Tyco BB, AP, SD, HIP User Manual

Models BB, SD, HIP, and AP Specific Application Sprinklers For Protecting Attics
Worldwide
Contacts
www.tyco-fire.com
General Description
The TYCO Models Back to Back Dual Directional (BB), Single Directional (SD), HIP, and Attic Plus (AP) Specific Appli­cation Attic Sprinklers for Protecting Attics are fire sprinklers for combus­tible and non-combustible sloped attic spaces.
While Models BB, SD, and HIP are specific application attic sprinklers, the Model AP is a specific application combustible concealed-space sprin­kler with specific application criteria for use with Models BB, SD, and HIP in attic spaces.
Specific Application Attic Sprinklers provide superior fire protection in attic spaces. When compared to Stan­dard Spray Sprinklers, cost savings are achieved by eliminating branchline materials and the associated installa­tion labor.
Specific Application Attic Sprinklers for Protecting Attics have undergone the most extensive fire testing ever per­formed for sloped attic spaces. They are UL Listed with their specific appli­cation guidelines for use as special sprinklers as defined by the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA).
Specific Application Attic Sprinklers provide an extended coverage spacing alternative to the restricted spacing of Standard Spray Sprinklers.
IMPORTANT
Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information.
The Specific Application Attic Sprin­klers are the first sprinklers to be:
• Listed for extended coverage in com­bustible construction
• Full-scale fire tested in both wet and dry system scenarios
• Full-scale tested for use in wood truss construction
• Listed for specific roof slopes (Ref. Table A )
The Specific Application Attic Sprin­klers provide cost control with the best level of protection by eliminat­ing the need for additional sprinklers and branchline piping. In many cases, an attic can be entirely protected with just one line of piping located below the peak of the roof using Model BB Sprin­klers. If Model SD Sprinklers or Model HIP Sprinklers are needed, one line of either at each area being covered is sufficient.
For example, while using Standard Spray Sprinklers, a system in a 60 ft (18,3 m) wide attic with up to a 12:12 roof pitch designed to NFPA 13, could require seven branchlines to cover the main portion of the attic and several additional branchlines to cover the hip areas. With Specific Application Attic Sprinklers, the required coverage can be obtained with just one branchline running below the peak and one down each slope of the hip beam. This would result in approximately 90% less pipe needed for installation. This reduction in the number of branchlines saves the cost of the pipe, fittings, hangers, and associated labor by eliminating up to five branchlines.
Another important aspect of the Spe­cific Application Attic Sprinkler technol­ogy, which also allows for cost savings, is the reduction in system volume. This volume reduction may result in reduc­ing the size of a dry pipe valve and air compressor, and possibly allows for quicker water delivery times, eliminat­ing the need for an accelerator.
Page 1 of 28 AUGUST 2018 TFP610
TFP610
SECTION ELEVATION
ELEVATION
SECTION
1
ELEVATION
SECTION
FRAME
FLOW
SECTION ELEVATION
10
Page 2 of 28
Components:
-
Frame
1
-
Button
2
-
Sealing
3
Assembly
2-1/4"
(57,2 mm)
1-1/8"
(28,6 mm)
FLOW FLOW
4
1
3
CROSS
5
THREAD
1/2" (12,7 mm)
(54,0 mm)
2
RELIEF
NOMINAL
MAKE-IN
-
Bulb
4
-
Compression
5
Screw
-
Deector
6
6
2-1/8"
13/16"
(20,6 mm)
WRENCH
FLATS
1-5/8"
(41,3 mm)
3/4" NPT
FRAME
ARMS
FIGURE A
MODELS BB1, BB2, AND BB3 WITH 8.0 K-FACTOR
SPECIFIC APPLICATION ATTIC SPRINKLERS
Components:
-
1
-
2
-
3
-
4
1-9/16"
(39,7 mm)
10
2
CROSS
Body Cap Sealing Assembly Saddle
11
3
-
Compression
5
Screw Lever
6
-
Deector
7
Frame
9
8
FLOW FLOW
7
2-1/2"
(63,5 mm)
6
5
4
(11,1 mm) NOMINAL
MAKE-IN
7/16"
WRENCH
8
9 10 11
2-1/4"
(57,2 mm)
HEX
-
Deector
-
Rivet
--
Diffuser
-
Link Assembly
1-1/8"
(28,6 mm)
1/2" NPT
FRAME
ARMS
FIGURE B
MODELS BB1, BB2, AND BB3 WITH 5.6 K-FACTOR
SPECIFIC APPLICATION ATTIC SPRINKLERS
Components:
-
Frame
1
-
Button
2
-
Sealing
3
Assembly
2-1/4"
(57,2 mm)
1-1/8"
(28,6 mm)
4
1 2
3
CROSS
5
7/16" (11,1 mm)
FLOW
THREAD
(54,0 mm)
RELIEF
NOMINAL
