Tripp Lite SU80K User Manual

PROTECT YOUR
INVESTMENT!
Owner’s Manual
1
Completed and signed start-up forms
MUST be submitted and approved
by Tripp Lite to activate your warranty.
SmartOnline™ 3-Phase UPS System
Model: SU80K
Input/Output: 120/208V AC, 50/60 Hz, 3Ø, 4-wire + ground, wye
2
3
4
5
6
7
8
9
10
11
12
13
1111 W. 35th Street, Chicago, IL 60609 USA
(773) 869-1234 • www.tripplite.com
Copyright © 2008 Tripp Lite. All trademarks are the sole property of their respective owners.
1
200803004 93-2793 SU80k manual 4C.indd E1200803004 93-2793 SU80k manual 4C.indd E1 6/16/2008 1:43:06 PM6/16/2008 1:43:06 PM
Table of Contents
1
1 Introduction 3
2 Important Safety Instructions 4
2
3 Control Panel Features 6 4 Front and Rear Panel Features 7 5 Cabinet Installation 9
3
5-1 Preparation 9 5-2 Unpacking 9 5-3 Placement 10
6 Wiring 11
4
6-1 Wiring Warnings 11 6-2 Wiring Preparation 11 6-3 UPS System Terminal Block Diagram 12 6-4 External Battery Cabinet Wiring Diagrams 12
5
6-5 Electrical and Cable Data 13 6-6 External Battery Cabinet Wiring 14 6-7 AC Input/Output Wiring (Single UPS) 15 6-8 AC Input/Output Wiring (Parallel UPS – Single Input) 16
6
7 Operating Modes 17
7-1 Online (Normal) Mode (Single UPS) 17 7-2 Battery Backup Mode (Single UPS) 17
7
7-3 Auto Bypass Mode (Single UPS) 17 7-4 Manual Bypass Mode (Single UPS) 17 7-5 Online Mode (Parallel UPS) 18 7-6 Battery Backup Mode (Parallel UPS) 18
8
7-7 Auto Bypass Mode (Parallel UPS) 18 7-8 Manual Bypass Mode (Parallel UPS) 19
8 Start-Up, Shutdown and Bypass 20
8-1 Control Panel and Breaker Diagrams 20
9
8-2 Preliminary Checklist (Single UPS) 20 8-3 Normal Start-Up Procedure (Single UPS) 20 8-4 Battery Start-Up Procedure (Single UPS) 21 8-5 Manual Bypass Procedure (Single UPS) 22
10
8-6 Shutdown Procedure (Single UPS) 22 8-7 Preliminary Checklist (Parallel UPS) 23 8-8 Start-Up Procedure (Parallel UPS) 23 8-9 Shutdown Procedure (Parallel UPS) 24
11
8-10 Manual Bypass Procedure (Parallel UPS) 25 8-11 Switching from Manual Bypass to Normal (Parallel UPS) 26
9 Display and Confi guration 27
9-1 Control Panel Diagram 27 9-2 Display Hierarchy 27 9-3 Default Display 27 9-4 Status Messages and Diagrams 28 9-5 Main Menu 30 9-6 UPS System “Measure” Menu 30 9-7 UPS System Setup Menu 31 9-8 Bypass Setup Menu 31 9-9 Output Setup Menu 32 9-10 Battery Setup Menu 33 9-11 Local Setup Menu 35 9-12 Maintenance Menu 36 9-13 Statistics Menu 37 9-14 Event Log Menu 38 9-15 Manual Setup & Test Menu 39 9-16 Firmware Upgrade Menu 40 9-17 Other Menu Choices 40
10 Communications 41
10-1 Communications Interfaces 41 10-2 SNMPWEBCARD Slot 41 10-3 Input Dry Contact Interface 41 10-4 Remote Emergency Power Off (EPO) Circuit Diagram 42 10-5 Auxiliary Dry Contact Input Circuit Diagram 42 10-6 External Battery Cabinet Temperature Inputs 42 10-7 External Battery Status Input 42 10-8 Output Dry Contact Interface Detail 43 10-9 Output Dry Contact Circuit Diagram 44 10-10 RS-232 Serial Port Circuit Diagram 45 10-11 Parallel Redundancy Port 45
11 Specifi cations 46
11-1 UPS System Technical Specifi cations 46 11-2 UPS System Floor Loading Table 46 11-3 Battery Pack Floor Loading Table 46
12 Storage and Service 47 13 Warranty and Warranty Registration 47
Español 48 Français 95
12
13
2
200803004 93-2793 SU80k manual 4C.indd E2200803004 93-2793 SU80k manual 4C.indd E2 6/16/2008 1:43:07 PM6/16/2008 1:43:07 PM
1 – Introduction
Tripp Lite’s SmartOnline 3-Phase UPS Systems are ideal for backing up and protecting data centers, telecommunications (VoIP), networks, industrial facilities, security/emergency systems and more.
1
Advanced Features:
True on-line double conversion with superior IGBT inverter technology• Low input current THD allows 1:1 generator sizing for maximum efficiency and cost savings• Internal N+1 power module redundancy• Built-in parallel redundancy (1+1) capability for increased capacity or fault-tolerance• Up to 80kVA capacity in a compact footprint; up to 160kVA in parallel redundancy (1+1) configuration• High input power factor and high efficiency with low thermal loss and low noise• Simplified, easy-to-repair, long-life, high-availability system design• Redundant auxiliary power and control circuits• All models support external battery cabinets for extended battery backup runtime• High-resolution LCD status screen simplifies operation and delivers detailed operational information, including system block diagrams
2
3
4
5
6
7
8
9
10
11
12
13
3
200803004 93-2793 SU80k manual 4C.indd E3200803004 93-2793 SU80k manual 4C.indd E3 6/16/2008 1:43:07 PM6/16/2008 1:43:07 PM
2 – Important Safety Instructions
1
SAVE THESE INSTRUCTIONS
All sections of this manual contains instructions and warnings that should be followed during the installation and operation of the UPS
2
systems described in this manual. Read all instructions thoroughly before attempting to move, install or operate the UPS systems described in this manual. Failure to comply may invalidate the warranty and cause property damage and/or personal injury.
Location Warnings
3
Install the UPS system in a controlled indoor environment, away from moisture, temperature extremes, flammable liquids and gasses, conductive • contaminants, dust and direct sunlight.
Install the UPS system in a level, structurally sound location.
4
The UPS system is extremely heavy; be extremely careful when moving or lifting the unit.• Operate the UPS system at indoor temperatures between 32° F and 104° F (0° C and 40° C) only. For best results, maintain indoor temperatures
between 62° F and 84° F (17° C and 29° C). Leave adequate space around all sides of the UPS system for proper ventilation. Do not block, cover or insert objects into the external ventilation
5
openings of the cabinet. Do not place any object on the unit, especially containers of liquid.• Do not mount the unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the unit’s internal
cooling, eventually causing product damage not covered under warranty.
