Guarantee, service policy, etc. ...............................................rear cover
WARNING
This appliance can be used by children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience or knowledge if
they have been given supervision or instruction concerning use of the appliance in a safe
way and understand the hazards involved. Children may not play with the appliance.
Cleaning and user maintenance shall not be made by children without supervision.
To check the product suitability for commercial and multiple installations, please contact Triton’s
specification advisory service before installation.
Telephone:
Facsimile:
0844 980 0730
0844 980 0744
E mail:
technical@tritonshowers.co.uk
6
Page 3
SALSA
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
Products manufactured by Triton are safe and without risk provided they are installed, used and
maintained in good working order in accordance with our instructions and recommendations.
WARNING:DO NOT operate shower if frozen, or suspected of being frozen. It must thaw out
before using.
DO NOT operate the unit if the showerhead or spray hose becomes damaged.
DO NOT restrict flow out of shower by placing showerhead in direct contact with your body.
DO NOT operate the shower if water ceases to flow during use or if water has entered inside
the unit because of an incorrectly fitted cover.
WARNING: If restarting the shower immediately after stopping, be aware that a slug of
hot water will be expelled for the first few seconds.
1 GENERAL
1.1 Isolate the electrical and water supplies before
removing the cover.
1.2 Read all of these instructions and retain them
for later use.
1.3 DO NOT take risks with plumbing or electrical
equipment.
1.4 Isolate electrical and water supplies before
proceeding with the installation.
1.5 The unit must be mounted onto the finished
wall surface (on top of the tiles). DO NOT tile
up to or seal around ANY PART of the unit
using silicone sealer after fixing to the wall.
Special care must be taken NOT TO BLOCK OR SEAL ANY PRD VENTS ON THE UNIT.
1.6 Contact Customer Service (see back page), if
any of the following occur:
a) If it is intended to operate the shower at
pressures above the maximum or below the
minimum stated.
b) If the unit shows a distinct change in performance.
c) If the shower is frozen.
1.7 If it is intended to operate the shower in areas
of hard water (above 200 ppm temporary
hardness), a scale inhibitor may have to be
fitted. For advice on the Scale Inhibitor,
contact Customer Service.
1.8 The showerhead must be cleaned regularly
with descalent to remove scale and debris,
otherwise restrictions to the flow on the outlet
of the unit will result in higher temperatures
and could also cause the (PRD) Pressure Relief
Device in the unit to operate.
1.9 This product is not suitable for mounting into
steam rooms or steam cubicles.
PLUMBING
2
2.1 The plumbing installation must comply with
Water Regulations, Building Regulations or any
particular regulations as specified by Local
Water Company or Water Undertakers and
should be in accordance with BS EN 806.
2.2 The supply pipe must be flushed to clear debris
before connecting to the shower unit.
2.3 DO NOT solder pipes or fittings within 300mm
of the shower unit, as heat can transfer along
the pipework and damage components.
2.4 DO NOT fit any form of outlet flow control as
the outlet acts as a vent for the heater can.
2.5 DO NOT use excessive force when making
connections to the flexible hose or
showerhead, finger tight is sufficient.
2.6 All plumbing connections must be completed
before making the electrical connections.
2.7 This appliance MUST not be connected to the
inlet supply by a hose-set.
3
ELECTRICAL
3.1 The installation must comply with BS 7671
‘Requirements for electrical installations’ (IEE
wiring regulations), building regulations or any
particular regulations as specified by the local
Electrical Supply Company.
3.2 This appliance MUST be earthed.
3.3 In accordance with ‘The Plugs and Sockets etc.
(Safety) Regulations 1994’, this appliance is
intended to be permanently connected to the
fixed wiring of the electrical mains system.
3.4 Make sure all electrical connections are tight to
prevent overheating.
3.5 A 30mA residual current device (RCD) MUST
be installed in all UK electric and pumped
shower circuits. This may be part of the
consumer unit or a separate unit.
3.6 Switch off immediately at isolating switch if
water ceases to flow during use.
3.7 Other electrical equipment i.e. extractor fans,
pumps must not be connected to the circuits
within the unit.
3.8 Switch off at isolating switch when not in use.
This is a safety procedure recommended with
all electrical appliances.
3.9 As with all electrical appliances it is
recommended to have the shower and
installation checked at least every two years by
a competent electrician to ensure there is no
deterioration due to age and usage.
1
Page 4
SALSA
INTRODUCTION
This book contains all the necessary fitting and
operating instructions for your electric shower.
