Tripp Lite SmartOnline Rackmount UPS Systems with interactive LCD interface feature online, double-conversion UPS protection with fulltime sinewave output and zero transfer time suitable for all advanced networking applications. Each system provides long running battery
support with optional extended-run and Web communications ability. Built-in interfaces include USB, RS-232 serial and Emergency
Power Off (EPO). The interactive front panel LCD screen provides detailed UPS status, preset and control options. Optional max efficiency
and auto-adaptive power strategy options enable high-efficiency operation with reduced power consumption and BTU heat output.
*Visit the specification page for your UPS system at tripplite.com for detailed extended runtime data and additional accessory options.
** For External battery configuration, see the Operations section for options and configuration method. SMART battery packs are automatically detected by the UPS.
BP24V36-2USBP36V27-2USBP48V27-2USBP72V18-2US
BP24V15RT2U (limit 1)
BP24V28-2U (limit 1)
BP24V70-3U
BP36V15-2U (limit 1)
BP36V42-3U
BP48V24-2U (limit 1)
BP48V60RT3U
BP72V15 (limit 1)
BP72V28RT3U
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the installation, operation and storage of all
Tripp Lite UPS Systems. Failure to heed these warnings may affect your warranty.
UPS Location Warnings
• Install your UPS indoors, away from excess moisture or heat, conductive contaminants, dust or direct sunlight.
• For best performance, keep the indoor temperature between 0º C and 40º C.
• Leave adequate space around all sides of the UPS for proper ventilation.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the
unit’s internal cooling, eventually causing product damage not covered under warranty.
2
Important Safety Instructions
UPS Connection Warnings
• Connect your UPS directly to a properly grounded AC power outlet. Do not plug the UPS into itself; this will damage the UPS.
• Do not modify the UPS's plug, and do not use an adapter that would eliminate the UPS’s ground connection.
• Do not use extension cords to connect the UPS to an AC outlet. Your warranty will be voided if anything other than Tripp Lite surge
protectors are used to connect your UPS to an outlet.
• If the UPS receives power from a motor-powered AC generator, the generator must provide clean, filtered, computer-grade output.
• The mains socket outlet that supplies the UPS should be near the UPS and be easily accessible.
• To remove AC voltage from the UPS, pull the plug from the socket outlet.
Equipment Connection Warnings
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of
the life support equipment or to significantly affect its safety or effectiveness is not recommended.
• Do not connect surge protectors or extension cords to the output of your UPS. This might damage the UPS and may affect the surge
protector and UPS warranties.
• Connect the UPS to an outlet that is adequately protected against excess currents, short circuits and earth faults, as part of the
building installation. The outlet protection for the UPS should be in series with the mains input.
• To reduce the risk of fire, connect only to a circuit that has branch circuit over current protection with an ampere rating in accordance
with the National Electrical Code® (NEC®), ANSI/NFPA 70 or your local electrical code. In Europe, the circuit breaker must meet the
IEC/EN 60934 standard and have a contact air gap of at least 3 mm. The recommended circuit breaker rating for building installation
is 240V/20A and must meet the rated short circuit capacity of at least 1 KA.
Battery Warnings
• Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of
the batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn
off the UPS before performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside the
UPS. Battery replacement should be performed only by authorized service personnel using the same number and type of batteries
(Sealed Lead-Acid). The batteries are recyclable. Refer to your local codes for disposal requirements or visit tripplite.com/
UPSbatteryrecycling for recycling information. Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges
(R.B.C.).Visit Tripp Lite on the Web at tripplite.com/support/battery/index.cfm to locate the specific replacement battery for your UPS.
Note: For External battery configuration, see the Operations section for options and configuration method. SMART BATTERY PACKS are automatically detected by the UPS.
UPS Circuit Block Diagram
3
Installation
Rack Mounting
Mount your equipment in either a 4-post or 2-post rack or rack enclosure. The user must determine the fitness of hardware and
procedures before mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or
rack enclosure. The procedures described in this manual are for common rack and rack enclosure types and may not be appropriate for
all applications.
4-Post Mounting
1
The included plastic pegs A will temporarily support the empty
rackmount shelves B while you install the permanent
mounting hardware. Insert a peg into the third hole from the
top on the front end of each bracket. On the rear end, insert a
peg into the center hole. (Each front bracket has 6 holes and
each rear bracket has 5 holes.) The pegs will snap into place.
After installing the pegs, expand each shelf to match the depth
of your rack rails. The pegs will fit through the square holes in
the rack rails to support the shelves. Refer to the rack unit
labels to confirm that the shelves are level in all directions.
Note: The support ledge of each shelf must face inward.
2
Remove the pegs at the front end of each bracket. Secure the
shelves B to the mounting rails permanently using the
included screws and cup washers C as shown. Place 2 screws
at the front of each rail (4 total) and 2 screws at the back of
each rail (4 total). Tighten all screws before proceeding.
Note: The rear pegs can be left in for installation, but the front ones must be
removed before the bracket is secured by screws.
WARNING!
Do not attempt to install your UPS until you have inserted and tightened the required screws. The plastic
pegs will not support the weight of your UPS.
1
2
A
B
A
C
B
C
3
Attach your UPS’s mounting brackets D to the forward
mounting holes E of the UPS using the included hardware F.
The mounting bracket “ears” should face forward.
E
D
3
4
With the aid of an assistant (if necessary), lift your UPS and
slide it into the shelves. Attach the UPS mounting brackets to
the forward mounting rails with user-supplied screws and
washers G. Tighten all screws securely.
G
4
G
2-Post Mounting
If you mount 2U UPS models in 2-post racks, they require the addition of a Tripp Lite 2-Post Rackmount Installation Kit (model:
2POSTRMKITWM, sold separately). See Installation Kit owner’s manual for installation procedure.
F
4
Installation
Tower Mounting
Your UPS can be mounted in an upright tower position with
optional base stands sold separately by Tripp Lite (model:
2-9USTAND). When mounting the UPS on adjustable base stands,
make sure that the control panel is toward the top. The control
panel may be rotated to make it easier to read. Remove the 4
front screws from the front panel and take it off. Pinch the tabs
located on the sides of the LCD panel, and then rotate it. Replace
the front panel and secure it. Front panel setup should be
operated by service personnel only.
WARNING!
All UPS systems are extremely heavy. Use caution when
lifting and mounting. User must properly stabilize the UPS
when lifting and mounting.
8.6 x 43.8 x 39.6 cm8.6 x 43.8 x 49.6 cm8.6 x 43.8 x 49.6 cm8.6 x 43.8 x 61.6 cm
5
2
1
Installation
Smart Battery Communications Connection
Your UPS supports automatic detection of its internal batteries and up to 6 external SMART BATTERY PACKS. Prior to powering up the
UPS from AC mains power, you must connect the internal SMART BATTERY communication cable in the following manner:
1
Remove the 4 front screws from the front bezel and take it off.
12
2
Loosen the 2 screws securing the front plate.
3
Open the front plate.
3
5
Tighten the 2 screws to secure the front plate.
4
Connect the SMART BATTERY communication cable. Close the
front plate.
4
6
Replace the 4 front screws to secure the bezel.
56
EXTERNAL BATTERY CONFIGURATION NOTE
If external battery packs are to be used with this UPS, install them following the mounting/installation documentation included with each
battery pack. External battery pack installation requires the UPS be configured one of two ways:
1. Via the UPS front panel LCD interface
2. Via Tripp Lite’s EXTERNAL BATTERY CONFIGURATION software
This UPS is factory programmed with discharge curves and charging profiles for external battery pack configurations accessible using the
UPS front panel LCD interface. Additional battery pack options using larger or multiple external battery packs are also supported, but
require configuration using Tripp Lite’s EXTERNAL BATTERY CONFIGURATION software and a serial port connection to the UPS.
6
Basic Connection and Start-Up
Quick Start Guide - First Time UPS Power-On
1
Plug your UPS line cord into an electrical outlet
Your UPS must be connected to a dedicated circuit of sufficient
amperage.
Refer to the rating table labelled on the UPS for more details.
1
2
Select your Language
When your UPS is plugged in for the first time, the INPUT AC
LED will light up and the front panel LCD screen will request a
language selection.
Using the UP / DOWN buttons
preference, then press the NEXT
The interface will confirm your selection and provide options to
go back (press BACK
(press NEXT
ESC
) or to go to the next step
).
, select your language
button.
Language
English
BackNext
SETUP
ESC
2
4
Select your Password
Next, the UPS will prompt you to pick the desired PASSWORD.
Using the UP / DOWN
your desired password and press the NEXT
advance to the second digit. Repeat for digits 2 through 4.
