detailed in the Ordering Procedure sec­tion. Valves with NPT threaded ports will readily accept the trim arrange­ments detailed in Figures 4 through 6.
For Fire Pr otecti on pres sure ra ting, li sting
and approval information, contact
your Tyco Representative.
* 4, 6, and 8 inch (DN100, DN150, and DN200) valve sizes
Page 1 of 20 SEPTEMBER 2014 TFP910
TFP910
8
VALVES
Page 2 of 20
VALVE PARTS
NO.
DESCRIPTION REF.
1
Valve Body NR
2
Handhole Cover
3
Handhole Cover
. . . . . . . . . .
Gasket
4
Seat Ring NR Clapper See (b)
5 6 7 8
9
10
11
11
5
. . . . . . . . . .
Clapper Washer Lock Nut, 2-1/2 Inch Valve See (b) Self-Locking Hex Cap Screw, 4, 6, & 8 Inch Valves See (b)
Clapper Hinge Pin Bushing, 2-1/2 Inch Valve NR 4, 6, & 8 Inch Valves
. . . . . . . . . . .
QTY.
. . . . . . .
. . .
. . . . . . . .
. . . .
. . .
. . .
. . . . . . .
. .
. . .
. . . .
11
5
1 1
1 1 1 1 1
1
1 1
2
4 1
NR
See (a)
See (a) or (b)Clapper Facing See (b)
See (b)Clapper Hinge Pin
NR See (b)Clapper Spring
VALVE PARTS
NO.
DESCRIPTION REF.
Handhole Cover
12
Hex Bolt, 2-1/2 Inch Valve, 1/2-13 UNC-2A x 1-1/4" Long CH 4 Inch Valve, 1/2-13 UNC-2A x 1-3/4" Long CH 6 Inch Valve, 1/2-13 UNC-2A x 1-3/4" Long CH 8 Inch Valve, 3/4-10 UNC-2A x 2" Long CH
13
Clapper Hinge Pin Square Head Pipe Plug, 3/8" NPT, 4, 6, & 8 Inch Valves only CH
1
. . . . .
. . . . .
. . . . .
. . . . . . . . .
. . . . . . .
QTY.
4
4
6
6
1
REPLACEMENT PARTS
NO.
DESCRIPTION P/N
(a)
Repair Parts Kit, Includes 3 & 6 2-1/2 Inch Valve 4 Inch Valve 6 Inch Valve 8 Inch Valve
(b)
Clapper Assembly, Includes 5-9, 11 2-1/2 Inch Valve Includes 5-11 4 Inch Valve 6 Inch Valve 8 Inch Valve
NOTES:
1.
2.
3.
. . . . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . .
F x F valve shown for reference; components for G x G and F x G valves are shared.
NR: Not Replaceable CH: Common Hardware
. . . . . .
. . . . . .
92-200-1-216 92-200-1-416 92-200-1-620 92-200-1-816
92-200-1-218
92-200-1-423 92-200-1-623 92-200-1-823
10
9
10
4
3
13
2
12
CLAPPER ASSEMBLY 2-1/2 INCH
VALVE
6
7
10
6
7
8
CLAPPER
ASSEMBLY
4, 6, & 8 INCH
FIGURE 1
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200)
MODEL AV-1-300 ALARM CHECK VALVE ASSEMBLY
Nominal
Valve Size,
Inches
(DN)
2-1/ 2
(65)
4
(100)
6
(150 )
8
(200)
Groove x Groove,
Lbs.
(kg)
22
(10,0)
38
(17, 2 )
58
(26,3)
102
(46,3)
TABLE A
Flange x Groove,
Lbs.
(kg)
28
(12,7 )
47
(21, 3)
70
(31, 8)
120
(54,4)
Flange x Flange,
Lbs.
