Triton Luxury Body Dryer Installation And Operating Instructions Manual

Page 1
INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER
2180514G June 2008
Installation and
operating
instructions
Luxury
body dryer
Page 2
the nation’s favourite for
PLUMBING & HEATING SUPPLIES
SECURE PAYMENTS
shop online with confidence
FREE SHIPPING
on all orders over £100 to mainland UK
FINANCE AVAILABLE
spread the cost with low interest rates
PRICE MATCH
always get the best deals available
Boilers Radiators Heating controls

Cylinders Fires Renewable energy
Bathroom suites Kitchen sinks & taps Showers Wet rooms Towel warmers Bathroom furniture & much more
HUGE REDUCTIONS
we have
ON THOUSANDS OF ITEMS
0844 800 3460
CALL US ON
visit our website
plumbnation.co.uk
Page 3
Body dryer
ii
CONTENTS Page
Important safety information........................................ 1
Introduction ................................................................. 2
Specifications ............................................................... 2
Advice to users ............................................................. 2
Fault finding ................................................................ 3
Key to main components ............................................. 3
Electrical requirements ................................................. 4
Siting ........................................................................ 6
Fitting the body dryer .................................................. 8
Electrical connections .................................................. 10
Replacing the cover .................................................... 12
Commissioning ........................................................... 13
Operating functions .................................................... 14
Overheat cut out ........................................................ 15
Cleaning ..................................................................... 16
Servicing ..................................................................... 16
Spare parts ................................................................. 17
Guarantee, service policy, etc. ................................ rear cover
To check the product suitability for commercial and multiple installations, please contact Triton’s specification advisory service before installation.
Telephone:
Facsimile:
E mail:
0870 067 3767
0870 067 3334
technical@tritonshowers.co.uk
Page 4
Body dryer
1
1 GENERAL
1.1 Isolate the electrical supply before removing
the cover.
1.2 Read all of these instructions and retain
them for later use.
1.3 DO NOT take risks with plumbing or
electrical equipment.
1.4 Isolate electrical supplies BEFORE proceeding
with the installation.
1.5 Contact Customer Service (see back page)
if the unit shows a distinct change in performance.
1.6 The mesh grill on the air inlet should be
regularly inspected for any build up of fluff and cleaned if found.
1.7 This product is not suitable for mounting
into shower cubicles, steam rooms or steam cubicles.
1.8 To enable future servicing to be carried out
on the unit:
a) When installed in a loft space the body
dryer must be sited in an accessible and safe location.
b) A safe means of access must be provided
into the loft e.g. fixed loft ladder.
c) Ceiling joists in the loft must be adequately
boarded to provide safe unobstructed access to and around the body dryer.
d) There must be adequate lighting in the
loft for servicing purposes.
2 ELECTRICAL
2.1 The electrical installation must comply
with BS7671 ‘Requirements for electrical installations” (IEE wiring regulations), Building Regulations or any particular regulations as specified by the local Electrical Supply Company.
2.2 The appliance and any associated electric
shower MUST be earthed using the main feed earth wire connections provided in the appliances.
2.3 In accordance with ‘The Plugs and Sockets,
etc (Safety) Regulations 1994’, this appliance is intended to be permanently connected to the fixed wiring of the electrical mains system.
2.4 Make sure all electrical connections are tight
to prevent overheating.
2.5 Fuses DO NOT provide personal protection
against electric shock.
2.6 To enhance electrical safety a 30mA residual
current device (RCD) MUST be installed in all body dryer/shower circuits. This may be part of a consumer unit or a separate circuit.
2.7 Switch off the unit immediately at the pull
cord isolation switch if the unit comes into contact with water. DO NOT reconnect until a qualified electrician has checked the unit for safety.
2.8 The unit is designed to work in association
with an instantaneous electric shower where the circuit protective device (fuse) is 40A or 45A rating. No other electrical equipment i.e. extractor fans or pumps should be connected to the body dryer unit.
2.9 Always electrically isolate the dryer or
dryer/shower combination at the pull cord isolation switch when not in use. This is a safety procedure recommended with all electrical appliances.