Note: To quickly set the password to “0 0 0 0” press the NEXT button 4 times.
buttons, select the first digit of
button to
3
Select your Power Strategy
Next, the UPS will prompt you to pick the desired POWER
STRATEGY.
Using the UP / DOWN
STRATEGY preference and press the APPLY
See the Power Strategy Selection Options and UPS
Operating Modes sections under the Operations section for
operating characteristics of each power strategy.
buttons, select your POWER
button.
Power Strategy
Auto-Adaptive
Max Efficiency
Max Quality
Freq. Regulation
Freq. Conv. To 60Hz
Freq. Conv. To 50Hz
Back Select Apply
SETUP
ESC
3
5
Select UPS Output Voltage
Next, the UPS will prompt you to select the desired OUTPUT
VOLTAGE.
Using the UP / DOWN
voltage, then select APPLY
buttons, select the UPS output
.
Password Setup
0 0 0 0
Back Select Next
SETUP
ESC
4
Output Voltage
200 Vac
208 Vac
220 Vac
230 Vac
240 Vac
Back Select Apply
SETUP
ESC
5
7
Basic Connection and Start-Up
6
Select UPS Battery Age Alert
Next, the UPS will prompt you to select the timing of the
BATTERY AGE ALERT.
Using the UP / DOWN
battery age alert in months, then press APPLY
buttons, select the timing of the
.
Batt Age Alert
Months:36
Back Select Apply
SETUP
ESC
6
7
Select Audible Alarm ENABLE / DISABLE status
Next, the UPS will prompt you to select the alarm ENABLE /
DISABLE status.
Using the UP / DOWN
DISABLE status, then press APPLY
Note: Disabling the alarm prevents the audible alarm from sounding during
power failures and UPS fault conditions only. The alarm will still “chirp” to
confirm operator input via the front panel LCD navigation buttons when the alarm
is set to disable.
buttons, select the alarm ENABLE /
.
Audible Alarm
Enabled
Disabled
Back Select Apply
SETUP
ESC
7
8
Plug your equipment into the UPS
Your UPS is designed to support network, server and computer
equipment only.
Your model and outlet may differ.
8
9
Turn your UPS on
Press and hold the POWER
release as the alarm begins to sound.
button for 3 seconds and
9
The UPS will then go through a series of diagnostic checks
before turning on output power. Once the UPS reports the
operating status of NORMAL / LOAD PROTECTED with the
configured POWER STRATEGY enabled, your UPS can
immediately be put into service to provide reliable protection
from a wide variety of power problems.
8
Features
Before installing and operating your UPS, familiarize yourself with the locations and function of the features of each component.
Front Panel Controls, LEDs and LCD Screen
The graphical LCD on the front panel contains a wide range of UPS
operating conditions and diagnostic data. It also displays UPS
settings and options when viewing the UPS setup screens. The five
buttons below the LCD can be used to navigate the various
information, configuration and UPS control screens by following the
on-screen prompts and selection options. Additional LED indicators
above the LCD screen also provide at-a-glance status of AC input
source, availability of output, battery status, and warning/fault status.
See Operations section for detailed descriptions of LCD functions,
buttons and LEDs.
Rear Panel Features
1
Input Cord Connection: This connects to AC power via a user-supplied cord with country-specific plug or permanently attached
power cord.
2
AC Receptacles (varies by model): These output receptacles provide connected equipment with pure sine-wave AC output during
normal operation and battery power during blackouts and severe brownouts. Power provided by these outlets is filtered to protect
connected equipment against damaging surges and line noise. The receptacles are divided into numbered load banks, as labeled on
the unit. Using PowerAlert software and cabling, load banks one and two may be individually turned off and on from a remote
location, allowing users to reset or reboot connected equipment.
3
Telephone or Telephone/Network Protection Jacks: These jacks protect your equipment against surges over a telephone line or
telephone/network data line. Connecting your equipment to these jacks is optional. Your UPS will work properly without this
connection.
Note: Not compatible with PoE (Power Over Ethernet) applications.
4
Communications Ports (USB or RS-232): These ports connect your UPS to any workstation or server. Use with Tripp Lite’s
PowerAlert Software and included cables to enable your computer to automatically save open files and shut down equipment during
a blackout. Also use PowerAlert Software to monitor a wide variety of AC line power and UPS operating conditions. Consult your
PowerAlert Software manual or contact Tripp Lite Customer Support for more information. The 9-pin RS-232 port also supports drycontact communications. See USB & RS-232 Serial Communications in the Optional Connections section for installation
instructions.
5
EPO (Emergency Power Off) Port: Your UPS features an EPO port that may be used to connect the UPS to a contact closure
switch to enable emergency inverter shutdown. See Optional Connections section for details.
6
Accessory Slot: Remove the small cover panel from this slot to use optional accessories to remotely monitor and control your UPS.
Visit tripplite.com to see a full list of accessories, including the WEBCARDLX for remote control and UPS monitoring, as well as a
wide variety of network management and connectivity products.
7
External Battery Pack Connector (configuration varies by model): Your UPS supports the use of optional Tripp Lite external
battery packs for additional runtime. See Model Specific Accessories section under the Overview section for compatible models
and limitations and Configuring External Battery Packs section under Operations section for configuration instructions.
Note: External battery pack options require configuration using front panel LCD interface or via Tripp Lite’s EXTERNAL BATTERY CONFIGURATION software.
8
Ground Screw: Use this to connect any equipment that requires a chassis ground.
9
External Battery Detection Port: For external batteries with communication built-in, plugging the battery communication cable
into this port will allow the UPS to automatically detect the external battery.
9
Features
SUINT1000LCD2U
8
SUINT1500LCD2U
8
SUINT2200LCD2U
29
1
1
1
2
2
2
2
9
9
7
7
3
4
56
3
4
5
6
3
8
SUINT3000LCD2U
8
SU3000LCD2UHV
2
2
2
15
2
23
7
9
7
9
3
4
5
6
4
6
4
8
6
2
1
10
57
Operations
This section explains how to use your Tripp Lite Online UPS System, including front-panel LCD operation, operating modes, UPS startup
and shutdown, transferring between modes, setting power strategy, and configuring bypass settings, load segments and battery settings.
LCD Front-Panel Display and Controls
There is a 5 button graphical LCD screen with additional LED indicators on the front of the UPS that provides information on UPS status,
load level information, event information, measurements, settings and a wide variety of UPS configuration and power strategy options.
AC Output LED (Green)Battery Mode LED (Yellow)
AC Input LED (Green)
LCD Screen
Fault LED (Red)
Escape
Page Up/Page Down
On/Off
Enter
LED Front Panel Indicators
There are 4 LEDs above the front panel LCD screen that offer information on AC INPUT, BYPASS, AC OUTPUT, BATTERY MODE and UPS
FAULT status.
AC INPUT indicator
On AC input is available AND AC input is WITHIN the configured ECONOMY / BYPASS mode range.
When this LED is ON SOLID, AC input is of adequate quality for UPS operation in BYPASS or ECONOMY MODE.
Flashing AC input is available AND AC input is OUTSIDE the configured BYPASS mode range.
When this LED is ON FLASHING, AC input is not of adequate voltage or frequency for UPS operation in BYPASS or
ECONOMY MODE.
Off AC input is NOT available.
When this LED is OFF, AC input is not available.
AC OUTPUT indicator
On UPS AC output is ON
UPS output is available at the UPS output receptacles.
Off UPS AC output is OFF
UPS AC output is not available.
BATTERY MODE indicator
On UPS is running in battery mode
UPS batteries are discharging as the UPS runs in battery mode. Also lights momentarily during self-test operation.
Flashing UPS is running in battery mode - Low battery warning
UPS batteries are discharging as the UPS runs in BATTERY mode and are becoming low. The indicator will flash at
2 second intervals to report LOW BATTERY and 0.5 second intervals to report BATTERIES ARE NEAR FULLY
DISCHARGED and the UPS is near shutdown.
UPS FAULT indicator
On UPS is experiencing a pre-defined fault state
See front panel display for explanation of error state or code information. See on-screen instructions and manual
for troubleshooting tips.
Off Normal
UPS is not reporting fault conditions when this indicator is OFF.
11
Operations
Front Panel Button Functions
There are 5 front panel buttons that offer UPS control and configuration options. To navigate the various information, configuration and
UPS control screens, use the 5-button front panel interface and follow the on-screen prompts and selection options.
Power On / Off Button: This control offers three main functions: Power-On, Power-Off and Clear UPS Fault.
