Trumeter 8981-5, 8981-1, 8980-1 User manual

Model 898X
Electronic Preset Counter
with two presets
hsilgne
Model 899X
www.GlobalTestSupply.com
con dos preselecciones
Elektronischer Vorwahlzähler
mit zwei Vorwahlen
Compteur à présélection électronique
avec deux présélections
Contatore elettronico a preselezione
con due preselezioni
022792-01 Issue 1.0 03/17
loñapse
hcstued
siaçnarf
onailati
Table of Contents
1 Preface 2
Safety instructions and Warnings
2.1 Use according to the intended purpose 4
2.2 Mounting in a control panel 4
2.3 Electrical Installation 5
2.4 Cleaning and maintenance 5
3 Description 5 4
Display/Operating elements 6
5
Inputs 6
5.1 INP A, INP B 6
5.2 RESET 6
5.3 GATE 6
5.4 LOC.INP 6
5.5 MPI 1 / MPI 2 6
6 Outputs 6
6.1 Output 1 / Output 2 6
6.2 Active Outputs 6
7 Programming 6
7.1 Entering the programming 6
7.2 Selecting the main menus 7
7.3 Entering a sub-menu 7
7.4 Selecting the parameters 7
7.5 Changing parameter values 7
7.6 Setting count values 7
7.7 Ending the programming 7
7.8 Programming menu 7
7.8.1 Select language 7
7.8.2 Setting the Basic Function 8
7.8.3 Pulse Counter 8
7.8.4 Tacho/Frequency meter 10
7.8.5 Timer 11
8 Operation 15
8.1 Switching the display during operation 15
8.2 Setting the presets 15
8.2.1 Setting via front keys 15
8.2.2 Teach Function 16
8.2.3 Teach-In with tracking presets 16
8.3 Set Function 16
8.4 Default Parameters 16
8.4.1 Entry into the default setting 16
8.4.2 Selecting the parameter sets 16
8.4.3 Accepting the setting 16
8.4.4 Parameter Set Table 17
9 Error Message 17 10
Connections 17
10.1 Signal and Control Inputs 17
10.2 Supply Voltage and Outputs 17
11 Technical Data 17
11.1 General Data 17
11.2 Pulse Counter 17
11.3 Tacho/Frequency Meter 18
(German is the original version)
4 4
Page 2 | ENG
www.GlobalTestSupply.com
11.4 Timer 18
11.5 Signal and Control Inputs 18
11.6 Outputs 18
11.7 Supply Voltage 18
11.8 Sensor Supply Voltage 18
11.9 Climatic Conditions 18
11.10 EMC 18
11.11 Device Safety 18
11.12 Mechanical Data 18
11.13 Connections 19
12 Scope of Delivery 19 13 Ordering Codes 19 14 Frequencies (typical) 19
14.1 Pulse Counter 19
14.2 Frequency Meter 19
15 Input modes: Pulse counting 20 16 Input modes: Timing 22 17 Input modes: Frequency meter 23 18 Output operations 24 19 Help Texts 26 20 Dimensional Drawings 28
english
Page 3 | ENG
www.GlobalTestSupply.com
entirely and carefully before installation
warnings and advice, both for your own
with this instruction manual, then the
Please bear in mind safety aspects and
device is integrated is the responsibility
work.
protected with approved external fuses.
that the terminals are out of the reach
1 Preface
Please read this instruction manual
and start-up. Please observe all
safety and for general plant safety. If the device is not used in accordance
intended protection can be impaired.
2 Safety instructions and
Warnings
Please use the device only if its technical condition is perfect. It should be used only for its intended purpose.
potential dangers and adhere to the operating instructions at all times. Defective or damaged devices should be disconnected from the mains immediately and taken out of operation. The device shall not be opened. Use the repair service of the manufacturer. Only connect the device to the electricity networks provided to that purpose. The safety of the system in which the
of the installer. Disconnect all electricity networks prior to any installation or maintenance
Use exclusively cables approved in your country and designed for your temperature and power ranges. Installation and service work shall be carried out exclusively by qualified personnel. The device must compulsorily be
The value of these fuses can be found in the technical information.
This symbol is used on the device to remind of the existence of dangers, which are referred to in this manual.
2.1 Use according to the intended purpose
The preset counter detects and measures pulses, times and frequencies up to max. 60 kHz and offers a wide variety of different operating modes. At the same time, the preset counter processes programmed presets. Use for any purpose over and beyond this will be deemed as not in accordance with its intended purpose and thus not complying with the requirements.
The application area for this device lies in industrial processes and controls, in the fields of manufacturing lines for the metal, wood, plastics, paper, glass, textile and other like industries. Over­voltages at the terminals of the device must be kept within the limits of over-voltage Category II. The device must only be operated when mounted in a panel in the correct way and in accordance with the section “Technical Data”.
The device is not suitable for use in hazardous areas and for areas excluded in EN 61010 Part 1. If the device is used to monitor machines or processes in which, in the event of a failure of the device or an error made by the operator, there might be the risk of damaging the machine or causing an accident to the operators, it is your responsibility to take the appropriate safety measures.
The device has been designed for indoor operation. It may nevertheless be used outdoors, provided the technical data is adhered to. In this case, take care to provide suitable UV protection.
2.2 Mounting in a control panel
Mount the device away from heat sources and avoid direct contact with corrosive liquids, hot steam or similar.
CAUTION
Provide a free space of 10mm all around the device for its ventilation.
The device should be mounted so
of the operator and cannot be touched by him. When mounting the device, consider the fact that only the front side is classified as accessible
Mounting instructions
1. Remove the mounting clip from the device.
2. Insert the device from the front into the panel
3. Slide the fixing clip from the rear onto the
Note: In case of proper installation, IP65 can be
reached on the front side.
for the operator.
cut-out, ensuring the front-panel gasket is correctly seated.
housing, until the spring clamps are under tension and the upper and lower latching lugs have snapped into place.
Page 4 | ENG
www.GlobalTestSupply.com
2.3 Electrical Installation
via a switch or circuit breaker installed
Installation or maintenance work must
voltages entering or exiting the device
During installation, make sure that the supply
The cables and their insulation must be designed
Before starting the device, check the cables for
The device must be disconnected from any power supply prior to any installation or maintenance work. Make sure that no more voltages
DANGER
LIABLE TO CAUSE AN ELECTROCUTION
are present.
AC-powered devices must only be connected to the low-voltage network
close to the device and marked as their disconnecting device.
only be carried out by qualified personnel and in compliance with the applicable national and international standards.
Take care to separate all extra-low
from hazardous electrical conductors by means of a double or reinforced insulation (SELV circuits).