(kg)
N/A
57
(25,9)
84
(38,1)
149
(67, 6 )
AVAILABLE VALVE END CONNECTIONS AND VALVE WEIGHTS
FLOW RATE IN LITRES PER MINUTE (LPM)
FLOW RATE IN GALLONS PER MINUTE (GPM)
NOMINAL PRESSURE DROP
4.0
(1 PSI = 0,06895 BAR)
Bolt Holes
600400 1000
(1 GPM = 3,785 LPM)
2000
TFP910
Page 3 of 20
1000050003000 7000 15000
Nominal
Valve
Size
2-1/2 Inch
(DN65)
4 Inch
(DN100)
6 Inch
(DN150)
8 Inch
(DN200)
3.0 0,20
2.0
0,10
2-1/2 INCH (DN65)
1.0
0.9
IN POUNDS PER SQUARE INCH (PSI)
0.8
0.7
200100
300
4 INCH (DN100)
500400
6 INCH (DN150)
8 INCH (DN200)
3000700 1000 2000 4000
0,09 0,08
0,07
0,06
0,05
GRAPH A
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200) MODEL AV-1-300 ALARM CHECK VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW
Flange Drilling Specication
Nominal Dimensions in Inches and (mm)
ANSI B16.1
(Class 125)
1
ISO 2084
(PN10)
2 3
ISO 2084
(PN16)
JIS B 2210
(10K)
Dim.ADim.BQty. Dim.ADim.BQty. Dim.ADim.BQty. Dim.ADim.BQty. Dim.
5.50
(139,7)
7.50
(190,5)
9.50
(241,3)
11.75
(298,5)
0.75
(19,0)
0.75
(19,0)
0.88
(22,2)
0.88
(22,2)
4
USE
8
ISO 2084
(PN16)
8
11.61
8 8
(295,0)
0.87
(22,0)
Dim. A
Bolt Circle
Diameter
12
5.51
4
(140,0)
6.89
8
(175,0)
9.45
8
(240,0)
11.42
(290,0)
0.75
(19,0)
0.75
(19,0)
0.91
(23,0)
0.91
(23,0)
4
8
8
12
5.71
(145,0)
7.09
(180,0)
9.45
(240,0)
11.61
(295,0)
1
Same drilling as for B16.5 (Class 150) and B16.42 (Class 250).
2
Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10).
3
Same drilling as for BS 4504 Section 3.2 (PN16) and DIN 2532 (PN16).
0.71
(18,0)
0.71
(18,0)
0.87
(22,0)
0.87
(22,0)
Dim. B Bolt Hole Diameter
Qty. N
Number of
AS 2129 (Table E)
A
5.00
(127,0)
7.00
(178,0)
9.25
(235,0)
11.50
(292,0)
NOMINAL PRESSURE DROP IN BAR
Dim.BQty.
0.71
(18,0)
0.71
(18,0)
0.87
(22,0)
0.87
(22,0)
4
8
8
8
FLANGE DRILLING SPECIFICATIONS
TABLE B
TFP910
WATERFLOW
RESTRICTION
ALARM PORT
PRESSURE
PRESSURE
SCREEN
DRAIN RESTRICTION WITH 0.125" (3,2 mm) ORIFICE
INLET RESTRICTION WITH 0.219" (5,6 mm) ORIFICE
Page 4 of 20
Operation
When the re protection system is ini­tially pressurized, water ows into the system until the water supply and sys­tem pressure become equalized, and the torsion Spring closes the Water­way Clapper in the Alarm Check Valve. Once the pressures stabilize, the Alarm Check Valve is in service and the cen­trally located groove in the Seat Ring is sealed. Consequently, with the Alarm Check Valve set for service, there is no ow through the alarm port to the alarm devices (i.e., water motor alarm and/or pressure alarm switch).
When there is a steady ow of water into the sprinkler system due to a sprin­kler operation, the Waterway Clapper opens as shown in Figure 2. Water is then permitted to ow into the centrally located groove in the Seat Ring and out through the alarm port towards the Restriction Assembly (Figure 3). When the ow through the Inlet Restriction of the Restriction Assembly exceeds the ow through the Outlet Restriction, the Retard Chamber (where provided for systems with variable pressure), begins to ll.