6
Do not install the UPS system near magnetic storage media, as this may result in data corruption. Keep all recorded magnetic media a minimum • of 60 cm (24 inches) away from the UPS system.
Do not attempt to stack the UPS system. Attempting to stack the UPS system may cause permanent damage and create a potential for serious • personal injury.
7
The casters are designed for minor position adjustments within the final installation area only. The casters are not designed for moving the UPS • system over longer distances.
The casters are not designed to provide long-term support for the UPS system after final installation. Use the levelers to provide long-term • support.
8
When moving the UPS system, push from the front or rear, not from the sides.• Do not attempt to unpack or move the UPS system without assistance.
Connection Warnings
9
The power supply for this unit must be three-phase rated in accordance with the equipment nameplate. It also must be suitably • grounded according to all applicable local electrical wiring regulations.
The UPS system contains hazardous high voltages that have the potential to cause personal injury or death from electric shock.
10
11
12
The UPS system has its own energy source (battery – internal and/or external). The output terminals may be live even when the UPS system is • not connected to an AC supply.
If the UPS system receives power from a motor-powered AC generator, the generator must provide clean, filtered, computer-grade output.• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
The UPS system is designed to power modern computer loads and associated peripheral devices. Do not use the UPS system to power pure • inductive or capacitive loads.
Input and output wiring should be performed by trained, qualified electricians only.• Due to high leakage current, a proper earth ground connection is essential before connecting the AC supply.• Isolate the UPS system before working on the circuit. An easily accessible disconnect device should be incorporated in the fixed wiring. The
disconnect device must be a 4-pole device and must disconnect all line conductors and the neutral conductor.
13
4
200803004 93-2793 SU80k manual 4C.indd E4200803004 93-2793 SU80k manual 4C.indd E4 6/16/2008 1:43:08 PM6/16/2008 1:43:08 PM
2 – Important Safety Instructions (continued)
Battery Warnings
The UPS system does not require routine maintenance. There are no user-serviceable parts inside. Only qualified service personnel should open • the access panels for any reason.
Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement should be performed • only by qualified service personnel, observing proper precautions. Turn off the UPS system before connecting or disconnecting internal batteries. Use tools with insulated handles. Do not open the batteries. Do not short or bridge the battery terminals with any object.
Replace batteries with equivalent batteries available from Tripp Lite. Do not operate the UPS system without batteries.• The batteries are recyclable. Refer to local codes for disposal requirements.• Do not dispose of the batteries in a fire, mutilate the batteries or open the battery coverings.• Battery fuses should be replaced by qualified service personnel only. Blown fuses must be replaced with the same number and type of fuses. • Potentially lethal voltages exist within the UPS system as long as the battery supply is connected. Service and repair should be performed
by trained personnel only, while the UPS system is turned off or placed into bypass mode. Disconnect internal batteries (if present) before performing any service work by switching off the internal battery circuit breaker and removing the battery fuse(s). Disconnect external batteries (if present) by switching off the external battery cabinet breaker and disconnecting the external battery cabling from the UPS system.
Do not connect or disconnect batteries when the UPS system is operating from the battery supply or when the unit is not in bypass mode.• Do not remove the plastic sleeves covering internal batteries.• Internal and external batteries must be replaced by equivalent batteries available from Tripp Lite.• Before connecting an external battery cabinet to the UPS system, read the external battery cabinet’s documentation. Use only external battery
cabinets that have been approved by Tripp Lite. If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS
system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.
Wiring Warnings
See Section 6-1 for wiring warnings
1
2
3
4
5
6
7
8
9
10
11
12
13
5
200803004 93-2793 SU80k manual 4C.indd E5200803004 93-2793 SU80k manual 4C.indd E5 6/16/2008 1:43:08 PM6/16/2008 1:43:08 PM
3 – Control Panel Features
1
A E F G H I J KBCD
2
3
4
“NORMAL” LED: This green light illuminates to indicate that the UPS system is in online (normal) mode. The primary AC input supply is
A
present and within standard operating parameters. “BATTERY” LED: This amber light illuminates when the UPS system is in battery backup mode, discharging the batteries to provide power
B
5
6
7
8
9
10
11
12
to connected equipment. An audible alarm will also sound. “BYPASS” LED: This amber light illuminates when the UPS system is in bypass mode (auto bypass or manual bypass). Battery backup
C
power will not be available to connected equipment while the UPS system is in bypass mode, but connected equipment loads will be supported by the bypass power source.
“FAULT” LED: This red light illuminates when any UPS system or input power fault occurs. Available diagnostic information will be
D
displayed on the LCD screen. LCD Status Screen: This illuminated LCD status screen displays text and graphics to indicate a wide range of UPS system operating
E
conditions and diagnostic data. Note: The LCD backlight will turn off after 10 minutes of inactivity. Turn on the backlight by momentarily pressing the ON button or one of the scroll buttons.
“ESC” (Escape) Button: Press this button to return to the previous page or menu.
F
G
Scroll Buttons ( and ): Press these buttons to move the cursor up or down and navigate the control panel menus and screens. These buttons are also used for data entry in several screens.
Enter Button ( ): Press this button to select a menu item or confirm a setting change.
H
ON Button: Press and hold this button for 3 seconds to turn the UPS system’s inverter ON.
I
J
OFF Button: Press and hold this button for 3 seconds to turn the UPS system’s inverter OFF. If the UPS system is in online (normal) mode, it will switch to auto bypass mode. Note: If the UPS system remains off for an extended period of time, the batteries should be recharged
periodically. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.
“EPO” (Emergency Power Off) Button: Press this button to turn the UPS system’s output OFF and also disable bypass output.
K
If the UPS system is in battery backup mode when the EPO button is activated:
Main output and bypass output are turned off, the alarm sounds, fans shut down after approximately one minute, and control circuitry
remains active.
Releasing the EPO button (by pressing it again) turns off the UPS system completely, including the alarm and control circuit. Press the
ON button for 3 seconds to restart the UPS system.
If the UPS system is in online (normal) mode when the EPO button is activated:
Main output and bypass output are turned off, the alarm sounds, fans and control circuitry remain active.• Releasing the EPO button (by pressing it again) turns off the alarm and places the UPS system in auto bypass mode. Press the ON button
for 3 seconds to return the UPS system to online (normal) mode.
See Section 9 – Display and Configuration for detailed information about the control panel’s menus and displays.
13
6
200803004 93-2793 SU80k manual 4C.indd E6200803004 93-2793 SU80k manual 4C.indd E6 6/16/2008 1:43:08 PM6/16/2008 1:43:08 PM
4 – Front and Rear Panel Features
A
1
2
B
4
5
3
C
6
7
8
D
E
SU80K shown (front)
Note: Individual models may vary from diagrams. Unit shown with front bezels removed.