The device must be protected externally for its proper operation. Information about the prescribed fuses can be found in the technical
DANGER
information.
The relay outputs are not protected internally in the device. Without suitable protection of the relay outputs, undesired heat development or even fire may occur. The relay outputs must be protected externally by the manufacturer of the plant. It must also be made sure that, even in case of a malfunction, the values stated in the technical data are under no circumstances exceeded.
voltage and the wiring of the output contacts are both fed from the same mains phase, in order not to exceed the maximum permitted voltage of 250V.
for the planned temperature and voltage ranges. Regarding the type of the cables, adhere to the applicable standards of the country and of the plant. The cross sections allowed for the screw terminals can be found in the technical data.
proper wiring and tightening. The screws of
unused screw terminals must be screwed to the stop, so that they cannot loosen and get lost.
The device has been designed for overvoltage category II. If higher transient voltages cannot be excluded, additional protection measures must be taken in order to limit the overvoltage to the values of CAT II.
Advice on noise immunity
All connections are protected against external sources of interference. The installation location should be chosen so that inductive or capacitive interference does not affect the device or its connecting lines! Interference (e.g. from switch­mode power supplies, motors, clocked controllers or contactors) can be reduced by means of appropriate cable routing and wiring.
Measures to be taken:
Use only shielded cable and control lines. Connect shield at both ends. The conductor cross-section of the cables should be a minimum of 0.14 mm². The shield connection to the equipotential bonding should be as short as possible and with a contact area as large as possible (low-impedance). Only connect the shields to the control panel, if the latter is also earthed. Install the device as far away as possible from noise-containing cables. Avoid routing signal or control cables parallel to power lines.
2.4 Cleaning and maintenance
The front side of the unit should only be cleaned using a soft damp (water!) cloth. Cleaning of the embedded rear side is not planned and is the responsibility of the service personnel or of the installer.
In normal operation, this device is maintenance­free. Should the device nevertheless not operate properly, it must be sent back to the manufacturer or to the supplier. Opening and repairing the device by the user is not allowed and can adversely affect the original protection level.
3 Description
6-digit 14-segment LED display, 14 mm Help Text display Preset counter with two relay outputs Preset entry via the front keys or via the Teach-In function Step or tracking preset Pulse counter, Frequency meter, Timer or Hour meter Preset-, Batch- or Total counter Set function for pulse counter and timer
www.GlobalTestSupply.com
english
Page 5 | ENG
Multiplication and division factor Averaging and Start Delay for frequency meter Input modes: Pulse counter: cnt.dir, up.dn, up.up, quad, quad2, quad4, A/B, (A-B)/Ax100% Frequency meter: A, A – B, A + B, quad, A/B, (A-B)/Ax100% Timer: FrErun, Auto, InpA.InpB, InpB.InpB Output operations: Add, Sub, AddAr, SubAr, AddBat, SubBat, AddTot, SubTot, Trail, TrailAr 4-stage RESET mode 3-stage keypad locking (Lock) MPI input for Display Latch, Teach-In or Set function Supply voltage 100 … 240 V AC ±10% or 10 ... 30 VDC
4 Display/Operating elements
6-digit LED display
1
Status display LED1 / LED2
2
RESET key / ENTER key
3 4 Key LEFT 5 Key UP 6 Key DOWN 7 Key RIGHT
5 Inputs
5.1 INP A, INP B
Signal inputs: function acc. to operating mode. Max. frequency 60 kHz, can be damped in the programming menu to 30 Hz. Pulse counter: Count inputs Frequency meter: Frequency inputs Timer: Start input or Start/Stop inputs
5.2 RESET
Dynamic reset input: resets the pulse counter or timer to zero (‘Add’ output operations) or to preset value 2 (‘Sub’ output operations). The reset input can be inhibited in the programming menu. Pulse counter: RESET input Frequency meter: no function Timer: RESET input
5.3 GATE
Static gate input: function dependent on operating mode. Pulse counter: no counting while active Frequency meter: no counting while active Timer: no time measurement while active
5.4 LOC.INP
Static keypad lock input for preset or programming. Lock-out level can be set in the programming menu.
5.5 MPI 1 / MPI 2
User Input. Programmable as Display Latch, Set or Teach-In input.
6 Outputs
6.1 Output 1 / Output 2
Relays with potential-free changeover contacts.
6.2 Active Outputs
LED1 and LED2 indicate an active output. For safety switching the relays can be inverted, i.e. the relays will be de-energized when the presets are reached. To do this, the parameters Pr.OUT1 and Pr. OUT2 must be set to signal) and to
or (for timed signal).
7 Programming
7.1 Entering the programming
Simultaneously press the UP key and the DOWN key for 3 sec.
The security prompt appears alternately in the display
Programming can be exited again using the ENTER key.
Press the UP key or DOWN key to continue with the programming.
(for permanent
Page 6 | ENG
www.GlobalTestSupply.com
PROG.
The security prompt YES appears in the display
Enter the main menu by pressing the ENTER key
The first menu item in the main menu appears in the display
When ending the programming via NO the counter contents are not reset.
7.2 Selecting the main menus
The main menus are selected using the UP and DOWN keys
Indicated by LED1
7.3 Entering a sub-menu
Press the ENTER key. The first parameter is displayed with the current setting flashing.
Indicated by LED1 and LED2
7.4 Selecting the parameters
The parameters are selected using either the RIGHT key or the LEFT key.
7.5 Changing parameter values
Press the ENTER key.
Change the parameter value using the UP or DOWN keys.
Press the ENTER key. The new setting is again displayed flashing.
7.6 Setting count values
Press the ENTER key.
Select the decade using the RIGHT key or the LEFT key.
the corresponding
decade flashes
Change the count value using the UP key or the DOWN key.
Press the ENTER key. The new setting is again displayed flashing.
7.7 Ending the programming
Select the menu item
Pressing the ENTER key acknowledges this prompt and allows the programming to be repeated. The previously­programmed values are preserved. These can now be checked or changed once again.
Pressing the UP key or the DOWN key selects the termination of the programming.
The security prompt YES appears in the display
Pressing the ENTER key acknowledges this prompt and terminates the programming; the modified settings are saved in the EEPROM.
The text SAVE is shown in the display for 2 sec.
When ending the programme via END.PRG. YES the counter contents are reset.
No count pulses, frequencies or times are detected or measured whilst programming is taking place.
7.8 Programming menu
Factory settings are highlighted in grey
7.8.1 Select language
Submenu: Select language
Help Text
Help Text ON
Help Text OFF
english
Page 7 | ENG
www.GlobalTestSupply.com
Select language for Help Text
English German (Deutsch)
When ‘Help Text ON’ is selected, a running text in English or German automatically appears after 3 sec. in the display. This provides an explanation of the menu item. Once a running text has started, it can be cancelled by pressing any key.
