Tyco AS0073-001, RM-CAN, AS0074-000, RM-DCM-CAN, AS0073-CSI User Manual

DATA SHEET
Input/Output Modules
Features That Make a Difference:
Provides cost-effective expansion of input and output capacity Compatible with full range of Software House® iSTAR and apC
access control panels
flexible two-wire RS-485 RM bus
Reduces length of sensor and control wiring to save installation
costs I8 provides eight Class A supervised inputs R8 provides eight Form C relay outputs I8-CSI, configurable supervised input model, allows use of existing
input wiring without changing end-of-line (EOL) resistors Three status LEDs per input (red/yellow/green) and one per output
enable quick diagnostics and troubleshooting Small, modular size requires minimal panel space Dedicated tamper input included on each module Optional UL-listed enclosure available
The Software House I8, R8, and I8-CSI modules provide a flexible, cost-effective means to expand the input and output functionality of any iSTAR or apC access controller. Common applications include alarm monitoring and control and elevator control.
The I8 input module provides eight Class A supervised inputs. Three LEDs per input help the installer commission and troubleshoot each input circuit – red if the input is in alarm, green for normal, and yellow for a supervision error. LEDs may be turned off via a DIP switch setting.
The I8-CSI module enhances the functionality of the standard I8 module by supporting numerous supervised circuit types and EOL resistance values. This allows the I8-CSI to accommodate existing field wiring without changing EOL resistors. More than 20 different circuit types are supported. The circuit type is selected via a bank of DIP switches and applies to all eight inputs on the I8-CSI.
The R8 output module provides eight Form C dry contact relay outputs. A red status LED per output shows the state of the relay.
All modules feature a dedicated input for an external cabinet tamper switch and mount easily in the Software House RM-CAN or RM-DCM-CAN enclosure. The modules communicate with iSTAR or apC controllers via the two-wire RM bus that allows total wiring distances of up to 1,220 m (4,000 ft). Up to eight I8s and eight R8s can be connected to each apC, iSTAR eX, and iSTAR Pro eight-reader model; up to 16 of each module can be connected to the iSTAR Pro 16-reader model.
®
The modules are fully compatible with both C•CURE and C•CURE 9000.
800/8000
SPECIFICATIONS
0
1
2
3
F
E
D
C
B
A
4
5
6
7 8 9
1
SW1
4
SOFTWARE HOUSE
MADE IN USA
P9
P2
P3
P4
P8
P7
P6
P5
W1
TAMPER INPUT
P1
R8 OUTPUT MODULE
AS-0074-000 REV.A
NO
NO
NO
NO
NO
NO
NO
NO
NC
NC
NC
NC
NC
NC
NC
NC
C
C
C
C
C
C
C
C
NOTE: All mounting holes are 1/8" dia.
Max. component height 1/2".
23
1
2 3
1
2 3
1
2 3
1
2 3
1
2
3
1
2
3
1
2
3
1
2
3
Pb
Pb-Free
P5
INE 1
P6
INF 1
P7
ING 1
P8
INH 1
P10P9
GND GNDTS +D -D+12V
1
1
P4
IND 1
P3
INC 1
P2
INB 1
P1
INA 1
S1-1 ON = LED Power S1-2 ON = Disable Tamper S1-3 ON = Not Used S1-4 ON = 485 Termination
DS4
DS25
DS3
DS2
DS27Y1DS26
DS1
DS24
DS23
DS22
S3
1 2 3 4
NO
DS21
DS20
DS7
DS6
DS5
DS10
DS9
DS8
DS13
DS12
DS11
S3
DS19
DS18
DS17
DS16
S2
1 2 3 4
ON
DS15
DS14
S2
S1
U3
FOR SWH STD 1K DUAL S2:3-4, S3:1-4 = OFF
SEE QUICKSTART DOC FOR OTHER SETTINGS
CYCLE POWER AFTER SETTING
1234
ON
S1
SW1
1
TYCO
SOFTWARE HOUSE
ASSEMBLED IN USA
C
COPYRIGHT 2007
"WARNING Damage may result from incorrectly wiring power terminals, input and output lines, and central-supervising station lines. Check all connections before powering the unit."
0312–5008–01 Rev.
18–CSI BOARD
®
Input Rating P9 12VDC 125mA
Refer to Quick Start Installation Guide, P/N UM-218, Rev B0, July 2008
General
Dimensions (H x W) .....11.0 x 15.0 cm (4.3 x 5.9 in)
Environmental.......... 0° to 50° C (32° to 122° F); 5 to 85% relative
humidity, non-condensing
Power Input Voltage .....12 VDC +/- 10%
Tam pe r ...............Dedicated input for external tamper switch
Weight................0.23 kg (8 oz)
Regulatory ............ UL 294, UL 1076, FCC Part A
CE, EN 50133, ROHS
I8 Input Module
Power Requirements ....180 mA @ 12 VDC
R8 Output Module
Power Requirements ....45 mA @ 12 VDC plus 32 mA per active relay
Outputs...............Eight Form C dry contact relays
LED per Output.........Red (relay active)
Relay Contact Ratings ... 30 VDC, 2.0 A resistive
30 VDC, 1.0 A inductive 125 VAC, 4.0 A
Optional Metal Enclosures with Tamper Switch
RM-DCM-CAN
Dimensions...........356 x 305 x 89 mm (14 x 12 x 3.5 in)
Capacity .............Up to four input or output modules
Inputs ................Eight Class A supervised
LEDs per Input ......... Red (alarm), green (normal), and yellow
(supervision error)
I8-CSI Input Module
Power Requirements ....80 mA @ 12 VDC
Inputs ................Eight Class A supervised, configurable via DIP switch
LEDs per Input ......... Red (alarm), green (normal) and yellow
(supervision error)
Circuits Supported ...... Single resistor: 1K, 5K, 10K
Double resistor: 1K, 5K, 10K,
RM-CAN
Dimensions...........210 x 184 x 83 mm (8.25 x 7.25 x 3.25 in)
Capacity .............One input or output module
Model Numbers
AS0 073-001 ...........I8 input module
AS0073-CSI ...........I8-CSI input module
AS0074-000 . . . . . . . . . . .R8 output module
RM-DCM-CAN .........Large metal enclosure with tamper switch
RM-CAN ..............Small metal enclosure with tamper switch
1K/2K, 6.8K/18K, 200/10K Unsupervised: NO, NC
Wiring Summary
Signal From To Belden # Gauge # of Pairs Shielded Maximum Length
Comm
(two-wire RS485)
ap C/i STAR I8/R8 9841* 24 1 Yes
Power ap C/i STAR I8/R8 9841* 24 1 No
Control Point R8 Strike, Siren, etc. 8442/8461 18 1 No
Supervised Input I8 REX or Door Contact 8442/8461 22/18 1 No 610 m (2,000 ft)
1,220 m
(4,000 ft)
Based on
voltage drop
Based on
voltage drop
Wiring Configuration Diagram
I8 Input Module Configuration
R8 Output Module Configuration
Sample System Configuration: Combination Bus/Star Wiring Diagram
(*) For plenum or underground applications, use Belden 89182 for one pair 22 AWG, 100 ohm 12.95 pf/ft.
Note: Control, supervised, and unsupervised input cables must be shielded for FCC Class B operation.
Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all products include all features. Availability varies by region; contact your sales representative. Certain product names mentioned herein may be trade names and/or registered trademarks of other companies.
© 2008 Tyco International Ltd. and its respective companies. All rights reserved. SH0146-DS-200810-R01-LT-EN