True GDM Series, GDT Series Technical & Service Manual

Technical Service Manual
(All Models)
Index
Page
Cabinet Installation and Set-Up _____________________________________________________4
Electrical Requirements______________________________________________________________5 Conductors and Circuits _____________________________________________________________6 Cabinet Installation and Set-Up Checklist ______________________________________________7 Cabinet Installation and Set-Up (Swing & Slide Doors) ___________________________________8 GDM/T - Series Freezers_____________________________________________________________9 Remote Condensing Unit____________________________________________________________10 Temperature Control Altitude Adjustment_____________________________________________11 Temperature Control Altitude Adjustment(new temp. control) ____________________________12 Defrost Controls ________________________________________________________________13-14
Preventative Maintenance __________________________________________________________16
Cabinet Maintenance Schedule_______________________________________________________17 Condenser Cleaning________________________________________________________________18
Refrigeration Section _______________________________________________________________20
Polyol Ester Lubricant - The CFC Report _____________________________________________21 Service Contractors: Attention Please _________________________________________________22 Basic Refrigeration - The Capillary Tube System _______________________________________23 The Refrigeration Cycle ____________________________________________________________24 True’s Remote System - How it Works ________________________________________________25 Basic Refrigeration - Control of Liquid Refrigerant Floodback... __________________________26
General Maintenance & Repairs ___________________________________________________28
Top Removal for TBB and TDD Units_________________________________________________29 Top Removal forTD and T-GC Units _________________________________________________30 TPPCountertop Replacement Instructions_____________________________________________31 Top Removal for Various Coolers - TSSU, TWT,TUC ___________________________________32 Top Removal forTRCB 50 and 79 ____________________________________________________33 End Cap Replacement-T-Series Swing Door _________________________________________34-35 Side Panel Replacement - GDM Series ________________________________________________36 Side Panel Replacement - GDM-33C-PT_______________________________________________37 Floral Case Baffle Installation _______________________________________________________38 GDM-23FC Mirror Retrofit Kit______________________________________________________39 Undercounter Refrigerator/Freezer Perimeter Heater Wire Replacement ___________________40 GDM & T-Series Freezer Perimeter Heater Wire Replacement____________________________41 TD-Series and Glass Chillers ________________________________________________________42 Temperature Control Replacement for Cabinets Larger than 1/3 HPCompressors ________43-47 Temperature Control Change-Out - GDM _____________________________________________48 Temperature Control Change-Out - GDM & T-Series____________________________________49 Replacing Temperature Controls in GDM-7, GDM-10, & GDM-12 models__________________50 Surge Protector’s for the GDM-Series ______________________________________________51-52
Door and Lock Repair ______________________________________________________________54
Glass Insert - Slide Door ____________________________________________________________55 Slide Door Instruction - To improve slide door closing___________________________________56 Wiper Gasket Installation ___________________________________________________________57 Removal and Installation of GDM-Swing Door ______________________________________58-59 Torsion Spring Replacement - Swing Door __________________________________________60-61 IDLLamp Replacement ____________________________________________________________62
Index
Page
Glass Insert - Swing Door ________________________________________________________63-64 Glass Insert Gas Release (High Altitude Installation) ____________________________________65 GDM & T-Series IDLGlass Insert Replacement ________________________________________66 Replacement of Door Frame Heater on IDL Freezer Doors _______________________________67 IDL Door Wire Harness Replacement______________________________________________68-69 Shimming the Glass Insert________________________________________________________70-71 Lock Installations - GDM Single Swing Door (GDM-23/26)_______________________________72 Barrel Lock Installation (GDM Slide DoorModels) _____________________________________73 Slide Barrel Lock (Top View) ________________________________________________________74 Slide Barrel Lock (Front View)_______________________________________________________75 Lock Installation (GDM-5 & GDM-5PT Swing Door Models) _____________________________76 Ratchet Lock & Plastic Door Stop - Slide Door ______________________________________77-78 Lock Installation - TD Models _______________________________________________________79
General Instructions________________________________________________________________80
Overshelf Option - TSSU, TWT, TUC_________________________________________________81 Installing The Crumb Catcher _______________________________________________________82 Field Installing The TSSU Series 19” Cutting Board_____________________________________83 Anchoring the TSSU Hood Cover ____________________________________________________84 Installing the TTPSeries Service Shelf ________________________________________________85 Field Installing the TPPService Shelf _________________________________________________86 Sneezeguard Option - TSSU _________________________________________________________87 Castor and Leg Frame Installation ___________________________________________________88 GDM-33C-PT Castor Mounting Assembly _____________________________________________89 TDD-1 CO TDD-2,3,4 (and Club Top models) CO2 Knock-out ______________________________________91 Vandal Panel Installation for a GDM-33CPT-54 ________________________________________92 Vandal Panel - GDM-69 __________________________________________________________93-94
Troubleshooting ____________________________________________________________________96
Calibrate Temperature Control____________________________________________________97-98 Troubleshooting and Service Chart _______________________________________________99-100 Capillary Tube Replacement Instructions - Upright GDM/T-Series Equipment__________101-102 Refrigeration Trouble Shooting Chart - Refrigerator________________________________103-104 Refrigeration Trouble Shooting Chart - Freezer ____________________________________105-106 Capillary Tube Replacement Instructions - Refrigerators and Freezers ____________________107 Field Troubleshooting__________________________________________________________108-110 Troubleshooting Fluorescent Lighting Circuits
GDM & T Series Coolers IDLConnector _____________________________________________112
Equipment Care and Cleaning ____________________________________________________114
Cleaning Your Cabinet_____________________________________________________________115 Stainless Steel Equipment Care and Cleaning (NAFEM)_____________________________116-120
Knock-out______________________________________________________________90
2
Rapid Start, Electric, and Preheat Fluorescent Light Circuits ____________________________111
4
Please read these instructions. Failure to follow maintenance guidelines
may result in a n o n - w a r r a n t e d service call.