MAKE-IN
-
Bulb
4
-
Compression
5
Screw
-
Deector
6
6
2-1/8"
13/16"
(20,6 mm)
WRENCH
FLATS
1-5/8"
(41,3 mm)
1/2" NPT
ARMS
FIGURE C
MODELS BB1, BB2, AND BB3 WITH 4.2 K-FACTOR
SPECIFIC APPLICATION ATTIC SPRINKLERS
Components:
(54,0 mm)
1-5/16"
WRENCH
-
8
-
9
--
10
2-1/8"
HEX
Deector Rivet Link Assembly
1/2" NPT
8
9
7
6
5
4
-
1
-
2
-
3
-
4
3
Body Cap Sealing Assembly Saddle
1-5/16"
(33,3 mm)
2 1
CROSS
-
Compression
5
Screw Lever
6
-
Deector
7
Frame
3"
(76,2 mm)
7/16" (11,1 mm)
NOMINAL
MAKE-IN
(33,4 mm)
FLOW
FRAME
ARMS
FIGURE D
MODELS SD1, SD2, AND SD3 WITH 5.6 K-FACTOR
SPECIFIC APPLICATION ATTIC SPRINKLERS
TFP610
SECTION ELEVATION
SECTION ELEVATION
2
1
3
4
5
6
(57,2 mm)
Page 3 of 28
Components:
1
3
2-1/8"
(54,0 mm)
4
CROSS
-
Frame
1
-
Button
2
-
Sealing
3
Assembly
1-1/16"
(27,0 mm)
5
2
THREAD
RELIEF
7/16" (11,1 mm)
4 5
6
6
2-1/8"
(54,0 mm)
NOMINAL
MAKE-IN
-
Bulb
-
Compression Screw
-
Deector
1-1/4"
(31,8 mm)
FLOW
WRENCH
FLATS
2"
(50,8 mm)
1/2" NPT
FRAME
ARMS
FIGURE E
MODEL HIP WITH 5.6 K-FACTOR
SPECIFIC APPLICATION ATTIC SPRINKLERS
MODEL AP WITH 4.2 OR 5.6 K-FACTOR SPECIFIC
APPLICATION COMBUSTIBLE CONCEALED
Components:
-
1
-
2
-
3
-
4
CROSS
Frame Sealing Assembly Button Bulb
SPRINKLER
FRAME
ARMS
WRENCH
FLATS
1/2" NPT
FIGURE F
-
Compression
5
Screw
-
Deector
6
-
Ejection
7
Spring
1-11/16"
(42,9 mm)
7
7/16" (11,1 mm)
NOMINAL MAKE-IN
2-1/4"
SPACE SPRINKLERS
Another cost reduction is the Listing of BLAZEMASTER CPVC for use in attic spaces to feed the wet system Specific Application Attic Sprinklers for Protect­ing Attics, as well as to feed the wet system sprinklers below the ceiling. Traditionally, BLAZEMASTER CPVC has been used on the lower floors in the joist space above a ceiling that do not require sprinklers. The cost of using CPVC on those floors can now be translated to the upper floor even if sprinklers are required in the attic.
There are four models of the Specific Application Attic Sprinklers used for protecting attics: BB, SD, HIP, and AP. The Model BB and Model SD Sprinklers have three separate versions used for different roof pitches. The pitches, as applicable, can vary from a minimum of 3:12 to a maximum of 12:12. For more information, refer to Table A.
BB Sprinkler (Back to Back Dual Directional)
The Model BB Specific Application Attic Sprinkler, as seen in Figure A, B and C, throws a narrow and long pattern. The narrow spacing along the ridge serves two purposes: the response time is reduced by placing the sprinklers no farther than 6 ft (1,8 m) apart, and the spray can be concentrated in the throw direction to obtain a pattern that will cover up to 30 ft (9,1 m) in each direction when measured horizontally.
There are three different models that account for different roof slopes: BB1, BB2, and BB3. Each model is provided in one of three different orifice sizes: K=4.2, 5.6, or 8.0.
SD Sprinkler (Single Directional)
The Model SD Specific Application Attic Sprinkler, as seen in Figure D, throws a narrow but long pattern like the Model BB. However, unlike the Model BB, the Model SD only throws in one direction.
Model BB Sprinklers are primarily used where shear walls or draft curtains have been installed within an attic space. Model BB Sprinklers are also used when the framing direction is parallel with the outside wall in the hip area. For more information, refer to Figure
13. In this case, the SD Model Sprinkler would be used on one side of the slope and AP Sprinklers or Standard Spray Sprinklers would be used to protect the other side.
The Model SD Sprinklers must be installed in a vertical upright orientation and not angled with the slope. Achiev­ing the vertical upright orientation may require the use of a swing joint if the SD Sprinklers are being fed from a line running along and parallel to the roof hip.
There are three different models that account for different roof slopes: SD1, SD2, and SD3.
HIP Sprinkler
The Model HIP Specific Application Attic Sprinkler, as seen in Figure E, covers the area of the hip in the attic. This is a slightly different concept than the BB Model or SD Model Sprinklers.
The HIP Sprinkler is located along the slope running down the hip, and throws a 90° pattern toward the outside eaves. This pattern allows the water to “corner” and control the fire.
