Datasheet FGEN-IOM88-4001/CS30007 Datasheet (Turck)

Compact fieldbus I/O modules for EtherNet/IP 8 digital PNP inputs 8 digital outputs 2 A FGEN-IOM88-4001/CS30007
Type designation FGEN-IOM88-4001/CS30007
Ident-No. 6825443
CS30007: IP address 136.129.1.xxx
EtherNet/IP™ supports QuickConnect
(QC)
Integrated Ethernet Switch
Input diagnostics per port
Output diagnostics per channel
Two inputs or outputs per port
7/8", 4-pin, for power supply
Power supply, galvanically separated
Fibre-glass reinforced PA6 housing
Vibration and shock-resistant
Encapsulated module electronics
Metal connectors
Degree of protection IP67
System data
Transmission rate Ethernet 10 MBit/s / 100 MBit/s Fieldbus connection technology 2 × M12 Service interface Ethernet
EtherNet/IP™
Quick Connect (QC) < 100 ms Device Level Ring (DLR) supported Class 1 connections 6
Number of channels (8) 3-wire pnp sensors Switching threshold EN 61131-3
low max.: 1.5 mA / high min.: 2 mA Input delay 2.5 ms Electrical isolation galvanically separated against the bus and outputs Input voltage 18…30 VDC from operating voltage UB
Number of channels (8) DC actuators Output voltage 18…30 VDC from load voltage Output current per channel 2.0 A, short-circuit proof Simultaneity factor 0.25 for entire module
1* 2A or 2* 1A per port
total current max. 9 A per module Load type resistive, inductive, lamp load Electrical isolation galvanically separated against bus and inputs
Vibration test acc. to EN 60068-2-6 Shock test acc. to EN 60068-2-27 Electromagnetic compatibility acc. to EN 61131-2 UL Certificate pol. deg.2, env. temp. max. 40 °C, cl.2 ps req.
Dimensions (W x L x H) 60 x 220.5 x 27mm Operating temperature 0…+55 °C Storage temperature -25 …+70 °C Altitude max.5000 m Protection class IP67 Housing material fibre-glass reinforced Polyamide (PA6-GF30) Halogen-free yes Mounting 4 mounting holes Ø 5,4 mm
Edition • 2019-01-21T22:43:31+01:00
1 / 4 TURCK Inc.
Compact fieldbus I/O modules for EtherNet/IP 8 digital PNP inputs 8 digital outputs 2 A FGEN-IOM88-4001/CS30007
Accessories
Ethernet cable (example):
RSSD-RSSD-441-2M/S2174
Ident no. 6914218
Accessories
Connection cable , 2-channel (example):
RK 4.4T-2-RS 4.4T
Ident no. U2445
Splitter (example): VBRS 4.4-2RK 4T-*/*
Ident-No. U0117
M12 x 1 Ethernet
M12 x 1 Input
M12 x 1 Output
Accessories
Power supply cable (example):
RKM43-1-RSM43
Ident no. 6914312
7/8" Power Supply
Edition • 2019-01-21T22:43:31+01:00
2 / 4 TURCK Inc.
Compact fieldbus I/O modules for EtherNet/IP 8 digital PNP inputs 8 digital outputs 2 A FGEN-IOM88-4001/CS30007
LED status module
LED Color Status Description
ETH1 / ETH2 green on Ethernet Link (100 Mbps)
flashing Ethernet communication (100 Mbps)
yellow on Ethernet Link (10 Mbps)
flashing Ethernet communication (10 Mbps)
off no Ethernet link
Bus green on Active connection to a master
flashing ready
red on IP address conflict or Restore Mode
flashing DHCP / BootP waiting for assignment of IP address
off No power supply
Power green on Operating voltage UB and load voltage UL within the defined tolerances
red on Load voltage UL below the defined tolerances
off Operating voltage UB below the defined tolerances
LED status IOs
LED Color Status Description
C0.I1 … C3.I8 green on Input active
red on Overload of sensor supply at the corresponding connector
off Input inactive
C4.O9 … C7.O16 green on Output active
red on Output active with overload / short circuit
off Output inactive
Edition • 2019-01-21T22:43:31+01:00
3 / 4 TURCK Inc.
Compact fieldbus I/O modules for EtherNet/IP 8 digital PNP inputs 8 digital outputs 2 A FGEN-IOM88-4001/CS30007
Process data mapping of single protocols
EtherNet/IP™ Data Mapping
Word Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input (Station -> Scanner)
GW Status 1 - - - - - - UB - UL - - - - - - Diag
Warn
Input 2 - - - - - - - - DI7
Diag 3 - - Sched
Diag
Diag 4 SCO7 SCO6 SCO5 SCO4 SCO3 SCO2 SCO1 SCO0 - - - - SCS3 SCS2 SCS1 SCS0
Output (Scanner -> Station)
Control 1 reserved
Outputs
Legend:
DI Digital input -
DO Digital output -
Cx female -
Px Pin I/ODiag I/O diagnostics available
DiagWarn Diagnostic at least on 1 channel SchedDiag Manufacturer-specific diagnostics configured and active
UL Undervoltage UL SCSx Short-circuit on sensor supply at female x
UB Undervoltage UB SCOx Short-circuit output x
2 - - - - - - - - DO7
- - - - - - - - - - - - I/O
C3P2
C7P2
DI6
C3P4
DO6
C7P4
DI5
C2P2
DO5
C6P2
DI4
C2P4
DO4
C6P4
DI3
C1P2
DO3
C5P2
DI2
C1P4
DO2
C5P4
DI1
C0P2
DO1
C4P2
DI0
C0P4
Diag
DO0
C4P4
Edition • 2019-01-21T22:43:31+01:00
4 / 4 TURCK Inc.
Loading...