Please read them carefully.
The shower installation must be carried out by a
suitably qualified person and in the sequence of this
instruction book.
Care taken during the installation will guarantee
a long, trouble-free life from your shower.
SPECIFICATIONS
Electrical
Nominal power Nominal power
rating at 240V rating at 230V
Backplate, cover, controls, showerhead – ABS.
Sprayplate – Acetal.
Elements – Minerally insulated corrosion resistant
metal sheathing.
Dimensions
Height – 230mm
Width – 217mm
Depth – 103mm
Standards and Approvals
Splashproof rating IPX4.
Complies with the requirements of current British
and European safety standards for household and
similar electrical appliances.
Complies with requirements of the British
Electrotechnical Approvals Board (BEAB).
Meets with Compliance with European
Community Directives (CE).
ADVICE TO USERS
The following points will help you understand
how the shower operates:
a. The electric heating elements operate at a
constant rate at your chosen power setting.
It is the rate of the water passing through
the heater can which determines the water
temperature. (The slower the flow the hotter
the water becomes, and the faster the flow
the cooler the water).
b. During winter, the mains water supply will be
cooler than in summer, so the temperature
of the shower will vary between seasons on
any one setting of the temperature control.
At different times of the year you may have to
adjust the position of the temperature control
to maintain your desired temperature setting.
c. The stabiliser valve minimises variations in
shower temperature during mains water
pressure changes. If changes in shower
temperature are experienced during normal
use, it will most likely caused by the water
pressure falling near to or below the minimum
level. The drop in pressure may be due to
water being drawn off at other points in the
house while the shower is in use. If pressure
drops appreciably below the minimum, the
heating elements will automatically cut out.
If ever the water becomes too hot and you
cannot obtain cooler water, first check
that the sprayplate in the showerhead has
not become blocked.
DO NOT place items such as soap or shampoo
bottles on top of the unit. Liquid could seep
through the joint between the cover and
backplate, and possibly damage the sealing
rubber.
Replacement parts can be ordered from Customer
Service. See ‘spare parts’ for details and part numbers.
2
Page 5
SALSA
MAIN COMPONENTS
1.Top pipe/cable entry
2. Bottom pipe/cable entry
3. Area for rear pipe and cable entry
4. Water inlet
5. Wall screw fixings
6. Cover screw fixings
7. Terminal block
8. Power selector assembly
9. Stabilising valve
10. Can and element assembly
11. Thermal cut-out
12. Pressure relief device – PRD
13. Shower outlet
Fig.1
217 mm
1
6
11
8
5
7
12
10
9
3
5
5
4
6
2
40 mm
13
NOTE: Not all wiring is shown for reasons of clarity
230 mm
3
Page 6
SALSA
Meter
Incoming
supply
fuse
Meter
tails
Consumer
unit
Pull cord
isolating switch
Shower
unit
Fuse or
MCB
RCD
(can be part of
consumer unit)
80A or 100A
main switch
MCB
30/32A
32A
40A
40A
40A
40/45A
45A
cartridge
fuse
30A
35A
35A
45A
45A
45A
45A
unit
rating
7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW
10.5kW
CIRCUIT PROTECTION
Triton Showers,
Triton Road, Nuneaton,
Warwickshire, CV11 4NR
xxxx
ELECTRICAL REQUIREMENTS
WARNING!
THIS APPLIANCE MUST BE EARTHED
The installation, supply cable and circuit
protection must conform with BS 7671 (IEE
wiring regulations) and be sufficient for the
amperage required.
The following notes are for guidance only:
1 The shower must only be connected to a
230-240V ac supply. If you are installing a
shower with a kilowatt rating above 9kW, it
is advisable to contact the local electricity
supply company.
1.1 The electrical rating of the shower is shown
on the rating label (Fig.3) within the unit.
2 Before making any sort of electrical
connection within the installation make
sure that no terminal is live. If in any doubt,
switch off the whole installation at the mains
supply and remove the correct fuse.
3 The shower must be connected to its own
independent electrical circuit. IT MUST NOT
be connected to a ring main, spur, socket
outlet, lighting circuit or cooker circuit.
3.1 The electrical supply must be adequate for
the loading of the unit and existing circuits.
4 Check your consumer unit (main fuse box)
has a main switch rating of 80A or above
and that it has a spare fuse way which will
take the fuse or Miniature Circuit Breaker
(MCB) necessary for the shower (Fig.4).
4.1 If your consumer unit has a rating below
80A or if there is no spare fuse way, then the
installation will not be straightforward and
may require a new consumer unit serving
the house or just the shower.