CABINET
INSTALLATION
AND SET-UP
5
ELECTRICAL REQUIREMENTS
There are several factors that will affect the proper operation of your True unit. A m o n g these factors, the electrical installation is the most important and should always be checked before connecting your True cabinet as follows:
1. Make sure the circuit is dedicated exclusively to your True unit.
2. Make sure the electrical installation complies with national, state, and local codes.
3. Make sure the circuit is properly ground.
4. Check circuit for proper voltage at receptacle (+/-10% 115 Volt) (- 5% + 10% 208/230 Volt)
5. Make sure that the wire gauge and breaker sizes are correct and comply with the min-
imum allowance for voltage drops
WARNING: FAILURE TO COMPLY WITH THESE REQUIREMENTS MIGHT R E S U LT IN PERSONAL I N J U RY AND (OR) PROPERTY DAMAGE, AND W I L L V O I D WA R R A N T Y.
6
CONDUCTORS AND CIRCUITS
Wi re Gauge for 2% Voltage Drop in Supply Circ u i t s
115 Vo l t Distance In Feet To Center of Load
A m p s 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 1 0 0 1 2 0 1 4 0 1 6 0
2 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 3 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 2 1 2 1 2 5 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0 6 1 4 1 4 1 4 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0 1 0
7 1 4 1 4 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0 1 0 8 8 1 4 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0 1 0 8 8
9 1 4 1 4 1 4 1 2 1 2 1 2 1 2 1 0 1 0 8 8 8 1 0 1 4 1 4 1 4 1 2 1 2 1 0 1 0 1 0 1 0 8 8 8 1 2 1 4 1 4 1 2 1 2 1 0 1 0 1 0 8 8 8 8 6
1 4 1 4 1 4 1 2 1 0 1 0 1 0 8 8 8 6 6 6 1 6 1 4 1 2 1 2 1 0 1 0 8 8 8 8 6 6 6 1 8 1 4 1 2 1 0 1 0 1 0 8 8 8 8 8 8 5 2 0 1 4 1 2 1 0 1 0 8 8 8 6 6 6 5 5 2 5 1 2 1 0 1 0 8 8 6 6 6 6 5 4 4
3 0 1 2 1 0 8 8 6 6 6 6 5 4 4 3 3 5 1 0 1 0 8 6 6 6 5 5 4 4 3 2 4 0 1 0 8 8 6 6 5 5 4 4 3 2 2 4 5 1 0 8 6 6 6 5 4 4 3 3 2 1 5 0 1 0 8 6 6 5 4 4 3 3 2 1 1
230 Vo l t s Distance In Feet To Center of Load
A m p s 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 1 0 0 1 2 0 1 4 0 1 6 0
5 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4
6 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 2
7 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 2 1 2
8 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 2 1 2 1 2
9 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0 1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0
1 2 1 4 1 4 1 4 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0 1 0 1 4 1 4 1 4 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0 1 0 8 1 6 1 4 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0 1 0 8 8 1 8 1 4 1 4 1 4 1 2 1 2 1 2 1 0 1 0 1 0 8 8 8
2 0 1 4 1 4 1 4 1 2 1 2 1 0 1 0 1 0 1 0 8 8 8 2 5 1 4 1 4 1 2 1 2 1 0 1 0 1 0 1 0 8 8 6 6 3 0 1 4 1 2 1 2 1 0 1 0 1 0 8 8 8 6 6 6 3 5 1 4 1 2 1 2 1 0 1 0 1 0 8 8 8 6 6 6 4 0 1 4 1 2 1 0 1 0 8 8 8 6 6 6 5 5
5 0 1 2 1 0 1 0 8 8 6 6 6 6 5 4 4 6 0 1 2 1 0 8 8 6 6 6 6 5 4 4 3 7 0 1 0 1 0 8 6 6 6 5 5 4 4 3 2 8 0 1 0 8 8 6 6 5 5 4 4 3 2 2 9 0 1 0 8 6 6 6 5 4 4 3 3 2 1
1 0 0 1 0 8 6 6 5 4 4 3 3 2 1 1
7
CABINET INSTALLATION AND SET UP CHECKLIST
1) Make sure cabinet is plugged into dedicated outlet. Before plugging in cabinet check to make sure
voltage is adequate for your cabinet. Do not use an extension cord, this will void cabinet
w a r r a n t y.