2.10 As with all electrical appliances it is
recommended to have the body dryer and any associated shower unit installation checked at least every two years by a competent electrician to make sure there is no deterioration due to age and usage.
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
F Products manufactured by Triton are safe and without risk provided they are installed, used and
maintained in good working order in accordance with our instructions and recommendations.
F All required safety features have been designed and built into the product for your complete protection. F WARNING: Always isolate electrically the dryer or dryer/shower combination when not in
use. This is a safety procedure recommended with all electrical appliances.
F The dryer has been designed for use in a bathroom or shower room for the purpose of personal
body drying and will heat a bathroom rapidly. The dryer should not be used for any other purpose.
This dryer MUST NOT be installed directly above a bath or within a shower cubicle. It MUST be sited as shown in Fig.3. on Page 6 of these instructions.
Page 5
Body dryer
2
INTRODUCTION
This book contains all the necessary fitting and operating instructions for your Triton Luxury Body Dryer. Please read them carefully.
The Body Dryer installation must be carried out by a suitably qualified person and in the sequence of this instruction book.
Care taken during the installation will provide a long, trouble-free life from your body dryer.
The Body Dryer has been designed for use in a bathroom or shower room for the purpose of personal body drying. The dryer should not be used for any other purpose.
Never install in a shower cubicle or steam room.
SPECIFICATIONS
Electrical
Nominal power Nominal power rating at 240V rating at 230V
9.0kW – (40A MCB rating) 8.3kW – (40A MCB rating)
Trickle current on OFF mode is 0.04A at 240V (9.6W) but is not isolated.
Minimum cross sectional area of supply cable is 6mm². Derating factors should always be taken into consideration when selecting cable size.
Materials
Main unit – 20% Glass filled Polypropylene Cover – ABS
Dimensions
Width – 335mm, Length – 625mm, Height – 175mm
Above ceiling – 140mm Below ceiling – 70mm (cover)
Weight – 7kg Packed weight – 10kg
Standards and Approvals
Complies with requirements of current British and European safety standards for household and similar electrical appliances.
Complies with requirements of the British Electrotechnical Approvals Board BEAB.
Meets with compliance with European Community Directives CE. EMC
ADVICE TO USERS
The following points will help you understand how the Body Dryer operates:
a. The unit consists of a high powered two speed fan and 2 x 4.5kW heater elements which are fully controllable using the hand-held controller (supplied). Air is drawn in through the filter, passed across the elements and then discharged downwards.
b. DO NOT place pressurised aerosol cans in or under the hot air flow. Always electrically isolate the dryer or dryer/shower combination when not in use.
c. Temperature sensors are fitted to the unit for your safety. However, the best sensor is you. If you find the airflow or room temperature rises to uncomfortable levels switch off or regulate the flow through use of the controller. Never leave alone those unable to recognise or react to discomfort with the dryer switched on.
For ideal comfort and drying time the ceiling height should be between 2.2m to 2.5m.
The dryer has a 10-minute preset cut off.
d. The unit can be connected in combination with an electrical shower rated from 8kW up to 10.5kW. The electrical safety features incorporated in the unit do not allow the Body Dryer to be operated while the shower is on and vice versa.
e. The hand-held controller should be kept away from sources of water.
f. The LED’s incorporated into the cover show the operational status of the Body Dryer or any fault condition. If you suspect the unit to be faulty unqualified attempts to rectify the situation should be limited to isolating and switching on the unit via the pull cord and operation of the hand-held controller (see commissioning instructions). All other problems MUST be attended to by a competent electrician or service engineer.
Due to continuous improvement and updating, specification may be altered without prior notice.
Replacement parts can be ordered from Customer Service. See ‘spare parts’ for details and part numbers.
Page 6
Body dryer
3
Fig.1
FAULT FINDING
Follow the instructions for commissioning. If findings do not match expectations contact Triton Customer Service.
If the green LED is on but the unit does not operate then the hand-held controller or its battery should be suspected.
DO NOT attempt any repairs since there are no user serviceable parts in the unit.