Subsequently, the Water Motor Alarm and/or the pressure alarm switch will be actuated. The alarms will continue to be actuated as long as the Water­way Clapper remains open. Water in the alarm lines will automatically drain out through the 1/8 inch (3,2 mm) Drain Orice in the Restriction Assembly (Figure 3) when the Waterway Clap­per closes (due to a stop in the ow of water into the sprinkler system).
For variable pressure systems, slow as well as small transient increases in water supply pressure may continue to build up in the system (via the Bypass Check Valve) without opening the Waterway Clapper.
A transient surge in supply pres­sure that is sufcient only to open the Waterway Clapper momentarily will not cause a false alarm, and a portion of the increase in pressure will be trapped within the system, thus reducing the possibility of another opening. Any water in the alarm line is automatically drained, further reducing the possibil­ity of a false alarm due to a successive transient surge in supply pressure.
Design Criteria
In planning installation of the TYCO Model AV-1-300 Alarm Check Valves, consideration must be given to the dis­posal of the large quantities of water that may be associated with draining the system or performing a ow test.
PRESSURE
RETARD
CHAMBER
ASSEMBLY
1/8" (3,2 mm) ORIFICE OUTLET
WHEN FLOW THROUGH
RESTRICTION ASSEMBLY
INLET EXCEEDS OUTLET,
RETARD CHAMBER
BEGINS TO FILL
ALARM SWITCH
WATERFLOW
TO WATER
MOTOR ALARM
7/32" (5,6 mm) ORIFICE
INLET
MAIN DRAIN VALVE
ONCE RETARD CHAMBER OVERFLOWS, WATERFLOW PRESSURE
ALARM SWITCH AND
WATER MOTOR
ALARM ACTUATE
FIGURE 2
2-1/2, 4, 6 & 8 INCH (DN65, DN100, DN150 & DN200)
MODEL AV-1-300 ALARM CHECK VALVE
OPERATION
FIGURE 3
RESTRICTION ASSEMBLY
(Provided with Alarm Check Valve Trim)
Valves installed in the vertical position must have the ow going up. Valves installed in the horizontal position must be positioned so that the drain connec­tion points down.
The sprinkler system designer must be aware that the conguration of the piping network and its tendency to trap pockets of air (such as in the case of a peaked-roof gridded sys­tem) can affect the performance of the alarm system. Although a slight amount of trapped air is desirable to prevent signicant pressure increases due to thermally induced expansion of the water, a large quantity of trapped air in a system may result in the possibility of an intermittent alarm.
UPON SPRINKLER FLOW, WATERWAY
CLAPPER OPENS
WATERFLOW
TO SYSTEM
SYSTEM
GAUGE
SUPPLY
GAUGE
ALARM CHECK
WATERFLOW
THROUGH SEAT
RING GROOVE AND
VALVE
The possibility of an intermittent alarm condition is a consequence of the fact that the ow out of the system through the test valve or a single sprinkler is very small relative to the ow that can be passed through the valve. This dif­ference increases with valve size. If the system were free of trapped air, ow in would equal ow out and the Waterway Clapper would always stabilize at some open position (as needed to accommo­date the required ow). With trapped air in the system, however, the Water­way Clapper rst opens wider since the system initially demands greater ow until the air pockets are compressed (back to nearly the supply pressure), and then it will tend to return closer
TFP910
Page 5 of 20
to the Seat Ring. If the volume of the air pockets is excessive, ow into the system can be momentarily reduced to nearly zero (once the air pockets are compressed) and the Waterway Clapper may close, causing ow to the alarms to be shutoff.
After the Waterway Clapper has closed, sufcient water must ow out of the system before the Waterway Clapper will again open. A repetition of the above described condition is termed an intermittent alarm.