To turn the UPS ON into a protected operating mode, press and hold this button for 3 seconds as the UPS is connected to
input AC power. Release the button when the alarm begins to sound and the UPS will startup into the last configured power
strategy.
To “cold start” the UPS on into battery mode during power failure conditions, press and hold this button for 3 seconds.
Release the button when the alarm begins to sound and the UPS will startup in battery mode.
To turn the UPS OFF as it’s running in battery or protected mode, press and hold this button for 3 seconds. Release the
button when the alarm begins to sound. The UPS will turn off AC output. Once AC output is off, disconnect input power to the
UPS and the UPS will power off completely.
To CLEAR UPS FAULT, press and hold this button as directed on-screen for 3 seconds. The UPS will clear the fault conditions
and return to standby or bypass mode.
ENTER Button: This control is used to make selections, confirm options and move forward to the next selection as the UPS is
configured in setup mode. Press this button as directed on-screen in Setup mode to Enter, Confirm or Move Forward in the
configuration process.
UP / DOWN Buttons: These controls offer two main functions: “Up” and “Down” directional control, plus enter / exit setup
mode (when pressed simultaneously). These buttons are used to navigate setup-mode menu options and scroll up or down to
view screen contents as necessary.
To ENTER or EXIT UPS SETUP MODE, press these two buttons simultaneously for 3 seconds. Release the button when the
alarm begins to sound. The UPS will automatically enter setup mode if both buttons are pressed during LCD display modes.
The UPS will automatically exit setup mode if both buttons are pressed as the UPS runs in UPS setup mode.
ESCAPE Button: This control offers three main functions: Alarm Cancel, Clear Fault and Back / Cancel operations.
To CANCEL UPS ALARM, press this button. If a new alarm condition occurs, the alarm will sound again.
To CANCEL or GO BACK ONE LEVEL, press this button as directed on-screen in Navigation and Setup modes.
Home Screen Layout
The UPS front panel LCD screen is set up to provide continuous UPS operating information using NORMAL MODE and BATTERY MODE
home-screens that continuously report operating mode, protection status, power strategy and a number of battery and load-level
operating parameters.
Normal Mode Home Screens
Operating ModeProtection Status
Online
<Battery> <Load>
Battery Charge %Output Load %
Battery Charge
“Bars”
Battery Voltage
Power Strategy
0.5 KW
0.5 KVA26.1VDC
Max Efficiency
SETUP
ESC
Load Protected
<Battery> <Load>
0.5 KW
0.5 KVA26.1VDC
Enabled
SETUP
ESC
Output Load
(Kilowatts)
Output Load
(KVA)
Output Load
“Bars”
Power Strategy
(Continued)
12
Operations
Power Strategy Selection Options
Tripp Lite SmartOnline LCD UPS systems offer several built-in power strategy options that enable the UPS to optimize performance to
meet user needs for MAXIMUM POWER QUALITY, MAXIMUM EFFICIENCY, and FREQUENCY REGULATION or FREQUENCY CONVERSION
operation. An additional AUTO-ADAPTIVE power strategy combines the benefits of high-efficiency and maximum power quality. Each
power strategy option enables the UPS to automatically shift between specific operating modes as power and UPS status dictates.
Available power strategy options include:
• Auto-Adaptive Power Strategy enables the UPS to automatically switch between ONLINE MODE and ECONOMY MODE as dictated by
the quality and reliability of UPS input power. If the UPS does not experience a power failure in a week’s time (not including UPS selftest) the UPS will automatically switch to ECONOMY MODE. If a power failure occurs, the UPS will maintain output in BATTERY MODE.
When power is restored, the UPS will repeat the cycle by running in ONLINE MODE until there are no power failures for one week’s
time.
• Max-Efficiency Power Strategy enables the UPS to run continuously in ECONOMY MODE anytime incoming AC power is within the
configured bypass low/high voltage range. If UPS input voltage is outside the configured bypass range, the UPS will automatically
switch to ONLINE MODE until AC input voltage is restored within the configured bypass voltage range. This is similar to Auto-Adaptive
Power Strategy, except transfer to ECONOMY MODE is immediate as voltage levels recover. There is no one-week time period of power
failure free operation required in order for the UPS to return to ECONOMY MODE operation.
• Max-Quality Power Strategy enables the UPS to run continuously in ONLINE MODE the entire time incoming AC power is within the
range for online mode operation. The UPS will remain operating continuously in Online Double-Conversion mode, providing the highest
quality output power with zero transfer time. Auto-bypass mode is available during UPS failure modes when AC input is within the
bypass range.
• Frequency Regulation Power Strategy is similar to Max-Quality Power Strategy, except the UPS will actively regulate output
frequency within +/-0.05Hz of the 50 or 60Hz nominal frequency measured on startup. The UPS will remain operating continuously in
Online Double-Conversion mode, providing the highest quality output power with zero transfer time. Auto-bypass mode is available
during UPS failure modes when AC input is within the bypass range.
• Frequency Conversion to 60Hz & Frequency Conversion to 50Hz Power Strategies are similar to Max-Quality power strategy,
except the UPS will actively regulate output within +/-0.05Hz of the 50Hz (Freq. Conv. to 50Hz setting) or 60Hz (Freq. Conv. to 60Hz
setting). Auto-bypass is not available in FREQUENCY CONVERSION mode. Typical applications include converting 50 to 60Hz (or 60 to
50Hz) for sensitive electronic devices.
Note: Maximum power supported in Frequency Regulation/Conversion modes is derated by 30%.
UPS Operating Modes
Tripp Lite SmartOnline UPS systems are able to automatically switch between operating modes under conditions specified in the
configured Power Strategy. The UPS continuously indicates status using front panel LEDs and the interactive LCD viewing screen.
• Battery Mode is the UPS system’s automatic response to power failures and voltage variations outside of the online voltage range. In
BATTERY MODE, the UPS maintains sine wave AC output power from battery reserves. Once power is restored, the UPS will return to
the protected operating mode as dictated by the configured power-strategy and input power conditions.
• Online Mode (also known as ONLINE, DOUBLE CONVERSION MODE) offers the highest level of UPS equipment protection. In ONLINE
MODE, the UPS actively regenerates power from AC to DC, then from DC to AC to provide continuously regulated AC output within 2%
of the selected nominal output voltage with zero transfer time as the UPS switches between ONLINE and BATTERY modes.
• Economy Mode offers power saving operation with the highest level of UPS operating efficiency. In ECONOMY MODE, the UPS saves
energy by turning off the online, double-conversion process whenever input power is within the ECONOMY MODE voltage range. If line
voltage falls outside of the ECONOMY MODE, the UPS will respond by automatically switching to ONLINE MODE until line voltage
recovers.
• Frequency Regulation Mode gives the UPS the ability to correct frequency variations present on UPS input power. See Power
Strategy Selection Options section for details.
• Frequency Conversion to 60Hz and Frequency Conversion to 50Hz Modes give the UPS the ability to convert frequency from 50Hz to 60Hz (or 60Hz to 50Hz). See Power Strategy Selection Options section for details.
Note: Maximum power supported in Frequency Regulation/Conversion modes is derated by 30%.
• Bypass Mode offers filtered and unregulated power to connected equipment.
13
Operations
Power Strategy Operating Features and Supported UPS Operating Modes
The configured UPS Power Strategy provides a framework for UPS operation as it switches between operating modes as dictated by
power events and UPS status. Each Power Strategy offers a unique set of operating parameters that the UPS adheres to in order to
meet user preferences for high-performance or high efficiency. Additional frequency regulation and conversion options are also available
for advanced applications. The chart below lists the UPS operating modes supported for each Power Strategy option.
UPS OPERATING MODES
UPS automatically switches operating modes as dictated by the configured power strategy, current
power and UPS status conditions.
Support for
ONLINE MODE
AUTO ADAPTIVE
UPS runs continuously in
ECONOMY MODE after
running in ONLINE MODE
for one continuous week
without a power failure.
MAX. QUALITY
UPS runs in ONLINE MODE
continuously to maintain
the highest quality output
power for connected
equipment.
MAX. EFFICIENCY
UPS runs in ECONOMY
MODE full time when input
is within the bypass range.
FREQUENCY
REGULATION
UPS regulates output
to within +/-0.05Hz of
nominal.
FREQUENCY
CONVERSION to 60Hz
UPS converts 50Hz input
to 60Hz.
(+/-0.05Hz)
FREQUENCY
CONVERSION to 50Hz
UPS converts 60Hz input
to 50Hz.
POWER STRATEGY SELECTION OPTIONS
Your power strategy selection enables the UPS to switch between operating modes
as described
(+/-0.05Hz)
* LCD displays FREQUENCY REGULATION as the operating mode with derating information.
