Tripp Lite SU8000RT3UG User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SU8000RT3UG
Highlights
Global 8000VA (8kVA) on-line 6U rack/tower UPS with expandable runtime
(3U power module + 3U battery pack)
Zero transfer time, on-line, double-conversion and economy-mode operation
supported
Detachable PDU with manual bypass switch enables hot-swap UPS
replacement without powering off connected loads
200, 208, 230 or 240V selectable input/output voltage, with hardwire input and
six individually breakered C19 outlets
2% output voltage regulation over an input voltage range of 156 to 296
Simultaneous-use RS232 and contact closure monitoring ports, SNMP/Web
Card Slot and EPO interfaces
$250,000 Ultimate LIfetime Insurance (USA, Puerto Rico & Canada only)
Description
Global 8000VA (8kVA) on-line, double-conversion UPS system for critical server, network and telecommunications equipment. Installs in only 6 rack
spaces (3U power module and 3U battery pack). Worldwide shipping version with 6 C19 outlets. Maximum installed rack depth of 32.5 in.
Expandable battery runtime with optional external battery packs. Full-time sine wave 200, 208, 220, 230, or 240V +/-2% output. Actively converts
raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output. Operates continuously without using battery
power during brownouts to 156V and overvoltages to 276V. Standard 3-wire 208V hardwire input connection; 6 individually breakered C19
output receptacles. Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without disrupting power to
connected equipment. Network-grade AC surge and noise suppression. Zero transfer time between AC and battery operation. Network management
interfaces support communications via RS-232, contact-closure port and optional SNMPWEBCARD slot. Supports detailed monitoring of equipment
load levels, self-test data and utility power conditions via network interfaces. Includes PowerAlert monitoring software and complete cabling.
Emergency Power Off (EPO) interface. Front panel LEDs offer at-a-glance confirmation of line power status, battery power status, AC-to-DC
conversion, DC-to-AC conversion, bypass mode and output power status. LCD panel with scroll buttons offers detailed diagnostic test information at
startup and during self tests, plus real-time data on input and output voltage, frequency (Hz), load percentage and battery charge level. LED/LCD
display panel easily rotates for viewing in rackmount or tower configurations. Audible alarm. Self-test. Fault-tolerant auto-bypass mode. 4-post
rackmount accessories and 2-9USTAND tower kit included; 2POSTRMKITWM 2-post rackmount hardware accessories available. Field replaceable,
hot-swappable power module and external battery packs. Attractive all-black color scheme. 2-year warranty and $250,000 connected equipment
insurance; extended warranty and service contracts available.
Applications
Ideal for protection of sensitive electronics in any application calling for upright tower or 19 inch rackmount UPS protection. Common applications include any mix of servers, workstations, hubs, routers, concentrators, IP telephony and traditional PBX switching systems
Global C19 outlet configuration allows a single UPS model to be specified for worldwide use.
Package Includes
3U power module with detachable hot-swap PDU input/output panel and bypass switch 3U external battery pack Two sets of 4 post rackmount rails (one for each of the 3U components) One set of tower stands for upright tower configuration PowerAlert software, complete data cabling, user manual with warranty information
Features
Global 8,000 VA (8kVA) on-line, double-conversion UPS system (High voltage input/High voltage output) Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without powering off connected equipment Installs in only 6 rack spaces (3U power module/3U battery pack) with a maximum installed depth of 32.5 inches Offers 6 min. runtime at full load (8000VA/6400W) and 15 min. at half load (4000VA/3200W). Runtime is expandable with any number of optional external battery packs Full-time sine wave 200, 208, 220, 230, or 240V +/-2% output (user selectable) Actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output Operates continuously without using battery power during brownouts to 156V and overvoltages to 276V Standard 3-wire 208V hardwire input connection 6 individually breakered C19 outlets Detailed LCD panel with scroll buttons offers detailed diagnostic test information on startup and during self tests, plus real-time data on input and output voltage, frequency (Hz), load percentage, battery charge level and more Network-grade AC surge and noise suppression Zero transfer time between AC and battery operation Network management interfaces support communications via RS-232, contact-closure port and optional SNMPWEBCARD slot Supports detailed monitoring of equipment load levels, self-test data and mains power conditions via network interfaces. Includes PowerAlert monitoring software and complete cabling Emergency Power Off (EPO) interface Front panel LEDs offer at-a-glance confirmation of line power status, battery power status, AC-to-DC & DC-to-AC conversion, bypass mode and output power status. Fault-tolerant auto-bypass mode prevents loss of output during UPS fault conditions or excessive UPS loading 4-post rackmount and upright tower installation accessories included. 2POSTRMKITWM two post rackmount hardware accessories available Field replaceable, hot swappable power module and external battery packs Attractive all-black color scheme 2-year warranty; $250,000 connected equipment insurance Extended warranty and service contracts available
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208V AC (200/208/220/230/240V)
Frequency compatibility
50/60 Hz
OUTPUT
Output VA 8000
Output watts 6400
Output nominal voltage
208V AC (200/208/220/230/240V)
Output voltage regulation
Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 3% total harmonic distortion when used with computer loads
Output frequency regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity / type 6 individually breakered C19 outlets