2) Follow installation instructions for your specific cabinet. Each cabinet is shipped with specific installation and set up instructions. It is very important to read all information sent with your new cabinet
3) Make sure shipping blocks (slide doors) and door support brackets (swing doors) are removed. Doors will not function correctly if this step is not followed.
4) Make sure that your cabinet is leveled correctly. Follow specific instructions with your cabinet and use castor shims were they are needed. Make sure that legs and castors are installed per instruc­tions. If directions are not followed this may cause premature unwarranted failure of cabinet legs or castors. If your cabinet is not level this can cause performance problems that will not be cov­ered as warranty repairs.
5) When cabinet is set in its final location, make sure the specific clearance guidelines are followed. These are very important for ventilation in the condensing unit area. If not followed can cause
premature compressor failure.
6) Follow altitude adjustment for temperature control if applicable.
7)
IF YOU HAVE ANY QUESTIONS ABOUT SET UP OR INSTALLATION OF YOUR
NEW CABINET PLEASE CALL OUR TECHNICAL SERVICE DEPARTMENT AT 1­800-325-6152.
CABINET INSTALLATION AND SET UP CHECKLIST
8
INSTALLATION INSTRUCTION
CABINET INSTALLATION AND SET-UP (SWING & SLIDE DOORS)
SWING DOORS
A. Remove all other tape securing the doors to the cooler. Remove the blue foam blocks approximate­ly 1”x3”x1” (2.5 x 7.6 x 2.5 cm) that are between the door and the cooler. One foam block is located on each side of the door frame. (left and right).
NOTE
Your True Merchandiser has been
secured for safe shipping. During
installation, it is necessary to remove
the door support bracket.
SLIDE DOORS
A. Remove all transparent tape on the door area. Remove the foam blocks in top channel in front on the right door approximately 1”x1”x20” (2.5 x 2.5 x 50 cm).
B . Remove both plastic brackets secured by tape from under the left door.
C. Open the left door. D. Remove the foam block from the
top channel behind the left door.
B. Remove the two phillips screws
that secure the bracket to the door. (see figure 1).
C. Remove bracket and save for
future shipping.
D. Replace screws securely into door.
E. Remove both plastic brackets from
under the right door (see figure 2).
NOTE
Door packing materials should NOT be removed until cooler is placed on
location.
TRANSPORTATION OF THE
COOLER WITHOUT THE DOOR
PACKING MATERIALS IN
PLACE CAN RESULT IN DAM-
AGE TO DOORS, DOOR
ROLLERS AND V-TRACK
(figure 2)
(figure 1)
INSTALLATION INSTRUCTION
9
GDM / T-Series Freezers
______ Installing Castors _______
Install castors in the bottom rail assembly on the underside of the cooler. Castors with brakes should be installed in front. To obtain maximum strength and stability of the unit, it is important that you make sure each castor is secured with a 3/4" (19mm) open-end wrench. The bearing race on the castor must make firm contact with the rail.
______ Installing Leg Levelers _______
Screw leg levelers into the four corners of the lower rail assembly (larger models include levelers centered front and back also).
CAUTION
To avoid damage to lower rail assembly, raise unit slowly and carefully to upright position.
LEVELING
A. Set unit in its final location. Be sure there is adequate ventilation in your room. Under extreme heat conditions, (100°F+, 38°C+), you may want to install an exhaust fan.
Warning
Warranty is void if
ventilation is insuff i c i e n t .
B. Proper leveling of your True cooler is
critical to operating success. Effective condensate removal and door operation will be effected by leveling.
C . The cooler should be leveled front to back and side to side with a level (see figure
4). Place the level in the interior floor of the unit in the four positions illustrated. For Castored Models: Four shims have been provided in warran­ty packet for leveling castored units posi-
tioned on uneven floors. Shims must be positioned between rail end and bearing race. (see figure 3).
If the cabinet is not level use a 3/4" (19mm) open-end wrench to turn the anchoring bolt under the bearing race counter-clockwise until the cabinet is level.
Install the desired number of shims, making sure the slot of the shim is in contact with the threaded stem of the castor.
If more than one shim is used, turn the slot at a 90° angle so they are not in line.
Turn the anchoring bolt clockwise with a 3/4" (19mm) open-end wrench to tighten and secure the castor.