** LCD displays FREQUENCY CONVERSION as the operating mode with derating information.
YES. When input is within
the ONLINE voltage range,
but outside the BYPASS
voltage range, and after
AC power is restored.
YES. When input is within
the ONLINE voltage range.
YES. When input is within
the ONLINE voltage range,
but outside the BYPASS
voltage range.
YES. When input is within
the ONLINE voltage
range.*
YES. When input is within
the ONLINE voltage
range.**
YES. When input is within
the ONLINE voltage
range.**
Support for
ECONOMY MODE
YES. When input is within
the ECONOMY MODE
voltage range and there
are no power failures for
one week.
NO.YES. YES. In the event of
YES. When input is within
the ECONOMY MODE
voltage range.
NO.YES. YES. In the event of
NO.YES. NO.
NO.YES.NO.
Support for
BATTERY MODE
YES. YES. In the event of
YES. YES. In the event of
Support for
AUTO-BYPASS
UPS inverter fault while
input voltage is within the
BYPASS voltage range.
UPS inverter fault while
input voltage is within the
BYPASS voltage range.
UPS inverter fault while
input voltage is within the
BYPASS voltage range.
UPS inverter fault while
input voltage is within the
BYPASS voltage range.
14
Operations
Front Panel LCD Selection and Configuration Options
MAIN MENU / SUBMENUDISPLAY / SETTING OPTIONSDISPLAY / SETTING DESCRIPTION
STATUS
Load Status• Load level (%, kW, kVA, A, PF)
• Available capacity (%, kW, kVA)
In/Out Status• Input voltage & frequency (Vac, Hz)
• Output voltage & frequency (Vac, Hz)
• Load Group1 (On, Off)
• Load Group2 (On, Off)
Energy Status• Efficiency (%)
• Avg. Power (kw/hr.)
• Configured power strategy
Int. Batt. Status• Installed (mm/dd/yyyy)
• Expires (mm/dd/yyyy)
Ext. BP. Status• Battery pack model & serial number
• Installed (mm/dd/yyyy)
• Expires (mm/dd/yyyy)
Power Flow Chart• View UPS operational flow chartDisplays UPS operating mode in a graphical flow chart.
CONTROL
Start Batt. Test• Initiates a manual battery testInitiates a momentary UPS battery self-test with immediate
Reset Batt. Age• Resets the battery ageResets battery age to today’s date. Use this option after NON-
Reset Fault State• Resets any fault state messagesUse this option to clear UPS fault messages.
Auto Batt. Testing• Set regular battery self-test interval
EVENT LOG
On Batt. Events• Event counter
All Events• Event counter (all events)
Reset Batt. Events• Resets battery events onlyResets all data in the on-battery events screen set.
Reset All Events• Resets all eventsResets all data in the all-events screen set.
SETTINGS
Basic setup
o Disable
o 4 weeks (factory setting)
o 13 weeks
o 26 weeks
(UPS On-battery events only)
• Total minutes (total minutes of
on-battery mode operation)
• Most recent power failure (date)
• Days until battery replacement alert
(days)
• Event details (date, time &
description for the last 20 logged events)
• Most recent event (date)
• Date time log
• Event details (date, time and description
of each logged event)
UPS capacity available in percent (%), kilowatts (kW)
& kilovoltamps (kVA).
Displays UPS input and output status information for input /
output voltage (Vac), frequency (Hz) and outlet group power
status (On/Off) information.
Displays UPS efficiency percentage (%), connected equipment
kilowatt hour consumption (kw/hr.) and configured power
strategy.
Displays internal Replacement Battery Cartridge install date and
user configured expiration date.
Displays external Battery Pack model number & serial number
(Tripp Lite SMART BATTERY PACKS) only, installation date and
user configured expiration date.
Pass/Fail results.
SMART battery replacement.
Use this option to initiate automatic UPS battery testing at
regular intervals.
Displays a summary of all ON-BATTERY events where the UPS
switched to battery mode in response to a protected condition.
Event details lists the last 20 battery events. As additional alerts
occur, the oldest records will be automatically removed.
Displays a summary of all Recorded events. Event details lists
the last 20 events. As additional alerts occur, the oldest records
will be automatically removed.
Displays, sets and resets date, time, audible alarm status and
language settings.
Note: Audible Alarm DISABLE setting prevents power fail and
operating fault alarms only, the UPS will always “beep” to
confirm the UPS is accepting user input from the front-panel
LCD navigation buttons.
Use the SETTINGS / BASIC / OUTPUT VOLTAGE option to display
or set the nominal UPS output voltage (changes take effect on
next restart).
15
Operations
MAIN MENU / SUBMENUDISPLAY / SETTING OPTIONSDISPLAY / SETTING DESCRIPTION
SETTINGS
Basic setup
(continued)
Advanced setup
Power strategy:
• Auto-Adaptive
• Max Efficiency
• Max Quality
• Freq. Regulation
• Freq. Conversion to 60Hz
• Freq. Conversion to 50Hz
Battery:
• External battery configuration
o Configure via UPS
o PC configured
o Battery Replacement
• Battery Age Alert
System:
• Display brightness
o High
o Medium (factory setting)
o Low
• Backlight dim: Enter 10-120 seconds
(factory setting is 60 seconds)
• Password: Set your 4 digit password
(factory setting is 0000)
• Factory reset (resets all UPS preferences
to factory settings, including battery
configurations)
In/Out:
• Overload Alert Lvl: Enter a value 5-105%
(factory setting is 100%)
• Conf. Fault Action
(UPS response to fault)
o Go to bypass (factory setting)
o Go to standby
• Bypass Low Limit: Enter a value -5% to
-20% (factory setting is -15%)
• Bypass High Limit: Enter a value +5% to
+20% (factory setting is +10%)
On/Off:
• Cold Start
o Enable (factory setting)
o Disable
• Auto Restart
o Enable (factory setting)
o Disable
• Auto Restart Delay
o Enter: 0 to 60 seconds
(factory setting is 5 seconds)
• Energy Saving
o Enter: 0-100%
o Disable (factory setting)
• Off Mode
o Standby
o Bypass (factory setting)
• Min. Batt to Restart
o Enter: 10-90%
o Disable (factory setting)
Use the SETTINGS / BASIC / POWER STRATEGY option to display
or set the UPS Power strategy.
See Power Strategy Selection Options section under the Operations section for more info on the available power
strategy options.
Use the SETTINGS / BASIC / BATTERY option to configure the
UPS with external battery packs. Battery replacement option can
be used to update installation date for non-smart external
battery replacement of the same type. Also sets the battery age
alert duration for battery replacement reminder.
See Configuring External Battery Packs section under the Operations section for information on how to configure external
battery packs.
Use the SETTINGS / ADVANCED / SYSTEM option to set the
display brightness, the display backlight dim time-out, password
or factory reset options.
Use SETTINGS / ADVANCED / IN-OUT for these options:
Sets the UPS output load percentage before an overload alert
is sent.
Sets the UPS response to fault conditions that require the UPS
to exit double-conversion mode. GO TO BYPASS option
maintains AC output (so long as input voltage is within bypass
high/low limits). GO TO STANDBY option causes the UPS to turn
off output AC in response to fault conditions.
Specifies the lowest acceptable input voltage for bypass
operation.
Specifies the highest acceptable input voltage for bypass
operation.
Use SETTINGS / ADVANCED / ON-OFF for these options:
Enabling Cold-start allows the UPS to be manually turned on
into battery mode during a power failure.
Enabling Auto-restart allows the UPS to automatically turn back
on into a protected operating mode when power is restored.
Auto-restart delay forces the UPS to wait 0-60 seconds after
power is restored before automatically restarting.
Requires that Auto-restart when power is restored be enabled.
Energy saving enables the UPS to automatically shutdown when
the output load is less than the selected percentage
continuously for 5 minutes.
Off mode setting of BYPASS allows the UPS to provide
unregulated line power within configured bypass low / high limits
to be available at the output of the UPS when it is turned off.
Minimum battery charge level to restart forces the UPS to wait
until batteries have recharged to the selected percentage before
automatically restarting.
Note: UPS can be manually started using the power button if battery is
below the minimum battery restart threshold.
Requires that Auto-restart when power is restored be enabled.