The HIP does not throw much water directly up or down the hip, but rather it throws most of the pattern out to each side (90°) down the slope of the roof. This sprinkler is typically spaced 6 ft (1,8 m) to 3 ft (0,9 m) on center down the slope.
To use the HIP Sprinkler, the framing must be perpendicular to the outside wall (refer to Figure 12) and the maximum throw cannot exceed 28 ft (8,5 m) measured horizontally. The HIP, unlike the BB Model and SD Model, is installed with the deflector parallel with the slope. There is only one model with flows and pressures for two different spacings.
TFP610
Page 4 of 28
AP Sprinkler (Attic Plus)
The AP Specific Application Attic Sprin­kler are to be installed in the upright orientation with their deflector parallel to the roof. The Model AP Sprinklers, as seen in Figure F, are intended to be used to provide protection of attic areas outside the scope of applica­tions for the BB, SD, or HIP Sprinklers. The AP Sprinklers must only be used in conjunction with other Specific Appli­cation Attic Sprinklers (BB, SD, and HIP), or as permitted in other sections of this document. The AP Sprinklers will provide a hydraulic advantage over Standard Spray Sprinklers for the pro­tection of attic areas outside the scope of application for the BB Model, SD Model, or HIP Model Sprinklers.
NOTICE
The Specific Application Attic Sprin­klers for Protecting Attics described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of NFPA, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the perfor­mance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Sprinkler Identification Number (SIN)
TY4180* BB1 K= 8.0 TY4181* BB2 K= 8.0 TY4182* BB3 K= 8.0 TY3180* BB1 K= 5.6 TY3181* BB2 K = 5.6 TY3182* BB3 K = 5.6 TY2180 BB1 K= 4.2 TY2181 BB2 K=4. 2 TY2182 BB3 K=4.2 TY3183* SD1 K= 5.6 TY3184* SD2 K= 5.6 TY3185* SD3 K= 5.6 TY3187* HIP K= 5.6 TY3190 AP K= 5.6 TY2190 AP K= 4.2
* The “TY” prefix is a re-designation of the previous “C” prefix. For example, TY4180 is a re-designation for C4180.
Technical Data
Approvals
UL and C-UL Listed
These Approvals only apply to the service conditions indicated in the Design Criteria section on Page 6 and the Design Guidelines section on Page 8.
Pipe Thread Connection
1/2 inch NPT for K= 4.2 and 5.6
3/4 inch NPT for K= 8.0
Discharge Coefficient
K = 4.2 GPM/psi½ (60,5 LPM/bar½) K = 5.6 GPM/psi½ (80,6 LPM/bar½) K = 8. 0 GPM /psi½ (115,5 LPM/bar½)
Temperature Rating
Intermediate Temperature as follows: –200°F ( 93°C) for BB (K4.2 and K8.0), H I P, A P
–212°F (100°C) for BB ( K5.6), SD
Finish
Natural Brass
Physical Characteristics (Figures A, C and E)
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button .....................Bronze/Copper
Sealing Assembly ..Ber yllium Nickel w/TEFLON
Bulb .....................Glass (3 mm dia.)
Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . Brass /Bronze
Physical Characteristics (Figures B and D)
Body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Sealing Assembly ..Ber yllium Nickel w/TEFLON
Saddle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Link Assembly . . . . . . . . . . . . . . . . . . . . . . Nickel
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . Brass /Bronze
Lever .....................Bronze Deflector
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Diffuser . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Rivet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Physical Characteristics (Figure F)
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Sealing Assembly ..Ber yllium Nickel w/TEFLON
Bulb .....................Glass (3 mm dia.)
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Operation
BB (K=8.0 and 4.2), HIP (K=5.6) and AP (5.6 and 4.2)
The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.
BB (K=5.6) and SD (K=5.6)
The fusible link assembly is comprised of two link halves which are joined by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, allowing the sprinkler to activate and water to flow.
Installation
"A" ONLY
"A" ONLY
"A" ONLY
"A" ONLY
The TYCO Specific Application Attic Sprinklers for Protecting Attics must be installed in accordance with this section.
NOTICE
Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin­kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 155°F (68°C) and 3/32 inch (2,4 mm) for the 200°F (93°C) tem­perature ratings.
A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a min­imum-to-maximum torque of 7 to 14 lb-ft ( 9,5 to 19,0 N·m). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.
To install the Specific Application Attic Sprinklers, complete the following:
Step 1. Sprinklers must be oriented correctly as follows:
• Model BB Sprinklers are to be installed in the upright vertical posi­tion with the flow arrows on the deflector pointing down the two opposing slopes.
• Model SD Sprinklers are to be installed in the upright vertical posi­tion with the flow direction arrow on the deflector pointing down the slope.
• The Model HIP Sprinklers are to be installed with the deflector at the top, the sprinkler centerline perpendicular to the ridge of the hip roof, and the flow direction arrows on the deflec­tor pointing down the two oppos­ing slopes. Unlike the Model BB and Model SD, the Model HIP is installed angled so that its deflector is paral­lel with the slope of the hip ridge line.