7.8.2 Setting the Basic Function
Submenu: Basic function
Basic Function
Pulse counter (7.8.3) Timer/Hour meter (7.8.5) Tacho/Frequency meter (7.8.4)
Changing the basic function causes all parameters to be reset to factory settings.
7.8.3 Pulse Counter
7.8.3.1 Submenu for the Signal and Control inputs
Submenu for programming the signal and control inputs
Input polarity
PNP: switching to Plus for all inputs in common
NPN: switching to 0 V for all inputs in common
Filter for signal inputs INP A and INP B
Maximum count frequency Damped to approx. 30 Hz
(for control with mechanical contacts)
Count Input mode
(See also under 15.)
Count/Direction control
INP A: count input INP B: count direction input
Differential counting [A – B]
INP A: count input add INP B: count input sub
Totalising [A + B]
INP A: count input add INP B: count input add
Quadrature input INP A: count input 0° INP B: count input 90°
Quadrature with pulse doubling (x2)
INP A: count input 0° INP B: count input 90° Each pulse edge of INP A will be counted
Quadrature x4
INP A: count input 0° INP B: count input 90° Each pulse edge of INP A and INP B will be counted.
Ratio measurement [A / B]
INP A: count input A INP B: count input B
Percentage differential counting [(A – B) / A in %]
INP A: count input A INP B: count input B
User input 1 User input 2
When the MPI input is activated the display is “frozen” and remains “frozen” until the MPI input is deactivated. Internally the preset counter continues counting.
When the MPI input is activated the current count value for the preset that has just been selected will be adopted as the new preset value. (See also 8.2.2)
When the MPI input is activated the preset counter will be set to the value specified in the parameter SETPT. (See also 8.3)
Lock input
When the Lock input is activated, the programming is inhibited.
When the Lock input is activated, the setting of the preset values is inhibited.
Page 8 | ENG
www.GlobalTestSupply.com
When the Lock input is activated, the setting of the preset values and the programming are both inhibited.
7.8.3.2 Submenu for Output operations
Submenu for determining the operation of the outputs
Output operation (See also under 18.)
Count mode ADDING
Outputs active when count status > preset value Reset to zero
Count mode SUBTRACTING
Output 1 active when count status < preset value 1 Output 2 active when count status < 0 Reset to preset 2
Count mode ADDING with automatic reset
Output 1 active when count status > preset value 1 Output 2 (timed signal) active when count status = preset value 2 Automatic reset to zero when count status = preset value 2 Reset to zero
Count mode SUBTRACTING with automatic reset
Output 1 active when count status < preset value 1 Output 2 (timed signal) active when count status = 0 Automatic reset to preset 2 when count status = 0 Reset to preset 2
Count mode ADDING with automatic reset and Batch counter
Output 2 (timed signal) active when main counter = preset value 2 Automatic reset to zero when main counter = preset 2 Batch counter counts the number of automatic repetitions of preset 2 Output 1 active when Batch counter > preset 1 Manual reset sets both counters to zero.
Electrical reset sets only the main counter to zero.
Count mode SUBTRACTING with automatic reset and Batch counter
Output 2 (timed signal) active when main counter = zero Automatic reset to preset 2 when main counter = zero Batch counter counts the number of automatic repetitions of preset 2 Output 1 active when Batch counter > preset 1 Manual reset sets main counter to preset value 2 batch counter to zero Electrical reset only sets the main counter to preset value 2
Count mode ADDING with automatic reset and Total counter
Output 2 (timed signal) active when main counter = preset value 2 Automatic reset to zero when main counter = preset value 2 Total counter counts all the count pulses from the main counter Output 1 active when total counter > preset value 1 Manual Reset sets both counters to zero Electrical reset sets only the main counter to zero
Count mode SUBTRACTING with automatic reset and Total counter
Output 2 (timed signal) active when main counter = zero Automatic reset to preset value 2 when main counter = zero Total counter counts (sub from preset value 1) all count pulses from main counter Output 1 active when Total counter < zero Manual reset sets both counters to the preset values Electrical reset sets only main counter to preset value 2
Tracking Preset mode
When preset 2 is changed then preset 1 automatically tracks it. Reset to zero Preset 1 relative to Preset 2
Tracking Preset mode with automatic reset
english
www.GlobalTestSupply.com
Page 9 | ENG
Ele
ctrical Reset
:
if the
7.8.3.3 Submenu for configuration
7.8.3.4 Submenu for reset mode
Page 10 | ENG
When preset 2 is changed then preset 1 automatically tracks it. Reset to zero. Automatic reset to zero when main counter = preset value 2. Preset 1 relative to Preset 2
Submenu for matching the input pulses to the display.
Multiplication factor can be programmed from
00.0001 to 99.9999 The setting
00.0000 will not be accepted.
Division factor
can be programmed from
01.0000 to 99.9999 A setting < 01.0000 will not be accepted.
Decimal point setting (only optical function) 0 no decimal place
0.0 1 decimal place
0.00 2 decimal places
0.000 3 decimal places
0.0000 4 decimal places
0.00000 5 decimal places
Set value
Set value can be programmed from -999999 to 999999 A previously programmed decimal point will be displayed
Submenu for setting the reset mode
Reset mode
Manual reset (reset key) and electrical reset (reset input)
No reset possible (reset key and reset input inhibited)
Only electrical reset possible (reset input)
Only manual reset possible (reset key)
www.GlobalTestSupply.com
Always resets only the main counter.
Manual Reset: Resets the main counter (ACTUAL) and auxiliary counters (BATCH or TOTAL), value of the main counter or the value of an auxiliary counters is shown on the display.
7.8.3.5 Preset 1
see below 7.9.5.5
7.8.3.6 Preset 2
see below 7.9.5.6
7.8.4 Tacho/Frequency meter
7.8.4.1 Submenu for the Signal and
Control inputs
Submenu for programming the signal and control inputs
Input polarity
PNP: switching to Plus for all inputs in common
NPN: switching to 0 V for all inputs in common
Filter for signal inputs INP A and INP B
maximum count frequency Damped to approx. 30 Hz
(for control with mechanical contacts)
Input mode Frequency measurement (see also under 17.)
Simple frequency measurement
INP A: Frequency input INP B: no function
Differential measurement [A – B]
INP A: Frequency input A INP B: Frequency input B
Total measurement [A + B]
INP A: Frequency input A INP B: Frequency input B
Frequency measurement with direction detection [Quad]
INP A: Frequency input 0° INP B: Frequency input 90°
Ratio measurement [A / B]
INP A: Frequency input A INP B: Frequency input B
Percentage differential measurement [(A-B) / A in %]
INP A: Frequency input A INP B: Frequency input B
User input 1
User input 2
When the MPI input is activated the display is “frozen” and remains “frozen” until the MPI input is deactivated. Internally the frequency meter continues running (Display store).