Control Panel: The control panel allows the operator to monitor and control the UPS system. See Section 3 – Control Panel Features for
A
more information.
B
Internal Power Modules: 20kVA internal power modules can be replaced in the field without powering down connected equipment loads. The number of internal power modules varies by model. The internal power modules are capable of N+1 redundancy.
Main Input Circuit Breaker Switch (Q1): Controls AC input power to the UPS system during online (normal) operation.
C D
Levelers: The levelers provide long-term support for the UPS system.
E
Casters: The casters are designed for small position adjustments within the final installation location only; they are not designed for moving the UPS system over longer distances. The casters are not designed to provide long-term support for the UPS system after final installation. Use the levelers to provide long-term support.
D
9
10
11
12
13
7
200803004 93-2793 SU80k manual 4C.indd E7200803004 93-2793 SU80k manual 4C.indd E7 6/16/2008 1:43:09 PM6/16/2008 1:43:09 PM
4 – Front and Rear Panel Features (continued)
1
H
2
3
4
5
F
I G J
L
M N
6
7
8
D
SU80K shown (rear)
Note: Individual models may vary from diagrams. Unit shown with breaker guard removed.
9
D
Levelers: The levelers provide long-term support for the UPS system.
E
Casters: The casters are designed for small position adjustments within the final installation location only; they are not designed for moving the UPS system over longer distances. The casters are not designed to provide long-term support for the UPS system after final installation.
10
11
12
13
Use the levelers to provide long-term support.
F
Accessory Slot: Remove the cover panel to install a Tripp Lite SNMPWEBCARD accessory. The SNMPWEBCARD accessory provides an Ethernet interface for the UPS system and enables remote monitoring and control via SNMP, Web browser or telnet. Call (773) 869-1234 for more information about the SNMPWEBCARD accessory.
G
RS-232 Serial Communications Port: This DB9 port connects the UPS system to compatible workstations or servers, enabling automatic shutdown during extended blackouts and monitoring of operating and power conditions.
H
Parallel Redundancy Port: This DB9 port connects the UPS system to another UPS system of identical type and capacity for use in a parallel redundancy (1+1) configuration. See Section 6 – Wiring and Section 7 – Operating Modes for more information.
I
Input Dry Contact Interface: This interface receives dry contact signals that allow the UPS system to receive commands and monitor external battery conditions. See Section 10 - Communications for more information.
J
Output Dry Contact Interface: This interface allows the UPS system to send information via dry contact communications. See Section 10 –
Communications for more information.
K
Terminal Block Cover: Remove the terminal block cover to access the UPS system’s input, external battery cabinet, output and grounding connection terminals. Wiring conduits pass through the circular knockouts in the terminal block cover. The UPS system includes alternate circular knockouts in the bottom panel. See Section 6 – Wiring for more information, including a detailed diagram of the terminal block.
L
Bypass Input Circuit Breaker Switch (Q2): Controls AC input power to the UPS system during auto bypass operation.
M
Manual Bypass Circuit Breaker Switch (Q3): Controls AC input power to the UPS system during manual bypass operation.
N
Output Circuit Breaker Switch (Q4): Controls AC output power.
E
K
D
8
200803004 93-2793 SU80k manual 4C.indd E8200803004 93-2793 SU80k manual 4C.indd E8 6/16/2008 1:43:09 PM6/16/2008 1:43:09 PM
5 – Cabinet Installation
1
Read Section 2 – Important Safety Instructions Before Installation
5-1 Preparation
The UPS system must be installed in a structurally sound area with a level floor that is able to bear the weight of the UPS system, any external battery cabinet and other equipment that will be installed nearby. The installation site should also have a dedicated AC circuit available that is compatible with the UPS system’s input requirements. (See Section 11 – Specifications for details on input requirements and floor loading requirements.) Before unpacking the unit, you should transport the shipping container closer to the final installation site to minimize the distance you will need to move the unit after the protective shipping container has been removed. If you plan to store the UPS system for an extended period before installation, follow the instructions in Section 12 – Storage and Service. (Unpacking and storage instructions are also printed on the “Unpacking and Storage Instructions” sheet secured to the shipping container.) Warning: Do not attempt to unpack or move the UPS system
without assistance.
5-2 Unpacking
1-2
Inspect the shipping container(s) for visible damage. If you determine that the unit has been damaged during shipping, contact Tripp Lite for assistance. Do not attempt to use the UPS system if it has been damaged or mishandled.
Confirm that the shipping container is upright and use a screwdriver to remove its top panel, front panel and back panel. Also remove the plastic wrap and interior cushioning material. Confirm that the model name and rating at the rear of the cabinet match the unit you ordered. Examine the cabinet for any damaged or loosened parts. Confirm that the shipping container includes the accessories that ship with the unit. The UPS system should include an RS-232 serial cable, a parallel redundancy cable, a remote EPO wiring connector, a dry contact input connector (4 contacts), a dry contact output connector (12 contacts) and a software CD-ROM. If anything is missing or damaged, contact Tripp Lite for assistance.
Confirm that the unit is stable, then remove the side panels from the shipping container.
1
2
3
4
5
6
7
8
Remove the bolts from the shipping brackets securing the unit
3
to the pallet, then remove the shipping brackets from the UPS system. Warning: Be extremely careful, as the unit could shift
unexpectedly.
Use several of the screws you removed in step 1 to attach the top panel of the shipping container to the front edge of the shipping pallet. The smooth surface of the panel should face upward so that it can be used as a ramp for rolling the unit off the shipping pallet. Do not attempt to use the top panel as a ramp if it is cracked or otherwise structurally damaged. Make sure the casters at the bottom of the unit are unlocked. Using extreme caution, slowly roll the unit down the ramp with the aid of several assistants.
9
10
2
11
12
13
3
9
200803004 93-2793 SU80k manual 4C.indd E9200803004 93-2793 SU80k manual 4C.indd E9 6/16/2008 1:43:10 PM6/16/2008 1:43:10 PM
5 – Cabinet Installation (continued)
1
5-3 Placement
Use the casters to move the UPS system for a short distance over
1
2
3
4
5
6
7
8
9
a level, smooth, stable surface. Do not attempt to use the casters to move the UPS system over longer distances. The UPS system should be moved close to its final installation location inside its shipping container before it is unpacked from the shipping container. Use a mechanical device of sufficient capacity to move the shipping container. Warning: The UPS system could tip if it
is moved over an unstable surface. Be extremely careful when moving the UPS system. Push the UPS system from the front or rear, not from the sides.
2
Position the UPS system in a structurally sound area with a level floor that is able to bear the weight of the UPS system, any external battery cabinets and other equipment that will be installed nearby. The installation site should also have a dedicated AC circuit available that is compatible with the UPS system’s input requirements. (See Section 11 – Specifications for more information about input requirements and floor loading requirements.) The UPS system must be installed in a clean, secure environment with a relative humidity less than 90% (non­condensing). Operate the UPS system at indoor temperatures between 17° C and 29° C (62° F and 84° F). Prevent damage to cabling by using suitable protective conduits. In order to maintain proper airflow and service access, you must maintain the following clearances:
At least 100 cm clearance in front of the UPS system.• At least 50 cm clearance behind the UPS system.• At least 50 cm clearance above the UPS system.