Using a vent (which can also serve as an end-of-line Inspector’s Test Connection) piped from the top of a cross main or end of a branch line at the point most remote from the alarm valve, and lling the system slowly in accordance with the steps described in the Setting Procedure section, can pre­vent an excessive amount of air from being trapped.
Installation
NOTICE
Proper operation of the TYCO Model AV-1-300 Alarm Check Valves depends upon the trim described in this data sheet installed in accordance with the following instructions. Failure to fol­low the appropriate trim installation instructions may prevent the device from functioning properly as well as void listings/approvals and the manu­facturer’s warranties.
The Alarm Check Valves must be installed in readily visible and acces­sible locations.
It is recommended that provision be made for viewing the alarm line drain water by locating the main drain outlet in a readily visible area.
Wet pipe fire protection systems must be maintained at a minimum tempera­ture of 40°F (4°C).
Step 1. Trim the Alarm Check Valve in accordance with Figure 4, 5, or 6, as applicable. Apply pipe-thread sealant sparingly to male threads only.
Step 2. The Alarm Vent Trim illustrated in Figure 8 must be installed if a water motor alarm is not to be used.
Step 3. Plug unused alarm connections.
Step 4. Suitable provision must be made for disposal of alarm line and system drainage water. Drainage water must be directed so that it will not cause damage or result in danger­ous conditions.
Step 5. The alarm line drain must be arranged so that there will be no dan­ger of freezing.
Step 6. The check valve in the exter­nally mounted bypass around the Waterway Clapper must be installed with its arrow pointed up, and the drain check valve must be installed with its arrow pointing towards the drain.
Step 7. It is recommended that a vent connection (which may also be used as an end-of-line Inspector’s Test Connection), be piped from a cross main or branch line at the point most remote from the alarm valve. The vent line should be connected to the top of a cross main or to the end of a branch line and be located at the highest level of a multi-level installation.
The vent connection can be used to bleed-off excessive air from the sys­tem, and therefore, minimize the possibility of a false alarm due to a transient surge in supply pressure. The contraction/expansion associated with an excessive amount of trapped air could also cause the Waterway Clap­per to cycle open and shut during an inspector’s test or during a discharge by a single sprinkler.
Setting Procedure
Steps 1 through 11 are to be performed when initially setting the Model AV-1­300 Alarm Check Valve or after system operation due to a re.
NOTICE
Filling the system with water will result in operation of the associated alarms. Consequently, notification must first be given to the owner and fire department, central station, or other signal station to which the alarms are connected.
Notify the proper authorities and all personnel who may be affected that an alarm test is to be performed.
After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni­toring proprietary and/or central station alarms.
Step 1. Open the 1/4 inch Gauge Test Valves for the Supply and System Pres­sure Gauges.
Step 2. Check to see that the Hand­hole Cover bolts are tight. If not, cross-tighten them.
Step 3. Close the Alarm Test Valve. Step 4. Open the remote cross main or
branch line vent connection. (Refer to Step 7 in the Installation section.)
Step 5. Slowly open the main control valve until the sound of owing water just begins and then open the valve one more turn.
Step 6. Close the remote branchline vent connection after the discharge of aerated water ceases, and the outlet has owed full for at least 15 seconds.
Step 7. Fully open the main control valve.
Step 8. Open the end-of-line Inspec­tor’s Test Connection (or Alarm Test Valve, if acceptable to the authority having jurisdiction) and verify that the system alarms operate.
Step 9. Close the end-of-line Inspec­tor’s Test Connection (or Alarm Test Valve).
Step 10. Verify that water ceases to ow from the alarm line drain. If water continues to ow, follow the corrective procedure described in the Care and Maintenance section.
The Restriction Assembly has a 1/8 inch (3,2 mm) diameter drain orice. Sufcient time must be allowed for drainage of the Retard Chamber and the piping to the water motor alarm.
Step 11. After verication that the ow of water out of the alarm line drain has stopped, the alarm valve is set and is ready for service.
