LT0232 VERSION 1.14 26 FEBRUARY 2013 PAGE 2 OF 4
Timer Disable- Input (J18) requires a normally open switch (or transistor), close to 0V to terminate and
hold off automatic battery checks.
PSU Fault- Output (J8) is an open collector transistor, closing to 0V when active. Example of wiring a
relay to the PSU Fault- output:
Battery connection: Connect red lead to battery + terminal, connect black lead to battery - terminal.
E.g. For a 24V system connect as shown.
3. CONTROLS & CONFIGURABLE OPTIONS (FIELD ADJUSTMENTS)
Mains On/Off (fuse holder in terminal block acts as a mains switch. Remove fuse to switch off, Fuse is
20x5,1A rating).
- Switches mains (but not the batteries).
Output Adjust (potentiometer PT1 on pcb)
- Adjusts output voltage (and fault thresholds), preset in factory for nominal output.
If field adjustment is required, rotate clockwise to increase voltage, anti-clockwise to decrease.
Timer Disable (remove link LK1 on pcb)
- Disables all automatic battery tests (i.e. battery connected check, hourly and 48 hourly battery
capacity tests).
Current Limit (snip out resistors R13, R14, R15 on pcb).
- Reduces current limit (also charger current rating) if required by battery manufacturer's ratings.
See specifications for details.
Charger Fault (LK2 on pcb)
- If the link is fitted the PSU Fault- output will be active during a charger high or low condition.
Remove the link for AS1603.4 or NZ operation as this feature is not required.
Mains Fail (LK3 on pcb) (software V2.01 onwards)
- If the link is not fitted the PSU Fault output will be active after 90 minutes of continuous mains
failure.
4. STANDARDS COMPLIANCE
To comply with AS1603.4 Clause 2.8.8 an appropriate external battery test load needs to be applied
at the same time as activating the Charger Disable input.
AS4428.5:1998 has two clauses that only need to be complied with if the standard for the product the
PSU is powering requires them. At present there are no such standards. The 1948 PSU cannot meet
Clause 2.2(c) when a short circuit or polarity reversal is applied to the battery terminals. The 1948
PSU does not support disconnecting the battery from the PSU load when the final voltage is reached.
(Clause 2.3(c)).
To signal the loss of mains power (Clause 2.4(a)), remove LK3 (see Section 3 above).