Warning: The cooling fans circulate air from front to back. Do not use any air conditioning or fan that blows air directly toward the rear of the UPS system.
After moving the UPS system to its final location, lock the casters
3
A
and use the levelers B to stabilize the cabinet. Ensure that all
four levelers make firm contact with the floor.
1
50 cm
50 cm
100 cm
2
10
A
B
11
For emergency use, install a fire extinguisher rated for energized
4
electrical equipment fires (Class C rating or exact equivalent, with a non-conductive extinguishing agent) near the UPS system.
3
12
13
200803004 93-2793 SU80k manual 4C.indd E10200803004 93-2793 SU80k manual 4C.indd E10 6/16/2008 1:43:10 PM6/16/2008 1:43:10 PM
4
10
6 – Wiring
DANGER! LETHAL HIGH VOLTAGE HAZARD!
All wiring should be performed by a qualifi ed electrician, in accordance with the warnings in this manual and all applicable electrical and safety codes. Incorrect wiring may damage the UPS system severely and cause serious personal injury and property damage. Read
Section 2 – Important Safety Instructions before proceeding.
1
2
6-1 Wiring Warnings
De-energize all input and output power sources of the UPS system before installing cables or making electrical connections.• Use flexible cable of sufficient length to permit UPS system servicing. The maximum cable length is 10 m (32.8 ft).• Use ferrule caps to cover termination cables and prevent frayed ends from shorting on the UPS system terminal block.• Use cabling rated VW-1, FT-1 or better.• Use cable sleeves and connector clamps.• The neutral conductor must be the same size as the current conductors.• Tighten all connections with a torque of at least 3.95 N·m (35 in·lb)• Confirm that all cables are marked correctly according to their purpose, polarity, phase and diameter.• If the UPS system’s input/output power source is wye-wye, then “Neutral” and “Ground” must not be connected.• If the input power source has V
system’s “Neutral” and “Ground” together. For equipment requiring a neutral connection to an IT power distribution system, the disconnect device must be a four-pole device and must
disconnect all line conductors and the neutral conductor. If a disconnect device interrupts the neutral conductor, it must simultaneously interrupt all line conductors.
Allow the batteries to charge uninterrupted for 24 hours after the initial wiring connection.• Observe proper polarity by connecting negative to negative and positive to positive. Failure to observe proper polarity will damage the UPS
system and create a serious risk of personal injury and property damage. Observe proper phase by connecting R to R, S to S, T to T and N to N. Failure to observe proper phase will damage the UPS system and create a
risk of personal injury and property damage.
>0, install an isolation transformer before the UPS system and input power source, then connect the UPS
NG
3
4
5
6
7
8
6-2 Wiring Preparation
De-energize all input and output (AC and DC) of the UPS system and external battery cabinet (if present).• Mark all cables according to their correct purpose, polarity, phase and diameter.• Review the diagrams in Section 6-3 and Section 6-4 to familiarize yourself with the terminal blocks. Consult the table in Section 6-5 to find the correct electrical input/output characteristics for the UPS system.
Note: If the UPS system’s input/output power source is wye-wye, then “Neutral” and “Ground” must not be connected. If the input power source has VNG>0, install an isolation transformer before the UPS system and input power source, then connect the UPS system’s “Neutral” and “Ground” together.
9
10
11
12
13
11
200803004 93-2793 SU80k manual 4C.indd E11200803004 93-2793 SU80k manual 4C.indd E11 6/16/2008 1:43:11 PM6/16/2008 1:43:11 PM
6 – Wiring (continued)
1
6-3 UPS System Terminal Block Diagram
2
Input
3
4
5
6
7
6-4 External Battery Cabinet Wiring Diagrams
Output
External
Battery
Connection
Grounding Terminals
10
11
12
13
8
9
External Battery Cabinet Breaker
Switch
+
+
SU80K and BP480V40C shown for illustration only; consult the battery cabinet’s documentation for exact specifications
12
200803004 93-2793 SU80k manual 4C.indd E12200803004 93-2793 SU80k manual 4C.indd E12 6/16/2008 1:43:11 PM6/16/2008 1:43:11 PM
6 – Wiring (continued)
T
6-4 External Battery Cabinet Wiring Diagrams (continued)
1
XFMR XFMR
UPS
B+ N B-
External Battery Cabinet B Cabinet: 26AH per Battery
C Cabinet: 40AH per Battery
6-5 Electrical and Cable Data
Q1Q2
12V, 20 Batteries 12V, 20 Batteries
AC/DCMAIN INPUT
B+ B-N
DC/AC
Q3
Q4
2
3
OUTPU
4
5
6
7
Input and Output Battery Input and Output Battery Model Input/Output Breaker Size Fuse Size Cable Size Cable Size
SU80K 120/208V AC, 3Ø, 300A 220A 4/0 AWG 2 AWG 4-wire + ground, wye
8
9
10
11
12
13
13
200803004 93-2793 SU80k manual 4C.indd E13200803004 93-2793 SU80k manual 4C.indd E13 6/16/2008 1:43:13 PM6/16/2008 1:43:13 PM
6 – Wiring (continued)
1
6-6 External Battery Cabinet Wiring
Warning: External battery cabinets vary. Read the external battery cabinet’s documentation before attempting to connect it to the UPS
2
system. Use only external battery cabinets that have been approved by Tripp Lite.
Note: An external battery cabinet is required. Contact Tripp Lite for external battery cabinet ordering information.
De-energize all input and output (AC and DC) of the UPS system
1
and external battery cabinet, and confirm that the external battery
A
3
cabinet breaker switch been wired to an AC power source, see instructions.)
4
is off. (If the UPS system has already
Section 8-6 for shutdown
A
10
11
5
external battery cabinet.
Remove the terminal block covers from the UPS system and
2
1
6
Connect the positive (+), neutral (N) and negative (-) UPS
3
7
8
9
system connection terminals of the external battery cabinet to the corresponding positive (+), neutral (N) and negative (-) external battery connection terminals of the UPS system. See Section 6-3 and the external battery cabinet’s documentation for terminal block diagrams. See Section 6-4 for wiring diagrams. See Section
6-5 for cable size requirements. Cabling should be protected by
flexible conduit and routed through the appropriate knockouts in the terminal block cover. Warning: Observe proper polarity by
connecting negative to negative and positive to positive. Failure to observe proper polarity will damage the UPS system and create a risk of personal injury and property damage.
Connect the external battery cabinet’s grounding terminal
4
UPS system’s corresponding grounding terminal (5.189 mm) ground cable. Keep the ground cable connected at all times after installation.