4.2 You will need to contact the local electricity
company. They will check the supply and
carry out what is necessary.
5 For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated
Miniature Circuit Breaker (MCB) or cartridge
fuse (see Table A).
5.1 A 30mA residual current device (RCD)
MUST be installed in all UK electric and
pumped shower circuits. This may be part of
the consumer unit or a separate unit.
W-006-A
(Fig.2)
(Fig.3).
Fig.3
Fig.2
Fig.4 Schematic of installation circuit
Fig.3 Schematic of installation circuit
Table A
4
Page 7
SALSA
Note: Cable selection is dependent on
derating factors
Twin and earth PVC insulated cable
Current carrying capacity
In conduit
trunking
6mm²
38A
10mm²
52A
16mm²
69A
Installed in an
insulated wall
6mm²
32A
10mm²
43A
16mm²
57A
Clipped direct
or buried in a
non-insulated
wall
6mm²
46A
10mm²
63A
16mm²
85A
6 A 45 amp double pole isolating switch with
a minimum contact gap of 3 mm in both
poles must be incorporated in the circuit.
6.1 It must have a mechanical indicator showing
when the switch is in the OFF position, and
the wiring must be connected to the switch
without the use of a plug or socket outlet.
6.2 The switch must be accessible and clearly
identifiable, but out of reach of a person
using a fixed bath or shower, except for the
cord of a cord operated switch, and should
be placed so that it is not possible to touch
the switch body while standing in a bath or
shower cubicle. It should be readily accessible
to switch off after using the shower.
7 Where shower cubicles are located in any
8 The current carrying capacity of the cable
8.1 To obtain full advantage of the power
rooms other than bathrooms, all socket
outlets in those rooms must be protected by
a 30mA RCD.
must be at least that of the shower circuit
protection (see Table B).
provided by the shower, use the shortest
cable route possible from the consumer unit
to the shower.
8.2 It is also necessary to satisfy the disconnection
time and thermal constraints which means
that for any given combination of current
demand, voltage drop and cable size, there is
a maximum permissible circuit length.
9 The shower circuit should be separated from
other circuits by at least twice the diameter
of the cable or conduit.
9.1 The current rating will be reduced if the
cabling is bunched with others, surrounded
by thermal loft or wall insulation or placed
in areas where the ambient temperature
is above 30°C. Under these conditions,
derating factors apply and it is necessary to
select a larger cable size.
9.2 In the majority of installations, the cable
will unavoidably be placed in one or more
of the above conditions. This being so, it is
strongly recommended to use a minimum
of 10mm cabling throughout the shower
installation.
9.3 In any event, it is essential that individual
site conditions are assessed by a competent
electrician in order to determine the correct
cable size and permissible circuit length.
Table B
*The method below may be used by
installers to determine the approximate
size of the incoming cable.
6mm
2
10mm
2
16mm
2
1. Measure the width of an individual strand,
and half that measurment to find (r),
e.g: 1.34mm ÷ 2 = (r) 0.67mm
2. Multiply (r) x (r) x 3.14,
e.g: (r)0.67 x (r)0.67 x 3.14 = 1.41mm
3. Multiply this by the number of wire strands
(usually 7), e.g: 1.41mm2 x 7 = 9.87mm2.
4. The number obtained would suggest
10mm2 wiring.
*PLEASE NOTE: If unsure, consult a qualified Electrician.
2
5
Page 8
Isolating
stopvalve
Mains
water
supply
Shower
unit
Mains electric supply (via double pole switch)
Double
pole
isolating
switch
Separate permanently
connected supply
from consumer unit
Fig.4
Diagrammatic view (not to scale)
SALSA
WATER REQUIREMENTS
The installation must be in accordance with
Water Regulations/Bylaws.
To guarantee activating the heating elements,
the shower must be connected to a mains water
supply with a minimum running pressure of
100kPa (1.0 bar) at a minimum flow rate of eight
litres per minute, and a maximum static pressure
of 1 000kPa (10 bar) for 8.5 and 9.5Kw.
10.5Kw requires 150kPa (1.5 bar) at a minimum
flow rate of eleven litres per minute, and a
maximum static pressure of 1 000kPa (10 bar).
Note: If the stated flow rates are not available,
it may not be possible to achieve optimum
performance from the unit throughout the year.
During periods of high ambient temperatures it
may be necessary to select a low power setting
to achieve your preferred shower temperature.