• The Model AP Sprinklers are to be installed in the upright position with the deflector parallel to the roof slope. There are no flow arrows on the deflector to consider; however, a good piping practice is to position all the Model AP Sprinklers so that their frame arms are in the same direction.
DO NOT
DO NOT GRASP DEFLECTOR
USE END MARKED
W-TYPE 3 SPRINKLER WRENCH
BB (K=8.0) SPRINKLERS’
USE END MARKED
W-TYPE 6 SPRINKLER WRENCH
Step 2. With pipe thread sealant applied to the pipe threads, hand­tighten the sprinkler into the sprinkler fitting.
Note: With reference to Figure G, do not grasp the sprinkler by the deflector.
Step 3. Wrench-tighten the sprin­kler using only the wrenches shown in Figures H through M. Wrenches are only to be applied to the sprin­kler wrench flats or wrench hex, as applicable.
FIGURE G
WRENCH
FLATS
ENGAGE
SPRINKLER
THREAD RELIEF
WITH WRENCH JAW FLANGES
WRENCH
JAW FLANGE
FIGURE H
FOR USE WITH
WRENCH
FLATS
ENGAGE
SPRINKLER
THREAD RELIEF
WITH WRENCH
JAW FLANGES
WRENCH
JAW FLANGE
FIGURE J
For Use with
BB (K= 4.2) Sprinklers
TFP610
Page 5 of 28
WRENCH
FLATS
ENGAGE
SPRINKLER
THREAD RELIEF
WITH WRENCH
JAW FLANGES
WRENCH
HEX
WRENCH JAW
TO FIT WRENCH
WRENCH
FLATS
ENGAGE
JAW FLANGE
ADJUST
HEX
WRENCH
JAW FLANGE
USE END
MARKED
FIGURE K
W-T Y P E 2 0
SPRINKLER WRENCH
For Use with
HIP (K= 5.6) Sprinklers
WRENCH
APPLY
WRENCH
TO WRENCH
HEX ONLY
FIGURE L
ADJUSTABLE WRENCH
For Use with BB ( K= 5.6) and
SD (K= 5.6) Sprinklers
SPRINKLER
THREAD RELIEF
WITH WRENCH
JAW FLANGES
USE END
MARKED
FIGURE M
W-TYPE 6 SPRINKLER WRENCH
For Use with
AP (K= 4.2 and 5.6) Sprinklers
TFP610
Page 6 of 28
Design Criteria
Area of Use
The TYCO Specific Application Attic Sprinklers are designed for use in roof structures and combustible and non-combustible sloped attic spaces, including wood joist/rafters and wood trussed attics with a ceiling below.
System Type for BB, SD, HIP, or AP Sprinklers
Wet using CPVC pipe Wet or dry using steel pipe
Note: Use of the 4.2 K sprinklers in dry pipe systems is permitted by NFPA 13 where piping is corrosion resistant or internally galvanized.
Hazard
Light Hazard.
BB, SD, or HIP Allowable Roof Span (Coverage) and Roof Pitch
Refer to Table A for allowable roof spans and roof pitches, and for the associated minimum sprinkler flows and pressures. Figures 1, 2, 11 and 12 illustrate where the roof span is to be measured.
Coverage Beyond BB, SD or HIP Allowable Roof Spans
Up to 10 ft (3,1 m) of coverage at the eave(s) beyond the allowable roof spans for BB, SD, or HIP Sprinklers may be obtained by using a single row of AP Sprinklers. For more information, refer to Figure 14A, 14B, and 15.
BB, SD, HIP, or AP Minimum Distance Between Sprinklers
4 ft (1,2 m) as measured along the branchline for BB and SD. For more information, refer to Figure 3.
3 ft (0,9 m) as measured along the branchline for HIP. For more informa­tion, refer to Figure 12.
7 ft (2,1 m) between AP Sprinklers.
BB, SD, HIP, or AP Maximum Distance Between Sprinklers
6 ft (1,8 m) on center along the branch­line for BB, SD, and HIP. For more infor­mation, refer to Figure 3 and 12.
For AP, the maximum spacing is 10 ft (3,1 m) perpendicular to slope and 12 ft (3,6 m) parallel to slope. When there is more than one row of AP Sprin­klers, the sprinklers must be staggered as seen in Figure 20-B-3.
BB, SD, HIP, or AP Minimum Distance to AP Sprinklers or Standard Spray Sprinklers
As measured along the peak/ridge direction, 6 ft (1,8 m) from BB, SD, and HIP to Standard Spray Sprinklers. For more information, refer to Figure 4.
As measured along the peak/ridge direction, 7 ft (2,1 m) from AP to Stan­dard Spray Sprinklers. For more infor­mation, refer to Figure 4.
In the slope direction, 26 ft (7,9 m) from BB or HIP Sprinklers to AP Sprinklers or Standard Spray Sprinklers. For more information, refer to Figure 6.