Leg Levelers For GDM Models: If the cabinet is not level adjust leg levelers by first relieving weight to leveler and adjusting by either hand or wrench. Repeat with all leg levelers until cabinet is level in all directions.
D . Ensure that the drain hose or hoses are positioned in the pan.
I M P O R TA N T
Make certain the metal strap holding the c o m p re s s o r during shipment is re m o v e d . F a i l u re to cut strap could result in excessive noise and vibration (fre e z e r ) .
E. Free plug and cord from inside the
figure 3.
l o w e r re a rof the cooler(do not plug in). F. The unit should be placed close
enough to the electrical supply so that extension cords are never used.
figure 4.
Warning
Compressor warranties are void if the unit is more than 6-1⁄2 ft. (2m) from plug­in connection.
10
INSTALLATION INSTRUCTION
Remote Condensing Unit
For cabinet installation, use instal­lation instructions with cabinet.
Receiving: Upon receiving this piece of equipment remove all outer packaging and inspect for concealed damage. If damage is found, indicate such on the carriers Bill of Lading for claim to be filed. In order to minimize damage to this equipment, it is recommended that the packaging remains in place until it is in its final location.
Condensing units located indoors or in confined areas must have ade­quate ventilation. Condensing units require 1000 cfm of air per ton of refrigeration.
True Manufacturing Company strongly recommends the use of compressor crankcase heaters and headmaster valves be used at all times with a remote compressor unit. Not using these components may void the compressor warranty.
Refrigerant Lines: All refriger­ant piping should be ACR type. It is recommended that all brazed joints be made with “hard solder” such as Silphos or Unibraze. Solder such as 95-5 or other soft solders are not recommended.
All suction lines must be insulat­ed, with at least 1/2” wall insula­tion. Keep all lines as short as pos­sible.
Always pitch suction lines down­ward in the direction of flow. Generally 1/2” pitch for each 10 ft. of line is adequate for good oil return. Field installation vibration eliminators should be field installed
parallel with the compressor crank shaft and as close to the compressor as possible.
Leak Check and Evacuation:
After all refrigerant line connections have been complete, the entire sys­tem should be leak checked. This includes field and factory connec­tions. Charge system with refrigerant vapor and add enough nitrogen to raise pressure to 150 PSIG maxi­mum.
Leak check the entire system.
Make repairs as necessary.
Evacuation Process: To obtain
the proper level of dehydration in the refrigeration system, a vacuum of at least 500 microns must be drawn. Do not use the system’s compressor as a vacuum pump and do not operate compressor while system is in a vac­uum.
Open all system service valves to discharge any pressure in the system. Connect vacuum pump to high and low side of system. Pull vacuum.
Break the vacuum with system refrigerant. Pull vacuum again, down to 500 microns or lower.
Shut valves before charging.
Charging Process: When initially charging a system that is in a vacuum, liquid refrigerant can be added direct­ly into the receiver tank w i t h o u t
compressor running.
If you have difficulty charging the correct amount of refrigerant into the system you may start the system to complete the charging process.
Add the correct amount or until the sight glass indicates a full charge, with a clear window, bubbles indicate more refrigerant is required. Care should be taken not to overcharge the system at this point. The evaporator fans must be operational while charg­ing; cooler fans must run continuous­ly, freezer fans will be delayed by the fan control. Make sure freezer fans are running during final charg i n g process.
Keep a close check on suction and discharge pressures. After system has stabilized, check for excessive liquid floodback to the compressor. If flooding occurs (less than 8˚ super­heat in freezers, 12˚ in coolers) adjust expansion valve Clockwise, 1/2 a turn at a time, recheck before leaving installation.
Check full load amps on the com­pressor, this can be found on the com­pressors nameplate, Check compres­sor oil level. Normal charge is indi­cated by 1/2 of the sight glass having oil in it.
Final Check: Check high and low pressure control settings. Set thermo­stat to desired cabinet temperature. Check defrost timer settings (if appli­cable). Check voltage, this must be 100% of the nameplate rated voltage for operation. Anything more or less should be corrected immediately.
Replace all service valve caps and secure all unit covers.
11
This scale may be used as a guide for measuring degrees of rota­tion required for altitude correction. The arrows indicate direction of screw rotation.
REQUIRED TOOLS
• Phillips Head Screwdriver
• Hex Head Driver
• Jewelers Screwdriver
IMPORTANT
Upright models ordered with "High
Altitude" temperature controls
are pre-calibrated and do not
require adjustment.
___________ STEP 1 ___________
Unplug the cooler.
___________ STEP 2 ___________
Turn the temperature control to the "9" position.
___________ STEP 3 ___________
Remove the screws that secure the mounting plate to the evaporator top. ("A") See figure 1.
___________ STEP 4 ___________
Pull control down gently from housing.
___________ STEP 5 ___________
Turn screws counterclockwise (CCW) See Chart and figure 2.