When the MPI input is activated the current frequency for the preset that has just been selected will be adopted as the new preset value. (See also 8.2.2)
Lock input
When the Lock input is activated the programming is inhibited
When the Lock input is activated the setting of the preset values is inhibited.
When the Lock input is activated the setting of the preset values and the programming are both inhibited
7.8.4.2 Submenu for configuration
Submenu for matching the input pulses to the display.
Multiplication factor can be programmed from
00.0001 to 99.9999 .The setting
00.0000 will not be accepted
Division factor
can be programmed from
01.0000 to 99.9999 A setting < 01.0000 will not be accepted.
Display mode
Calculation and display of the frequency / speed in 1/sec
Calculation and display of the frequency / speed in 1/min
Decimal point setting (determines the resolution) 0 no decimal place
0.0 1 decimal place
0.00 2 decimal places
0.000 3 decimal places
Moving average
Moving average calculated AVG 2 over 2 measurements AVG 5 over 5 measurements AVG 10 over 10 measurements AVG 20 over 20 measurements
Start delay
Programmable from 00.0 up to
99.9 sec. At the start of a measurement the measurement results within this time-period are ignored.
Waiting time
Programmable from 00.1 up to
99.9 sec. This value specifies how much time should elapse, after the last valid edge, before zero is to be displayed.
7.8.4.3 Preset 1
See below 7.9.5.5
7.8.4.4 Preset 2
See below 7.9.5.6
7.8.5 Timer
7.8.5.1 Submenu for the Signal and
Control inputs
Submenu for programming the signal and control inputs
Input polarity
PNP: switching to Plus for all inputs in common
NPN: switching to 0 V for all inputs in common
Filter for signal inputs INP A and INP B
for electronic control of the signal inputs
for mechanical control of the signal inputs (for control with mechanical contacts)
english
www.GlobalTestSupply.com
Page 11 | ENG
Page 12 | ENG
Input mode Time measurement
(see also under 16.) Start: Edge to INP A
Stop: Edge to INP B Start: 1. Edge to INP B
Stop: 2. Edge to INP B Timing can only be controlled via
the Gate input. INP A and INP B have no function.
The timer is reset by means of a RESET (to zero when adding, to preset 2 when subtracting) and then starts timing again. Timing is stopped with adding operations when preset 2 is reached. Timing is stopped with subtracting operations when zero is reached. A RESET during the timing process also causes this to stop. . INP A and INP B: no function.
With AUTO: no output operations with automatic repeat.
User input 1
User input 2
When the MPI input is activated the display is “frozen” and remains “frozen” until the MPI input is deactivated. Internally the preset timer continues counting.
When the MPI input is activated the current count value for the preset that has just been selected will be adopted as the new preset value. (See also under 8.2.2)
When the MPI input is activated the preset counter will be set to the value specified in the parameter SETPT. (See also under 8.3)
Lock input
When the Lock input is activated the programming is inhibited
When the Lock input is activated the setting of the preset values is inhibited.
When the Lock input is activated the setting of the preset values and the programming is both inhibited.
www.GlobalTestSupply.com
7.8.5.2 Submenu for output operations
Submenu for determining the operation of the outputs
Output operation (See also under 18.)
Count mode ADDING
Outputs active when count status > preset value Reset to zero
Count mode SUBTRACTING
Output 1 active when count status < preset value 1 Output 2 active when count status < 0 Reset to preset 2
Count mode ADDING with automatic reset
Output 1 active when count status > preset value 1 Output 2 (timed signal) active when count status = preset value 2 Automatic reset to zero when count status = preset value 2 Reset to zero
Count mode SUBTRACTING with automatic reset
Output 1 active when count status < preset value 1 Output 2 (timed signal) active when count status = 0 Automatic reset to preset 2 when count status = 0 Reset to preset 2
Count mode ADDING with automatic reset and Batch counter
Output 2 (timed signal) active when main counter = preset value 2 Automatic reset to zero when main counter = preset 2 Batch counter counts the number of automatic repetitions of preset 2 Output 1 active when Batch counter > preset 1 Manual reset sets both counters to zero. Electrical reset sets only the main counter to zero.
Count mode SUBTRACTING with automatic reset and Batch counter
Output 2 (timed signal) active when main counter = zero Automatic reset to preset 2 when
Ele
ctrical Reset
:
auxiliary counters (BATCH or TOTAL), if the
main counter = zero Batch counter counts the number of automatic repetitions of preset 2 Output 1 active when batch counter > Preset 1
Manual reset sets main counter to preset value 2 and batch counter to zero Electronic reset only sets the main counter to preset value 2
Count mode ADDING with automatic reset and Total counter
Output 2 (timed signal) active when main counter = preset value 2 Automatic reset to zero when main counter = preset value 2 Total counter counts all the count pulses from the main counter Output 1 active when total counter > preset value 1 Manual Reset sets both counters to zero Electrical reset sets only the main counter to zero
Count mode SUBTRACTING with automatic reset and Total counter
Output 2 (timed signal) active when main counter = zero Automatic reset to preset value 2 when main counter = zero Total counter counts (sub from preset value 1) all count pulses from main counter Output 1 active when Total counter < zero Manual reset sets both counters to the preset values Electrical reset sets only main counter to preset value 2
Tracking Preset mode
When preset 2 is changed then preset 1 automatically tracks it. Reset to zero Preset 1 relative to Preset 2
Tracking Preset mode with automatic reset
When preset 2 is changed then preset 1 automatically tracks it. Reset to zero. Automatic reset to zero when
main counter = preset value 2. Preset 1 relative to Preset 2
7.8.5.3 Submenu for configuration
Submenu for matching the input pulses to the display.
Unit of time
Seconds
Decimal point setting determines the resolution
Minutes
Decimal point setting determines the resolution
Hours Decimal point setting determines the resolution
Hrs. Min. Sec.
Decimal point setting
(determines the resolution) 0 no decimal place
0.0 1 decimal place
0.00 2 decimal places
0.000 3 decimal places
Set value
Set value can be programmed from 000000 to 999999 A previously programmed decimal point will be displayed
7.8.5.4 Submenu for reset mode
Submenu for setting the reset mode
Reset mode
Manual reset (reset key) and electrical reset (reset input)
No reset possible (reset key and reset input inhibited)
Only manual reset possible (reset key)
Only manual reset possible (reset key)
Always resets only the main counter.
