Tripp Lite SU8000RT3UN50TF User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SU8000RT3UN50TF
Highlights
8,000VA (8kVA) on-line 8U rack/tower UPS with expandable runtime (3U
Power Module + 3U Battery Pack + 2U step-down transformer) with twist-lock
208/240V 50A input plug
Zero transfer time, on-line, double-conversion and economy-mode operation
supported
Detachable PDU with manual bypass switch enables hot-swap UPS
replacement without powering off connected loads
Maintains 208V and simultaneous 120V output
2% output voltage regulation over an input voltage range of 156 to 276
Enhanced serial communications ports, SNMP/Web Card Slot and EPO
interfaces
$250,000 Ultimate LIfetime Insurance (USA, Puerto Rico, & Canada only).
Description
8,000VA (8kVA) on-line, double-conversion UPS system for critical server, network and telecommunications equipment. Installs in only 8 rack
spaces (3U power module, 3U battery pack and 2U step-down transformer). Maximum installed rack depth of 32.5 in. Expandable battery runtime
with optional external battery packs. Full-time sine wave 208 and 120V +/-2% output. Actively converts raw incoming AC power to DC, then
re-converts output back to completely regulated, filtered AC output. Operates continuously without using battery power during brownouts to 156V
and overvoltages to 276V. Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs. Includes Hubbell
twist-lock 208V 50A input plug for simple installation; NEMA L6-30R, L6-20R and Nema 5-15/20R output receptacles. Detachable input-output PDU
module with manual bypass switch enables hot-swap UPS replacement without disrupting power to connected equipment. Network-grade AC surge
and noise suppression. Zero transfer time between AC and battery operation. Network management interfaces support communications via RS-232,
contact-closure port and optional SNMPWEBCARD slot. Supports detailed monitoring of equipment load levels, self-test data and utility power
conditions via network interfaces. Includes PowerAlert monitoring software and complete cabling. Includes PowerAlert monitoring software and
complete cabling. Emergency Power Off (EPO) interface. Front panel LEDs offer at-a-glance confirmation of line power status, battery power status,
AC-to-DC conversion, DC-to-AC conversion, bypass mode and output power status. LCD panel with scroll buttons offers detailed diagnostic test
information on startup and during self tests, plus real-time data on input and output voltage, frequency (Hz), load percentage and battery charge
level. LED/LCD display panel easily rotates for viewing in rackmount or tower configurations. Audible alarm. Self-test. Fault-tolerant auto-bypass
mode. 4-post rackmount accessories and 2-9USTAND tower kit included; 2POSTRMKITWM two post rackmount hardware accessories available.
Field replaceable, hot-swappable power module and external battery packs. Attractive all-black color scheme. 2-year warranty and $250,000 connected equipment insurance
connected equipment insurance; extended warranty and service contracts available.
Applications
Ideal for protection of sensitive electronics in any application calling for upright tower or 19 inch rackmount UPS protection. Common applications include any mix of servers, workstations, hubs, routers, concentrators, IP telephony and traditional PBX switching systems
Package Includes
3U power module with detachable hot-swap PDU input/output panel and bypass switch 3U external battery pack, 2U step-down transformer Three sets of 4 post rackmount rails (one for each of the 2U and 3U components) One set of tower stands for upright tower configuration PowerAlert software, complete data cabling, user manual with warranty information
Features
8,000 VA (8kVA) on-line, double-conversion UPS system (High voltage input/High AND low voltage output) Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without powering off connected equipment Installs in only 8 rack spaces (3U power module/3U battery pack/2U step-down transformer) with a maximum installed depth of 32.5 inches Offers 6 min. runtime at full load (8000VA/6400W) and 15 min. at half load (4000VA/3200W). Runtime is expandable with any number of optional external battery packs Full-time sine wave 208V and simultaneous 120V +/-2% output Actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output Operates continuously without using battery power during brownouts to 156V and overvoltages to 276V Includes Hubbell twist-lock 50A AC input plug for simple installation; input cordset is removeable to support professional hardwire installation 2 x NEMA L6-30R, 2 x L6-20R and 12 x 5-15/20R output receptacles Detailed LCD panel with scroll buttons offers detailed diagnostic test Network-grade AC surge and noise suppression Zero transfer time between AC and battery operation Includes slot for internal SNMP/web card, plus DB9 enhanced serial monitoring port, and contact closure port for unattended shudown, remote control and monitoring of UPS system and power data Supports detailed monitoring of equipment load levels, self-test data and mains power conditions via network interfaces. Includes PowerAlert monitoring software and complete cabling Emergency Power Off (EPO) interface Front panel LEDs offer at-a-glance confirmation of line power status, battery power status, AC-to-DC & DC-to-AC conversion, bypass mode and output power status. Fault-tolerant auto-bypass mode prevents loss of output during UPS fault conditions or excessive UPS loading 4 post rackmount and upright tower installation accessories included. 2POSTRMKITWM two post rackmount hardware accessories available Field replaceable, hot swappable power module and external battery packs Attractive all-black color scheme 2-year warranty: $250,000 connected equipment insurance Extended warranty and service contracts available
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208V & 120V AC
Frequency compatibility
50/60 Hz
OUTPUT
Output VA 8000
Output watts 6400
Output nominal voltage
208V & 120V AC
Output voltage regulation
Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 3% total harmonic distortion when used with computer loads
Output frequency regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity / type 4 NEMA L6-20R, 2 NEMA L6-30R, 12 NEMA 5-15/20R
INPUT
Maximum input amps 208V - 36A
Input connection type Hubbell CS8265C 50A input plug (input cordset is removeable to support professional hardwire input)