___________ STEP 6 ___________
Reassemble to cooler housing and return the temperature control to the "5" position.
INSTALLATION INSTRUCTION
TEMPERATURE CONTROL ALTITUDE ADJUSTMENT
Figure 1
Chart
CCW
Adjustment
(based on 360°/
Height complete turn)
2000' 42° 3000' 78° 4000' 114° 5000' 150° 6000' 186° 7000' 222° 8000' 258° 9000' 294°
10,000' 330°
Figure 2
12
INSTALLATION INSTRUCTION
Danfoss Temperature Control Adjustment for High Altitude Applications
Terms:
Cut-out - Temperature sensed by the controller that shuts the compressor off.
Cut-in - Temperature sensed by the controller that turns the compressor on.
Instructions: ___________ STEP 1 ___________
Mechanical temperature controllers are affected when functioning at high alti­tude. The cut-in and cut-out tempera­tures will be colder than when the con­troller function closer to sea level.
___________ STEP 2 ___________ For installations above 2,000 ft., it may be necessary to “warm-up” the set points. To make the adjustment, insert the appropriate tool in each adjustment screw and turn 1/4 of a revolution clock-wise (to the right). This proce­dure will adjust both the cut-in and cut-out about 2˚F warmer.
___________ STEP 3 ___________ Make sure to re-connect the pink wires to the proper spade terminal when re-installing.
Cut-out Adjustment Screw Allen (5/64” or 2 mm.)
Cut-in Adjustment Screw Torx (T-7)
Compressor Connection (pink)
Compressor Connection (pink)
13
Recommended Defrost Settings
True Manufacturing has factory set your defrost time clock to a recommended time and duration defrost scenario. All refrigeration equipment operating below 30˚F will accumulate frost on the evaporator coil and will require routine defrost. Your True equipment has been designed for three defrost periods (8:00 a.m., 12:00 p.m. and 4:00 p.m.). If you decide to deviate from these defrost time settings please follow the procedures and adjustment below.
DEFROST CONTROLS
Defrost Time Clock Adjustment
REQUIRED TOOLS
Graduated Time Disk
Adjusting Knob
• Slotted Screwdriver
Locating The Defrost Timer
Take off lower grill assembly by removing four (4) corner screws.
Single door models: Defrost timer is located in the lower right corner behind the louvered grill.
Two door models: Defrost timer is located in the middle of the cabinet, behind the louvered grill. Timer is mounted to the left of the centered ballast box.
Three door models: Defrost timer is located on the left upright post behind the louvered grill.
Adjusting The Defrost Control
(time initiated, temperature terminated)
Your True freezer contains a defrost system that is temperature terminated, however the time clock has been designed with a time termination back-up so that the defrost period will not exceed twenty minutes. While True recommends 3 defrost periods not to exceed 20 minutes the procedure below should be followed to customize your specific needs.
Time Indicator
Duration Indicator
Warning
Always follow the manufactures
recommended settings when program-
ming the amount and duration of the
defrost cycles.
___________ STEP 1 ___________
Referencing the outer graduated time disk, position the current time of day to align with the “TIME” indicator. To move the graduated time disk, grasp the adjusted knob and turn counter clockwise until the current time of day aligns with the “TIME indicator.
Trip Pin
Extra Trip Pin
Trip Pin Hole
___________ STEP 2 ___________
In order to program the time to begin the defrost cycle, insert threaded trip pins into the graduated time disk hole that corresponds to your customized defrost needs.
___________ STEP 3 ___________
True recommends a 20 minute defrost cycle three times per day. Changing the recommended duration requires pressing down and sliding the copper duration indicator.
14
2. TIME INITIATED, TIME TERMINATED
Like in the time initiated, temperature terminated controls; these systems have a temperature sensor that will disconnect the heaters to keep the cabinet from over heating. However it won’t restart the freezing cycle until the control completes the factory set time, which in our case is usually 20 minutes. These systems are also equipped with temperature sensors to delay the fan motors once the defrost cycle has been completed, to pre­vent the circulation of warm air inside the cabinet.
To adjust the defrost cycle time there is only one possible adjustment; Once the cabinet has reach the design temperature, pick the time of the day that you want the unit to defrost. T urn the actuating gear clockwise until the contacts change position initiating the defrost c y c l e .
MOTOR
DEFROST CONTROLS
3 Line 4 Compressor
1 Comun
2 Heaters
Actuating Gear
Common
Notes
16
Please read these instructions. Failure to follow maintenance
guidelines may cause a n o n - w a r r a n t e d cabinet repair service.