Manual Reset: Resets the main counter (ACTUAL) and
value of the main counter or the value of an auxiliary counters is shown on the display.
english
www.GlobalTestSupply.com
Page 13 | ENG
7.8.5.5 Submenu for Preset 1
Submenu Preset 1
Preset 1 ON/OFF
Preset 1 ON
Preset 1 OFF and no function
Output signal
ADD mode output operations: permanent signal at Output 1, becomes active when count > Preset 1 SUB mode output operations: permanent signal at Output 1, becomes active when count < Preset 1
ADD mode output operations: permanent signal at Output 1, becomes passive when count > Preset 1 SUB mode output operations: permanent signal at Output 1, becomes passive when count < Preset 1
ADD mode output operations: timed signal at Output 1, becomes active when count > Preset 1. (Activation only in positive direction) SUB mode output operations: timed output at Output 1, becomes active when count < Preset 1 (Activation only in negative direction)
ADD mode output operations: timed signal at Output 1, becomes passive when count > Preset 1. (Deactivation only in positive direction) SUB mode output operations: timed output at Output 1, becomes passive when count < Preset 1. (Deactivation only in negative direction)
ADD mode output operations: timed signal at Output1, becomes active with positive direction and when count > Preset 1 and subsequently active with negative direction and when count < Preset 1 SUB mode output operations: timed signal at Output 1, becomes active with negative direction and when count < Preset 1 and subsequently active
with positive direction and when count > Preset 1
ADD mode output operations: timed signal at Output1, becomes passive with positive direction and when count > Preset 1 and subsequently passive with negative direction and when count < Preset 1 SUB mode output operations: timed output at Output 1, becomes passive with negative direction and when count < Preset 1 and subsequently passive with positive direction and when count > Preset 1
Duration of timed signal of Output 1
programmable from 00.01 to
99.99 sec. Timed signal is post-triggered
7.8.5.6 Submenu for Preset 2
Output signal
ADD mode output operations: permanent signal at Output 2, becomes active when count > Preset 2 SUB mode output operations: permanent signal at Output 2, becomes active when count < zero
ADD mode output operations: permanent signal at Output 2, becomes passive when count > Preset 2 SUB mode output operations: permanent signal at Output 2, becomes passive when count < zero
ADD mode output operations: timed signal at Output 2, becomes active when count > Preset 2 (Activation only in positive direction). SUB mode output operations: timed signal at Output 2, becomes active when count < zero (Activation only in negative direction)
ADD mode output operations: timed signal at Output 2, becomes passive when count > Preset 2 (Deactivation only in positive direction) SUB mode output operations: timed signal at Output 2,
Page 14 | ENG
www.GlobalTestSupply.com
becomes passive when count < zero (Deactivation only in negative direction).
ADD mode output operations: timed signal at Output 2, becomes active with positive direction and when count > Preset 2 and subsequently with negative direction and when count < Preset 2 SUB mode output operations: timed signal at Output 2, becomes active with negative direction and when count < zero and subsequently with positive direction and when count > zero
ADD mode output operations: timed signal at Output 2, becomes passive with positive direction and when count > Preset 2 and subsequently with negative direction and when count < Preset 2 SUB mode output operations: timed signal at Output 2, becomes passive with negative direction and when count < zero and subsequently with positive direction and when count > zero
Duration of timed signal of Output 2
programmable from 00.01 to
99.99 sec. Timed signal is post-triggered
Active: Relays are activated when the preset value is reached. Passive: Relays becomes de-energized when the preset value is reached.
Timed outputs that have started are not aborted by a RESET.
8 Operation
8.1 Switching the display during
operation
Pressing the DOWN key or the UP key once causes the name of the currently selected display
t = 2 sec
function to be displayed for 2 sec. If within this time the DOWN key or the UP key is pressed a second time, then the display switches to the next or previous display function. This is confirmed by displaying the new name for a period of 2 sec. After 2 sec the count value that corresponds to the selected display function is displayed.
Main counter
Batch counter
Total counter
Preset 1
Preset 2
8.2 Setting the presets
8.2.1 Setting via front keys
Using the UP key or the DOWN key, select the preset to be changed, either PRES1 or PRES2 (see 8.1).
Select the decade using the RIGHT key or the LEFT key.
the corresponding
decade flashes
Set the count value using the UP key or the DOWN key.
The new setting is accepted either by pressing the ENTER key or after a period of 2 sec.
Preset setting is inhibited if the lock function for the presets is active (Parameter LOC.INP set to PRESET or PRG.PRE and keypad lock input LOCK active).
english
www.GlobalTestSupply.com
Page 15 | ENG
8.2.2 Teach Function
acknowledgment of the parameter sets, all
1. In the programming menu, programme MPI input 1 or MPI input 2 (MP.INP.1 / MP.INP.2) to TEACH
2. In operating mode, select the preset to be changed: PRES1 or PRES2
3. In operating mode, briefly activate MPI input 1 or MPI input 2 (NPN or PNP input logic)
the current count value will be adopted as the new preset value
See also 9. Error messages.
The preset value can subsequently be further modified via the keypad. If preset entry is inhibited (see note 8.2.1), then the Teach Function is also locked out.
8.2.3 Teach-In with tracking presets
If a tracking (trailing) preset (TRAIL or TR.AR) has been programmed, the value for Preset 2 can be set either via the keypad or via the Teach-In function. However the value for Preset 1 must be entered via the keypad. In this instance, it is not possible to use the Teach-In function. .
With output operations ADD.BAT, SUB.BAT, ADD.TOT, SUB.TOT, TRAIL and TR.AR, the Teach-In function is not available for Preset 1.
8.3 Set Function
The pulse counter and the timer can be set to a value by means of the Set function.
1. In the programming menu, programme MPI Input 1 or MPI Input 2 (MP.INP1 / MP.INP2) to SET
2. In the programming menu, set the parameter SETPT to the desired value
3. In operating mode, briefly activate MPI input 1 or MPI input 2 (NPN or PNP input logic)
For add. output operations the pulse
counter or timer will be set to the SETPT value
For sub. output operations the pulse
counter or timer will be set to the difference between the value of Preset 2 and the value of SETPT
See also 9. Error messages
Page 16 | ENG
8.4 Default Parameters
Note: Three default parameter sets have been permanently stored; these can be adapted as required. With each
parameters will be reset to the values listed in the table.
8.4.1 Entry into the default setting
8.4.2 Selecting the parameter sets
8.4.3 Accepting the setting
www.GlobalTestSupply.com
Simultaneously press the UP key and the DOWN key for 3 sec.
The security prompt appears in the display
Programming can be exited again using the ENTER key.
Press the UP key or the DOWN key to continue with the programming.
