Guarantee, service policy, etc. ...................................................rear cover
WARNING
This appliance can be used by children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience or knowledge if
they have been given supervision or instruction concerning use of the appliance in a safe
way and understand the hazards involved. Children may not play with the appliance.
Cleaning and user maintenance shall not be made by children without supervision.
To check the product suitability for commercial and multiple installations, please contact Triton’s
specification advisory service before installation.
Telephone:
Facsimile:
0844 980 0730
0844 980 0744
E mail:
technical@tritonshowers.co.uk
IVORY 4 electric shower
before connecting to the shower unit.
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
Products manufactured by Triton are safe and without risk provided they are installed, used and
maintained in good working order in accordance with our instructions and recommendations.
WARNING:DO NOT operate shower if frozen, or suspected of being frozen. It must thaw out
before using.
DO NOT operate the unit if the showerhead or spray hose becomes damaged.
DO NOT restrict flow out of shower by placing showerhead in direct contact with your body.
DO NOT operate the shower if water ceases to flow during use or if water has entered inside
the unit because of an incorrectly fitted cover.
WARNING: If restarting the shower immediately after stopping, be aware that a slug of
hot water will be expelled for the first few seconds.
1 GENERAL
1.1 Isolate the electrical and water supplies before
removing the cover.
1.2 Read all of these instructions and retain them
for later use.
1.3 DO NOT take risks with plumbing or electrical
equipment.
1.4 Isolate electrical and water supplies before
proceeding with the installation.
1.5 The unit must be mounted onto the finished
wall surface (on top of the tiles). DO NOT tile
up to or seal around ANY PART of the unit
using silicone sealer after fixing to the wall.
Special care must be taken NOT TO BLOCK OR SEAL ANY PRD VENTS ON THE UNIT.
1.6 Contact Customer Service (see back page), if
any of the following occur:
a) If it is intended to operate the shower at
pressures above the maximum or below the
minimum stated.
b) If the unit shows a distinct change in performance.
c) If the shower is frozen.
1.7 If it is intended to operate the shower in areas
of hard water (above 200 ppm temporary
hardness), a scale inhibitor may have to be
fitted. For advice on the Scale Inhibitor,
contact Customer Service.
1.8 The showerhead must be cleaned regularly
with descalent to remove scale and debris,
otherwise restrictions to the flow on the outlet
of the unit will result in higher temperatures
and could also cause the (PRD) Pressure Relief
Device in the unit to operate.
1.9 This product is not suitable for mounting into
steam rooms or steam cubicles.
PLUMBING
2
2.1 The plumbing installation must comply with
Water Regulations, Building Regulations or any
particular regulations as specified by Local
Water Company or Water Undertakers and
should be in accordance with BS EN 806.
2.2 The supply pipe must be flushed to clear debris
2.3 DO NOT solder pipes or fittings within 300mm
of the shower unit, as heat can transfer along
the pipework and damage components.
2.4 DO NOT fit any form of outlet flow control as
the outlet acts as a vent for the heater can.
2.5 DO NOT use excessive force when making
connections to the flexible hose or
showerhead, finger tight is sufficient.
2.6 All plumbing connections must be completed
before making the electrical connections.
2.7 This appliance MUST not be connected to the
inlet supply by a hose-set.
3
ELECTRICAL
3.1 The installation must comply with BS 7671
‘Requirements for electrical installations’ (IEE
wiring regulations), building regulations or any
particular regulations as specified by the local
Electrical Supply Company.
3.2 This appliance MUST be earthed.
3.3 In accordance with ‘The Plugs and Sockets etc.
(Safety) Regulations 1994’, this appliance is
intended to be permanently connected to the
fixed wiring of the electrical mains system.
3.4 Make sure all electrical connections are tight to
prevent overheating.
3.5 A 30mA residual current device (RCD) MUST
be installed in all UK electric and pumped
shower circuits. This may be part of the
consumer unit or a separate unit.
3.6 Switch off immediately at isolating switch if
water ceases to flow during use.
3.7 Other electrical equipment i.e. extractor fans,
pumps must not be connected to the circuits
within the unit.