BB, SD, or HIP Deflector Installation Position Below Peak/Ridge or Deck
For roof pitches of 4:12 (33%) to 12:12 (100%), 22 in. (558,8 mm) maximum and 16 in. (406,4 mm) minimum. For more information, refer to Figure 2 and
5.
For roof pitches of 3:12 (25%) up to 4:12 (33%), (only 4.2K Model BB), 12 in. (304,8 mm) maximum below the peak and a minimum of 1 in. (25,4 mm) below the bottom of the top chord or solid wood rafter.
AP Deflector Position and Roof Pitch
1 to 3 in. (25,4 to 75,6 mm) below the bottom of the top chord or bottom of solid wood rafter, where the roof pitch is 3:12 to 12:12 and the top chord or solid wood rafter is a nominal 12 in. (600 mm) or less.
BB or SD Deflector Installation Position Above Scissor Truss
18 in. (457,2 mm) minimum. For more information, refer to Figure 5.
BB, SD, or HIP Minimum Distance Away from Trusses
Attic Sprinklers must be installed 6 in. (152,4 mm) away from the face of trusses. For more information, refer to Figure 7.
SD Distance from Shear Wall or Draft Curtain
4 to 6 in. (101,6 to 152,4 mm) from face, and a minimum of 8 in. (203,2 mm) above the bottom of the draft curtain. For more information, refer to Figure 2.
Draft Curtains
Draft curtains installed to permit the installation of Attic Sprinklers shall be constructed so as to not allow heat to escape through or above the draft curtain. The draft curtain may be con­structed of 1/2 in (12,7 mm) plywood.
BB or HIP Maximum Distance from the Center Line of the Ridge
6 in. (152,4 mm) with the deflector located 16 to 22 in. (406,4 mm to 558,8 mm) from the peak. For more informa­tion, refer to Figure 8.
Use of UL Listed BLAZEMASTER CPVC Piping with Specific Application Attic Sprinklers for Protecting Attics (Wet Systems Only)
BLAZEMASTER CPVC piping may be used in a combustible concealed attic space requiring sprinklers when installed in accordance with the follow­ing guidelines:
Note: Where the use of non-com­bustible insulation is specified, verify with the insulation manufacturer as to the non-combustibility of the insula­tion. The non-combustible insulation (fiberglass) may be faced or unfaced. Where faced, the facing need not be non-combustible. The insulation is to have a flame spread index of not more than 25.
Verify chemical compatibility of the insulation with BLAZEMASTER CPVC by consulting www.lubrizol.com.
• BLAZEMASTER CPVC may be used to feed the wet system ceiling sprin­klers on the floor below. There must be 6 in. (152,4 mm) of non-combus­tible insulation covering the horizon­tal or vertical pipe extending 12 in. (304,8 mm) on each side away from the centerline of the pipe. Refer to Figures 9A, 9B, and 9C. The area above the pipe must be protected by BB, SD, HIP, or AP Sprinklers. For more information, refer to Figure 9A. If the pipe is located inside the ceil­ing joist, the joist channel must be covered or filled with 6 in. (152,4 mm) of non-combustible insulation on top of the pipe and the area above must be protected by BB, SD, HIP, or AP Sprinklers. For more information, refer to Figure 9B. Insulation is for re
protection purposes. It is not freeze protection. BLAZEMASTER CPVC
must be installed in accordance with the BLAZEMASTER installation guide instructions.
• With reference to Figure 19, BLAZE­MASTER CPVC may be used exposed to feed wet system BB, SD, or HIP Sprinklers where:
Risers are vertical and protected by BB, SD, or HIP Sprinklers locat­ed at a maximum lateral distance of 12 in. (304,8 mm) from the riser centerline.
BB, SD, or HIP Sprinklers are di­rectly mounted on the branchline.
BB, SD, or HIP Sprinklers are on arm-overs and located at a max­imum lateral distance of 6 in. (152,4 mm) from the branchline centerline.
BB, SD, or HIP Sprinklers are on vertical sprigs attached to the branchline.