PREVENTATIVE
MAINTENANCE
17
CABINET MAINTENANCE SCHEDULE
MONTHLY
1. Check product temperature.
2. Brush off condenser coil.
3. Inspect lamps and lamp holder connections.
QUARTERLY
1. Check physical condition of condenser coil and evaporator coil (straighten fins if necessary.
2. Blow out condenser coil with compressed air.
3. Brush off evaporator coil if needed.
4. Check physical condition of gaskets and also make sure they are sealing correctly.
YEARLY
1. Check operation of all moving parts (fan motors, doors, defrost timers, & IDL door cords)
2. Check all electrical connections, make sure they are all tight and crimps in good condition.
3. Check defrost timer contacts, make sure they are not pitted.
4. Check rear condenser coil screen (clean if necessary).
CABINET MAINTENANCE SCHEDULE
Monthly, Quarterly, and Yearly
GENERAL MAINTENANCE
18
CONDENSER CLEANING
Step 4
Step 6
REQUIRED TOOLS
• Phillips Screwdriver
• Stiff Bristle Brush
• Adjustable Wrench
____________ STEP 1 ____________
Disconnect power to unit.
____________ STEP 2 ____________
Take off lower grill assembly by removing four (4) corner screws.
____________ STEP 3 ____________
Remove bolts anchoring compressor assembly to frame rails and carefully slide out. (tube connections are flexible)
____________ STEP 4 ____________
Clean off accumulated dirt from condensing coil with a stiff bristle brush.
____________ STEP 5 ____________
Lift cardboard cover above fan at plastic plugs and carefully clean condenser coil and fan blades.
____________ STEP 6 ____________
After brushing condenser coil vacuum dirt from coil, and interior floor.
____________ STEP 7 ____________
Replace cardboard cover. Carefully slide compressor assembly back into position and replace bolts. When reinstalling
condensing unit becareful not to crimp or damage the tubing between the con­densing unit and the cabinet.
____________ STEP 8 ____________
Reinstall louver assembly onto unit with appropriate fastener and clips. Tighten all screws.
____________ STEP 9 ____________
Connect unit to power and check to see if compressor is running.
Notes
20
In this section you can find information that is helpful for the
customer and the service technician to help you understand how
our refrigeration system works along with how to diagnose
and correct any problems that might arise.
REFRIGERATION
SECTION
21
Polyol Ester Lubricant
After exhaustive research and testing, Copeland has determined that PolyolEster (POE) lubricants pro­vide the best combination of characteristics for use with the new generation of chlorine-free refrigerant. In addition to providing superior lubrication. POE has other advantages which increase its attractive­ness for use in refrigeration.
Polyol Ester is a synthetic lubricant used primarily for jet engine lubrication. It is manufactured by numerous companies and there are various types and grades available. Therefore, it is important to recog­nize that all POE's are not the same.
Since POE is synthetic, it has better resistance to high temperature degradation than refrigeration min­eral oils. POE is also made from more expensive base stocks making it significantly more expensive than other refrigeration oils. Furthermore, POE is compatible with common refrigerant and mineral oil. Therefore, a compressor containing the oil can be installed in a system containing HCFC's or HFC's. In short, POE provides significant flexibility in the face of changes brought on by the CFC issue.
HFC refrigerant require the use of POE for all Copeland compressors. This is necessary for two specific reasons. First, mineral oils are not readily miscible in HFC's. When using HFC's conventional oils will not return to the compressor. Secondly, the chlorine contained in CFCs and HCFCs aids in the lubricity of mineral oil.
One drawback from using POE is that they absorb moisture from the air at a much greater rate than do mineral oils. As a result, they must be handled and
packaged with much more care than conventional oils. Copeland has not tested all types of compressors or all combinations of refrigerant and con-Industry knowledge of POE must rapidly increase in order to maintain and improve expected reliability.
After conducting extensive tests for both compressor durability and reliability on more than 40 refriger­ant/oil combinations, Copeland identified Mobil Oil Corporation as our preferred U.S. supplier of polyol ester oil in terms of both the oil itself and Mobil's ability to package and deliver the oil with acceptable low moisture levels. Because of its technical superi­ority. Copeland has approved Mobil's EAL Artic 22 CC polyol ester oil for use in our compressors.
To serve our customers, Copeland will distribute E A L Artic 22 CC to the after market through Copeland's network of 800 authorized wholesalers. The lubricant will be charged into our new produc­tion compressors whenever a polyol ester is specified. C u r r e n t l y, certain approved compressor models sold to OEMs are available with this oil installed during manufacture. Refrigeration service compressors charged with POE will be supplied in the near future.
POLYOL ESTER LUBRICANT
THE CFC REPORT - LEADING THE WAY INTO A NEW AGE
22
SERVICE CONTRACTORS
..... ATTENTION PLEASE .....
SERVICE CONTRACTORS
..... ATTENTION PLEASE .....
This is a Tecumseh hermetic compressor specifically designed for use with environmentally friendly HFC refrigerant R404A. However, it is acceptable to use this compressor as a service replacement with R502.