If it is intended to operate the shower at
pressures above the maximum or below the
minimum stated, contact Customer Service for
advice.
Fig.4 shows a typical system layout.
DO NOT use jointing compounds on any pipe
fittings for the installation.
6
Page 9
SALSA
SITING OF THE SHOWER
IMPORTANT: If installing onto a tiled wall
always mount the unit on the surface of the
tiles. NEVER tile up to the unit.
Refer to fig.5 for correct siting of shower.
Position the unit where it will NOT be in direct
contact with water from the showerhead.
Position the shower unit vertically.
Allow enough room between the ceiling and the
shower to access the cover top screws.
Note: Water Regulations requires the
showerhead be ‘constrained by a fixed or sliding
attachment so that it can only discharge water at
a point not less than 25mm above the spill-over
level of the relevant bath, shower tray or other
fixed appliance’. The use of the supplied soap
dish will in most cases meet this requirement, but
if the showerhead can be placed within a bath,
basin or shower tray, then a double check valve,
or similar, must be fitted in the supply pipework
to prevent back-flow.
Pressure relief safety device
A pressure relief device (PRD) is designed into
the shower unit which complies with European
standards. The PRD provides a level of appliance
protection should an excessive build up of
pressure occur within the shower.
DO NOT operate the shower with a damaged
or kinked shower hose, or a blocked
showerhead which can cause the PRD to
operate.
When commissioning, the showerhead must
be removed from the flexible hose, while at the
same time the temperature control must be at
the minimum flow position. Failure to follow this
procedure may also cause the PRD to operate.
Make sure the shower is positioned over a bath
or shower tray because if the PRD operates, then
water will eject from the bottom of the unit.
Should this happen, turn off the electricity and
water supplies to the shower at the isolating
switch and stopvalve. Contact Customer Service
for advice on replacing the PRD.
WARNING!
THE SHOWER MUST NOT BE POSITIONED
WHERE IT WILL BE SUBJECTED TO
FREEZING CONDITIONS.
Shower unit can
be mounted either
side of riser rail
Height of
sprayhead
and
shower
to suit
Retaining
ring
Fig.5
25mm minimum
Outline of bath
or shower tray
Diagrammatic view (not to scale)
user's
requirement
Shower unit
must not
be within
an area
1 metre
from base
IMPORTANT: The unit must be mounted
on a flat surface which covers the full width
and length of the backplate. It is important
that the wall surface is flat otherwise
difficulty may be encountered when fitting
the cover and subsequent operation of the
unit may be impaired.
7
Page 10
SALSA
T00151
Fig.6
Fig.7
FITTING THE SHOWER TO THE WALL
WARNING!
Check there are no hidden cables or
pipes before drilling holes for wall
plugs. Use great care when using
power tools near water. The use of
a residual current device (RCD) is
recommended.
Unscrew the top and bottom retaining screws
(fig.6) and lift the cover from the backplate.
Note: The control knobs are an integral part of
the cover — do not attempt to remove them.
Entry positions for the mains water and electrical
supplies are at the top, bottom, or at the rear of
the unit.
If a bottom entry has been chosen, fit the
appropriate cut-out in the top of the backplate
(fig.7).
If a top entry has been chosen, fit the appropriate
cut-out in the bottom of the backplate (fig.8).
Fig.8
8
Page 11
SALSA
20
mm
Note: Deviations from the designated entry
points will invalidate product approvals.
If installing a feed pipe from the back or bottom,
the centre of the inlet valve to the wall surface is
20mm (fig.9).
Note: If entry is from the back, the nut of the
compression fitting will be partially behind the
surface of the wall (fig.9). This area MUST be
left clear when plastering over the pipework
in order to make the nut accessible for future
adjustments.
After choosing the site for the shower, use the
backplate as a template and mark the top fixing
hole and one of the lower holes (fig.10).
Drill and plug the wall.
(An appropriate drill bit should be used. If the
wall is brick, plasterboard or a soft building block,
appropriate wall plugs and screws should be fitted).
Screw top fixing screw into position leaving the
base of the screw head protruding 6mm out
from the wall.
Hook the backplate over the top screw and fit the
bottom fixing screw into position.
NOTE: Do not fully tighten the screws
at this stage, as the fixing holes are
elongated to allow for out of square
adjustment after the plumbing
connections have been completed.
Fig.9
Fig.10
9
Page 12
SALSA
Fig.11
Plastic lter
Water inlet pipe
WARNING!
The outlet of the shower acts as a
vent and must not be connected to
anything other than the hose and
showerhead supplied.