Connect the UPS system’s grounding terminal
5
earth ground ground cable connected at all times after installation.
Replace the terminal block cover of the external battery cabinet. If
6
you do not plan to wire the AC input/output of the UPS system at this time, replace the terminal block cover of the UPS system.
with a 4 AWG (5.189 mm) ground cable. Keep the
B
with a 4 AWG
B
to your facility’s
A
A
to the
2
+
3
A
4
+
B
12
A
B
13
65
14
200803004 93-2793 SU80k manual 4C.indd E14200803004 93-2793 SU80k manual 4C.indd E14 6/16/2008 1:43:13 PM6/16/2008 1:43:13 PM
6 – Wiring (continued)
6-7 AC Input/Output Wiring (Single UPS)
After de-energizing all input and output (AC and DC) of the UPS
1
system, remove the terminal block cover from the UPS system.
1
2
3
If you did not connect the ground cable in
2
UPS system’s grounding terminal
B
with a 4 AWG (5.189 mm) ground cable. Keep the ground cable
Section 6-6, connect the
A
to your facility’s earth ground
connected at all times after installation.
Remove the UPS system’s front bezel to expose the circuit breaker.
3
First, confirm that the main input circuit breaker switch the bypass input circuit breaker switch
are both off. Second,
B
confirm that the manual bypass circuit breaker switch Third, confirm that the output circuit breaker switch
Confirm the phase of each cable, then connect the cables according
4
to the UPS system terminal block diagram in
Section 6-3. See
D
A
C
is off.
Section 6-5 for cable size requirements. Cabling should be
protected by flexible conduit and routed through the appropriate knockouts in the terminal block cover. Warning: Observe proper
phase by connecting R to R, S to S, T to T and N to N. Failure to observe proper phase will damage the UPS system and create a risk of personal injury and property damage.
and
is off.
1
4
B
2
Front Panel
3
OFF
Main Input
O
A
A
5
6
O
OFF
B C D
O
OFF
Back Panel
OFF
O
7
8
9
10
Replace the UPS system’s terminal block cover.
5
4
11
12
5
15
200803004 93-2793 SU80k manual 4C.indd E15200803004 93-2793 SU80k manual 4C.indd E15 6/16/2008 1:43:19 PM6/16/2008 1:43:19 PM
13
6 – Wiring (continued)
1
6-8 AC Input/Output Wiring (Parallel UPS – Single Input)
Parallel Redundancy Warnings:
2
3
4
1
5
2
The total input cable length must be equal to the total • output cable length in order to prevent unbalanced load sharing between two UPS systems under reserve mode (i.e. IP1 + OP1 = IP2 + OP2; deviation must be <10%).
Parallel redundancy only supports 2 UPS systems (1+1 • redundancy ). Do not attempt to link more than two UPS systems via parallel redundancy.
The UPS systems must have the same rating and capacity • for parallel redundancy installation. Attempting to link dissimilar UPS systems will damage the UPS systems and create a serious risk of personal injury and property damage.
Follow the steps in in the diagram.
Connect the included parallel redundancy cable redundancy port
Section 6-7, wiring the UPS systems as shown
A
to the parallel
of each UPS system.
B
1
AC I/P
IP1
IP2
Main I/P
Main I/P
UPS1
UPS2
O/P
Parallel Port
O/P
Parallel Port
OP1
Parallel Cable
Load
OP2
10
11
6
B
A
B
7
2
8
9
12
13
16
200803004 93-2793 SU80k manual 4C.indd E16200803004 93-2793 SU80k manual 4C.indd E16 6/16/2008 1:43:24 PM6/16/2008 1:43:24 PM
7 – Operating Modes
This section provides a basic description of the UPS system’s operating modes. For more information about switching between operating modes, refer to Section 8 – Start-Up, Shutdown and Bypass.
7-1 Online (Normal) Mode (Single UPS)
In online (normal) mode, the UPS system’s rectifier converts incoming AC utility power to DC power that charges the batteries and supplies the inverter. The inverter transforms the DC power to precision-regulated, pure sine wave AC power that supports the operation of connected equipment. This dual conversion technology isolates connected equipment from all power problems and ensures that connected equipment receives ideal power at all times.
MAIN
CB3
CB2
CB1
XFMR XFMR
CB5
STS
CB4
1
2
3
LOAD
4
7-2 Battery Backup Mode (Single UPS)
When a blackout or other extreme power event occurs, the UPS system automatically switches from normal mode to battery backup mode. The UPS system’s batteries (internal and/or external) provide emergency DC power to the inverter. The inverter transforms the DC power to precision-regulated, pure sine wave AC power that supports the operation of connected equipment.
7-3 Auto Bypass Mode (Single UPS)
If the inverter malfunctions due to excessive temperature, overload, output short circuit, abnormal voltage or battery problems, the inverter will shut down. If the UPS system detects a bypass power source that conforms to normal parameters, then the UPS system automatically switches to auto bypass mode to continue supplying power to connected equipment. When all problems are eliminated, the UPS system switches back to online (normal) mode automatically.
7-4 Manual Bypass Mode (Single UPS)
If UPS system maintenance or repair is required, you can bypass the UPS system and enable bypass power manually. After confirming that bypass power is present, switch the UPS system into manual bypass mode. This allows service technicians to perform maintenance or repair jobs without interrupting the flow of AC power to connected equipment.
Warning: The UPS system must be de-energized completely before performing maintenance or repair by shutting it down completely after switching it to manual bypass mode.
LOAD
5
6
MAIN
CB3
CB2
CB1
XFMR XFMR
CB5
STS
CB4
7
MAIN
CB3
CB2
CB1
XFMR XFMR
CB5
STS
8
CB4
LOAD
9
10
CB3
11
MAIN
CB2
CB1
XFMR XFMR
CB5
STS
CB4
LOAD
12
13
17
200803004 93-2793 SU80k manual 4C.indd E17200803004 93-2793 SU80k manual 4C.indd E17 6/16/2008 1:43:27 PM6/16/2008 1:43:27 PM
7 – Operating Modes (continued)
1
7-5 Online Mode (Parallel UPS)
Parallel redundancy (1+1) provides UPS system redundancy or increased total capacity. Under parallel redundancy, the total load is
2
shared by two UPS systems. If one of the UPS systems malfunctions, the total connected equipment load is supported by the remaining UPS system. If the total load exceeds the capacity of the remaining UPS system, it will switch to auto bypass mode.
3
4
MAIN
CB3
CB2
CB3
CB1
XFMR XFMR
CB5
STS
CB4
UPS1
LOAD
5
7-6 Battery Backup Mode (Parallel UPS)
6
Similar to on battery backup mode for a single UPS system (Section
7-2), except the total connected equipment load is shared by the parallel
(1+1) UPS systems.