The Tecumseh approved polyolester (POE) oil contained in this compressor is compatible with all internal component materials and is miscible (mixes) with R502 to effect proper oil return. Using R502 with this R404A compressor will result in very similar performance to the replaced R502 compressor. But, the following precautions should be taken.
1) Care must be taken to assure that most of the mineral oil is removed from the system before the new compressor is installed. Small amounts of mineral oil (up to 5%) left in the system are acceptable but 1% or less if achievable is desired.
2) POE oils are 100 times more hygroscopic (ability to absorb moisture) than mineral oils thus the utmost care must be taken to prevent moisture from entering the system. The compressor or system should not be left open to the atmosphere for longer than 15 min­utes maximum.
3) The appropriate new drier provided must be installed in the system.
4) Established industry procedures for recovery, evacuation, refrigerant charging and leak testing should be followed.
TRUE MANUFACTURING COMPANY
23
CFC & Refrigeration Basics
BASIC REFRIGERATION
THE CAPILLARY TUBE SYSTEM
Suction
Line
Capillary Tube
Heat
Exchanger
Evaporator
Accumulator
Condenser
Filter­Drie
Motor Compressor
LOW PRESSURE
GAS
Starting at the Capillary Tube, refrigerant flows into the evaporator and changes from a liquid to a gas. As it absorbs heat, after leaving the evaporator, it flows through the accumulator. The accumulator is a part that is designed like a reservoir to allow any refrigerant, that has not changed from a liquid to a gas, space to do so before returning to the compressor. After flowing through the accumulator, refrigerant flows through the s u c t i o n line as a low pressure gas into the compressor. The compressor pumps the refrigerant from a low pres­sure gas to a high pressure gas and forces it into the condenser. In the condenser with a fan circulating air over it the refrigerant condenses from high pressure
HIGH PRESSURE
GAS
LOW PRESSURE
LIQUID
HIGH PRESSURE
LIQUID
gas to high pressure liquid. After leaving the condenser refrigerant flow through the drier which is designed to remove any particles or moisture in the system. Refrigerant then flows through the liquid line into the capillary tube. The capillary tube is designed to allow a certain amount of refrigerant to flow through it to keep the evaporator evenly flooded. The capillary tube is taped to the suction line to cool the liquid to allow the best heat transfer. When the refrigerant enters the evaporator as a liquid, warm air from inside the cabinet is circulated through the evaporator coil and the heat from the air is then absorbed in the refrigerant.
Thermostat
Senses evaporator temperature
@40°F cuts in ­starts compressor
@18°F cuts out ­shuts compressor
off
Evaporator
As air is pushed through the evaporator by the fan motors liquid refrigerant absorbs heat through the walls of the
evaporator coils and vaporizes - thus becoming a low pressure gas.
®
24
®
Evaporator Fan Motor
Condensate
Pan
The resulting warm air from the condensor blows over the condensate pan and evaporates the water.
Hot air out
Cool air in
Capillary
Tube
Meters the amount of liquid refrigerant
into the evaporator where it absorbs heat.
Color Chart
Dark Blue = Low pressure liquid
Light Blue = Low pressure gas
Red = High pressure gas
Pink = High pressure liquid
Compressor Fan Motor
Compressor
Combines heat absorbed in the evaporator coils with heat of compression from the piston stroke then pushes high pressure gas (vapor) on into the condenser.
Condenser
High pressure gas is condensed into a high pressure liquid when the heat is removed. By pulling air in the front of the condenser by means of the fan motor. The air will be
used to evaporate the drain pan water.
25
TRUE’S REMOTE SYSTEM - HOW IT WORKS
Liquid and Suction
Tubing
‘P’ Trap
TXV Bulb
Suction Line
External
Equalizer
Refrigeration Schematic Diagram
TXV
Liquid Line
Solenoid
Distributor
with Nozzle
The suction line will exit the evaporator coil as usual for self-contained models, except it shall include an Oil “P” trap. This is used to trap oil in low velocity suction gases at a point just prior to a vertical rise. Whether the compressor is to be located above or below the evaporator, (True does not have control over this), the suction will always have a “P” trap in case the compressor is installed overhead.
The liquid line shall enter the cabinet and go direct­ly to the liquid line solenoid, this is a normally closed refrigerant valve which will be energized and wired in series with the thermostat. When the ther­mostat is closed (requires refrigeration) the solenoid will be energized to open, allowing refrigerant to pass to the “thermal expansion valve” (TXV). The TXV allows refrigerant through to the evaporator coil. If the evaporator has more than one circuit, a
Feeder
Tubes
Evaporator
Coil
distributor is used which evenly distributes refriger­ant to each circuit. The TXV is made to open and close by its sensing bulb which senses suction line temperature on the other side of the evaporator. The sensing bulb has the same refrigerant that is used in the refrigeration system. When hot air passes over the evaporator coil and warms the refrigerant, the sensing bulb senses the warm condition and pushes the sensing valve open. When too much refrigerant flows into the evaporator, the sensing bulbs refriger­ant cools and contracts allowing the diaphragm to ease away the needle valve, thus closing the valve.