KEY TO MAIN COMPONENTS
1. Body dryer unit
2. Front cover
3. Fixing kit
4. Communications cable
5. Remote control
6. User guide (not shown)
1
2
4
3
5
Page 7
Body dryer
4
ELECTRICAL REQUIREMENTS
The installation, supply cable and circuit protection must conform with BS7671 (IEE wiring regulations) and be sufficient for the amperage required.
The following notes are for guidance only:
1 The body dryer must only be connected to
a 230 – 240V ac supply (single phase).
2 If an instantaneous electric shower
circuit already exists the body dryer may be connected in series with the shower subject to confirmation that the electrical circuit complies with current IEE regulations.
2.1 The electrical rating of the body dryer is
shown on the rating label within the unit.
3 Before making any electrical connection
within the installation make sure that no terminal is live. If in any doubt switch off the whole installation at the mains and remove the correct circuit fuse.
4 If the installation is undertaken by
anyone who is not registered to issue a Part P electrical certificate then it will be necessary to notify the local Building Control office before installing.
5 The body dryer must be connected to
its own independent electrical circuit as determined by the IEE regulations but it can share the same supply as an electric shower providing the wiring connections follow that of the wiring schematic shown in the electrical connections section.
The body dryer MUST NOT be connected
to a ring main, spur socket outlet, lighting circuit or cooker circuit.
Note: Safety features built into the body
dryer prevent the unit and any shower fed via the body dryer from operating at the same time.
5.1 The electrical supply must be adequate for
the maximum loading of the unit and/or any existing shower circuit.
6 Check the consumer unit (main fuse
box) has a main switch rating of 80A or above and that the fuse way will take the necessary fuse or MCB to provide the maximum electrical load (amps) of the body dryer and shower if applicable.
6.1 If the consumer unit has a rating below
80A or there is no spare fuse way then the installation may require a new consumer unit serving the house or just the body dryer/shower.
6.2 If you do not have the necessary supply
you will need to contact the local electricity company regarding upgrading the incoming supply.
Table A
Fig.2
WARNING!
WHEN USED INDEPENDENTLY OR IN
TANDEM WITH AN ELECTRIC SHOWER
THIS APPLIANCE MUST BE EARTHED
(EARTH CONTINUITY MUST BE
MAINTAINED).
CIRCUIT PROTECTION
unit cartridge rating MCB fuse
8.0kW 40A 35A
8.5kW 40A 45A
9.0kW 40A 45A
9.5kW 40/45A 45A
10.5kW 45A 45A
Page 8
Body dryer
5
7 The earth continuity conductor of the
electrical installation must be effectively connected electrically to all exposed metal parts of other appliances and services in the room in which the body dryer and an electric shower is to be installed, to conform to current IEE regulations.
8. For close circuit protection DO NOT use
a rewireable fuse, instead use a suitably rated miniature circuit breaker (MCB) or cartridge fuse (see table A).
8.1 A 30mA residual current device (RCD)
MUST be installed in wiring for all body dryer installations.
9 A 45 amp double pole isolating switch
with a minimum contact gap of 3mm in both poles must be incorporated in the circuit.
9.1 This isolating switch must also have a
mechanical indicator showing when the switch is in the OFF position and the wiring must be connected to the switch without the use of a plug or socket outlet.
9.2 The switch must be accessible and clearly
identifiable, but out of reach of a person using a fixed bath or shower, except for the cord of a cord operated switch. The switch should be placed so that it is not possible to touch the switch body while standing in the bath or shower cubicle. It should, however, be readily accessible to switch off after using the shower.
10 Where a shower cubicle is located in any
room other than a bathroom, all socket outlets in that room must be protected by a 30mA RCD.
11 The current carrying capacity of the cable
must be at least that of the shower circuit protection.
11.1 To obtain full advantage of the power
provided by the body dryer, use the shortest cable route possible from the consumer unit to the body dryer and to the shower if applicable.
11.2 It is also necessary to satisfy the
disconnection time and thermal constraints, which means that for any given combination of current demand, voltage drop and cable size, there is a maximum permissible circuit length.