3.8 Switch off at isolating switch when not in use.
This is a safety procedure recommended with
all electrical appliances.
3.9 As with all electrical appliances it is
recommended to have the shower and
installation checked at least every two years by
a competent electrician to ensure there is no
deterioration due to age and usage.
1
IVORY 4 electric shower
INTRODUCTION
This book contains all the necessary fitting and
operating instructions for your Triton electric
shower. Please read them carefully.
The shower installation must be carried out by a
suitably qualified person and in the sequence of
this instruction book.
Care taken during the installation will provide a
long, trouble-free life from your shower.
SPECIFICATIONS
Electrical
Nominal power Nominal power
rating at 240V rating at 230V
Backplate, cover, controls, showerhead – ABS.
Sprayplate – Acetal.
Elements – Minerally insulated corrosion resistant
metal sheathing.
Dimensions
Height – 300 mm
Width – 220 mm
Depth – 100 mm
Standards and Approvals
Splashproof rating IPX4.
Complies with the requirements of current British
and European safety standards for household and
similar electrical appliances.
Meets with Compliance with European
Community Directives (CE).
Replacement parts can be ordered from Triton Customer
Service. See ‘spare parts’ for details and part numbers.
ADVICE TO USERS
The following points will help you understand
how the shower operates:
IMPORTANT: When first installed the unit
will be empty. It is essential the unit should
contain water before the elements are
switched on. It is vital that the commissioning procedure is followed. Failure to carry
out this operation will result in damage to
the unit and will invalidate the guarantee.
a. The electric heating elements operate at a
constant rate at your chosen power setting.
It is the rate of the water passing through
the heater can which determines the water
temperature. (The slower the flow, the hotter
the water becomes; the faster the flow, the
cooler the water.)
b. During winter the mains water supply will
be cooler than in the summer, so the flow
rate will vary between seasons at any one
temperature setting. At different times of the
year you may have to adjust the position of
the temperature control to maintain your
desired temperature setting.
c. The stabiliser valve minimises variations in
shower temperature during mains water
pressure changes. If changes in shower
temperature are experienced during normal
use, it will most likely be caused by the water
pressure falling near to or below the minimum
level. The drop in pressure may be due to
water being drawn off at other points in the
house while the shower is in use. If pressure
drops appreciably below the minimum, the
heating elements will automatically cut out.
If ever the water becomes too hot and you
cannot obtain cooler water, first check that
the sprayplate in the showerhead has not
become blocked.
DO NOT place items such as soap or shampoo
bottles on top of the unit. Liquid could seep
through the joint between the cover and backplate
and possibly damage the sealing rubber.
2
IVORY 4 electric shower
MAIN COMPONENTS
Inside unit (fig.1)
1. Top cable/water entry
2. Wall screw fixing
3. Terminal block
4. Power selector
5. Stabilising valve
6. Solenoid valve
7. Can and element assembly
8. Thermal cut-out - TCO
9. Earth connection
10. Outlet pipe
11. Start/Stop micro switch
- Pressure relief device
(see page 20)
Cover (fig.2)
12.Ivory 4 front cover
Fig.1
NOTE: Not all wiring shown for reasons of clarity
1
11
9
3
2
2
8
4
7
5
6
2
10
Inlet
Outlet
Fig.2
12
3
Meter
Incoming
supply
fuse
Meter
tails
Consumer
unit
Pull cord
isolating switch
Shower
unit
Fuse or
MCB
RCD
(can be part of
consumer unit)
80A or 100A
main switch
MCB
30/32A
32A
40A
40A
40A
40/45A
45A
cartridge
fuse
30A
35A
35A
45A
45A
45A
45A
unit
rating
7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW
10.5kW
CIRCUIT PROTECTION
ELECTRICAL REQUIREMENTS
Triton Showers,
Triton Road, Nuneaton,
Warwickshire, CV11 4NR
xxxx
WARNING!
THIS APPLIANCE MUST BE EARTHED
The installation, supply cable and circuit
protection must conform with BS 7671 (IEE
wiring regulations) and be sufficient for the
amperage required.