PLUMBING CONNECTIONS
Plumbing to be carried out before wiring.
DO NOT use jointing compounds on any pipe
fittings for the installation.
DO NOT solder fittings near the area of the
shower unit as heat can transfer along the
pipework and damage components.
Compression fittings MUST be used to connect
to the inlet of the shower.
Note: An additional stopvalve (complying with
Water Regulations) MUST be fitted in the mains
water supply to the shower as an independent
means of isolating the water in order to carry out
maintenance or servicing.
Procedure
Turn off the water supply either at the mains
stopvalve or the isolating stopvalve. Insert the
plastic inlet filter into the 15mm piping
(fig. 11) and connect the mains water supply
to the inlet of the shower via 15mm copper,
stainless steel or plastic pipe using a 15mm x
15mm brass compression fitting.
Note: The inlet fitting is designed to enter a
compression fitting only. DO NOT use push
fit connectors as full engagement cannot be
guaranteed. DO NOT use excessive force when
making these connections.
Make sure the backplate is square on the wall
and tighten the two retaining screws which hold
it to the wall.
Before turning on the mains water supply, the
stabilising valve should be fully closed. To make
sure that it is, replace the cover temporarily to
engage the splines and rotate the temperature
control fully clockwise until a ‘stop’ is felt. the
valve is now in the closed position. Remove the
cover.
Turn on the mains water supply and check for
leaks in the pipework connection to the shower.
Note: At this stage no water can flow through
the unit.
10
Page 13
SALSA
E
N
L
ELECTRICAL CONNECTIONS
SWITCH OFF THE ELECTRICITY SUPPLY AT THE
MAINS.
Fig.12 shows a schematic wiring diagram.
The cable entry points are shown in (fig.1).
The cable can be surface clipped, hidden or via
20mm conduit.
Note: Conduit entry can only be from rear.
Route the cable into the shower unit and connect
to the terminal block (fig.13) as follows:
Earth cable to terminal marked E
Neutral cable to terminal marked N
Live cable to terminal marked L
Important: Fully tighten the terminal block
screws and check that no cable insulation is
trapped under the screws. Loose connections
can result in cable overheating.
Note: The supply cable earth conductor must
be sleeved. The outer sheath of the supply cable
must be stripped back to the minimum.
The supply cable must be secured either by
routing through conduit or in trunking or by
embedding in the wall, in accordance with
current IEE regulations.
The use of connections within the unit, or other
points in the shower circuit, to supply power to
other equipment i.e. extractor fans, pumps etc.
will invalidate the guarantee.
DO NOT switch on the electricity supply until the
cover has been fitted.
Fig.12
1. Terminal block
2. Thermal cut-out
(main)
3. Microswitches
4. Element
L
N
E
1
2
4
5
5. Element
6. Microswitch
3
6
Terminal
block
11
Fig.13
Page 14
SALSA
Fig.14
Economy
position
o
l
c
n
r
u
T
REPLACING THE COVER
Position the power selector on the cover to the
'ECONOMY' position (fig.14).
Make sure the power selector spindle is aligned with
the screw at the 6 o'clock position - as shown in
(fig.15).
To make sure that the temperature control is correctly
positioned on the stabilising valve, temporarily place
the cover in position so that the splines engage and
rotate the temperature control fully clockwise until a
‘stop’ is felt(fig.15).
Fig.15
Power
selector
w
k
i
s
c
e
u
n
t
i
l
a
s
t
o
p
i
s
f
e
l
t
Temperature
control
warranty and approvals.
Cover
PRD
Tube
WARNING!
The PRD tube, MUST
be positioned correctly
when fitting the cover.
Failure to do so may
damage the unit if
the PRD operates and
will invalidate product
Fig.16
The valve is now in the closed position.
Remove the cover and position the temperature
control so that it points towards the ‘STOP’ position
(fig.16).
Replace the cover squarely to the backplate and guide into
position so that the knobs locate correctly into the spindle.
Should any difficulty arise, recheck the points above.
Secure the cover in position with the two retaining
screws.
DO NOT switch on the electricity supply to
the shower until the commissioning has
been carried out.
12
Page 15
SALSA
COMMISSIONING
WARNING!
Before normal operation of the
shower, it is essential the following
commissioning procedure is
completed correctly.
The first operation of the shower is intended
to flush out any unit debris and to guarantee
that the heater unit contains water before the
elements are switched on. This operation must
be carried out with the electricity switched
OFF at the isolating switch and without the
showerhead attached to the flexible hose. Make
sure the outlet of the hose is directed to waste.