Page 7 of 28
DRY PIPE
SYSTEM
MAXIMUM
WATER
DELIVERY
Seconds
MODEL K SIN
ALLOWABLE ROOF SPAN,
(a) (b) (e)
Feet (m)
MINIMUM
FLOW,
GPM (LPM)
MINIMUM
PRESSURE,
psi (bar)
PITCH,
Rise Over Run (%)
BB1 8.0 T Y4180 ≤60 (18,3) 38 (14 4) 22.6 (1,5) 4:12 (33) to less than 7:12 (58) (c)
BB2 8.0 TY4181 ≤60 (18,3) 38 (144 ) 22.6 (1,5) 7:12 (58) to less than 10:12 (83) (c)
BB3 8.0 T Y4182 ≤60 (18,3) 40 (152) 25.0 (1,7 ) 10:12 (83) to 12:12 (100) (c)
BB1 5.6 T Y3180 >40 (12,2) to ≤60 (18,3) 38 (14 4) 46.0 (3,2) 4:12 (33) to less than 7:12 (58) (c)
BB2 5.6 TY3181 >40 (12,2) to 60 (18,3) 38 ( 144) 46.0 (3,2) 7:12 (58) to less than 10:12 (83) (c)
BB3 5.6 T Y3182 >40 (12,2) to 60 (18,3) 38 (144) 46.0 (3,2) 10:12 (83) to 12:12 (100) (c)
BB1 5.6 T Y3180 ≤40 (12,2) 25 (95) 20.0 (1,4) 4:12 (33) to less than 7:12 (58) (c)
BB2 5.6 TY3181 ≤40 (12,2) 25 (95) 20.0 (1,4) 7:12 (58) to less than 10:12 (83) (c)
BB3 5.6 T Y3182 ≤40 (12,2) 25 (95) 20.0 (1,4) 10:12 (83) to 12:12 (100) (c)
BB1 4.2 T Y2180 ≤20 (6,1) 13 (4 9) 9.6 (0,7) 3:12 (25) to less than 7:12 (58) 45 (d)
BB2 4.2 T Y2181 ≤20 (6,1) 13 (49) 9.6 (0,7) 7:12 (58) to less than 10:12 (83) 45 (d)
BB3 4.2 T Y2182 ≤20 (6,1) 13 (4 9) 9.6 (0,7) 10:12 (83) to 12:12 (100) 45 (d)
SD1 5.6 T Y318 3 >30 (9,1) to ≤40 (12,2) 35 (132) 39.0 (2,7) 4:12 (33) to less than 7:12 (58) (c)
SD2 5.6 T Y3184 >30 (9,1) to ≤40 (12,2) 35 (13 2) 39.0 (2,7 ) 7:12 (58) to less than 10:12 (83) (c)
SD3 5.6 T Y3185 >30 (9,1) to ≤40 (12,2) 35 (132) 39.0 (2,7 ) 10:12 (83) to 12:12 (100) (c)
SD1 5.6 T Y318 3 >10 (3,0) to ≤30 (9,1) 25 (95) 20.0 (1,4) 4:12 (33) to less than 7:12 (58) (c)
SD2 5.6 T Y3184 >10 (3,0) to ≤30 (9,1) 25 (95) 20.0 (1,4) 7:12 (58) to less than 10:12 (83) (c)
SD3 5.6 T Y3185 >10 (3,0) to ≤30 (9,1) 25 (95) 20.0 (1,4) 10:12 (83) to 12:12 (100) (c)
SD1 5.6 T Y318 3 ≤10 (3,0) 19 (72) 11.5 (0,8) 4:12 (33) to less than 7:12 (58) (c)
SD2 5.6 T Y3184 ≤10 (3 ,0) 19 ( 72) 11.5 (0,8) 7:12 (58) to less than 10:12 (83) (c)
SD3 5.6 T Y3185 ≤10 (3,0) 19 ( 72) 11.5 (0,8) 10:12 (83) to 12:12 (100) (c)
HIP 5.6 T Y3187 >20 (6,1) to ≤28 (8,5) 3 4 (129 ) 36.9 (2,5) 4:12 (33) to 12:12 (100) (c)
HIP 5.6 T Y3187 ≤20 (6,1) 25 (95) 20.0 (1,4) 4:12 (33) to 12:12 (100) (c)
AP 5.6 TY319 0
AP 4.2 TY219 0 3:12 (25) to 12:12 (100) 60 (d)
NOTES
a. T he BB and S D roof spa n is measured ho rizont ally (no t along th e slope) a s shown in F igure 1 an d Figure 2. b. The HIP roof span is mea sured h orizontally as shown in Fi gure 2. c. R efer to NFPA 13. d. Maximum water delive ry tim e for all sy stem size s. e. T he AP roo f span is measured along the slop e. Maxi mum 10 ft (3, m) p erpendicul ar to slop e by maxi mum 12 ft (3,6 m) p arall el to slop e.
10 (3,1) x 12 (3,6)
-See note (e)
Minimum 7 psi (0,48 bar)
Minimum 0.10 gpm/ft2
(4,1 mm/min.) Design Density
3:12 (25) to 12:12 (100) 60 (d)
TFP610
TIME,
ALLOWABLE ROOF SPAN, FLOW, PRESSURE, AND PITCH FOR
SPECIFIC APPLICATION SPRINKLERS FOR PROTECTING ATTICS
TABL E A
TFP610
Page 8 of 28
BB, SD, or HIP Sprinklers are on arm-over or angled sprigs, and lo­cated at a maximum lateral dis­tance of 6 in. (152,4 mm) from the branchline centerline.
A minimum lateral distance of 18 in. (450 mm) is maintained be­tween the CPVC pipe and a heat producing device such as heat pumps, fan motors, and heat lamps.
• BLAZEMASTER CPVC may be used exposed to provide wet system, ver­tical or angled, sprigs to AP Sprin­klers (refer to Figures 17A and 17B) where:
• The exposed portion of an angled
sprig is a maximum length of 3 ft (0,9 m), the sprig is supported ad­jacent to the AP Sprinkler, and ver­tical restraint is provided using the CPVC hanger support for horizon­tal pipe runs.
