Tyco AMD-1 Quick Start Manual

Technical Services
800-381-9312 | +1-401-781-8220
www.tyco-fire.com
Model AMD-1 Automatic Air Maintenance Device Pressure Reducing Type with Field-Adjustable Pressure Regulator
General Description
The TYCO Model AMD-1 Automatic Air Maintenance Device is an automatic, eld-adjustable, pressure reducing device. It is used to control the pres­sure in a dry pipe sprinkler system, pre­action system, or dry pilot line system of a dry pilot actuated deluge or preac­tion valve.
The Model AMD-1 Device is utilized in applications where there is a com­pressed air (or nitrogen) source con­trolled at a higher pressure than the desired system pressure. Pressure sources include plant air supplies with their own automatic compressor con­trols or nitrogen supplies with sin­gle-stage, cylinder-mounted pressure regulators.
The Model AMD-1 Automatic Air Main­tenance Device is a re-designation for the Central Model D-2, Gem Model F324, and Star Model S460.
NOTICE
The Model AMD-1 Automatic Air Main­tenance Devices described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices.
Owners are responsible for maintain­ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.
Technical Data
Approvals
UL and C-UL Listed FM Approved NYC Approved under MEA 206-02-E
Maximum Inlet Air (or Nitrogen) Supply Pressure
200 psi (13,8 bar)
Field-Adjustable Outlet Pressure Range
5 to 70 psi (0,4 to 4,8 bar)
Assembly
Major components illustrated in Figure 1 are factory assembled with galva­nized steel nipples and malleable iron pipe ttings.
Operation
The By-Pass Valve in the Model AMD-1 Automatic Air Maintenance Device is opened to quickly ll the system during initial pressurization. Once the re quired system pressure has been reached, the By-Pass Valve is closed and the Air Supply Control Valve is left open to place the Model AMD-1 Device in auto­matic operation.
When there is a small leak in the sys­tem, the Pressure Regulator automati­cally maintains system pressure at the preset level. The 3/32 inch (2,4 mm) ori­ce in the Restrictor Check Valve limits the ow of air from the Pressure Regu­lator into the system to a value signi­cantly less than that exhausted by the operation of a 5.6 K-factor sprinkler.
Installation
The TYCO Model AMD-1 Automatic Air Maintenance Device must be installed in accordance with the following instructions.
NOTICE
Moisture build-up can adversely affect performance. Suitable consideration must be given to the removal of exces­sive moisture from the compressed air supply.
1.
Make connections a minimum of 1/2 inch (DN15) pipe size between the inlet air supply and the Model AMD-1 Device, as well as between the Model AMD-1 Device and the system to pressurize.
2. Place a 1/2 inch (DN15), non-spring loaded, rubber-faced, swing-type check valve between the Model AMD-1 Device and the system to pressurize. A check valve of this type is provided in the air supply trim of TYCO dry pipe valves, pre­action valves, and dry pilot trim.
Page 1 of 4 JULY 2010 TFP1221
TFP1221
Page 2 of 4
2"
(50,8 mm)
3-1/4"
(82,6 mm)
8-1/2"
(215,9 mm)
1/2" NPT OUTLET
CONNECTION
(TO SYSTEM)
LABEL
RESTRICTOR
CHECK VALVE
P/N 92-326-1-003
Setting Procedure
The TYCO Model AMD-1 Automatic Air Maintenance Device must be set in accordance with the following instructions.
1. Determine the pressure that meets the minimum requirements of the system to pressurize.
2. Close the Model AMD-1 By-Pass Valve, and close the Model AMD-1 Air Supply Control Valve.
3. Open the control valve in the air supply trim of the system to pres­surize and then reduce the system air pressure to 0 psi.
4. Close the control valve in the air supply trim of the system to pressurize.
5. Remove the system pressure gauge from its connection and temporarily install it in the 1/4 inch NPT Model AMD-1 Gauge Test Port.
CAUTIO N
Before removing the plug, make certain that the piping to which the Model AMD-1 Gauge Test Port is connected is at 0 psi. Failure to do so may result in personal injury or property damage.
6. Open the Air Supply Control Valve in the Model AMD-1 Device.
16-1/8""
(409,6 mm)
1/4" NPT
GAUGE
TEST PORT
PRESSURE
REGULATOR
(ADJUSTABLE)
P/N 92-324-1-012
STRAINER
P/N 52-353-1-002
FIGURE 1
MODEL AMD-1
AUTOMATIC AIR MAINTENANCE DEVICE
7. While observing the relocated pres­sure gauge, adjust the output pres­sure of the Pressure Regulator. Pull the knob out and away from the Pressure Regulator body and then slowly turn the knob clockwise, as viewed from the knob end of the Pressure Regulator, to increase pressure, and counter-clockwise to decrease pressure.
When decreasing pressure, the air pressure must be relieved down­stream of the Pressure Regulator by temporarily opening the control valve in the air supply trim of the system to pressurize, assuming that the system to pressurize is at 0 psi.
After the Pressure Regulator is set, push the knob in and towards the Pressure Regulator body to “snap” it in a locked position.
8. Close the Air Supply Control Valve in the Model AMD-1 Device.
9. Return the system air pressure gauge to its normal location. Re­install the 1/4 inch pipe plug in the Model AMD-1 Gauge Test Port. Apply pipe-thread sealant sparingly to the plug threads only.
CAUTIO N
Before removing the pressure gauge, make certain that the piping to which the Model AMD-1 Gauge Test Port is connected is at 0 psi. Failure to do so may result in per­sonal injury or property damage.
BY-PASS VALVE
(NORMALLY
CLOSED)
P/N 46-047-1-004
1/2" NPT
INLET CONNECTION
(FROM COMPRESSED
AIR SUPPLY)
AIR SUPPLY
CONTROL VALVE
(NORMALLY OPEN)
P/N 46-048-1-002
10. Open the control valve in the air supply trim to the system to pressurize.
11. Open the Air Supply Control Valve in the Model AMD-1 Device.
12. Open the By-Pass Valve in the Model AMD-1 Device.
13. Close the By-Pass Valve after the system is pressurized to approxi­mately 5 psi (0,4 bar) less than the minimum required system pres sure determined in Step 1.
14. After the system pressure stabi­lizes, note the value and compare with the requirement. Re-adjust the Pressure Regulator, as required.
NOTICE
If the system was over-pressur­ized during manual fill, open a suitable connection to the system and manually reduce the pressure to the desired value. The Model AMD-1 Automatic Air Maintenance Device then automatically maintains the preset system pressure. The Restrictor Check Valve prevents the Pressure Regulator from bleed­ing down the system pressure.
In order to minimize the time for system trip in the event of a sprin­kler operation, set the system pres­sure at the minimum required value.
Loading...
+ 2 hidden pages