The following notes are for guidance only:
1 The shower must only be connected to a
230-240V ac supply. If you are installing a
shower with a kilowatt rating above 9kW, it
is advisable to contact the local electricity
supply company.
1.1 The electrical rating of the shower is shown
on the rating label (Fig.3) within the unit.
2 Before making any sort of electrical
connection within the installation make
sure that no terminal is live. If in any doubt,
switch off the whole installation at the mains
supply and remove the correct fuse.
3 The shower must be connected to its own
independent electrical circuit. IT MUST NOT
be connected to a ring main, spur, socket
outlet, lighting circuit or cooker circuit.
3.1 The electrical supply must be adequate for
the loading of the unit and existing circuits.
4 Check your consumer unit (main fuse box)
has a main switch rating of 80A or above
and that it has a spare fuse way which will
take the fuse or Miniature Circuit Breaker
(MCB) necessary for the shower (Fig.4).
4.1 If your consumer unit has a rating below
80A or if there is no spare fuse way, then the
installation will not be straightforward and
may require a new consumer unit serving
the house or just the shower.
4.2 You will need to contact the local electricity
company. They will check the supply and
carry out what is necessary.
5 For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated
Miniature Circuit Breaker (MCB) or cartridge
fuse (see Table A).
5.1 A 30mA residual current device (RCD)
MUST be installed in all UK electric and
pumped shower circuits. This may be part of
the consumer unit or a separate unit.
W-006-A
IVORY 4 electric shower
Fig.3
Fig.4 Schematic of installation circuit
Table A
4
IVORY 4 electric shower
Note: Cable selection is dependent on
derating factors
Twin and earth PVC insulated cable
Current carrying capacity
In conduit
trunking
6mm²
38A
10mm²
52A
16mm²
69A
Installed in an
insulated wall
6mm²
32A
10mm²
43A
16mm²
57A
Clipped direct
or buried in a
non-insulated
wall
6mm²
46A
10mm²
63A
16mm²
85A
6 A 45 amp double pole isolating switch with
a minimum contact gap of 3 mm in both
poles must be incorporated in the circuit.
6.1 It must have a mechanical indicator showing
when the switch is in the OFF position, and
the wiring must be connected to the switch
without the use of a plug or socket outlet.
6.2 The switch must be accessible and clearly
identifiable, but out of reach of a person
using a fixed bath or shower, except for the
cord of a cord operated switch, and should
be placed so that it is not possible to touch
the switch body while standing in a bath or
shower cubicle. It should be readily accessible
to switch off after using the shower.
7 Where shower cubicles are located in any
rooms other than bathrooms, all socket
8 The current carrying capacity of the cable
8.1 To obtain full advantage of the power
8.2 It is also necessary to satisfy the disconnection
outlets in those rooms must be protected by
a 30mA RCD.
must be at least that of the shower circuit
protection (see Table B).
provided by the shower, use the shortest
cable route possible from the consumer unit
to the shower.
time and thermal constraints which means
that for any given combination of current
demand, voltage drop and cable size, there is
a maximum permissible circuit length.
9 The shower circuit should be separated from
other circuits by at least twice the diameter
of the cable or conduit.
9.1 The current rating will be reduced if the
cabling is bunched with others, surrounded
by thermal loft or wall insulation or placed
in areas where the ambient temperature
is above 30°C. Under these conditions,
derating factors apply and it is necessary to
select a larger cable size.
9.2 In the majority of installations, the cable
will unavoidably be placed in one or more
of the above conditions. This being so, it is
strongly recommended to use a minimum
of 10mm cabling throughout the shower
installation.
9.3 In any event, it is essential that individual
site conditions are assessed by a competent
electrician in order to determine the correct
cable size and permissible circuit length.
Table B
*The method below may be used by
installers to determine the approximate
size of the incoming cable.
6mm
2
10mm
2
16mm
2
1. Measure the width of an individual strand,
and half that measurment to find (r),
e.g: 1.34mm ÷ 2 = (r) 0.67mm
2. Multiply (r) x (r) x 3.14,
e.g: (r)0.67 x (r)0.67 x 3.14 = 1.41mm
3. Multiply this by the number of wire strands
(usually 7), e.g: 1.41mm2 x 7 = 9.87mm2.