12 The body dryer circuit should be separated
from other circuits by at least twice the diameter of the cable or conduit.
12.1 The current rating will be reduced if
the cabling is bunched with others, or surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30°C.
Under these conditions derating factors
apply and it is necessary to select a larger cable size.
12.2 In the majority of installations the cable
will unavoidably be placed in one or more of the above conditions. This being so, we strongly recommend using a minimum of 10mm² cabling throughout the installation.
12.3 In any event, it is essential that a
competent electrician assess individual site conditions in order to ensure the correct requirements are met.
Page 9
Body dryer
6
SITING
Consumer unit
Body dryer
Shower unit
2.2 - 2.5 metres
Isolating
switch
Fig.4 Typical system layout
The dryer has been designed for use in a bathroom or shower room for the purpose of personal body drying and will heat a bathroom rapidly. The dryer should not be used for any other purpose (It may be sited in Area C or
beyond defined areas); see fig.3.
WARNING!
The dryer must NOT be positioned
where it is likely to become in contact
with water from above or below or
in a damp environment e.g. inside a
steam room, shower cubicle or directly
over a bath in Area A or B - see fig.3.
Beyond defined Areas
Fig.3
Page 10
Body dryer
7
600mm diameter
Before installing consideration should be given to ease of installation, inspection, servicing and removal.
Access to electrical connections and the routing and security of electrical cables should always be paramount, particularly the isolation switch (see Electrical Requirements).
Fig.4 shows a typical system layout.
As a minimum, a floor area of 600mm diameter should be allowed directly below the output vent (rectangular nozzle) of the body dryer for the user to stand in (fig.5). However, the user will benefit most where the area under the dryer is the largest area possible of clear floor space.
Note: The body dryer MUST not be positioned over a bath or within a shower cabinet.
Use the template (fig.6) and cover to determine the best position for the body dryer. Careful observation and measurement both above and below the ceiling will ensure all factors are taken into account before any drilling or cutting takes place.
Always try the body dryer template in a selected location before proceeding further.
IMPORTANT: Loft insulation that occupies the space required for the dryer should be removed or rolled back. The unit must be installed on flat surfaces both above and below the ceiling otherwise difficulty may be encountered when fitting the ceiling cowling and subsequent operation of the unit may be impaired.
Note: To install the Body Dryer to a concrete ceiling with an additional suspended ceiling or a bathroom with a timber flat roof construction you will need to use an optional fitting kit (not supplied). Contact Triton Customer Service for further details.
Once installed, care should be taken to ensure the immediate area around the body dryer unit within the loft space remains a clear of of obstructions and that other items are not placed against the unit or in close proximity.
It is recommended that the electrical feed cables are secured to a convenient joist (fig.7).
Perforated line
E
B
D
C
B
A
B
Perforated Line
Minimum gap between joists
with template folded (350mm)
E
B
D
C
B
A
B
Fig.5
Fig.6
Secure
the cables
to joist
Fig.7
Key
A. Air intake. B. Bolt hole for solid
ceiling.
C. Communications
cable hole.
D. Water drainage. E. Exhaust nozzle.
Page 11
Body dryer
8
20mm
diameter
FITTING OF THE DRYER
Before installation check the parts for any signs of obvious damage.
Read, understand and follow the installation safety guidelines that come with this product.
The dryer has been designed for use in a bathroom or shower room for the purpose of personal body drying. The dryer should NOT be used for any other purpose; see 'Siting'.
Parts check list
Hand-held controller and battery (3V Lithium
12032) Main unit Ceiling cover Template Support straps and staples Ceiling fittings
Tools required
Electrical test meters Small bradawl/small screwdriver Marker pen/pencil and straight edge Pad saw Crosshead screwdriver Flat head screwdriver Hand-held drill with 8mm drill bit Protective goggles/glasses and face mask
Procedure
Use the template and cover to determine the best position for the body dryer. Careful observation and measurement both above and below the ceiling will ensure all factors are taken into account before any marking, drilling or cutting, takes place.
If the template does not fit easily between the roof joists then a section of joist may have to be removed and the remainder supported by cross members attached to the adjacent joists with suitable supports on either side of the unit.