7
8
9
MAIN
MAIN
MAIN
CB2
CB3
CB2
CB3
CB2
CB1
XFMR XFMR
CB1
XFMR XFMR
CB1
XFMR XFMR
CB5
CB5
CB5
STS
STS
STS
CB4
UPS2
CB4
UPS1
LOAD
CB4
UPS2
10
7-7 Auto Bypass Mode (Parallel UPS)
Similar to auto bypass mode for a single UPS system (Section 7-3), except with parallel (1+1) UPS systems.
CB3
11
12
MAIN
CB2
CB3
CB1
XFMR XFMR
CB5
STS
CB4
UPS1
LOAD
13
MAIN
CB2
CB1
XFMR XFMR
CB5
STS
18
200803004 93-2793 SU80k manual 4C.indd E18200803004 93-2793 SU80k manual 4C.indd E18 6/16/2008 1:43:27 PM6/16/2008 1:43:27 PM
CB4
UPS2
7 – Operating Modes (continued)
7-8 Manual Bypass Mode (Parallel UPS)
Similar to manual bypass mode for a single UPS system (Section 7-4), except with parallel (1+1) UPS systems. Note: Both UPS systems must
be switched into manual bypass mode.
1
CB3
2
MAIN
MAIN
CB2
CB3
CB2
CB1
XFMR XFMR
CB1
XFMR XFMR
CB5
CB5
STS
STS
CB4
UPS1
CB4
UPS2
3
LOAD
4
5
6
7
8
9
10
11
12
13
19
200803004 93-2793 SU80k manual 4C.indd E19200803004 93-2793 SU80k manual 4C.indd E19 6/16/2008 1:43:27 PM6/16/2008 1:43:27 PM
8 – Start-Up, Shutdown and Bypass
1
8-1 Control Panel and Breaker Diagrams
“NORMAL” LED
A
2
3
4
5
6
“BATTERY” LED
B
“BYPASS” LED
C
“FAULT” LED
D
LCD Status Screen
E
“ESC” (Escape) Button
F
Scroll Buttons ( and )
G
Enter Button ( )
H
ON Button
I
OFF Button
J
“EPO” (Emergency Power Off) Button
K
Output Circuit Breaker Switch
L
Manual Bypass Circuit Breaker Switch
M
Bypass Input Circuit Breaker Switch
N
Main Input Circuit Breaker Switch
O
O
OFF
Main Input
O
Front Panel
E
A
B
C
D
Control Panel
O
OFF
Circuit Breaker Switches
F
I
G
J
H
O
OFF
Back Panel
K
O
OFF
LN M
8-2 Preliminary Checklist (Single UPS)
All circuit breaker switches should be off, including the breaker of the external battery cabinet (if present).• Confirm that no voltage potential exists between Neutral and Ground.
7
Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS system.
Note: After start-up, the UPS system will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS system will provide AC power to the connected equipment load.
8
8-3 Normal Start-Up Procedure (Single UPS)
If there is an external battery cabinet connected, switch on the
1
circuit breaker A of the external battery cabinet.
9
A
10
1
11
12
2
Confirm that the manual bypass circuit breaker switch
A
is off.
Main
Main Input
Input
O
O
OFF
O
O
OFF
OFF
OFF
OFF
OFF
O
O
OFF
OFF
O
O
A
13
Front Panel
2
Back Panel
Back Panel
Front Panel
20
200803004 93-2793 SU80k manual 4C.indd E20200803004 93-2793 SU80k manual 4C.indd E20 6/16/2008 1:43:27 PM6/16/2008 1:43:27 PM
8 – Start-Up, Shutdown and Bypass (continued)
8-3 Normal Start-Up Procedure (Single UPS) (continued)
3
Switch on the output circuit breaker switch
B
circuit breaker switch
. After a brief initialization process, the LCD screen will show “ON AUTO BYPASS”, the “BYPASS” LED will illuminate and UPS system output will be supplied by the bypass power source.
4
Switch on the main input circuit breaker switch power source is normal, the UPS system is ready for start-up.
Press the ON button
5
A
for 3 seconds (until you hear a beep), then release the button. The inverter will activate and synchronize with the bypass source, then automatically switch from auto bypass mode to online (normal) mode. The “BYPASS” LED will darken and the “NORMAL” LED will illuminate.
A
and bypass input
A
. If the AC input
Front Panel
3
Front Panel
4
Main Input
Main Input
1
O
O
OFF
ON
I
OFF
ON
I
2
3
B A
Back Panel
O
ON
ON
I
I
OFF
ON
I
A
4
5
Back Panel
A
6
5
8-4 Battery Start-Up Procedure (Single UPS)
Note: The battery must be at least partially charged for this operation to succeed.
If there is an external battery cabinet connected, switch on the
1
circuit breaker A of the external battery cabinet.
1
2
Confirm that the manual bypass circuit breaker switch
3
Press the ON button
A
for 3 seconds (until you hear a beep), then release the button. The inverter will activate and use stored DC battery power to supply AC power to connected equipment. The “BATTERY” LED will illuminate.
A
is off.
2
ON
I
Main Input
Front Panel
7
8
A
9
10
O
ON
I
OFF
ON
I
11
A
Back Panel
12
A
13
3
21
200803004 93-2793 SU80k manual 4C.indd E21200803004 93-2793 SU80k manual 4C.indd E21 6/16/2008 1:43:31 PM6/16/2008 1:43:31 PM
8 – Start-Up, Shutdown and Bypass (continued)
1
8-5 Manual Bypass Procedure (Single UPS)
Warning: Placing the UPS system in manual bypass will disable the inverter and power all loads from the manual bypass source, but
2
the UPS system will still be energized. Before performing maintenance or repair on the UPS system, shut down and de-energize the UPS system completely by following the steps in they will not receive battery backup in the event of a utility power failure.
When the UPS system is in online (normal) mode, press the OFF
1
3
button A for 3 seconds (until you hear a beep), then release the button. The inverter will automatically switch to bypass mode and the “BYPASS” LED will illuminate.
4
Switch on the manual bypass circuit breaker switch
2
off the output circuit breaker switch B.
5
Section 8-6. Although connected equipment loads will be powered by the bypass power source,
A
1
A
, then switch
ON
Main Input
ON
I
I
ON
I
OFF
O
6
8-6 Shutdown Procedure (Single UPS)
7
Front Panel
2
A B
Back Panel
Warning: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm that all loads are turned off or place the UPS system in manual bypass mode to keep loads powered by the bypass power source.
Press the OFF button
1
8
release the button. If the UPS system is in online (normal) mode, it will switch to bypass mode. If the UPS system is in battery backup
A
for 3 seconds (until you hear a beep), then
mode, the inverter will shut down and AC output power will be interrupted.
9
10
11
12
1
2
Switch off the main input circuit breaker switch
A
.
OFF
Main Input
O
ON
I
A
Front Panel
2
3
Switch off the bypass input circuit breaker switch
A
.