16
Operations
MAIN MENU / SUBMENUDISPLAY / SETTING OPTIONSDISPLAY / SETTING DESCRIPTION
SETTINGS
Advanced setup
(continued)
ABOUT
UPS InformationUPS model number, UPS Serial number,
Network IDWeb management accessory card firmware,
FirmwareUPS firmwares
On battery:
• Low Batt. Alert
o Enter: 10-90% (factory setting is 20%)
• Timed Shutdown
o Enter: 15, 30, 45 sec., 1-30 min.
o Disable (factory setting)
• Low Battery Shutdown
o Enter: 5-100%
o Disable (factory setting)
• On Batt. Beep Delay
o Enter: 0-120 seconds
(factory setting is 5 seconds)
• Shutdown Completion
o Required (factory setting)
o Interrupt OK
USB/DB9 Settings:
• DB9 Settings
o Output pins 1&5
- On battery (factory setting)
- On bypass
- Output on
- Low battery
o Output pins 8&5
- On battery
- On bypass
- Output on
- Low battery (factory setting)
o Input pins 3&9
- Shutdown (factory setting)
- Output off
- Reboot
- Output on
- Power Toggle
• USB signal lost
o Line mode setup
- No action (factory setting)
- Reboot UPS after delay
- Reboot Load1 after delay
- Reboot Load2 after delay
o Battery mode setup
- Run to low battery (factory setting)
- Shutdown after delay
o USB lost timer
- Enter: 10-60 seconds
- Factory setting: 30 seconds
UPS installed date
IPv4 address, IPv6 address, MAC Address
Enables the UPS to send a low-battery alert as batteries
discharge to the selected charge level during a power failure.
Timed shutdown sets the maximum amount of battery runtime
in seconds or minutes the UPS will provide during a power
failure. Use the DISABLE setting for the longest possible battery
runtime.
Low battery shutdown sets the maximum amount of battery
discharge before the UPS shuts down due to low battery. The
setting of DISABLE allows the batteries to discharge to 0%
before shutdown.
The “Beep Delay” setting allows the audible alarm to be delayed
up to 120 seconds to prevent the audible-alarm from sounding
in response to short duration power failures.
The UPS will communicate shutdown messaging to connected
systems prior to UPS shutdown. The setting of INTERRUPT OK
will interrupt shutdown messaging if power is restored after
shutdown messaging is sent.
The UPS will signal the selected condition by shorting pins 1&5
on the DB9 port.
The UPS will signal the selected condition by shorting pins 8&5
on the DB9 port.
The UPS will perform the selected action when pins 3&9 are
shorted on the DB9 port for at least 3.8 seconds.
For the Reboot option (output off for 30 seconds before reboot):
Note the pins must be shorted for at least 3.8 seconds to
perform the reboot. The reboot happens at exactly 3.8 seconds.
If the pins continue to be shorted for more than 3.8 seconds,
no further action should be taken. The UPS takes no action on
release of the short.
The Power Toggle option is intended to keep the unit powered
on whenever the pins are not shorted and powered off whenever
the pins are shorted. Note this input cannot power on the unit
from an off state unless valid AC is applied (this function will not
impose a coldstart). To power on, the pins must be not shorted
for at least 3.8 seconds and AC must be valid. To power off, the
pins must be shorted for at least 3.8 seconds.
The UPS will perform the selected action if the USB signal from
a connected device is lost in line power mode for the duration
selected.
The UPS will perform the selected action if the USB signal from
a connected device is lost in battery power mode for the
duration selected.
This control sets the duration of USB signal loss before the
selected line power-mode / battery power-mode action engages.
UPS installed date is automatically set by the unit after 2 hours
of continuous operation.
17
Operations
Configuring External Battery Packs
Tripp Lite SmartOnline INT UPS systems support the connection of external battery packs to enable extended-run UPS operation. In order
for the UPS to provide efficient charging levels and accurate runtime predictions for optimal network runtime prior to sending autoshutdown messaging, external battery packs need to be configured to the UPS upon installation.
There are 3 methods available to configure external battery packs to the UPS, depending on battery pack selected and quantity added to
the UPS. Some battery pack configurations may require the use of more than one configuration method.
EXTERNAL BATTERIES can be
configured to the UPS…
Battery Pack Compatibility
…AUTOMATICALLY
(Using SMART Battery Packs)
UPS supports automatic detection
of up to 6 SMART BATTERY PACKS
connected to the UPS.
…MANUALLY
(Using LCD Screen)
LCD screen can be used to configure NON-SMART BATTERY PACKS
and any additional SMART BATTERY
PACKS beyond the 6 that can be
automatically detected.
…Using EXTERNAL BATTERY
CONFIGURATION SOFTWARE
External Battery Configuration
software can be used to configure
the UPS for any supported quantity
of SMART & NON-SMART external
battery packs.
Tripp Lite SMART Battery Packs include a wired data connection that enables automatic detection and configuration for up to 6 SMART
Battery Packs to the UPS. Tripp Lite Legacy NON-SMART battery packs are also supported for extended runtime applications, but require
user configuration using the front-panel LCD screen or through the use of EXTERNAL BATTERY CONFIGURATION SOFTWARE.
SmartOnline LCD SMART and NON-SMART External Battery Pack Options
Configuring SMART and NON-SMART BATTERY PACKS via the front panel LCD screen
Adding up to 6 SMART BATTERY PACKS to the UPS
Each SmartOnline UPS has a designated SMART BATTERY PACK, where up to 6 SMART battery packs can be connected to the UPS for
fully automatic detection and configuration. SMART battery packs include a wired data connection that connects to the UPS Battery Pack
Detection port for automatic recognition and configuration by the UPS.
To configure the UPS for use with up to 6 SMART BATTERY PACKS, just connect the included POWER and DATA cables between the UPS
and the first SMART BATTERY PACK. Then connect the POWER and DATA cables for additional SMART BATTERY PACKS to the one ahead
of it. The UPS will automatically detect and configure up to 6 SMART BATTERY PACKS to the UPS.
Adding more than 6 SMART BATTERY PACKS to the UPS
SmartOnline UPS systems support automatic detection of up to 6 SMART BATTERY PACKS as described above. It is possible to configure
the UPS for more than 6 SMART BATTERY PACKS by configuring all additional SMART PACKS as NON-SMART. When configuring the UPS
with more than 6 SMART BATTERY PACKS, configure BPs #1-6 using the BP Detection port method listed above. Then configure SMART
BATTERY PACKS #7 and above and any other supported battery pack models to be connected as NON-SMART BATTERY PACKS. See the
ADDING NON-SMART Battery Packs section for more information.
Adding BATTERY PACKS to the UPS manually (SMART and NON-SMART battery packs)
If you’re connecting more than the 6 SMART Battery Packs the UPS can automatically detect OR are connecting supported NONSMART
Battery Packs to the UPS, you can configure them via the UPS front panel LCD interface. First, install the Battery Pack power connections
to the UPS as described in the battery pack documentation. Then, using the SETTINGS / BASIC SETTINGS / BATTERY configuration
screens, select the EXTERNAL BATT menu option (see the Front Panel Button Functions and Front Panel LCD Selection and Configuration Options sections under the Operations section for instructions on accessing this section).
1
From the SETTINGS / BASIC SETTINGS / BATTERY menu, select EXTERNAL BATT, then press
NEXT
.
Battery
18
External Batt
Batt Age Alert
Back Select Next
Operations
2
The LCD screen will display the present configuration settings. Press NEXT
configuration.
3
Then select CONFIGURE VIA UPS and press NEXT .
4
The LCD screen will prompt you to move to the next screen where
the SMART and NON-SMART battery packs can be configured.
Then select NEXT
Note: The display will cycle between two screens to show all the text.
…
to edit the
Configure via UPS
Press NEXT to view
detected SMART BPs
(S column) and
specify NONSMART
BP qty (N column).
BackNext
External Batt
Note Presently
configured via UPS
on 04/07/2014
Press Next to change
BackNext
External Batt
Configure via UPS
PC Configured
External Batt
Back Select Next
Configure via UPS
SMART BPs beyond
qty 6 must be
configured as
NONSMART.
BackNext
5
The LCD screen will display the list of supported external battery packs preceded by a column
displaying the number of configured SMART and NON-SMART external battery packs. SMART
BATTERY PACKS detected via the BP DETECTION PORT will already be listed with the appropriate
quantity of 1-6 under the “S” Column of this screen.
To configure NON-SMART batteries and any SMART batteries beyond the 6 that were auto-detected,
use the UP/DOWN
ESC
press BACK
Note: The “S” column displays the number of configured SMART battery packs and the “N” column displays the number of
configured NON-SMART battery packs.
Note: Pressing the UP or DOWN buttons change the “N” column value. Pressing the NEXT button moves the cursor down one
row.
Note: When you reach the last row, NEXT will change to APPLY.
6
After the manually entered NON-SMART battery packs have been
to edit your entry or APPLY to enter the new values.
applied to the UPS, the LCD will report that the change has been
accepted and will suggest you verify that the actual set of external
battery packs match the UPS configuration.
