Tripp Lite SU30K3-3 User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SU30K3/3
Highlights
30,000 VA (30kVA) tower UPS with internal batteries
Saves valuable space: power and battery components combined into a single
small-footprint module
Simplifies runtime scalability: convenient front-panel battery access for
expandable runtime with additional internal battery packs
3-phase hardwire input and output (120/208VAC). Wide input voltage
correction range (88 - 144V AC / 166 - 250V AC)
IGBT technology and zero transfer time, on-line, double-conversion operation
3 communication ports, SNMP card slot and EPO jack
Description
Tripp Lite's SU30K3/3 30kVA SmartOnline 3-Phase Intelligent, True On-Line UPS System has been redesigned to save valuable space and simplify
runtime scalability. Power and battery components are combined into a single, small-footprint module (the smallest in its class). A robust internal
battery runtime capability can be easily extended by installing additional optional internal battery packs through the convenient front panel access
door.
The SU30K3/3 provides mission-critical equipment with the highest level of power protection available. Large capacity 30,000VA/24,000 watt UPS
continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly
regulated, continuous sine wave output with zero transfer time offers compatibility with all equipment types. IGBT inverter technology produces
output power with <3% THD (total harmonic distortion), allowing connected equipment to perform at its peak. A 3:1 crest factor safely supports a
variety of equipment, even those with wildly-fluctuating power demands. Extremely efficient operation saves money by lowering electricity
consumption. Hardwire input and output connections support a variety of permanent or PDU style power connections. SU30K3/3 features 120/208V
AC, 3-phase, 4-wire (plus ground), wye input and output. It also features a wide input voltage correction range: 88-144/166-250V AC. Frequency is
50 or 60 Hz (auto-selectable). SU30K3/3 includes internal power and battery components in a single small-footprint tower module. Battery support
can be extended with additional internal battery packs. A manual bypass switch as well as an automatic bypass function ensure 100% availability of
connected equipment by safely passing through AC power when the UPS requires maintenance. Three built-in communication ports (RS-232,
contact closure and AS-400) work with included PowerAlert Software to simultaneously provide shutdown commands and reporting on multiple
servers without the need for costly accessories. An accessory slot accepts an optional internal SNMP card (model # SNMPWEBCARD) for remote
shutdowns, reboots and more. A Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic
system access or data retrieval. An Emergency Power Off button turns UPS output OFF and disables Bypass output. Built-in Emergency Power Off
(EPO) interface supports remote emergency shutdown in large facilities. Front panel combination LCD/LED display alerts users to a variety of UPS
operational modes and conditions. A 1-year limited repair warranty is included. A start-up service program is recommended to enhance the reliability of
the installation.
Applications
Ideal for protecting critical 120/208V equipment in computing, networking or telecommunications environments.
Package Includes
SU30K3/3 UPS System (power and battery components in one module)
PowerAlert Software and cabling
Warranty information
Instruction manual
Features
Saves valuable space: power and battery components combined into a single small-footprint module
Simplifies runtime scalability: convenient front-panel battery access for expandable runtime with additional internal battery packs
True on-line, double conversion UPS with IGBT technology provides pure, sine wave AC output at all times
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
30,000VA/24,000 watt power capacity with 3-phase, hardwire 120/208V AC input/output connections
Features a wide input voltage correction range: 88 - 144/166 - 250V AC
Included internal batteries provide 13 minutes runtime at half load (12,000 watts) and 5 minutes runtime at full load (24,000 watts)
3:1 crest factor safely supports a variety of equipment, even those with wildly-fluctuating power demands
Extend runtime by installing an optional internal battery pack (model # SURBC2030) through the front panel access door. SU30K3/3
includes 3 internal battery packs and accepts 1 additional internal battery pack. A standalone battery module compartment with a 4 battery
pack capacity and daisy-chain capability (model # SUBF2030) is available to further extend runtime.
3 communication ports (RS-232, contact closure and AS-400)
Slot for optional SNMP card (model # SNMPWEBCARD)
Manual bypass switch as well as an automatic bypass function ensures 100% availability of connected equipment by safely passing
through AC power when the UPS system requires maintenance
Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval
Emergency Power Off button turns UPS output OFF and disables Bypass output
PowerAlert Universal UPS Power Management Software and 6 ft. communication cable included
1-year limited repair warranty
Start-up service program is recommended to enhance the reliability of the installation
Built-in Emergency Power Off (EPO) interface supports remote emergency shutdown in large facilities
Combination LED/LCD display
Specifications
SYSTEM OVERVIEW
Voltage compatibility
120/208V AC, 3-phase, 4-wire (plus ground), wye
Frequency compatibility
50/60 Hz (auto-selectable)
OUTPUT
Output VA 30,000 (30kVA)
Output watts 24000
Output nominal voltage
120/208V AC, 3-phase, 4-wire (plus ground), wye
Output voltage regulation
Maintains pure sine wave output at all times, regulated within 2% of nominal output voltage, less than 3% total harmonic distortion (using IGBT Inverter)
Output frequency regulation
Regulates line frequency at 50 or 60 Hz, +/- 3 Hz
Outlet quantity / type
Hardwire
INPUT
Maximum input amps
90A (per phase, online)
Input connection type
Hardwire
Recommended Electrical Service
120/208V AC (3-Phase, 4 Wire, wye)
BATTERY
Loading...