True GDM-26 User Manual

GDM-26
ELSTAT TRAINING BOOKLET
GDM SERIES COOLER EQUIPPED WITH EMS (ELSTAT) CONTROL
TABLE OF CONTENTS
· ELSTAT SEQUENCE OF OPERATION
· ELSTAT COMPONENTS
· FRONT VIEW OF ELSTAT
· REAR VIEW OF CONTROLLER
· NORMAL OPERATING CODES
· FAULT CODES/ TROUBLESHOOTING
· TROUBLESHOOTING GUIDE
2
ELSTAT SEQUENCE OF OPERATION
Once the cabinet is plugged in, the ELSTAT control will ash "888" and then go through a parameter check. Once completed, the control will do a "soft start". Lights come on rst, approximately 30 seconds later the compressor will start. Approximately 30 seconds from the compressor start up, the evap motor will start. The control will display "Use". The control will then cycle the compressor on and o at the predetermined temp (Model specic).
The whole time the controller is on it is learning the customer trac. Once enough data has been accumulated the controller will now cycle between two modes. "Standby" and "Use". In the standby mode the controller predicts that customer trac is nonexistent. It will display (---). It cycles the compressor to hold about 50˚F. It shuts the lights o and cycles the evap fan motor. It will hold this pattern until roughly 2 hours before customer trac is predicted to start. The controller will then switch into the "use" mode. Cycling the compressor on and o based on temperature (Approx 36˚F to 38˚F product temp). Running lights continuously. The controller will then cycle between these two modes.