O
OFF
OFF
Back Panel
O
OFF
OFF
A
O
O
ON
I
ON
I
Main Input
13
Front Panel
3
A
Back Panel
22
200803004 93-2793 SU80k manual 4C.indd E22200803004 93-2793 SU80k manual 4C.indd E22 6/16/2008 1:43:34 PM6/16/2008 1:43:34 PM
8 – Start-Up, Shutdown and Bypass (continued)
8-6 Shutdown Procedure (Single UPS) (continued)
Confirm that the UPS system is off and that all main output circuits
4
are off. If the UPS system is connected to an external battery cabinet, turn off the external battery cabinet circuit breaker switch
A
.
4
Switch off the output circuit breaker switch
5
power source is normal, the UPS system is ready for start-up.
Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.
A
. If the AC input
Front Panel
5
OFF
Main
Input
1
2
A
3
O
O
OFF
O
OFF
Back Panel
OFF
O
A
4
5
8-7 Preliminary Checklist (Parallel UPS)
Warning: Parallel redundancy requires exactly two UPS systems (1+1 redundancy). Do not attempt to link more than two UPS systems via parallel redundancy. The UPS systems must have the same rating and capacity for parallel redundancy installation. Attempting to link dissimilar UPS systems will damage the UPS systems and create a serious risk of personal injury and property damage.
All circuit breaker switches should be off, including the breakers of the external battery cabinets.• Confirm that no voltage potential exists between Neutral and Ground.• Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS systems.
You must use the control panel to set the parallel ID numbers of the UPS systems to be 1 and 2. See Section 9-11 for information
about setting the parallel ID numbers.
Note: After start-up, the UPS systems will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS systems will provide AC power to the connected equipment load.
8-8 Start-Up Procedure (Parallel UPS)
Connect the parallel redundancy cable
1
redundancy port B of each UPS system.
If the UPS systems have external battery cabinets connected,
2
switch on the external battery cabinet circuit breaker switch A of each battery pack.
A
to the DB9 parallel
B
B
1
A
A
6
7
8
9
10
11
12
2
23
200803004 93-2793 SU80k manual 4C.indd E23200803004 93-2793 SU80k manual 4C.indd E23 6/16/2008 1:43:37 PM6/16/2008 1:43:37 PM
13
8 – Start-Up, Shutdown and Bypass (continued)
1
8-8 Start-Up Procedure (Parallel UPS) (continued)
Switch on the bypass input circuit breaker switch
3
2
UPS system. After a brief initialization process, the LCD screen will show “ON AUTO BYPASS” and the “BYPASS” LED will illuminate.
3
4
Switch on the main input circuit breaker switch
4
system.
5
5
Press the ON button
6
(until you hear a beep), then release the button. The inverter will activate and synchronize with the bypass source. Press the ON button for the other UPS system for 3 seconds (until you hear a beep), then release the button. When the inverter of each UPS system is operating normally, they will automatically switch from
7
auto bypass mode to online (normal) mode at the same time. The “BYPASS” LED will darken and the “NORMAL” LED will illuminate.
6
Check the output voltage of each UPS system. The phase deviation
8
between each UPS system should be less than 5V. If the phase deviation is within the acceptable range, switch on the output circuit breaker switch A of each UPS system. Note: For more
information on checking the output voltage of each UPS system, see Section 9-6.
A
of one of the UPS systems for 3 seconds
9
A
of each
A
of each UPS
Front Panel
3
Front Panel
4
5
Front Panel
6
OFF
Main Input
Main Input
Main
Input
O
O
ON
I
OFF
OFF
O
A
Back Panel
O
ON
ON
I
I
OFF
OFF
O
A
Back Panel
A
O
ON
ON
I
I
OFF
ON
I
A
Back Panel
8-9 Shutdown Procedure (Parallel UPS)
10
Warning: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm that all loads are turned off or place the UPS systems in manual bypass mode to keep loads powered by the bypass power source.
1
For the UPS system you wish to shut down, press the OFF button
A
11
for 3 seconds (until you hear a beep), then release the button. If the other UPS system can support the connected equipment loads alone, the UPS system that was turned off will shut down its inverter and its LCD screen will read “LOAD NOT POWERED”. The other UPS system’s LCD screen will read “ONLINE MODE”.
12
If the total connected equipment load is too large to be handled by a single UPS system, both UPS systems will shut down their inverters and switch to bypass mode, and their LCD screens will
1
A
read “ON AUTO BYPASS”.
2
For the UPS system you wish to shut down, switch off the main
13
200803004 93-2793 SU80k manual 4C.indd E24200803004 93-2793 SU80k manual 4C.indd E24 6/16/2008 1:43:41 PM6/16/2008 1:43:41 PM
input circuit breaker switch A, then switch off the output circuit breaker switch B.
24
Front Panel
2
OFF
Main Input
O
ON
I
A B
O
OFF
Back Panel
OFF
O
8 – Start-Up, Shutdown and Bypass (continued)
8-9 Shutdown Procedure (Parallel UPS) (continued)
For the UPS system you wish to shut down, switch off the bypass
3
input circuit breaker switch
When the UPS system is completely shut down, the LCD screen
4
will be completely off. If the UPS systems have external battery cabinets connected, switch off the external battery cabinet circuit breaker switch A of each battery pack.
Note: If the UPS system remains off for an extended period of time, it
should be turned on periodically to allow the batteries to recharge. The
UPS system should be turned on and the batteries should be recharged
at least one uninterrupted 24-hour period every 3 months. Failure
to recharge the batteries periodically may cause irreversible battery
damage.
A
.
Front Panel
3
4
OFF
Main Input
1
2
O
O
OFF
OFF
O
OFF
O
3
A
Back Panel
A
4
5
8-10 Manual Bypass Procedure (Parallel UPS)
Warning: When the UPS system is in manual bypass, the inverter shuts down. Connected equipment loads are powered by the bypass
power source and will not receive battery backup during a utility power failure.
For the first UPS system you wish to shut down, press the OFF
1
button A for 3 seconds (until you hear a beep), then release the button. If the other UPS system can support the connected equipment loads alone, the UPS system that was turned off will shut down its inverter and its LCD screen will read “LOAD NOT POWERED”. The other UPS system’s LCD screen will read “ONLINE MODE”. If the total connected equipment load is too large to be handled by a single UPS system, both UPS systems will shut down their inverters and switch to bypass mode, and their LCD screens will read “ON AUTO BYPASS”. Repeat step 1 for the second UPS system you wish to shut down.
2
Switch off the main input circuit breaker switch
A
of each UPS
system.
3
Confirm that both UPS systems are shut down, then switch on the manual bypass circuit breaker switch A of each UPS system. The bypass power source will power the loads and the LCD screen will read “ON MANUAL BYPASS”.