Check the water supply is turned OFF at the
isolating stopvalve.
Rotate the temperature control fully anticlockwise to ‘10’, the minimum flow position
(fig.17).
Note: Leaving the control at any position other
than ‘10’ may cause the PRD to operate.
Turn the water supply back ON at the isolating
stopvalve.
Wait until water starts to flow from the flexible
hose, then slowly rotate the temperature control
clockwise to ‘1’, the maximum flow position
(fig.18).
It will take approximately thirty seconds for a
smooth flow of water to be obtained whilst
air and any debris is being dispersed from
the shower. When a smooth flow of water is
obtained, rotate the temperature control from
‘1’ to ‘10’ and back again several times to release
any trapped air within the unit.
Once the flushing out has been completed,
stop the water flow by rotating the temperature
control fully clockwise to the 'STOP' position.
Fit the showerhead to the flexible hose and place
in the holder.
Switch on the electricity supply to the shower at
the isolating switch.
The shower is now ready for normal operation.
Fig.17
Fig.18
WARNING
COVER RETAINING SCREWS
ONLY the SUPPLIED SCREWS should be
used. The use of none supplied screws WILL
invalidate product specifications & warranty.
13
Page 16
SALSA
Fig.19
Fig.20
Fig.21
OPERATING THE SHOWER
The flow of water is controlled by the
START/STOP temperature control. To obtain
warm water turn the control slowly
anti-clockwise to the mid position, ie. numbers
‘5’ or ‘6’ (fig.19).
If the water is too hot, turn the temperature
control slowly clockwise towards the lower
numbers (fig.20).
If the water is too cool, turn the temperature
control slowly anti-clockwise towards the higher
numbers (fig.21).
To stop the shower
Turn the temperature control fully clockwise to
the ‘STOP’ position, and water will cease to flow.
Power selector
The power selector (fig.22) has two positions,
ECONOMY and HIGH.
r
e
d
l
o
C
H
o
t
t
e
r
Single red symbol is the economy setting for using
less power during warmer months when the
ambient water temperature is high.
Note: If the stated flow rate required for the unit
cannot be met due to low water pressure, it will
be necessary to operate the unit on this setting
during the warmer months because of flow rate
limitations entering the unit.
Double red symbol is the high setting which allows
the highest flow achievable for your preferred
temperature. This setting should be regarded
as normal for optimum shower performance
throughout the year.
Note: It is advisable to be certain that the
showering temperature is satisfactory by testing
with your hand before stepping under the
showerhead.
There will always be a time delay of a few
seconds between selecting a flow rate and the
water reaching the stable temperature for that
flow rate.
14
Page 17
SALSA
OPERATING FUNCTIONS
Low water pressure cut-out
If the water pressure falls below the minimum
required for correct operation of the shower,
power will be switched off to the heating
elements preventing any maintained temperature
rises (water will continue to flow).
Power will automatically be restored when
adequate water pressure returns.
Temperature limiter
During normal operation if an overheat
temperature is sensed, power to the elements will
be reduced. Water will continue to flow. When
the temperature has cooled sufficiently, power to
the elements will be automatically restored to the
previous setting at the time of interruption.
Safety cut-out
The unit is fitted with a thermal cut-out safety
device. In the event of abnormal operation which
could cause unsafe temperatures within the unit,
the device will disconnect the power supply to
the heating elements. It will require a visit from a
qualified engineer to determine the nature of the
fault and replace the safety cut-out device, once
the unit has been repaired.
Fig.22
Power selector
Start/Stop temperature
control
NOTE: In normal use, it is in order to leave
the water supply permanently on to the
shower unit, but as with most electrical
appliances, the unit must be switched off
at the isolating switch when not in use.
WARNING!
After any servicing of the mains water
supply, always start the unit with the
electricity OFF at the isolating switch
and then rotate the temperature
control fully anti-clockwise in order
to purge any air in the pipework.
15
Page 18
SALSA
SPARE PARTS
Ref. Description Part No.