Press NEXT
7
The LCD screen will ask you to press NEXT to enter the battery installation date for manually
to move to the next screen.
and NEXT buttons. After the last battery pack on the list is configured,
Configure via UPS
Change accepted. For
true capacity and
runtime reporting,
verify connected BPs
match configuration
BackNext
configured external battery packs.
The following screen allows you to pick the current date for installation, or allow you to enter an
installation date in the past, in case the BP was added at a previous date.
Press Next to enter
Battery Installed
Date for manually
added battery packs.
19
BackNext
Optional Connections
Your UPS will function properly without these connections.
1
Phone Line or Phone/Network Line Surge Suppression
Your UPS has jacks which protect against surges on a phone
line.* Using appropriate telephone or network cords, connect
your wall jack to the UPS jack marked “IN.” Connect your
equipment to the UPS jack marked “OUT.” Make sure the
equipment you connect to the UPS's jacks is also protected
against surges on the AC line.
* Not compatible with PoE (Power Over Ethernet) applications.
Note: Use the same type of connector for the phone line surge suppression input
and output ports.
2
USB and RS-232 Serial Communications
Use the included USB cable (see 2a) and/or RS-232 serial
cable (see 2b) to connect the communication port of your
computer to the communication port of your UPS. Install on
your computer the Tripp Lite PowerAlert Software appropriate to
your computer's operating system. Your UPS may feature
additional communications ports; these ports may be
connected to additional computers that have PowerAlert
Software installed. Consult your PowerAlert manual for more
information.
2c
RS-232 Dry contact communications are simple, but some
knowledge of electronics is necessary to configure them. The
RS-232 port’s pin assignments are shown in the diagram. If
the UPS battery is low, the UPS sends a signal by bridging pins
8 and 5. If utility power fails, the UPS sends a signal by
bridging pins 1 and 5. To shut the UPS down remotely, short
pin 3 to pin 9 for at least 3.8 seconds. Additional functions of
these pins can be configured through the LCD or via Web
management accessory card communication.
Your model may differ.
1
Your model may differ.
2a
2b
2c
20
Your model may differ.
Optional Connections
3
EPO Port Connection
This optional feature is only for those applications that require connection to a facility’s Emergency Power Off (EPO) circuit. When the
UPS is connected to this circuit, it enables emergency shutdown of the UPS’s inverter and inhibits transfer to internal bypass.
Connect the EPO port of your UPS (see 3a) to a user-supplied normally closed or normally open switch according to the circuit diagram
(see 3b).
Note: If a non-latching EPO switch is used, the EPO must be held for a minimum of 1 second. This does not apply to a latching EPO switch.
4-5
Your model may differ.
3a3b
UPS state when asserting EPO with valid AC input present:
AC OutputLCD Screen StatusLEDs Status
OffEPO ActiveOnly AC Input Indicator is On.
To restart the UPS after EPO assertion with valid AC input present:
1. Verify that the EPO assertion has been removed or cleared.
2. Press and hold the POWER ON/OFF button until it beeps. Now the UPS will start back up in one of the pre-configured normal
operating modes.
UPS state when asserting EPO without valid AC input present (Battery Mode):
AC OutputLCD Screen StatusLEDs Status
OffEPO ActiveOff
To restart the UPS after EPO assertion without valid AC input present:
1. Verify that the EPO assertion has been removed or cleared.
2. Wait until the LCD completely turns off.
3. Press and hold the POWER ON/OFF button until it beeps. Now the UPS will start back up to Battery Mode.
To restart the UPS after EPO assertion with valid AC input present:
1. Verify that the EPO assertion has been removed or cleared.
2. Wait until the LCD completely turns off.
3. Reapply AC input power, press and hold the POWER ON/OFF button until it beeps. Now the UPS will start back up in one of the
pre-configured normal operating modes.
Note: If AC input power is reapplied before the LCD completely turns off, the UPS will automatically restart to one of the pre-configured normal operating line modes
without using the POWER ON/OFF button.
21
Optional Connections
4
External Battery Connection
Check the Model Specific Accessories section under
Overview for compatible battery packs and maximum quantities
for your UPS system. Ensure that your battery pack matches
the voltage listed next to your UPS battery connector. Adding
external batteries will increase recharge time as well as
runtime. See the battery pack owner’s manual for complete
installation and setup instructions. Make sure cables are fully
inserted into their connectors. Small sparks may result during
battery connection; this is normal. Do not connect or
disconnect battery packs when the UPS is running on battery
power.
IMPORTANT! In order for the runtime-remaining LCD and the software information screens to accurately predict runtime
with external battery packs connected, you must configure any connected packs by following the instructions under the
Configuring External Battery Packs section under Operations.
CAUTION: Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic. The following
precautions should be observed when working on batteries: Determine if the battery is inadvertently grounded. If inadvertently
grounded, remove the source from ground connection. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such a shock can be reduced if grounds are removed during installation and maintenance. (This is applicable to
equipment and remote battery supplies that do not have a grounded supply circuit.)
4
Your model may differ.
22
Troubleshooting and Event Log
See the chart below for explanation of UPS faults and warnings that can be accessed via the Event Log feature via the LCD screen or
PowerAlert software, as well as suggested solutions for each fault/warning.
Fault/Alarm
MessageLCD Screen Message
UPS Internal Errors/Faults:
LCD Header
BUS Start Voltage LowInverter
Error 1
Inverter error. Restart UPS.
If issue persists, contact
Tripp Lite.
Bus Over VoltageInverter
Error 2
Inverter error. Restart UPS.
If issue persists, contact
Tripp Lite.
Bus Under VoltageInverter
Error 3
Inverter error. Restart UPS.
If issue persists, contact
Tripp Lite.
Bus Voltage UnbalanceInverter
Error 4
Inverter error. Restart UPS.
If issue persists, contact
Tripp Lite.
Inverter Soft Start Failed Inverter
Error 5
Inverter error. Restart UPS.
If issue persists, contact
Tripp Lite.
Inverter Over VoltageInverter
Error 6
Inverter error. Restart UPS.
If issue persists, contact
Tripp Lite.
Inverter Under VoltageInverter
Error 7
Inverter error. Restart UPS.
If issue persists, contact
Tripp Lite.
Inverter Short CircuitInverter
Error 8
Inverter output short. Remove
the source of short circuit from
UPS output.
Battery/Charger Related Errors/Faults:
Charger FailureCharger
Failure
If issue persists, contact
Tripp Lite.
Over ChargeOver ChargeIf issue persists, contact
Tripp Lite.
Battery Over VoltageBatt. Over
Voltage
Check battery type used.
If issue persists, contact
Tripp Lite.
Battery Under VoltageBatt. Under
Voltage
Check battery type used.
If issue persists, contact
Tripp Lite.
Bad BatteryBad BatteryRestart UPS. If issue persists,
contact Tripp Lite.
Low BatteryLow BatterySave your data before UPS
shuts down.
Internal Battery Age
Alert
External Smart Battery
Age Alert
Battery-Age
Alert
Battery-Age
Alert
Internal battery may need
replacement.
External Smart battery:
{SerialNumber} may need
replacement.
External Non-Smart
Battery Age Alert
Smart Batt ChangedSmart Batt
Battery-Age
Alert
Changed
External battery may need
replacement.
The number of Smart battery
packs are changed at month/
date/year hr: min. Runtime has
been adjusted. If this change
is unexpected, please check
smart battery communications.
LCD Event Log Display (Event
Type with Date/Time Stamp)
Fault Or
Alarm?Additional Comments
mm/dd/yyyy Inv Err 1 hh:mmUPS fault
mm/dd/yyyy Inv Err 2 hh:mmUPS fault
mm/dd/yyyy Inv Err 3 hh:mmUPS fault
mm/dd/yyyy Inv Err 4 hh:mmUPS fault
mm/dd/yyyy Inv Err 5 hh:mmUPS fault
mm/dd/yyyy Inv Err 6 hh:mmUPS fault
mm/dd/yyyy Inv Err 7 hh:mmUPS fault
mm/dd/yyyy Inv Err 8 hh:mmUPS fault
mm/dd/yyyy Chrg Err 1 hh:mmWarningCharger is not working. No
charge current.
mm/dd/yyyy Chrg Err 2 hh:mmWarningCharger is working but
charge voltage is too high.
mm/dd/yyyy Batt Err 1 hh:mm
Note: If the UPS shuts down from Batt
Err 1, another event, “Batt Err 1 SD”,
is also logged on the event log screen.
mm/dd/yyyy Batt Err 2 hh:mm
Note: If the UPS shuts down from Batt
Err 2, another event, “Batt Err 2 SD”,
is also logged on the event log screen.
mm/dd/yyyy Batt Err 3 hh:mm
Note: If the UPS shuts down from Batt
Err 3, another event, “Batt Err 3 SD”,
is also logged on the event log screen.
mm/dd/yyyy Low Batt hh:mm
Note: If the UPS shuts down from Low
Batt, another event, “Low Batt SD”, is
also logged on the event log screen.