1
Front Panel
2
OFF
Main Input
OFF
O
ON
I
A
Back Panel
O
ON
I
OFF
ON
A
O
I
ON
I
ON
I
6
7
8
9
10
11
Main Input
12
13
Switch off the bypass input circuit breaker switch
4
A
circuit breaker switch B of each UPS system. The LCD screen will turn off completely.
and the output
Front Panel
3
OFF
Main Input
A
Back Panel
O
O
OFF
ON
I
OFF
O
A B
Front Panel
4
Back Panel
25
200803004 93-2793 SU80k manual 4C.indd E25200803004 93-2793 SU80k manual 4C.indd E25 6/16/2008 1:43:46 PM6/16/2008 1:43:46 PM
8 – Start-Up, Shutdown and Bypass (continued)
O
OFF
O
OFF
ON
I
1
8-10 Manual Bypass Procedure (Parallel UPS) (continued)
If the UPS systems have external battery cabinets connected,
5
2
switch off the external battery cabinet circuit breaker switch each battery pack.
3
6
In this mode, only the output circuit breaker switch
4
terminal block B contain hazardous voltage, allowing qualified service personnel to perform maintenance or repair. Note:
Qualified service personnel may prefer to de-energize the UPS systems completely, depending on local codes and the nature of the maintenance or repair.
A
5
and the
A
of
A
5
B
6
6
8-11 Switching from Manual Bypass to Normal Mode (Parallel UPS)
If the UPS systems have external battery cabinets connected,
1
switch on the external battery cabinet circuit breaker switch A of each battery pack.
7
8
2
Switch on the bypass input circuit breaker switch circuit breaker switch B of each UPS system.
A
and the output
1
9
3
Confirm that the LCD screens of both UPS systems read “ON
10
11
12
13
MANUAL BYPASS”, then switch off the manual bypass circuit breaker switch A of each UPS system. The LCD screen will read “ON AUTO BYPASS”.
Switch on the main input circuit breaker switch
4
A
of each UPS
system.
5
Press the ON button
A
of the first UPS systems for 3 seconds (until you hear a beep), then release the button. Press the ON button for the second UPS system for 3 seconds (until you hear a beep), then release the button. When the inverter of each UPS system is operating normally, they will switch to online (normal) mode at the same time.
O
ON
Main Input
ON
I
I
OFF
ON
I
Front Panel
2
Front Panel
3
OFF
Main Input
OFF
Main Input
O
O
Back Panel
A
A
ON
I
ON
I
A B
Back Panel
O
ON
I
OFF
A
Back Panel
A
ON
I
ON
I
A
Front Panel
4
200803004 93-2793 SU80k manual 4C.indd E26200803004 93-2793 SU80k manual 4C.indd E26 6/16/2008 1:43:50 PM6/16/2008 1:43:50 PM
Back Panel
5
26
9 – Display and Confi guration
9-1 Control Panel Diagram
“NORMAL” LED
A
“BATTERY” LED
B
“BYPASS” LED
C
“FAULT” LED
D
LCD Status Screen
E
“ESC” (Escape) Button
F
Scroll Buttons ( and )
G
Enter Button ( )
H
I
ON Button OFF Button
J
“EPO” (Emergency Power Off) Button
K
9-2 Display Hierarchy
1
2
E
A
B
C
D
Control Panel
F
I
G
K
3
J
H
4
5
6
7
8
9
10
11
12
13
27
200803004 93-2793 SU80k manual 4C.indd E27200803004 93-2793 SU80k manual 4C.indd E27 6/16/2008 1:43:56 PM6/16/2008 1:43:56 PM
9 – Display and Confi guration (continued)
1
9-3 Default Display
After the UPS system starts up and completes the self-test, the
1
2
3
4
5
6
7
LCD status screen will show the default display. The default display includes a status message and diagram that shows the operational status of the UPS system. If an alarm event occurs, an exclamation point will flash in the lower right corner of the LCD status screen.
Press the scroll down button ( ) to see an event message, which
2
may include diagnostic information. Press the scroll down button ( ) again to see the next message. If no other event messages exist, the screen will return to the default display. Note: Pressing
the “ESC” button will return to the default display.
9-4 Status Messages and Diagrams
The UPS system output is off and the connected equipment loads
1
are not powered. This condition may be due to automatic UPS shutdown or manually switching off the output circuit breaker switch.
1
2
10
11
12
13
8
Connected equipment loads are powered by the bypass power
2
source at initial UPS system start-up.
1
9
2
3
The UPS system is starting up from battery power.
3
The UPS system is in auto bypass mode. Connected equipment
4
loads will lose power if the bypass power source fails.
4
28
200803004 93-2793 SU80k manual 4C.indd E28200803004 93-2793 SU80k manual 4C.indd E28 6/16/2008 1:43:56 PM6/16/2008 1:43:56 PM
9 – Display and Confi guration (continued)
9-4 Status Messages and Diagrams (continued)
The UPS system is operating in online (normal) mode. Connected
5
equipment loads will receive battery backup power if the mains (utility or generator) power source fails.
The UPS system has switched to battery backup (on battery) mode.
6
Connected equipment loads are receiving battery backup power, and the estimated remaining runtime is shown. Note: The battery
parameters must be set correctly in order to receive accurate runtime estimates from the UPS system when it switches to battery backup mode. See Section 9-10 for more information.
7
The UPS system has switched to battery backup (on battery) mode. Connected equipment loads are still receiving AC power inverted from battery power, but battery power is nearly depleted.
1
2
3
5
4
5
6
6
8
The UPS system is performing a battery test.
9
The UPS system is operating in economy mode, and connected equipment loads are being powered by the bypass source.
7
7
8
9
8
10
11
9
12
The UPS system is in manual bypass mode in order to allow
10
qualified service personnel to perform maintenance or repair on the UPS system. Connected equipment loads will lose power if the bypass power source fails.
10
29
200803004 93-2793 SU80k manual 4C.indd E29200803004 93-2793 SU80k manual 4C.indd E29 6/16/2008 1:43:56 PM6/16/2008 1:43:56 PM
13
9 – Display and Confi guration (continued)
1
9-5 Main Menu
From the default display, press the enter button ( ) to access
1
2
3
4
5
6
the main menu. Press the scroll down button ( ) or the scroll up button ( ) to move the cursor. Press the enter button ( ) to select one of the available menu options.
9-6 UPS System “Measure” Menu
Press the enter button ( ) to select “MEASURE” from the main
1
menu. Use the scroll buttons ( or ) to scroll through the available data
2
screens. Press the “ESC” button to return to the previous menu.
1
1
10
11
12
13
7
8
45.0A
45.0A
45.0A
9
BAT STATUS:CHARGING
80.0KVA/64.0KW
80.0KVA/64.0KW
80.0KVA/64.0KW
74A
74A
74A
2
30
200803004 93-2793 SU80k manual 4C.indd E30200803004 93-2793 SU80k manual 4C.indd E30 6/16/2008 1:43:56 PM6/16/2008 1:43:56 PM
Loading...
+ 112 hidden pages