4. The number obtained would suggest
10mm2 wiring.
*PLEASE NOTE: If unsure, consult a qualified Electrician.
2
5
IVORY 4 electric shower
Isolating
stopvalve
Mains
water
supply
Shower
unit
Switch may
be wall
mounted
in accordance
with IEE regs.
Mains electric supply
(via double pole switch)
Double
pole
isolating
switch
Separate permanently
connected supply
from consumer unit
WATER REQUIREMENTS
The installation must be in accordance with Water Regulations/Bylaws.
Supply Source .......................................................... Mains pressure cold water
*Minimum running pressure and flow to 100kPa (1.0 bar) at 8 litres per minute
the inlet of the shower for full performance for 7.5Kw - 8.5Kw - 9.5Kw
*Minimum running pressure and flow to 150kPa (1.5 bar) at 11 litres per minute
the inlet of the shower for full performance for 10.5Kw
Maximum static pressure .........................................1000 kPa (10 bar)
Maximum inlet temperature ....................................28°C
Minimum inlet temperature ..................................... 2°C
* Note: the shower will continue to operate on
a reduced heat setting if the running pressure
falls to 0.7 bar (1.2 bar for 10.5kW), there
will be a noticeable reduction in flow and
temperature from the showerhead.
If the stated flow rates are not available, it
may not be possible to achieve optimum
performance from the unit throughout the year.
During periods of high ambient temperatures
it may be necessary to select the economy
power setting to achieve your preferred shower
temperature.
.............
.............
*Fig.5
*(diagrammatic view – not to scale)
Fig.5 shows a typical system layout.
Do not use jointing compounds on any pipe
fittings for the installation.
6
IVORY 4 electric shower
SITING OF THE SHOWER
IMPORTANT: If installing onto a tiled wall
always mount the unit on the surface of the
tiles. NEVER tile up to the unit.
Refer to (fig.6) for the correct siting of the
shower. Position the unit where it will NOT be in
direct contact with water from the showerhead.
Position the shower unit vertically.
Allow enough room between the ceiling and the
shower to access the cover top screws. Leave
enough space between the right-hand side of the
unit and the wall to allow access to the pressure
relief device (PRD) in the future.
Note: Water regulations require the showerhead
be ‘constrained by a fixed or sliding attachment
so that it can only discharge water at a point not
less than 25mm above the spill-over level of the
relevant bath, shower tray or other fixed appliance’.
The use of the gel hanger/hose guide (if supplied)
will in most cases meet this requirement, but if the
showerhead can be placed within a bath, basin or
shower tray, then a double check valve, or similar,
MUST be fitted in the supply pipework to prevent
back-flow.
Pressure relief device - PRD
A pressure relief device (PRD) is designed into
the shower unit which complies with European
standards. The PRD provides a level of appliance
protection should an excessive build up of pressure occur within the shower.
Do not operate the shower with a damaged or
kinked shower hose, or a blocked showerhead
which can cause the PRD to operate.
When commissioning, the showerhead must
be removed from the flexible hose, while at the
same time the temperature control must be at
the minimum flow position. Failure to follow this
procedure may also cause the PRD to operate.
Make sure the shower is positioned over a bath
or shower tray because if the PRD operates, then
water will eject from the bottom of the unit.
Should this happen, turn off the electricity and
water supplies to the shower at the isolating
switch and stopvalve. Contact Customer Service
for advice on replacing the PRD.
WARNING!
The shower must not be positioned
where it will be subjected to freezing
W-008-A
conditions.
Shower unit can
be mounted either
side of riser rail
Height of
showerhead
and shower
to suit user's
requirement
Shower unit
must not
be within
an area
1 metre
from base
Spillover
level
*Fig.6
25 mm minimum
Outline of bath
or shower tray
*(diagrammatic view – not to scale)
IMPORTANT: The unit must be mounted on
a flat surface which covers the full width
and length of the backplate. It is important
that the wall surface is flat otherwise
I-002-A
difficulty may be encountered when fitting
the cover and subsequent operation of the
unit may be impaired.
7
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.