1. Selector switch assembly ..... S25711020
1
7
2
2. Thermal cut-out (can) ......... 22012250
3. Heater can assembly
(8.5kW) .............................. P25910700
(9.5kW) .............................. P25910701
3
5
4
4. Stabiliser valve assembly (incl. inlet elbow)
(8.5Kw & 9.5Kw) ................82600720
6
8
5. Pressure Relief Device .......... 82800450
6. Inlet elbow..........................7051625
– Microswitch & wire assy. .....P07820905
(single)
– Microswitch & wire assy. .....P07820906
(double)
– Earth wire (can) .................. 2160560
7. Terminal block & wires
(8.5Kw & 9.5Kw) ............... 25711010
8. Cover assembly - white ....... P25710604
16
Page 19
SALSA
FAULT FINDING
IMPORTANT: Switch OFF the electricity at the mains supply and remove the circuit fuse
before removing the cover from the shower while attempting any fault finding inside
the unit.
Problem/Symptom Cause Action/Cure
1 Shower
inoperable, no
water flow.
2 Water too hot.
3 Water
temperature
cycling hot/cool at
intervals.
4 Water too cool
or cold.
1.1 No mains water
supply to shower.
1.2 Unit malfunction.
2.1 Not enough water
flowing through the
shower.
2.2 Blockage in supply.
2.3 Increase in ambient
water temperature.
3.1 Heater cycling on
temperature limiter.
4.1 Too much flow.
4.2 Water pressure
below minimum required
(see rating label).
4.3 Reduction
in ambient water
temperature.
4.4 Interrupted power
supply.
4.5 Electrical
malfunction or safety cutout operated.
1.1.1 Check if isolating valves are fully open.
Check if a blockage in inlet filter or in pipework.
1.2.1 Have unit checked. Ring Customer
Service.
2.1.1 Increase flow rate via temperature
control.
2.1.2 Blocked showerhead — clean or replace
blocked sprayplate in showerhead.
2.2.1 Check if stop valves are fully open. Check
if a blockage in inlet filter.
2.3.1 Readjust flow rate to give increased flow.
2.3.2 Select ‘economy’ power.
3.1.1 See 'Water too hot' causes 2.1, 2.2 and
2.3 and their appropriate action/cures. If it
continues, contact Triton Customer Service.
4.1.1 Reduce flow rate via temperature control.
4.2.1 Is water supply mains or tank fed?
4.2.2 If tank fed, replumb to mains water
supply or see 4.2.4.
4.2.3 If mains fed, make sure that mains
stopvalve is fully open and that there are no
other restrictions in the supply while shower is
in use, or see 4.2.4.
4.2.4 Fit pump to give minimum pressure
(see rating label). Contact Customer Service for
advice.
4.3.1 Readjust flow rate to give reduced flow.
4.3.2 Select ‘HIGH’ power.
4.4.1 Blown fuse or circuit breaker. Check
supply. Renew or reset fuse or circuit breaker. If
it fails again, consult a qualified electrician.
4.4.2 Power cut. Check other appliances and if
necessary, contact local Electricity Supply Co.
4.5.1 Have unit checked by suitably qualified
electrician or contact Triton Customer Service.
17
Page 20
SALSA
FAULT FINDING
Problem/Symptom Cause Action/Cure
5 Shower varies
from normal
temperature to cold
during use.
6 Pressure relief
device has operated
(water ejected from
PRD tube).
It is advised all electrical maintenance/repairs to the shower
5.1 Water pressure has
dropped below minimum
required
6.1 Blocked
showerhead.
6.2 Twisted/blocked
flexible shower hose.
6.3 Showerhead
not removed whilst
commissioning.
Note: Identify cause of operation before fitting new PRD unit.
When fitting a new PRD, follow the commissioning procedure.
5.1.1 Wait until the water pressure resumes to
normal.
6.1.1 Clean or replace blocked sprayplate in
showerhead and then fit new PRD.
6.2.1 Check for free passage through hose.
Replace the hose if necessary and fit new PRD.
6.3.1 Fit new PRD. Commission unit with
showerhead removed.
N-003-A
should be carried out by a suitably qualified person.
In the unlikely event of unit failure other than detailed in the fault finding page,
please contact Customer Service for advice.
Y-001-A
18
Page 21
Diagram Key:
Water Entry Points
Cable Entry Points
SALSA
Entry Points
19
Page 22
SALSA
20
Page 23
SALSA
As a producer and a supplier of electric showers, Triton Showers is committed to the protection of the environment
WEEE Directive – Policy Statement
via our own environmental policy and the compliance with the WEEE directive.
Triton Showers is fully registered with the Environment Agency under the following schemes:
Repic: Producers take-back scheme (PTS), registration number WEE/EJ3466QV
Valpak: Distributor take-back scheme (DTS), registration number 9659
All our electric products are labelled accordingly with the crossed out wheeled bin symbol. This indicates, for
disposal purposes at end of life, that these products must be taken to a recognised collection points, such as
local authority sites/local recycling centres; this will be free of any charges. Do not return to Triton Showers.