TFP910
TO DRAIN
PRESSURE ALARM
PRESSURE
Page 6 of 20
1/2 INCH NPT
CONNECTION
FOR WATERFLOW
SWITCH
LOCATION FOR OPTIONAL ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
MODEL RC-1
RETARD
CHAMBER
ORDERED
SEPARATELY
(FOR VARIABLE
PRESSURE
SYSTEMS)
NO.
DESCRIPTION P/N
1
300 psi/ 2000 kPa Water Pressure Gauge
2
1/4" Gauge Test Valve
3
1/2" Swing Check Valve
4
1/2" Globe Valve 46-047-1-004
5
1/2" Y-Strainer 52-353-1-005
6
Restriction Assembly
7
1-1/4" Angle Valve
8
External By-Pass Tube
9
Alarm Test Tube
10
1/2" NPT x 1/2" Tube Connector
11
1/2" NPT x 5/8" Tube Connector
12
1/4" Plug
13
1/2" Union
14
1/4" 90° Elbow
15
1/2" 90° Elbow
16
1/2" Tee CH
LOCATION FOR OPTIONAL ELECTRICALLY
SUPERVISED
N.O. ALARM
CONTROL
VALVE
RESTRICTION
ASSEMBLY,
SEE FIGURE 3
. . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . .
QTY.
2
. .
92-343-1-005
2
. .
46-005-1-002
2
.
46-049-1-004
1
. . . . . . .
. . . . . . . . .
. . . . . . . . .
. . . . . . . . .
CONNECTION FOR
FOR WATERFLOW
PRESSURE ALARM
18
22
22
1 1
. . . .
. . . . . .
1
. .
1
. . . . . . .
1
2
2 2 1 1 1 2
3/4 INCH NPT
WATER MOTOR
ALARM
1/2 INCH NPT
CONNECTION
SWITCH
CONNECTION FOR
WATER MOTOR
5
22
6
DRAIN VALVE
(NORMALLY
CLOSED)
15 13
22 22
92-210-2-005 46-048-1-007 92-304-1-017 92-304-1-047
CH
CH CH CH CH CH
3/4 INCH NPT
ALARM
MAIN
NO.
NOTES:
1.
2.
EXTERNAL
BY-PASS
TUBE
ALARM TEST VALVE (NORMALLY
CLOSED)
16
3
22
DESCRIPTION
17 18
1/2" x 1/2" x 3/4" Tee CH 19 20 21
1/4" x 2-1/2" Nipple CH 22 23
1/2" x 2" Nipple CH 24 25
1/2" x 3" Nipple 26
1/2" x 4" Nipple 27 28
1-1/4" x 2-1/2" Nipple CH 29
1-1/4" x 3-1/2" Nipple CH
All Fittings and Nipples are galvanized (Standard Order).
CH: Common Hardware.
8
11
3
11
16
10
4
23
2427
28
7
29
19
1-1/4 INCH NPT
CONNECTION
QTY.
. . . .
2
. . . .
1
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
22
1 2
. . . . .
1
. . . . .
7 2
. . . . .
1 1 1 1
. . . .
1
. . . .
1
9
10
23
25
2-1/2 INCH (DN65)
GROOVE x GROOVE
26
MODEL AV-1
ALARM VALVE,
P/N
CH1/2" x 1/4" x 1/2" Tee
CH1-1/4" x 1-1/4" x 1/2" Tee CH1/4" x 1" Nipple
CH1/2" x 1-1/2" Nipple
CH1/2" x 2-1/2" Nipple CH CH CH1/2" x 6" Nipple
TEST TUBE
20
17
17
SHOWN
ALARM
14
20
2
21
1
SYSTEM
PRESSURE
GAUGE
12
2
1
12
SUPPLY
GAUGE
FIGURE 4 (1 OF 3)
VERTICAL CLOSED DRAIN TRIM — STANDARD ORDER
FOR 2-1/2 INCH (DN65) MODEL AV-1-300 ALARM CHECK VALVES (P/N 52-204-4-950)
Loading...
+ 14 hidden pages