The security prompt YES appears in the display
Enter the default menu by pressing the ENTER key
The parameter set last programmed appears in the display
The parameter sets are selected using the UP key and the DOWN key.
Default parameter set 1
Default parameter set 2
Default parameter set 3
Pressing the ENTER key accepts the current setting and returns to the operating mode.
The text SAVE is shown in the display for 2 sec.
8.4.4 Parameter Set Table
P.SET1 P.SET2 P.SET3 HLP.TXT. ON ON ON SL.LANG. EN EN EN FUNCT COUNT COUNT COUNT INP.POL. PNP PNP PNP FILTER ON OFF OFF COUNT CNT.DIR UP.DN QUAD MP.INP.1 LATCH LATCH SET MP.INP.2 TEACH SET TEACH LOC.INP. PROG PROG PROG MODE ADD SUB TRAIL FACTOR 01.0000 01.0000 01.0000 DIVISO. 01.0000 01.0000 01.0000 DP 0 0 0.00 SETPT. 000000 000000 0000.00 RES.MOD. MAN.EL MAN.EL MAN.EL PRES.1 ON ON ON PR.OUT1 T.OUT1 00.10 PR.OUT2 T.OUT2 00.10 00.10
9 Error Message
Err 1 Set value 0 not allowed Err 2 Set value Preset 2 not allowed Err 3 negative Teach-In value for Preset 1 not
permitted
Err 4 Zero or negative Teach-In value for
Preset 2 not permitted
Err 45 EEPROM error
10 Connections
10.1 Signal and Control Inputs
N° Designation Function
1 INP A Signal input A 2 INP B Signal input B 3 RESET Reset input 4 LOCK Keypad lock 5 GATE Gate input 6 MPI 1 User input 1 7 MPI 2 User input 2 8 AC: 24 VDC/80 mA
DC: U
connected
B
through
9 GND (0 VDC) Common connection
Sensor supply voltage
Signal and Control inputs
10.2 Supply Voltage and Outputs
N° Designation Function
10 Relay contact C.2 11 Relay contact N.O.2 12 Relay contact N.C.2 13 Relay contact C.1 14 Relay contact N.O.1 15 Relay contact N.C.1 16 AC: 100…240 V AC ±10% N~
DC: 10..30 VDC
17 AC: 100…240 V AC ±10% L~
DC: GND (0 VDC)
Output 2
Output 1
Supply voltage
Supply voltage
11 Technical Data
11.1 General Data
Display 6-digit, 14-segment LED Digit height 14 mm Overload/ Blinking, 1 sec., counter loses Underload no pulses up to 1 decade Data retention > 10 years, EEPROM Operation 5 keys
11.2 Pulse Counter
Count frequency max. 55 kHz (see under 14. Frequencies - typical) Response time of the outputs: Add;Sub;Trail < 13 ms With automatic repeat < 13 ms A/B; (A-B)/A < 34 ms
english
www.GlobalTestSupply.com
Page 17 | ENG
11.3 Tacho/Frequency Meter
Frequency range 0.01 Hz to 65 kHz (see under 14. Frequencies typ. Measuring principle 76.3 Hz Time interval (Period measurement) > 76.3 Hz Gate time Gate time approx. 13.1 ms Measuring error < 0.1% per channel Response time of the outputs: 1-channel operation < 100 ms @ 40 kHz < 350 ms @ 65 kHz 2-channel operation < 150 ms @ 40 kHz < 600 ms @ 65 kHz
11.4 Timer
Seconds 0.001 sec ... 999 999 sec Minutes 0.001 min ... 999 999 min Hours 0.001 hrs … 999 999 hrs Hrs.Min.Sec 00hrs.00min.01sec ... 99hrs.59min.59sec Min. time measurable 500µs Measuring error < 100 ppm Output response time: < 13 ms
11.5 Signal and Control Inputs
SELV circuits, reinforced / double insulation Polarity: programmable NPN/PNP for all inputs in common Input resistance 5 k Pulse shape any Switching level with AC supply: HTL level Low: 0 ... 4 VDC High: 12 ... 30 VDC 4…30 V DC level Low: 0 ... 2VDC High: 3.5 … 30 VDC Switching level with DC supply: HTL level Low: 0 ... 0,2 x U High: 0.6 x U 4…30 V DC level Low: 0 ... 2 VDC High: 3.5 ... 30 VDC Minimum pulse length of the Reset input: 1 ms Minimum pulse length of the Control inputs:10 ms
11.6 Outputs
Output 1 / Output 2
Relays with changeover contacts Prescribed fuse: 3A Switching voltage max. 250 V AC/ 150 V DC Switching current max. 3 A AC/ DC min. 30 mA DC Switching capacity max. 750 VA/ 90 W
The maximum values shall in no case be exceeded!