IMPORTANT: This task is beyond the scope of this book and should NOT be attempted unless the installer is suitably experienced and has the knowledge and skills to maintain a secure structure.
The minimum distance between joists is 355mm.
Fig.8
Fig.9
Fig.10
Page 12
Body dryer
9
Tip: Remember, sound advice is to measure
twice, cut once.
Note: The cut-outs in the template are not symmetrical about the centre of the template. When positioning the template make sure to use the correct aspect.
Place the template supplied in the selected position in the roof space and push a bradawl or thin screwdriver through the plasterboard to mark the four corners of the rectangular cut out, the centre of the round hole and the centres of the two smaller holes (fig.8). Remember, you are pushing through plasterboard and the minimum effort required should be used.
From below, line up the template with the holes made in the ceiling and mark the cut outs and cover locating holes with a pen (fig.9).
Before making any cuts align the cover to these markings to confirm the chosen position.
Drill the four corners of the rectangular cut out and one point on the inner edge of the large round hole with an 8mm drill bit to allow for a pad saw to be used (fig.10). Open out the two smaller holes to 20mm diameter.
When drilling or cutting from below it is recommended that eye protection is used. Waste material should be collected at the highest convenient point since airborne particles can cause respiratory discomfort. A vacuum cleaner nozzle close to the drill bit or pad saw cut can also reduce the overall volume.
It is useful to have an assistant when drilling or cutting the plaster board to hold a catchment tray or box for the falling debris. Do not forget that they need personal protection too.
Clear out any debris that remains above ceiling height.
Position the body dryer from above (fig.11) and inspect from below. Fit temporarily the cover to confirm correct fit and alignment.
Support the unit between the joists using the support straps and staples provided (fig.12). The straps need only be slightly tensioned.
Connect the communications cable to the body dryer unit (fig.13) and route the cable through the hole in the plasterboard in preparation for plugging into cover (fig.13).
Support
straps
Fig.12
Fig.11
Feed
communication
cable through hole in ceiling
Fig.13
Page 13
Body dryer
10
ELECTRICAL CONNECTIONS
SWITCH OFF THE ELECTRICITY SUPPLY AT THE MAINS.
Fig.15 shows a schematic wiring diagram.
Fig.16 shows a connection diagram which
must be followed without deviation. This is particularly important where a body dryer and shower combination are using the same feed cable.
A built-in safety feature of the body dryer prevents both devices from operating at the same time and overloading the electrical wiring.
Note: The terminal block that connects the shower cable to the dryer is LIVE whenever the dryer is not electrically isolated.
Live conductor (Brown or Red) to terminal marked
L
Neutral conductor (Blue or Black) to terminal marked
N
Earth conductor to terminal marked (yellow and green)
E
The mains cable should be firmly secured using the clamps provided.
The earth wire should be physically longer than the live and neutral wires.
IMPORTANT: Where a shower is involved earth continuity is essential to provide a safe operating environment.
Fully tighten the terminal block screws and make sure no cable insulation is trapped under the screws. Loose connections can result in the cable overheating.
Notes
Good wiring practice advises that:
The supply cable earth conductor must be sleeved.
The outer sheath of the supply cable must be stripped back to the minimum.
The supply cable must be secured either by routing through conduit or in trunking or by embedding in the wall, in accordance with current IEE regulations.
240V Shower feed out
240V Mains feed in
Fig.16
Fig.17
L N N L
E
1
2
3 4
5
6
7
8
5
6
Fig.15
1. Terminal block
2. Earth post
3. Body dryer PCB
4. Fan
5. Heating element
6. Thermal contact
7. Cover PCB
8. Infrared receiver
Page 14
Body dryer
11
DO NOT switch on the electricity supply until all safety covers have been correctly fitted.
Replace the wiring safety cover (fig.17).
Connecting the body dryer to a shower
Where a shower is to share the same electrical supply the wiring should be routed as shown in fig.18. The connectivity at the body dryer is as shown in fig.15 and adjacent to the connecting blocks on the body dryer.
