Tripp Lite SU3000XLNAFTA User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SU3000XLNAFTA
Highlights
3000VA / 3KVA on-line, double-conversion, extended-run tower UPS
Maintains sine-wave 110/120V +/-2% output during overvoltages to 138 and
brownouts as low as 65V (50/60Hz auto-sensing)
Simultaneous use communications via HID compliant USB port, serial port,
SNMP/Web card slot and EPO interface
Fault tolerant auto-bypass mode, current monitoring and switched PDU control
via 2 switchable output load banks
Input: NEMA L5-30P (120V) / Output: 4 NEMA5-15R, 4 NEMA5-15/20R & 1
NEMA L5-30R
2 year product warranty / $250,000 Ultimate Lifetime Insurance (USA &
Canada only)
Description
3000VA on-line, double-conversion UPS system for critical server, network and telecommunications equipment. Upright tower form factor.
Expandable battery runtime with optional BP72V28-3UNAFTA external battery packs. Full-time sine wave 110 or 120V +/-2% output. Online,
double-conversion Uninterruptible Power Supply (UPS) actively converts raw incoming AC power to DC, then re-converts output back to completely
regulated, filtered AC output. Operates continuously without using battery power during brownouts to 65V and overvoltages to 138V. NEMA L5-30P
input plug; NEMA 5-15R, NEMA 5-15/20R and NEMA L5-30R output receptacles. Network-grade AC surge and noise suppression. Zero transfer
time between AC and battery operation. Network management interfaces support simultaneous communications via USB port, DB9 serial port and
SNMPWEBCARD slot. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows
and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility power conditions via all 3 network
interfaces. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. Integrated 2-bank PDU switching
supports load shedding and remote-reboot of connected equipment. 3-stage metered current monitoring and battery charge status LEDs. Dataline
surge suppression for dialup, DSL or network Ethernet connection. Utility power and voltage regulation LEDs. Audible alarm. Self-test. Fault-tolerant
auto-bypass mode. Field-replaceable, hot-swappable internal batteries and external battery packs. Attractive all-black color scheme. 2-year warranty
and $250,000 connected equipment insurance; extended warranty and service contracts available
Applications
Ideal for protection of critical servers, internetworking equipment and other other sensitive electronic loads. Common applications include corporate or departmental servers, workstations, hubs, routers, bridges, CAD/CAM workstations, concentrators, IP telephony and traditional PBX switching systems.
Package Includes
SU3000XLNAFTA UPS System PowerAlert Software and Cabling Instruction manual with warranty information
Features
SmartOnline high performance UPS system is ideal for critical voice, data, medical and industrial network applications
True on-line, double-conversion UPS provides perfectly regulated sine wave output within 2% of 110/120V (user selectable) under all usage conditions Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types Corrects line voltage conditions as low as 65V and as high as 138V back to selectable 110/120V (+/-2%) values Standard internal battery set offers 14 minutes runtime at half load (1200W) and 5 minutes at full load (2400W) Optional BP72V28-3UNAFTA external battery packs offer expandable battery runtime Space saving upright tower format Fault tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS suffers internal failure and requires maintenance Network interfaces support simultaneous communications via built-in USB, DB9 serial/contact-closure and SNMPWEBCARD slot HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS nominal voltage adjustment and UPS line to battery power voltage setpoints Built-in Emergency Power Off (EPO) interface with cable NEMA L5-30P input plug/NEMA 5-15/20R, L5-20R & L5-30R output receptacles Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each bank has four outlets) Front panel LEDs offer current monitoring and battery charge level information UPS ships fully assembled in full compliance with DOT regulations; no time consuming connection of internal batteries by user required Single line TEL/DSL or network ethernet line surge suppression 2 year manufacturer's product warranty; $250,000 Ultimate Lifetime Insurance
Specifications
SYSTEM OVERVIEW
Voltage compatibility
120V AC (110/120V)
Frequency compatibility
50/60 Hz compatible (auto-sensing)
OUTPUT
Output VA 3000
Output watts 2400
Output nominal voltage
120V AC (110/120V)
Output voltage regulation
Maintains full-time sine wave output within 2% of selected nominal, less than 3% total harmonic distortion (linear load) / 5% total harmonic distortion (computer load) (Less than 5% THD on-line and on-battery)
Output frequency regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity / type
4 NEMA 5-15R, 4 NEMA 5-15/20R, 1 NEMA L5-30R
Customized load management receptacles
2 controllable load banks support load shedding and remote reboot on demand of locked network devices (bank 1 has 4 outlets / bank 2 has 2 outlets)
Overload protection
Via 40A input breaker
INPUT
Maximum input amps
24A (120V) / 26.2A (110V)
Input connection type
NEMA L5-30P
Input cord length 10ft / 3m
Loading...
+ 3 hidden pages