UPS fault
UPS fault
Warning
Warning
mm/dd/yyyy Batt Alert 1 hh:mmWarning
mm/dd/yyyy Batt Alert 2 hh:mmWarning
mm/dd/yyyy Batt Alert 3 hh:mmWarning
mm/dd/yyyy S BP Changed hh:mm Warning
23
Troubleshooting and Event Log
Fault/Alarm
LCD Header
MessageLCD Screen Message
LCD Event Log Display (Event
Type with Date/Time Stamp)
Load/Temperature Related Errors/Faults:
Over Temperature FaultOver Temp
Fault
Over Temperature
Over Temp Check UPS ventilation and fan.
(warning only)
Check UPS ventilation and fan.
If issue persists, contact
Tripp Lite.
If issue persists, contact
mm/dd/yyyy OverTempFault
hh:mm
Note: mm/dd/yyyy OverTemp SD
hh:mm is also logged when the unit
actually shuts down after being in fault
mode.
mm/dd/yyyy OverTempAlert hh:mm WarningThis is a warning threshold
Tripp Lite.
Overload FaultOverloadReduce connected load.
Restart UPS.
mm/dd/yyyy Overload hh:mm
(mm/dd/yyyy Overload SD hh:mm
is also logged when the unit
actually shuts down after being in
fault mode)
Overload WarningOverload
Reduce connected load.mm/dd/yyyy Overload ALM hh:mmWarningOverload warning is triggered
Alarm
Other Warnings and Events:
EPO Active EPO ActiveCheck EPO switch. If issue
mm/dd/yyyy EPO SD hh:mmWarning
persists, contact Tripp Lite.
Bypass Out of RangeBypass
Range Error
Check AC input volt. and freq.
If issue persists, contact
mm/dd/yyyy Bypass Err 1 hh:mmWarningAC input voltage might be
Tripp Lite.
Bypass Frequency
Unstable
Bypass Freq.
Error
Check AC input freq. If issue
persists, contact Tripp Lite.
mm/dd/yyyy Bypass Err 2 hh:mmWarning
On BatteryN/AN/Amm/dd/yyyy On Batt hh:mm
Note: If the UPS shuts down in Battery
Mode based on preconfigured delay,
“On Battery” will be replaced with
“Timed SD”, and logged as another
event.
AC FailureN/AN/Amm/dd/yyyy AC Failure hh:mm
Note: If valid AC returns, “On Utility "
is logged as another event.
Fault Or
Alarm?Additional Comments
UPS fault At the time the over
temperature threshold is
reached, the OverTempFault
event will be triggered and
if AC is available, then
depending on the fault
mode setting, the unit will
either transfer to Bypass
mode or Standby mode. If
AC is unavailable, the unit
will transition to fault mode
with output turned off, then
shuts down.
only. The unit should not
take action based on this
event other than to display
and log the warning.
UPS fault At the time the overload
fault is triggered, the
Overload event will be
logged and if AC is available,
then depending on the fault
mode setting, the unit will
either transfer to Bypass
mode or Standby mode. If
AC is unavailable, the unit
will transition to fault mode
with output turned off, then
shuts down. UPS will not
intentionally shut down due
to overload in this mode
regardless how high the
load is.
Note: The circuit breaker may
trip due to the overload.
when the load level is
between 100% to 105%
or when load level reaches
the preconfigured overload
warning level.
meeting the preconfigured
bypass range requirement,
see Operations section for
more information.
Normal
Normal
24
Internal Battery Replacement
Battery Replacement Door: Under normal conditions, the original battery in your UPS will last several years. Battery replacement
should be performed only by qualified service personnel. Refer to “Battery Warnings” in the Safety section. If you require a replacement
battery, you can find it at tripplite.com/support/battery/index.cfm. See the chart below to find the right replacement battery for your UPS
system:
See the following diagrams for battery removal and installation procedures.
All Models
Note: The SUINT1000LCD2U is shown, but the procedure is the same for the other units.
1
Remove the four front screws from the front bezel and take
it off.
2
Loosen the two screws securing the front plate.
12
3
Open the front plate. Disconnect battery power cable and
communication cable.
3
5
Install new battery pack into the UPS in the same position as
the original pack.
4
Remove old battery pack.
4
6
Reconnect battery power cable and communication cable.
Close the front plate.
56
25
Internal Battery Replacement
7
Tighten the two screws to secure the front plate.
8
Replace the four front screws to secure the bezel.
78
Storage and Service
Storage
First turn your UPS OFF: press the “OFF” switch to turn power off at the UPS outlets, then disconnect the power cord from the wall
outlet. Next, disconnect all equipment to avoid battery drain. If you plan on storing your UPS for an extended period of time, fully
recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4-6 hours.
If you leave your UPS batteries discharged for an extended period of time, they may suffer permanent loss of capacity.
Service
A variety of Extended Warranty and On-Site Service Programs are also available from Tripp Lite. For more information on service, visit
tripplite.com/support. Before returning your product for service, follow these steps:
1. Review the installation and operation procedures in this manual to ensure that the service problem does not originate from a
misreading of the instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit tripplite.com/support.
3. If the problem requires service, visit tripplite.com/support and click the Product Returns link. From here you can request a Returned
Material Authorization (RMA) number, which is required for service. This simple on-line form will ask for your unit’s model and serial
numbers, along with other general purchaser information. The RMA number, along with shipping instructions will be emailed to you.
Any damages (direct, indirect, special or consequential) to the product incurred during shipment to Tripp Lite or an authorized Tripp Lite
service center is not covered under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must have
transportation charges prepaid. Mark the RMA number on the outside of the package. If the product is within its warranty period,
enclose a copy of your sales receipt. Return the product for service using an insured carrier to the address given to you when you
request the RMA.
26
Product Registration and Regulatory Compliance
Visit tripplite.com/warranty today to register your new Tripp Lite product. You'll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
Regulatory Compliance Identification Numbers:
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found
on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series
number. The series number should not be confused with the marketing name or model number of the product.
FCC Specifications for Models with FCC Class A Approval:
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. The user must use
shielded cables and connectors with this equipment. Any changes or modifications to this equipment not expressly approved by Tripp Lite could void the user’s authority to
operate this equipment.
EMC Specifications for Models with EMC Category C2 Approval (Select Models):
WARNING: This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take
additional measures.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment
from Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste
FCC Part 68 Notice (United States Only)
If your Modem/Fax Protection causes harm to the telephone network, the telephone company may temporarily discontinue your service. If possible, they will notify you in
advance. If advance notice isn’t practical, you will be notified as soon as possible. You will be advised of your right to file a complaint with the FCC. Your telephone company
may make changes in its facilities, equipment, operations or procedures that could affect the proper operation of your equipment. If it does, you will be given advance notice
to give you an opportunity to maintain uninterrupted service. If you experience trouble with this equipment’s Modem/Fax Protection, please visit tripplite.com/support for repair/
warranty information. The telephone company may ask you to disconnect this equipment from the network until the problem has been corrected or you are sure the equipment
is not malfunctioning. There are no repairs that can be made by the customer to the Modem/Fax Protection. This equipment may not be used on coin service provided by the
telephone company. Connection to party lines is subject to state tariffs. (Contact your state public utility commission or corporation commission for information.)
UPS and Battery Recycling
Please recycle Tripp Lite Products. The batteries used in Tripp Lite products are sealed Lead-Acid batteries. These batteries are highly recyclable.
Please refer to your local codes for disposal requirements.
You can call Tripp Lite for recycling info at +1.773.869.1234.
You can go the Tripp Lite Website for up-to-date information on recycling the batteries or any Tripp Lite product.
Please follow this link: tripplite.com/en/support/recycling-program.cfm
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos and illustrations may differ slightly from actual products.
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
27
19-09-287 93-32CB_RevD
Manual del Propietario
Sistemas UPS SmartOnline
Monofásicos en Línea para Instalación en Rack
con Pantalla LCD Integrada para Monitoreo y Control
No es adecuado para aplicaciones móviles.