The external equalizer is another sensing element which helps the sensing bulb to more accurately feed refrigerant. The external equalizer line must be down-stream of the TXV bulb. The TXV bulb should be insulated with corktape.
CFC & REFRIGERATION BASICS
26
BASIC REFRIGERATION
Control of Liquid Refrigerant Floodback To The Compressor During Operation
Compressor
LOW PRESSURE
GAS
Compressor
HIGH PRESSURE
GAS
Accumulator
Crankcase
Heater
Fan Fan
Filter
Evaporator Condenser
Expansion Device
LOW PRESSURE
LIQUID
Fan Fan
Filter
Evaporator Condenser
Expansion Device
HIGH PRESSURE
LIQUID
Liquid floodback during operation can be caused by fan failure, or dirty clogged filters that can reduce the heat transfer rate to such a point that the liquid refrigerant floods through, instead of vaporizing. When this situation occurs, liquid refrigerant may enter the compressor under conditions which result in separation of the oil and refrig­erant. This separation may result in an accumulation of the refrigerant under the oil. Thus, when the compressor is started, the first liquid to be pumped to the bearings will probably be refrigerant, not oil. Even if this oil-refrigerant separation does not occur, the large amount of liquid refrig­erant in the crankcase will instantly vaporize and boil away the oil charge when the compressor starts. Thereby leaving the compressor oil-starved for many seconds.
Liquid floodback can be prevented by the application of a properly designed and sized suction line accumulator. Using a totally new concept, Tecumseh engineers have designed a suction line accumulator available in eight basic sizes covering a full range of system applications and refrigerant. When properly selected based upon system c h a rge, a Tecumseh suction line accumulator will improve compressor reliability and endurance by preventing dam­aging liquid refrigerant floodback.
LOW PRESSURE
GAS
HIGH PRESSURE
GAS
LOW PRESSURE
LIQUID
HIGH PRESSURE
LIQUID REFRIGERANT ACCUMULATION IN THE COMPRESSOR CAN ALSO BE CAUSED BY LIQUID MIGRATION TOTHE COMPRESSOR DURING PERIODS OF SHUTDOWN. THIS CONDI­TION CAN BE CONTROLLED BY THE APPLICATION OF A CRANKCASE HEATER. A SUCTION LINE ACCUMULATOR DOES NOTHING TO PREVENT LIQUID MIGRATION AND ACRANKCASE HEATER DOES NOTHING TO PREVENT LIQUID FLOODBACK. EACH WITHOUT THE OTHER IS HALF A JOB - BOTH TOGETHER PROVIDE BALANCED COMPRESSOR PROTECTION.
LIQUID
Notes
28
Using the following instructions you will be able to make cabinet
exterior repairs along with other general cabinet repairs.
GENERAL CABINET
MAINTENANCE
AND REPAIRS
29
TOP REMOVAL FOR TBB & TDD UNITS
TOP REMOVAL FOR TBB & TDD UNITS
Disconnect the power to the unit.
Locate and remove screws on the inside of the cabinet going through the evaporator housing and into the bot­tom of the counter top.
Locate and remove the screws securing the line set cover to the top located to the left of the evaporator housing.
Remove the two screws inside the door jamb going through the jamb into the bottom of the top. There will be two screws in each door on multiple door units.
Cut the silicone seal that runs along both ends and along the back of the unit. Silicone seal is wrapped around the front wall of multiple door units.
To remove top lift front up approximately 2-3 inches and push backward to unlock lip in back of top.
To reinstall top, carefully align the groove in the back with lip on cooler base. Slide forward, reinstall all screws and re-silicone around cabinet edge.
3”
Top Screws
Top
Evaporator
Housing Screws
Evaporator Housing
30
TOP REMOVALFOR TD & T-GC UNITS
TOP REMOVAL FOR TD & T-GC UNITS
1. Turn unit off and remove lids.
2. Remove screws along back of cabinet top.
3. Remove screws on each side, going through lid slide rails, inside cooler.
4. Remove screws along front of top under inside ledge, also remove the two screws holding center trunion on units with more than one door.
5. Lift top to approximately 45 degrees while pushing top forward at same time. Top will lift off lip in front.
T-50-GC has heater wire looped through center trunion. Please becareful when removing top. Before reinstalling, inspect heater wire to make sure it is not damaged.
6. To reinstall top, while holding top at 45 degree angle hook top on lip at front of cabinet and lay down while pushing backwards on top, when laid completely down press firmly on top to provide a good seal.
7. Reinstall all screws along inside of cabinet and along back of top on outside of cabinet.
8. Reinstall doors and turn unit on.
Lid Trunion
Top Screws
Loading...
+ 91 hidden pages