Always be aware that the electrical supply and electrical safety MUST meet the requirement for the larger of the two loads.
Meter
Incoming supply fuse
Meter
tails
Consumer unit
Shower unit
Fuse or
MCB
RCD
(can be part of
consumer unit)
80A or 100A
main switch
Body dryer
unit
Pull cord
isolation
switch
Fig.18
Page 15
Body dryer
12
REPLACING THE COVER
Place the cover up to unit and align with the outlet nozzle. Mark the position of the four cover screw holes (fig.18). Remove the cover and screw the four plasterboard rawl plugs into the positions marked on the ceiling.
Connect up the multiway cable to the PCB unit within the ceiling cover (fig.19). Secure the multiway cable in the strain relief tabs located in the cover and then secure the cover to the ceiling using the screws supplied.
The unit is now ready for commissioning.
Retain the packaging should the unit need to be returned under warranty; otherwise dispose of in an environmentally friendly way.
Fig.19
Fig.18
Page 16
Body dryer
13
COMMISSIONING
IMPORTANT: Before commissioning make sure both the electrical connection cover and ceiling are in place.
The unit has two fan speeds and two heat settings in any combination.
A single audible signal confirms a change in speed has been effected. A double bleep confirms the unit is in full heat mode. The unit can also be used in fan only mode.
Establish the electrical supply to the pull cord switch assembly by replacing any fuses and activating the RCD device.
Operate the pull switch to connect mains power to the unit. Momentarily, all three LED’s will flash on but only the green LED will remain on.
Test Sequence
Carry out the functions shown in Table C.
When first operated you may experience an odour from the unit, this will be due to the heating elements being operated for the first few times. This odour should quickly disappear.
Overheating is a sign that something is wrong. If the reason for overheating is not obvious then switch off the unit at the mains supply and contact Triton Customer Service for advice.
DO NOT attempt any repairs as there are no user serviceable parts in the unit.
The body dryer has a 10-minute maximum run time after which the unit will switch itself off.
To restart the dryer reselect a setting; this prevents permanent operation of the dryer when a button is accidentally pressed.
Any associated electric shower should now be checked for functionality as shown in Table D.
FUNCTION
Press the Fan only button on the hand-held controller.
Press the Fan Fast button.
Press the Low Heat button.
Press the High Heat button.
Press the Fan Slow button.
Press the High Heat button.
Press the Fan only button.
Press STOP button.
EFFECT
Fan will start up in slow mode. Air output from the unit will be at ambient temperature.
Fan speed increases to the maximum.
First heat element is connected and warm air is felt.
Second heat element is connected and air temperature increases.
Fan speed decreases to lowest setting. Air temperature increases further.
Second heat element is disconnected. Air temperature decreases.
Fan runs at its slowest speed. Ambient temperature air will be felt from unit.
Fan stops.
Table C
If this works as it should, with the shower running, try to turn on the body dryer.
Switch the shower OFF.
END OF COMMISSIONING
Circuitry in the unit should prevent the body dryer switching on and the shower switching off.
Full functionality is returned to the body dryer controller.
Table D
Page 17
Body dryer
14
Note: As with most electrical appliances, the unit must be switched off at the isolating switch when not in use.
OPERATING FUNCTIONS
Normal use
The dryer has been designed for use in a bathroom or shower room for the purpose of personal body drying. The dryer MUST NOT be used for any other purpose.
The body dryer is designed to give maximum comfort and drying satisfaction.
The dryer is an extremely efficient personal body dryer and will heat a room rapidly.
It should be understood that when wet rapid evaporation results in a drop in body temperature. To maximise comfort and reduce drying time it is recommended that full heat and slow fan speed is selected immediately after exiting the shower or bath.
Typically, after a short period excess water on the skin will start to evaporate quickly and the user feels more comfortable with the fast speed setting and/or lower heat setting. Make these adjustments as required.
When first operated you may experience an odour from the unit, this will be due the heating elements being operated for the first few times. This odour should quickly disappear.
Remote control handset (fig.21)
Works by infra red frequency transmissions and has a range of about five metres line-of-sight.
