Tyco 1948 Series Installation & Operating Instructions Manual

LT0232 VERSION 1.14 26 FEBRUARY 2013 PAGE 1 OF 4
SERIES 1948, 2A POWER SUPPLIES
INSTALLATION & OPERATING INSTRUCTIONS
17 Mary Muller Drive
PO Box 19-545
Woolston
Christchurch 8241
NEW ZEALAND
Tel: +64-3-389-5096
Fax: +64-3-389-5938
To place into operation: (i) Install the cabinet as per Section 1.
(ii) Wire as per Section 2 (do not connect batteries). (iii) Configure options as per Section 3. (iv) Switch mains on and check the voltage, adjust if necessary. (v) Connect the batteries as per Section 2.
1. CABINET INSTALLATION WARNING: The 24V 2A models are Class A products. In a domestic environment these products
may cause radio interference in which case the user may be required to take adequate measures. The cabinet is intended for wall mounting at "eye" level. Allowance should be made for cable entry
(one hole is provided at top of rear wall, near centre). Relevant standards may apply (e.g. AS1670.1 and NZS4512).
The following conditions are required: dry area (inside building); moderate ambient temperature; clear access for viewing and maintenance.
THE UNIT IS NOT SUITABLE FOR INSTALLATION WITHIN A "HAZARDOUS AREA"
AS DEFINED BY AS3000.
Four mounting holes are provided (5mm diameter) on a rectangular pattern. The unit should be mounted with at least 2 screws (top and bottom of opposite sides).
2. WIRING ENSURE MAINS SUPPLY IS ISOLATED AT THE SWITCHBOARD BEFORE CONNECTING
MAINS WIRING MUST BE DONE BY A REGISTERED ELECTRICIAN
Mains Wiring: (Observe all relevant standards, e.g. AS3000)
(a) Terminate the mains cable to the 3-way terminal block: brown to A; blue to N;
green/yellow to E. (b) Do not "nick" wires when stripping, or leave exposed strands outside of the terminals. (c) Secure the wires to the cabinet with the P clamp and barrel nut. (d) Connect the supply
Field Wiring: Three terminals (J2) are provided for connection to external loads:
+VNB for non-battery backed loads (e.g. door holders); +V for battery-backed loads; 0V (for common return of both the above).
Three terminals are provided for connection to internal or co-located equipment. Terminate the wires with 2mm "fast-on" receptacles, (e.g. Utilux H1129).
Charger Disable- Input (J7), close to 0V with voltage free switch to reduce output voltage to 80%.
LT0232 VERSION 1.14 26 FEBRUARY 2013 PAGE 2 OF 4
Timer Disable- Input (J18) requires a normally open switch (or transistor), close to 0V to terminate and hold off automatic battery checks.
PSU Fault- Output (J8) is an open collector transistor, closing to 0V when active. Example of wiring a relay to the PSU Fault- output:
Battery connection: Connect red lead to battery + terminal, connect black lead to battery - terminal. E.g. For a 24V system connect as shown.
3. CONTROLS & CONFIGURABLE OPTIONS (FIELD ADJUSTMENTS) Mains On/Off (fuse holder in terminal block acts as a mains switch. Remove fuse to switch off, Fuse is
20x5,1A rating).
- Switches mains (but not the batteries). Output Adjust (potentiometer PT1 on pcb)
- Adjusts output voltage (and fault thresholds), preset in factory for nominal output. If field adjustment is required, rotate clockwise to increase voltage, anti-clockwise to decrease.
Timer Disable (remove link LK1 on pcb)
- Disables all automatic battery tests (i.e. battery connected check, hourly and 48 hourly battery capacity tests).
Current Limit (snip out resistors R13, R14, R15 on pcb).
- Reduces current limit (also charger current rating) if required by battery manufacturer's ratings.
See specifications for details.
Charger Fault (LK2 on pcb)
- If the link is fitted the PSU Fault- output will be active during a charger high or low condition. Remove the link for AS1603.4 or NZ operation as this feature is not required.
Mains Fail (LK3 on pcb) (software V2.01 onwards)
- If the link is not fitted the PSU Fault output will be active after 90 minutes of continuous mains failure.
4. STANDARDS COMPLIANCE
To comply with AS1603.4 Clause 2.8.8 an appropriate external battery test load needs to be applied at the same time as activating the Charger Disable input.
AS4428.5:1998 has two clauses that only need to be complied with if the standard for the product the PSU is powering requires them. At present there are no such standards. The 1948 PSU cannot meet Clause 2.2(c) when a short circuit or polarity reversal is applied to the battery terminals. The 1948 PSU does not support disconnecting the battery from the PSU load when the final voltage is reached. (Clause 2.3(c)).
To signal the loss of mains power (Clause 2.4(a)), remove LK3 (see Section 3 above).
12V
+
-
+ - 12V
+
-
PSU FAULT-
+V
+
-
IN4001
Loading...
+ 2 hidden pages