21
Page 24
UK SERVICE POLICY
In the event of a product fault or complaint occurring, the following
procedure should be followed:
1. Telephone Customer Service on 0844 980 0750 having available,
your details including post code, the model number and power
rating of the product, together with the date of purchase and, where
applicable, details of the particular fault.
2. If required, the Customer Service Advisor will arrange
for a qualified engineer to call.
3. All products attended to by a Triton service engineer must be installed
in full accordance with the Triton installation guide applicable to the
product. (Every product pack contains an installation guide, however, they can also be bought via our Customer Service Spares Department).
4. Our engineer will require local parking and if a permit is required this
must be available to the engineer on arrival at the call.
5. It is essential that you or an appointed representative (who must
be over 18 years of age) is present for the duration of the service
engineer's visit. If the product is in guarantee you must produce proof
of purchase.
6. Where a call under the terms of guarantee has been booked and
the failure is not product related (i.e. scaling and furring, incorrect
water pressure, pressure relief device operation or electrical/plumbing
installation fault) a charge will be made. A charge will also be issued
if nobody is at home when the service engineer calls or adequate
parking/permit is not available.
7. If the product is no longer covered by the guarantee an up front fixed
fee will be charged before the site visit.
8. Should proof of purchase not be available on an “in-guarantee” call,
or should the service engineer find that the product is no longer
under guarantee, the engineer will charge the same fixed price and
the customer will be expected to pay the engineer before he leaves.
If payment is not made on the day an administration charge will be
added to the fixed charge.
9. If a debt is outstanding from a previous visit, or from any other Triton
purchase, Triton reserves the right to withhold service until the debt
has been settled.
10. Triton takes the health, safety and wellbeing of its employees very
seriously and expects customers to treat all staff members with respect.
Should any employee feel threatened or receive abuse, either verbally
or physically, Triton reserves the right to withhold service and will
support the employee with a legal prosecution.
Replacement Parts Policy
Availability: It is the policy of the manufacturer to maintain parts
availability for the duration of production and a period of five years
thereafter, in accordance with industry standards.
Spare parts are available via our website, www.tritonshowers.co.uk,
or by telephoning Triton Customer Service Spares Department.
Payment should be made by credit/debit card (excluding American
Express or Diners Card). Payment can also be made by pre-payment
of a pro forma invoice by cheque or money order.
Telephone orders are based on information given during of the call.
Before contacting Triton, please verify your requirements
using the information contained in the supplied user guide.
Triton cannot accept liability for incorrect part identification.
TRITON STANDARD GUARANTEE
With the exception of accessories, Triton guarantee the
product against all manufacturing defects for a period of
2 years (for domestic use only) from the date of purchase,
provided that it has been installed by a competent person in
full accordance with the fitting instructions.
All accessories such as shower heads, hoses and riser rails
carry a 1 year parts only guarantee against manufacturing
defects.
Any part found to be defective during this guarantee period
we undertake to repair or replace at our option without
charge so long as it has been properly maintained and
operated in accordance with the operating instructions, and
has not been subject to misuse or damage. This product
must not be taken apart, modified or repaired except by a
person authorised by Triton. This guarantee applies only to
products installed within the United Kingdom and does not
apply to products used commercially. This guarantee does
not affect your statutory rights.
What is not covered:
1. Breakdown due to: a) use other than domestic use by
you or your resident family; b) wilful act or neglect;
c) any malfunction resulting from the incorrect use or
quality of electricity, gas or water or incorrect setting
of controls; d) failure to install in accordance with this
installation guide
2. Claims for missing parts once the product has been
installed.
3. Repair costs for damage caused by foreign objects or
substances.
4. Total loss of the product due to non-availability of parts.
5. Compensation for loss of use of the product or
consequential loss of any kind.
6. Call out charges where no fault has been found with the
appliance.
7. The cost of repair or replacement of pressure relief
devices, showerheads, hoses, riser rails and/or wall
brackets, isolating switches, electrical cable, fuses and/or
circuit breakers or any other accessories installed at the
same time.
8. The cost of routine maintenance, adjustments, overhaul
modifications or loss or damage arising therefrom,
including the cost of repairing damage, breakdown,
malfunction caused by corrosion, furring,
9. Call out charges where the water supply cannot be
isolated, this includes consequential losses arising from
unserviceable supply valves.