Body dryer controller
Each time a button is depressed it is accompanied by either one or two bleeps. The functions are shown in Table E.
Pressing the OFF button turns off the dryer unit and returns power to the shower (if fitted). An audible jingle is generated to confirm that the dryer has been switched off.
Off control
Power is always maintained to the dryer for control purposes but power to any associated electric shower will be switched off when the dryer is in use.
As a precaution against misoperation the dryer incorporates a 10 minute cut-off timer. If this is
Fan only
Fan fast
Fan slow
Stop
High heat
Low heat
Fig.21
Note: The fan motor will turn slowly
when an electric shower connected to the dryer is operated.
This appliance is not intended for use by young children or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure that they do not play with the appliance.
Page 18
Body dryer
15
activated then the reselection of a function on the remote controller will be required to restart the dryer.
OVERHEAT CUT OUT
The body dryer is designed with your safety in mind. The dryer incorporates sophisticated protection circuitry that shuts down the power if for any reason the dryer should overheat.
In the unlikely event that this should occur during use both the red and orange LED’s in the cover will be illuminated and the body dryer heaters and fan will have been turned off by the electrical safety circuitry.
When the red LED has extinguished the unit has cooled sufficiently for the body dryer to be safely switched on again. The unit will not reset
until after the red LED has extinguished.
The orange LED remains on to show that an overheat situation has occurred and can only be reset when the power to the body dryer is removed. Use the pull cord switch assembly to disconnect then reconnect the electrical power.
Overheating is a sign that something is wrong, if the reason for overheating is not obvious or is a regular occurrence then advice or support should be sought from an approved service engineer or the manufacturer.
DO NOT attempt any repairs as there are no user serviceable parts in the unit.
FUNCTION
Press the Fan only button on the hand-held controller.
Press the Fan Fast button.
Press the Low Heat button.
Press the High Heat button.
Press the Fan Slow button.
Press the High Heat button.
Press the Fan only button.
Press STOP button.
EFFECT
Fan will start up in slow mode (one bleep). Air output from the unit will be at ambient temperature.
Fan speed increases to the maximum (one bleep).
First heat element (4.5kW) is connected and warm air is felt (one bleep).
Second heat element (total
9.0kW) is connected and air temperature increases (two bleeps).
Fan speed decreases to lowest setting. Air temperature increases further (one bleep).
Second heat element is disconnected. Air temperature decreases (one bleep).
Fan runs at its slowest speed. Ambient temperature air will be felt from unit (one bleep).
Fan stops (longer bleep).
Table E
Page 19
Body dryer
16
CLEANING
Always isolate the power supply when cleaning.
DO NOT use detergents, abrasive cleaning powder, or polish of any kind on the cover.
Wipe with a dry cloth to remove dust and a damp cloth (not wet) to clean off stains.
Make sure that dust or fluff does not accumulate on the inlet mesh, this could lead to overheating of the element. Use a vacuum cleaner at regular intervals to remove dust or fluff.
SERVICING
Should any servicing or maintenance be required then contact Triton Customer Service or a suitably qualified and competent electrician or service engineer.
Page 20
Body dryer
17
SPARE PARTS
Ref. Description Spares No.
Complete unit
Airobe model DR-103 version 1.1
1. Main PCB 83309590
2. Heater element – single 83309600
3. Fan motor 83309610
4. Run capacitor 83309620
5. Cover, including: PCB Filter
83309630
6. Handset 83309640
7. Communication cord 83309650
Optional
Body dryer fitting kit 1 (for concrete ceilings)
Body dryer fitting kit 2 (for flat roofs)
1
2
3
4
5
6
7
Page 21
Triton Showers Triton Road Nuneaton Warwickshire CV11 4NR
Triton is a division of Norcros Group (Holdings) Limited
TRITON STANDARD GUARANTEE
Triton guarantee this product against all mechanical and electrical defects arising from faulty workmanship or materials for a period of two years for domestic use only, from the date of purchase, provided that it has been installed by a competent person in full accordance with the fitting instructions.