Mechanical service life (switching cycles) 20x10 N° of switching cycles at 3 A/ 250 V AC 5x10 N° of switching cycles at 3 A/ 30 V DC 5x10
B
... 30 VDC
B
11.7 Supply Voltage
AC supply: 100 ... 240 V AC / max. 11 VA 50/60 Hz, Tolerance ± 10%
ext. fuse protection: T 0.1 A
DC supply: 10 ... 30 V DC/ max. 5.5 W
ext. fuse protection T 0.25 A
reverse polarity protection, SELV, CLASS II (Limited Power Source)
11.8 Sensor Supply Voltage
(Voltage output for external sensors) SELV circuits, reinforced / double insulation for AC supply: 24 V DC ±15%, 80 mA for DC supply: max. 80 mA, ext. voltage
supply is connected through
11.9 Climatic Conditions
Operating temperature: -20°C … +65°C Storage temperature: -25°C … +75°C Relative humidity: R.H. 93% at +40°C, Non-condensing Altitude: up to 2000 m
11.10 EMC
Noise immunity: EN 61000-6-2
Noise emission: EN 55011 Class B
with shielded signal and control cables
11.11 Device Safety
Design to: EN 61010 Part 1 Protection Class: Protection Class 2 (front side)
Only the front side is classified as accessible
for the operator. Application area: Pollution level 2 over-voltage Category II Insulation: Front: double insulation, Rear side: basic insulation, Signal inputs and und sensor power supply: SELV
11.12 Mechanical Data
Housing: Panel-mount housing to DIN 43 700, RAL 7021 Dimensions: 96 x 48 x 102 mm Panel cut-out: 92 Installation depth: ca. 92 mm incl. terminals Weight: ca. 180 g Protection: IP65 (front, device only) Housing material: Polycarbonate UL94 V-2 Vibration resistance: 10 - 55 Hz / 1 mm / XYZ EN 60068-2-6 30 min. in each direction Shock resistance: EN 60068-2-27 100G / 2 ms / XYZ
6
3 times in each direction
4
EN 60068-2-29 10G / 6 ms / XYZ
4
2000 times in each direction
+0,8
+0,6
x 45
mm
Page 18 | ENG
www.GlobalTestSupply.com
11.13 Connections
Supply voltage and outputs: Plug-in screw terminal, 8-pin, RM 5.00 Core cross - section, max. 2.5 mm²
Signal and control inputs: Plug-in screw terminal, 9-pin, RM 3.50 Core cross - section, max. 1.5 mm²
12 Scope of Delivery
Preset counter Mounting clip Instruction manual
13 Ordering Codes
89XX-X
Interface 1 = None 5 = RS485
Supply voltage 0 = 10 … 30 V DC 1 = 100 … 240 V AC ± 10%
Input trigger levels 8 = 4 … 30 V DC level 9 = HTL level
14 Frequencies (typical)
NOTE: Switching levels of the inputs
Switching levels with AC supply: HTL level Low: 0 …4 V DC High: 12 … 30 V DC 4 … 30 V DC level Low: 0 … 2 V DC High: 3.5 … 30 V DC Switching levels with DC supply: HTL level Low: 0 … 0.2 x U High: 0.6 x U 4 … 30 V DC level Low: 0 … 2 V DC High: 3.5 … 30 V DC
14.1 Pulse Counter
HTL level, signal shape square wave 1:1
AC supply typ. Low 2.5 V typ. High 22 V DC supply 12V typ. Low 2 V typ. High 10 V DC supply 24V typ. Low 2.5 V typ. High 22 V
B
… 30 V DC
B
Cnt.Dir 55 kHz 2.6 kHz 2.5 k Hz Up.Dn ; Up.Up 29 kHz 2.6 kHz 2.5 kHz Quad ; Quad 2 28 kHz 1.2 kHz 1.1 kHz Quad 4 18 kHz 1.1 kHz 0.8 kHz A/B ; (A-B)/A 29 kHz
4…30 V DC level, signal shape square wave 1:1
typ. Low 1.0 V typ. High 4.0 V
Cnt.Dir Up.Dn ; Up.Up Quad ; Quad 2 Quad 4 A/B ; (A-B)/A
Add
AddAr
SubAr AddBat SubBat TrailAr
AddTot SubTot
Sub Trail
Add
AddAr
SubAr AddBat SubBat TrailAr
AddTot SubTot
Sub Trail
9 kHz 2.5 kHz 2.2 kHz 9 kHz 2.5 kHz 2.2 kHz 9 kHz 1.1 kHz 1.1 kHz 9 kHz 1.1 kHz 0.9 kHz
9 kHz
14.2 Frequency Meter
HTL level, signal shape square wave 1:1
AC supply typ. Low 2.5 V typ. High 22 V DC supply 12V typ. Low 2 V typ. High 10 V DC supply 24V typ. Low 2.5 V typ. High 22 V
4…30 V DC level, signal shape square wave 1:1
typ. Low 1.0 V
HTL 5V
A A – B ; A + B A / B ; (A-B)/A Quad
typ. High 4.0 V
65 kHz 9 kHz
65 kHz 9 kHz
30 kHz 9 kHz
english
www.GlobalTestSupply.com
Page 19 | ENG
15 Input modes: Pulse counting
Function Diagram
Note: No counting when GATE input is active P = Preset
CNT.DIR
PNP: Count on rising edge NPN: Count on falling edge
Inp A: Count input Inp B: Count direction Add: Display 0 --> Preset Sub: Display Preset -> 0
UP.DN
UP.UP
QUAD
QUAD2
Page 20 | ENG
www.GlobalTestSupply.com
Inp A: Count input add Inp B: Count input sub Add: Display 0 --> Preset Sub: Display Preset -> 0
Inp A: Count input 1 add Inp B: Count input 2 add Add: Display 0 --> Preset
A 90° B Inp A: Count input Count on one edge Inp B: Reverse direction Add: Display 0 --> Preset Sub: Display Preset -> 0
A 90° B Inp A: Count input Count on rising and on falling edges Inp B: Reverse direction Add: Display 0 --> Preset Sub: Display Preset -> 0
Function Diagram
QUAD4
A / B
Note: No counting when GATE input is active
PNP: Count on rising edge NPN: Count on falling edge
A 90° B Inp A: Count input Count on rising and on falling edges Inp B: Count input Count on rising and on falling edges, Reverse direction Add: Display 0 --> Preset Sub: Display Preset -> 0
Inp A: Count input 1 Inp B: Count input 2
Formula: A / B
english
A % B
www.GlobalTestSupply.com
Inp A: Count input 1 Inp B: Count input 2
Formula: (A – B)/A x100
Page 21 | ENG
16 Input modes: Timing
Function Diagram PNP: Count on rising edge
INA.INB
NPN: Count on falling edge
Inp A: Start Inp B: Stop
Add: Display 0 --> Preset Sub: Display Preset -> 0
INB.INB