Vertical sprigs have a maximum exposed length of 10 ft (3,05 m), the AP Sprinkler is located at a maximum lateral distance of 12 in. (3304,8 mm) from the sprig center­line, and the sprig is supported at the swing joint to the AP Sprinkler.
A minimum 6 in. (152,4 mm) deep of non-combustible insulation ex­tending 12 in. (304,8 mm) on each side away from the centerline of the CPVC branchline feeding the AP sprigs (refer to Figure 17A). If the CPVC branchline is located in­side the ceiling joist, the joist chan­nel must be covered or lled with a minimum of 6 in. (152,4 mm) deep of noncombustible insulation on top of the branchline feeding the AP sprigs (refer to Figure 17B). In­sulation is for re protection pur­poses. It is not freeze protection. Additional depth of non-combusti­ble insulation may be added to re­duce the exposed length of the AP sprigs.
A minimum lateral distance of 18 in. (450 mm) is maintained be­tween the CPVC pipe and a heat producing device such as heat pumps, fan motors, and heat lamps.
Mismatched Slopes
Refer to Figure 10.
Obstructions
For BB, SD, and HIP, refer to Figure 16. For AP Sprinklers, refer to Figure 18. BB, SD, HIP, and AP Sprinklers may be installed directly on maximum 2-1/2 inch NPS (DN65) branch lines without the need for sprigs. See NFPA 13 for requirements when installed on pipe greater than 2-1/2 inch NPS (DN65).
Hydraulic Requirements
Refer to Figure 20.
Determine the Correct Flow and Pressure
For BB, SD, or HIP Sprinklers, deter­mine the roof span (measured horizon­tally) and the slope of the roof, and then refer to Table A. There is no interpola­tion of the flow and pressure shown. Round all cases to the next higher spacing. For example, a 45 ft (13,7 m) span with the BB1 (K=8.0) would be calculated at the 60 feet (18,3 m) span.
For the AP Sprinklers, the minimum design pressure is 7 psi, and the minimum design density is
0.10 gpm/ft² (4,1 mm/min). The NFPA 13, 20 psi (1,4 bar) minimum operating pressure for Standard Spray Sprinkler spacings parallel to the ridge that are above 8 ft (2,4 m) does not apply to the A P.
Coverage Area
• Coverage area for the BB Sprinklers is determined by twice the distance of the furthest throw measured along the slope multiplied by the distance along the branchline. The maximum distance along branchline is 6 ft (1,8 m) regardless of the length of the throw.
Note: The distance along the branch­line may have to be reduced to less than the maximum of 6 ft (1,8 m) to remain under 400 ft² (37,2 m²) maximum depending on the slope and the span. In no case can the span exceed 60 ft (18,3 m) without additional Standard Spray Sprinklers.
• Coverage area for the SD (Single Directional) Sprinklers is the distance
along the branchline multiplied by the distance of the throw down the slope. Regardless of the throw, the maximum distance along the branch­line is 6 ft (1,8 m), the maximum throw measured horizontally is 40 ft (12,2 m), and the maximum coverage per sprinkler is 400 ft² (37,2 m²).
• Coverage area for the HIP Sprinklers is the distance down the larger slope multiplied by two, and multiplied by the distance between the sprinklers as measured along the slope of the hip.
• Coverage area for the AP (Attic Plus) Sprinklers is the distance along the branchline multiplied by the distance between the branchlines. The max­imum spacing is 10 ft (3,1 m) per­pendicular to the slope and 12 ft (3,6 m) parallel to slope, and as mea­sured on the slope. When there is more than one row of AP Sprinklers, the sprinklers must be staggered per Figure 20-B-3. The maximum spac­ing per sprinkler is 120 ft² (11,1 m²).
Design Guidelines
To design a project with the TYCO Spe­cific Application Attic Sprinklers, use these steps as a guideline:
• Determine if single, dual directional or hip sprinkler is needed.
• Determine the roof slope is between 3:12 to 12:12. If more than one slope is being used on a project, select the correct sprinkler for each area.
• Follow the guidelines for each type of sprinkler.
• Calculate the sprinkler system in accordance with the appropriate flow and pressure information provided in Table A, as well as Figure 20. There is no interpolation of the flows and pressures shown on the chart.
For BB Sprinklers (Back to Back Dual Directional)
• Verify the framing direction is per­pendicular to the outside wall (refer to Figure 12). If not, cover that area with AP Sprinklers or Standard Spray Sprinklers (refer Figure 13).
• Determine the throw needed. For more information, see the spac­ing requirements in Table A. If over 20 ft (6,1 m) and up to 60 ft (18,3 m) is required, use the 8.0 K-factor, BB Sprinklers to reduce the pressure required. If pressure is not a concern, use the 5.6 K-factor, BB Sprinklers to minimize over discharge.
• If less than 20 ft (6,1 m) is required, use the 4.2 K-factor, Back to Back Dual Directional to minimize pressure and flow requirements.