Any part found to be defective during this guarantee period we undertake to repair or replace at our option without charge so long as it has been properly maintained and operated in accordance with the operating instructions, and has not been subject to misuse or damage.
This product must not be taken apart, modified or repaired except by a person authorised by Triton. This guarantee applies only to products installed within the United Kingdom and does not apply to products used commercially. This guarantee does not affect your statutory rights.
What is not covered:
1 Breakdown due to: a) use other than domestic
use by you or your resident family; b) wilful act or neglect; c) any malfunction resulting from the incorrect use or quality of electricity, gas or water or incorrect setting of controls; d) faulty installation.
2 Repair costs for damage caused by foreign
objects or substances.
3 Total loss of the product due to non-availability
of parts.
4 Compensation for loss of use of the product or
consequential loss of any kind.
5 Call out charges where no fault has been found
with the appliance.
6 The cost of repair or replacement of pressure relief
devices, showerheads, hoses, riser rails and/or wall brackets, isolating switches, electrical cable, fuses and/or circuit breakers or any other accessories installed at the same time.
7 The cost of routine maintenance, adjustments,
overhaul modifications or loss or damage arising therefrom, including the cost of repairing damage, breakdown, malfunction caused by corrosion, furring, pipe scaling, limescale, system debris or frost.
TRITON reserve the right to change product specification without prior notice. E&OA. © TRITON SHOWERS 2008
Extended Warranty AVAILABLE NOW. Call 0870 067 3333 for more details.
Customer Service: % 0870 067 3333
Scottish and Northern Ireland
Customer Service: % 0845 762 6591
Trade Installer Hotline: % 0870 067 3767
Fax: 0870 067 3334
www.tritonshowers.co.uk
E mail: technical@tritonshowers.co.uk
Service Policy
In the event of a product fault or complaint occurring, the following procedure should be followed:
1 Telephone Customer Service on 0870 067 3333 (0845 762 6591
in Scotland and in Northern Ireland), having available, your details including post code, the model number and power rating of the product, together with the date of purchase.
2 Based on information given over the telephone, a Triton Customer
Service Advisor will attempt to diagnose the fault and confirm whether a site visit from a qualified service engineer is required.
3 All products attended to by a Triton service engineer must be
installed in full accordance with the Triton installation guide applicable to the product. (Every product pack contains an installation guide, however, they can also be bought via our Customer Service Spares Department).
4 Our engineer will require local parking and if a permit is required
this must be available to the engineer on arrival at the call.
5 It is essential that you or an appointed representa-tive (who must
be over 18 years of age) is present for the duration of the service engineer's visit. If the product is in guarantee you must produce proof of purchase.
6 Where a call under the terms of guarantee has been booked
and the failure is not product related (i.e. scaling and fur-ring, incorrect water pressure, pressure relief device operation or electrical/plumbing installation fault) a charge will be made. A charge will also be issued if nobody is at home when the service engineer calls or adequate parking/permit is not available.
7 If the product is no longer covered by the guarantee an up front
fixed fee will be charged before the site visit.
8 Should proof of purchase not be available on an “in-guarantee”
call, or should the service engineer find that the product is no longer under guarantee, the engineer will charge the same fixed price and the customer will be expected to pay the engineer before he leaves. If payment is not made on the day an administration charge will be added to the fixed charge.
9 If a debt is outstanding from a previous visit, or from any other
Triton purchase, Triton reserves the right to withhold service until the debt has been settled.
10 Triton takes the health, safety and wellbeing of its employees very
seriously and expects customers to treat all staff members with respect. Should any employee feel threatened or receive abuse, either verbally or physically, Triton reserves the right to withhold service and will support the employee with a legal prosecution.
Replacement Parts Policy
Availability: It is the policy of Triton to maintain availability of parts for the current range of products available and for a period of five years and thereafter in accordance with industry standards.
Spare parts are available via our website, www.tritonshowers.co.uk, or by telephoning Triton Customer Service Spares Department. Payment should be made by credit/debit card (excluding American Express or Diners Card).
Payment can also be made by pre-payment of a pro forma invoice by cheque or money order.
Loading...