®
SUINT1000LCD2U
(Número de Serie: AGPS8294)
1. Descripción General 29
Lista de Partes 29
Opciones de Accesorios Adicionales 29
Accesorios Específicos del Modelo 29
2. Instrucciones Importantes 29
de Seguridad
3. Diagrama de Bloques del 30
Circuito del UPS
4. Instalación 31
Instalación en Rack 31
Instalación en Torre 32
Conexión de las Comunicaciones 33
de la Batería Smart
5. Conexiones Básicas 34
y Arranque
Guía de Inicio Rápido 34
6. Características 36
Controles del Panel Frontal, 36
Grupo de LEDs y Pantalla LCD
Características del Panel Posterior 36
SUINT1500LCD2U
(Número de Serie: AGPS8295)
Guía de
Inicio Rápido—
Página 34
SUINT2200LCD2U
(Número de Serie: AGPS7958)
7. Operaciones 38
Pantalla de LCD y Controles del 38
Panel Frontal Funciones de los Botones del 39
Panel Frontal Distribución de la Pantalla de Inicio 39
Opciones de Selección de Estrategia 40
de Energía Opciones de Selección y Configuración 42
del LCD del panel Frontal del UPS Configuración de los Módulos de 45
Baterías Externas
8. Conexiones Opcionales 47
9. Solución de Problemas y 50
Registro de Eventos
10. Reemplazo de la Batería Interna 52
11. Almacenamiento y Servicio 53
12. Cumplimiento de las normas 54
English 1
Français 55
Русский82
Deutsch 109
SUINT3000LCD2U
(Número de Serie: AGPS7959)
SU3000LCD2UHV
(Número de Serie: AGPS8296)
NOTA: Las opciones de módulos de baterías externas requieren configuración usando la interfaz de LCD del Panel frontal LCD o mediante el software de
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
Para obtener las actualizaciones más recientes, visite tripplite.com
28
Descripción General
Sistemas UPS SmartOnline para Instalación en Rack de Tripp Lite; con interfaz de LCD interactiva cuenta con protección de UPS de
doble conversión, en línea, con salida permanente de onda sinusoidal y cero tiempo de transferencia adecuado para todas las
aplicaciones avanzadas de red. Cada sistema proporciona respaldo por batería de larga duración con autonomía extendida opcional y
capacidad de comunicaciones por Web. Las interfaces incorporadas incluyen USB, serial RS-232 y Apagado de Emergencia (EPO). La
pantalla LCD interactiva del panel frontal proporciona estado detallado del UPS, opciones de configuraciones predeterminadas y control.
La eficiencia máxima opcional y las opciones de estrategia de energía auto-adaptable permiten la operación con alta eficiencia con
consumo de energía y emisión de calor reducidos.
Lista de Partes
Sistema UPSOrejas de Instalación Atornillables (2)Juego de riel para 4 postes
Owner’s Manual
Owner’s Manual
Cable USBCable RS-232Manual del Propietario
Accesorios Adicionales (Todos los Modelos; Opcional)*
• SNMPWEBCARD: tarjeta de interna de interfaz de red para control y monitoreo por SNMP/Web
• WEBCARDLX: Tarjeta Para Administración Web
• 2POSTRMKITWM: Soporta UPS y módulos de baterías para instalación en rack en configuraciones para instalación en rack de 2
postes o instalación en pared
•
2-9USTAND: Soporta UPS y módulos de baterías en configuración de torre vertical
* Modelos selectos se embarcan también con cables adaptadores opcionales de Entrada/Salida.
Accesorios Específicos del Modelo (Opcionales)*
Modelo de UPSSUINT1000LCD2USUINT1500LCD2USUINT2200LCD2USUINT3000LCD2U / SU3000LCD2UHV
Módulos de Baterías
Externas “SMART”**
Módulos de Baterías
Externas “NON-SMART”**
* Para información detallada de autonomía extendida y opciones de accesorios adicionales, visite la página de especificación para su Sistema UPS en tripplite.com.
** Para configuración de batería externa, consulte opciones y método de configuración en la sección de Operaciones. Los módulos de baterías SMART son detectados
automáticamente por el UPS.
BP24V36-2USBP36V27-2USBP48V27-2USBP72V18-2US
BP24V15RT2U (límite 1),
BP24V28-2U (límite 1),
BP24V70-3U
BP36V15-2U (límite 1)
BP36V42-3U
BP48V24-2U (límite 1)
BP48V60RT3U
BP72V15 (límite 1)
BP72V28RT3U
Instrucciones Importantes de Seguridad
CONSERVE ESTAS INSTRUCCIONES
Este manual contiene instrucciones y advertencias que deben seguirse durante la instalación, operación y almacenamiento de
todos los Sistemas UPS de Tripp Lite. La omisión en la observancia de estas advertencias puede afectar su garantía.
Advertencias para la Ubicación del UPS
• Instale su UPS en interiores, alejado de humedad o calor excesivos, contaminantes conductores, polvo o luz solar directa.
• Para mejor desempeño, mantenga la temperatura interior entre 0º C y 40º C.
• Deje espacio adecuado alrededor del UPS para una ventilación apropiada.
• No instale la unidad con su panel frontal o posterior viendo hacia abajo (en cualquier ángulo). El instalar de esta manera
inhibirá seriamente el enfriamiento interno de la unidad, causando eventualmente daño al producto no cubierto por la garantía.
29
Instrucciones Importantes de Seguridad
Advertencias para la Conexión del UPS
• Conecte su UPS directamente a un tomacorriente de CA conectado correctamente a tierra. No enchufe el UPS en sí mismo; esto
dañará al UPS.
• No modifique la clavija del UPS y no use un adaptador que pueda eliminar la conexión a tierra del UPS.
• No use cables de extensión para conectar el UPS a un tomacorriente de CA. Si utiliza supresores de sobretensiones distintos a los
Tripp Lite para conectar su UPS a un tomacorriente, invalidará su garantía.
• Si el UPS recibe alimentación de un generador de CA activado por motor, debe probarse que el generador proporciona una salida de
grado computadora, limpia y filtrada.
• El tomacorriente que alimenta al UPS debe estar próximo al UPS y ser fácilmente accesible.
• Para eliminar el voltaje de CA del UPS, extraiga la clavija del tomacorrientes.
Advertencias para la Conexión del Equipo
• No se recomienda el uso de este equipo en aplicaciones de soporte de vida en donde la falla de este equipo pueda
consecuentemente causar la falla del equipo de soporte de vida o afectar significativamente su seguridad o efectividad.
• No conecte supresores de sobretensiones o cables de extensión a la salida de su UPS. Esto puede dañar al UPS y afectar las
garantías del supresor de sobretensiones y del UPS.
• Conecte el UPS a un tomacorriente que esté correctamente protegido contra corrientes excesivas, cortocircuitos, y fallas de conexión
a tierra como parte de la instalación del edificio. La protección del tomacorrientes para el UPS debe estar en serie con la alimentación
principal.
• Para reducir el riesgo de incendio, conecte solo a un circuito que tenga una protección contra sobre-corriente del circuito derivado con
una especificación de amperes de acuerdo con el National Electrical Code® (NEC®), ANSI/NFPA 70 o su código eléctrico local. En
Europa, el breaker debe cumplir la norma IEC/EN 60934 y tener una abertura de l contacto de al menos 3 mm. El breaker
recomendado para instalaciones en edificios es de 240V/20A.
Advertencias de la Batería
• Las baterías pueden presentar un riesgo de descarga eléctrica y quemaduras por la alta corriente de corto circuito. Observe las
precauciones apropiadas. No deseche las baterías en un fuego. No abra el UPS o las baterías. No ponga en corto o puentee las
terminales de la batería con objeto alguno. Desenchufe y apague el UPS antes de ejecutar el reemplazo de la batería. Use
herramientas con mangos aislados. No hay partes dentro del UPS a las que el usuario pueda dar servicio. El reemplazo de la batería
debe realizarlo sólo personal de servicio autorizado usando el mismo número y tipo de baterías (Plomo-Ácido Selladas). Las baterías
son reciclables. Para información sobre el reciclado, refiérase a sus códigos locales para los requisitos de desecho o visite
tripplite.com/UPSbatteryrecycling. Tripp Lite ofrece una línea completa de Cartuchos de Batería de Repuesto (R.B.C.) para Sistema
UPS. Visite Tripp Lite en el sitio tripplite.com/support/battery/index.cfm para determinar la batería de repuesto específica para su UPS.
Nota: Para la configuración de la batería externa, consulte opciones y método de configuración en la sección de Operaciones. Los MÓDULOS DE BATERÍAS SMART son
detectados automáticamente por el UPS.
Diagrama de Bloques del Circuito del UPS
30
Loading...
+ 106 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.