FREE.RN
AUTO
Page 22 | ENG
www.GlobalTestSupply.com
Inp A: no function Inp B: Start/Stop
Add: Display 0 --> Preset Sub: Display Preset -> 0
Inp A: no function Inp B: no function
Control of the timing only via the GATE input
Add: Display 0 --> Preset Sub: Display Preset -> 0
Inp A: no function Inp B: no function
Control of the timing via RESET (manual or electrical)
Add: Display 0 --> Preset Sub: Display Preset -> 0
17 Input modes: Frequency meter
Function Diagram PNP: Count on rising edge
A
A - B
A + B
QUAD
NPN: Count on falling edge Inp A: Frequency input
Inp B: no function
Inp A: Frequency input 1 Inp B: Frequency input 2
Formula: A - B
Inp A: Frequency input 1 Inp B: Frequency input 2
Formula: A + B
A 90° B Inp A: Frequency input 1 Inp B: Reverse direction
english
A / B
A % B
www.GlobalTestSupply.com
Inp A: Frequency input 1 Inp B: Frequency input 2
Formula: A / B
Inp A: Frequency input 1 Inp B: Frequency input 2
Formula: (A – B)/A x100
Page 23 | ENG
18 Output operations
Mode Diagram Mode Diagram
Only in mode and
ADD
SUB
Additionally in mode and
ADD.AR
ADD.BAT
ADD.TOT
Page 24 | ENG
SUB.AR
SUB.BAT
SUB.TOT
www.GlobalTestSupply.com
Mode Diagram
TRAIL
english
TR.AR
Page 25 | ENG
www.GlobalTestSupply.com
19 Help Texts
PROG. NO NO PROGRAMMING
PROG. YES ST ART PROGRAMMING LANGU. MAIN MENU SELECT LANGUAGE HLP.TXT. YES HELPTEXT ON SL.LANG. DE DEUTSCH SL.LANG. EN EN GLISH FUNCT. MAIN MENU BASIC FUNCTION FUNCT. COUNT BASIC FUNCTION COUNTER FUNCT. TIMER BASIC FU NCTION TIMER FUNCT. TACHO BASIC FUNCTION TACHOMETER/FREQUENCY METER INPUT MAIN M ENU INPUTS INP.POL. PNP INPUT POLARITY PN P INP.POL. NPN INPUT POLARITY NPN FILTER OFF INPUT 30HZ FILTER OFF FILTER ON INPUT 30HZ FILT ER ON CNT.INP. CNT.DIR INPUT MODE COUNT DIRECTION CNT.INP. UP.DN INPUT MODE UP-DOWN CNT.INP. UP.UP INPUT MODE UP-UP CNT.INP. QUAD INPUT MODE QUADRATURE CNT.INP. QUAD2 INPUT MODE QUADRATURE x 2 CNT.INP. QUAD4 INPUT MODE QUADRATURE x 4 CNT.INP. A/B INPUT MODE A/B CNT.INP. A%B INPUT MODE ( A-B)/A IN % START INA.INB START INPUT A / STOP INPUT B START INB.INB START INPUT B / STOP INPUT B START FRE.RUN TIMER IN FREE RUN MODE START AUTO TIMER IN AUTO ST OP MODE TAC.INP. A ONLY INPUT A TAC.INP. A-B INPUT MODE A-B TAC.INP. A+B INPUT MODE A+B TAC.INP. QUAD INPUT MODE QUADRATURE TAC.INP. A/B INPUT MODE A/B TAC.INP. A%B INPUT MODE (A- B)/A IN % MP.INP._ LATCH FUNCTION MP-INPUT _ LATCH MP.INP._ TEACH FUNCTION MP-INPUT_ TEACH MP.INP._ SET FUNCT ION MP-INPUT_ SET LOC.INP. PROG. LOCK PROGRAMMING LOC.INP. PRES ET LOCK EDITIN G OF PRESETS LOC.INP. PRG.PRE. LOCK PROGRAMMING A ND EDITING OF PRESETS MODE MAIN MENU OPERATION MODE MODE ADD MODE ADDING MODE ADD.AR MODE ADDING WITH AUTOMATIC RESET MODE ADD.BAT MODE ADDING WITH AUTOMATIC RESET + BATCH COUNTER MODE ADD.TOT MODE ADDING WITH AUTOMATIC RESET + TOTAL COUNT ER MODE TRAIL MODE ADDING OUTPUT 1 TRACKING PRESET OF OUTPUT 2 MODE TR.AR MODE ADDING OUTPUT 1 TRACKING PRESET OF OUTPUT 2 WITH AUTOMATIC
MODE SUB MODE SUBTRACTING
RESET
Page 26 | ENG
www.GlobalTestSupply.com
MODE SUB.AR MODE SUBTRACTING WITH AUTOMATIC RESET MODE SUB.BAT MODE SUBTRACTING W ITH AUTOMATIC RESET + BATCH COUNTER MODE SUB.TOT MODE SUBTRACTING WITH AUTOMATC RESET + TOTAL COUNTER CONFIG. MAIN MENU CONFIGURATION FACTOR MULTIPLICATION FACTOR DIVISO. DIVISION FACTOR T.MODE SEC TIME RANGE SECONDS T.MODE MIN TIME RANGE MINUTES T.MODE HOUR TIME RANGE HOUR S T.MODE HH.MM.SS TIME RANGE HH.MM.SS T.MODE SEC-1 TACHO RANGE SEC-1 T.MODE MIN-1 TACHO RANGE MIN-1 DP DECI MAL POINT SETPT. SET VALUE AVG OFF NO AVERAGE AVG AVG 2 AVERAGE OF 2 ME ASUREMENTS AVG AVG 5 AVERAGE OF 5 ME ASUREMENTS AVG AVG10 AVERAGE OF 10 MEASUREMENTS AVG AVG20 AVERAGE OF 20 MEASUREMENTS START START D ELAY TIME [SEC] WAIT 0 W AIT TIME UNTIL DISPLAY ZERO [SEC] RES.MOD MAIN MENU RESET MODE RES.MOD. NO.RES. NO RESET FUNCTION RES.MOD. MAN.RES. RESET VIA FRONT BUTTON RES.MOD. EL.RES. RESET VIA RE SET INPUT RES.MOD. MAN.EL. RESET VIA FRONT BUTTON OR RESET INPUT PRES. 1 MAIN MENU PR ESET 1 PRES. 1 ON PRESET 1 ON PRES. 1 OFF PRESET 1 OF F PR.OUT1 ____------ PERMANENT SIGNAL FORM AT OUTPUT 1 PR.OUT1 ------____ PERMANENT SIGNAL FORM AT OUTPUT 1 PR.OUT1 __---__ TIMED SIGNAL FORM IN MAIN DIRECTION AT OUTPUT 1 PR.OUT1 ---__--- TIMED SIGNAL FORM IN MAIN DIRECTIO N AT OUTPUT 1 PR.OUT1 __--__--__ TIMED SIGNAL FORM IN BOTH DIRECTION AT OUT PUT 1 PR.OUT1 --_----_-- TIMED SIGNAL FORM IN BOTH DIRECTION AT OUTPUT 1 T.OUT 1 ACTIVE TIME FOR OUTPUT 1 PRES. 2 MAIN MENU PR ESET 2 PR.OUT2 ____------ PERMANENT SIGNAL FORM AT OUTPUT 2 PR.OUT2 ------____ PERMANENT SIGNAL FORM AT OUTPUT 2 PR.OUT2 __---__ TIMED SIGNAL FORM IN MAIN DIRECTION AT OUTPUT 2 PR.OUT2 ---__--- TIMED SIGNAL FORM IN MAIN DIRECTIO N AT OUTPUT 2 PR.OUT2 __--__--__ TIMED SIGNAL FORM IN BOTH DIRECTION AT OUT PUT 2 PR.OUT2 --_----_-- TIMED SIGNAL FORM IN BOTH DIRECTION AT OUTPUT 2 T.OUT 2 ACTIVE TIME FOR OUTPUT 2 END.PRG. NO REPEAT PROGRAM MING END.PRG. YES EXIT PROGRAMMING AN D STORE DATAS
english
Page 27 | ENG
www.GlobalTestSupply.com
20 Dimensional Drawings
Dimensions in mm [inch]
Rear view:
Panel cut-out:
Page 28 | ENG
www.GlobalTestSupply.com
Loading...