• Determine the distance along the slope. If the distance is not equal, use the longer side. Multiply the lon­ger side by two to determine the spacing down the slope. Four hun­dred divided by this value will deter­mine the maximum spacing along the ridge. The maximum distance is 6 ft (1,8 m). For example, a 12:12 slope at the maximum span of 60 ft (18,3 m) will produce a slope length of approximately 42.5 ft (13,0 m). That number multiplied by two pro­duces an 85 ft (25,9 m) throw. A 400 ft² maximum divided by an 85 ft (25,9 m) throw only allows a 4 ft 8 in. (1,4 m) spacing along the ridge. Using the maximum spacing, space the sprinklers along the ridge.
• Avoid obstructions as shown in Fig­ure 16. If necessary, add Model AP Sprinklers or Standard Spray Sprin­klers to maintain coverage around obstructions.
TFP610
Page 9 of 28
For SD Sprinklers (Single Directional)
• Determine the throw needed.
• As the 400 ft² (37,2 m²) is not a factor with the SD Sprinklers, the maximum spacing is 6 ft (1,8 m) and the mini­mum is 4 ft (1,2 m). For more infor­mation, refer to Figures 2 and 11. The reason 400 ft² is not an issue with the single directional is because, at its maximum spacing, 6 ft (1,8 m) on center / covering 40 ft (12,2 m) flat / a 12:12 slope / and the throw being
56.5 ft (17,2 m), the 400 ft² (37,2 m²) maximum would not be exceeded.
• Avoid obstructions as shown in Fig­ure 16. If necessary, add Model AP Sprinklers or Standard Spray Sprin­klers to maintain coverage around obstructions.
For HIP Sprinklers
• Verify framing direction is perpendic­ular to outside wall (refer to Figure
12). If not, cover that area with AP Sprinklers or Standard Spray Sprin­klers (refer to Figure 13).
• From the intersection of the top of the hip and the ridge, the maximum distance down the slope of the hip is 3 ft (0,9 m). Start the layout with the first sprinkler as close to that point as possible, but no further, while staying 6 in. (152,4 mm) away from the face of the trusses. Remember the slope of the hip is not equal to the slope of the roof from the ridge to the out­side wall. Continue to space sprin­klers down the hip at a maximum of 6 ft (1,8 m) on center as measured along the slope of the hip. When the bottom of the hip is encountered, the last sprinkler must be within 7-1/2 ft (2,3 m) of the outside wall as mea­sured flat (plan view). If this pipe is “cut to fit”, remember to account for the different slopes of the hip and the roof, as well as distances measured along the slope verses horizontal in plan view must be accounted for.
• Avoid obstructions as shown in Fig­ure 16. If necessary, add Model AP Sprinklers or Standard Spray Sprin­klers to maintain coverage around obstructions.
Care and Maintenance
The TYCO Specific Application Attic Sprinklers for Protecting Attics must be maintained and serviced in accor­dance with this section.
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protec­tion system from the proper authorities and notify all personnel who may be affected by this action.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NFPA, such as NFPA 25. In addition to the standards of any other authori­ties having jurisdiction. Contact the installing contractor or product manu­facturer with any questions.
Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor­dance with local requirements and/or national code.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi­fied sprinklers must be replaced.
Over-heated solder type sprinklers must be replaced. Bulb-type sprin­klers that have been exposed to cor­rosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. For more informa­tion, refer to the Installation Section.
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indicate the full product name and Part Number (P/N).
Sprinkler Assemblies with NPT Thread Connections
Specify: Model (specify), K-factor (specify), SIN (specify), Specific Appli­cation Attic Sprinkler, P/N (specify):
BB1 (K=8.0),
T Y418 0 . . . . . . . . . . . . . . . . . . . . . . 51-62 3-1-2 00
BB2 (K=8.0),
T Y418 1 ...................... 51-6 21-1-20 0
BB3 (K=8.0),
T Y418 2 ......................51-6 22-1-200
BB1 (K=5.6),
TY3180 ......................50 -601-1-212
BB2 (K=5.6),
TY3181 ......................50 - 602 -1-212
BB3 (K=5.6),
TY3182 ......................50- 6 0 3 -1-212
BB1 (K=4. 2),
TY2180 ......................50-620-1-200
BB2 (K=4.2),
TY2181 ......................50- 621-1-2 00
BB3 (K=4. 2),
TY2182 ......................50 - 6 22 -1-20 0
SD1 (K= 5.6),
TY3183 ......................50 -611-1-212
SD2 (K=5.6),
TY3184 ......................50- 612-1-212
SD3 (K=5.6),
TY3185 ......................50 - 613-1-212
HIP (K=5.6),
TY3187 ......................51-620-1-2 00
AP (K= 5.6),
TY3190 ......................5 0-62 5 -1-20 0
AP (K= 4.2),
TY2190 ......................5 0 - 624 -1-20 0
Sprinkler Wrench
Specify: W-Type 3 Sprinkler Wrench, P/ N 5 6 -895-1- 001
Specify: W-Type 20 Sprinkler Wrench, P/ N 5 6 -00 0 -1-10 6
Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387
Loading...
+ 19 hidden pages