Tripp Lite SU30K3/3INT User Manual

SmartOnline 30kVA On-Line Double-Conversion UPS, 3 Phase input / output for international
MODEL NUMBER: SU30K3/3INT
Description
Tripp Lite's SU30K3/3INT SmartOnline 3-Phase Intelligent, True On-Line UPS System provides mission­critical equipment with the highest level of power protection available. Large capacity 30,000 VA/24,000 watt power module continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly regulated, continuous sine wave output with zero transfer time offers compatibility with all equipment types. SmartOnline models provide some of the highest levels of isolation from THD (total harmonic distortion) <3% allowing equipment to perform at its peak. A 3:1 crest factor safely supports a variety of equipment, even those with wildly­fluctuating power demands. Extremely efficient operation (up to 97% efficient in Economy Mode) saves money by lowering electricity consumption. Hardwire input and output connections support a variety of permanent or PDU style power connections. SU30K3/3INT features 50 or 60 Hz (auto-selectable) frequency. SU30K3/3INT includes a power module and an external battery module, both in tower format cabinets. Battery support can be extended with additional external battery modules. A manual bypass switch as well as an automatic bypass function ensure 100% availability of connected equipment by safely passing through AC power when the power module requires maintenance. Three built-in communication ports (RS-232, contact closure and AS-400) work with included PowerAlert Software to simultaneously provide shutdown commands and reporting on multiple servers without the need for costly accessories. An accessory slot accepts an optional internal SNMP card (model # SNMPWEBCARD) for remote shutdowns, reboots and more. A Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval.
Highlights
30,000 VA (30kVA) tower UPS with internal modular battery system
User-selectable 3-phase 220/380 or 230/400 or 240/415V AC input and output. Wide input voltage correction range (156­280V AC/270-485V AC)
IGBT technology and zero transfer time, on-line, double­conversion operation
Saves valuable space with single small-footprint module
Expandable runtime with additional internal battery modules
3 communication ports, SNMP card slot and EPO jack
Package Includes
SU30K3/3INT UPS System (power and battery components in one compact modular housing)
PowerAlert Software and cabling
Instructional manual with warranty information
Features
True on-line, double conversion UPS provides pure, sine wave AC output at all times
Simplifies runtime scalability: convenient front-panel battery access for expandable runtime with additional internal battery packs
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer
1 / 5
time
30,000VA/24,000 watt power capacity with hardwire input/output connections
User-selectable 3-phase 220/380 or 230/400 or 240/415V AC input and output. Wide input voltage correction range (156-280V AC/270-485V AC)
Standard included battery module provides 13 minutes runtime at half load (12,000 watts) and 5 minutes runtime at full load (24,000 watts)
3:1 crest factor safely supports a variety of equipment, even those with wildly-fluctuating power demands
Extremely efficient operation (up to 97% efficient in Economy Mode) saves money by lowering electricity consumption
Expandable runtime with additional internal battery modules and optional external modular battery frames
3 communication ports (RS-232, contact closure and AS-400)
Slot for optional SNMP card ( model # SNMPWEBCARD)
Manual bypass switch as well as an automatic bypass function ensures 100% availability of connected equipment by safely passing through AC power when the power module requires maintenance
Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval
Emergency Power Off button turns UPS output OFF and disables Bypass output
PowerAlert Universal UPS Power Management Software and cabling included
Combination LCD/LED display
Built-in Emergency Power Off (EPO) interface supports remote emergency shutdown in large facilities
Specifications
OVERVIEW
UPC Code 037332136756 UPS Type On-Line
INPUT
Rated input current (Maximum Load) 45A/43A/41A Nominal Input Voltage(s) Supported 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye Nominal Input Voltage Description 3-Phase Wye, 4 wire (L1, L2, L3, N, G) UPS Input Connection Type Hardwire Input Phase 3-Phase
OUTPUT
Output Volt Amp Capacity (VA) 30000