120V 3000VA 2700W Double-Conversion UPS - 9
Outlets, Extended Run, WEBCARDLX, LCD, USB,
DB9, 2U
MODEL NUMBER: SU3000RTXLCD2UN
Highlights
●
Offers network-grade protection
against power failures and
voltage fluctuations
●
Zero transfer time between online and battery modes for
uninterrupted operation
●
Optional external battery packs
provide additional runtime for
applications requiring it
●
Included WEBCARDLX network
interface allows you 24/7 remote
access from anywhere
●
Optional Economy mode helps
save electricity and lower your
energy costs
On-line double-conversion UPS provides pure sine wave AC output to server and network equipment in
data centers and computer rooms.
Features
Double-Conversion UPS Protects Equipment against Damage, Downtime and Data LossThis
100/110/120/127V 50/60 Hz UPS system with IGBT technology maintains perfect output by converting AC
input to DC, then reconverting UPS output to fully regulated sine wave AC with +/-2% voltage regulation in
online and battery modes. Featuring a 2.7kW capacity, high 0.9 power factor, 570 joules of surge
suppression, true on-line operation with pure sine wave output and zero transfer time to battery mode in
on-line double-conversion mode, the SmartOnline® SU3000RTXLCD2UN double-conversion UPS
provides the highest level of AC power protection and battery backup for critical network closet, computer
room and data center equipment.
Individually Controllable Load Banks Let You Access and Control Outlets RemotelyFour NEMA 515R outlets and four 5-15/20R outlets are split into two switchable load banks, allowing you to reboot
select components or shed loads remotely. In addition to those outlets, this UPS provides one NEMA L530R outlet for powering critical components.
Reliable, Expandable Battery Backup Keeps You Operational Through Power OutagesThe fieldreplaceable, hot-swappable internal battery provides 11.3 minutes of support at half load (1350W) and 4.1
minutes at full load (2700W), keeping protected equipment operational through power failures. For
mission-critical applications demanding scalable extended runtime, the UPS supports external battery
packs, such as Tripp Lite’s BP72V15-2U (sold separately). The intelligent battery management system
with temperature-compensated charging extends battery life.
Optional Economy Mode Helps You Save Money and Protect the EnvironmentA power-saving
Economy mode setting option offers enhanced efficiency and reduced BTU output when utility power is
already high quality, which helps you save on energy costs.
Automatically Turns Back On After Power Is RestoredBattery-independent restart ensures automatic
UPS power-up without user interaction after lengthy power outages, even when batteries are expired and
require replacement.
Intuitive Front-Panel Interface for Convenient UPS Operation and MonitoringThe front-panel LCD
features detailed UPS and site power status and operating data, plus configuration of voltage, frequency,
operating mode, alarm function and a variety of additional options. LEDs indicate line power availability,
AC to DC conversion, battery mode operation, inverter mode, ECO mode operation, bypass mode
operation and AC output status.
Advanced Communications Ports Allow for Automatic Saves and ShutdownsRS-232 and HIDcompliant USB ports connect to a computer running Tripp Lite’s free downloadable PowerAlert® software
to enable safe unattended file saves and system shutdown in case of a prolonged power failure. An EPO
Applications
●
Deliver perfectly regulated sine
wave output to mission-critical
equipment
●
Protect connected components
from dangerous surges, spikes
and line noise
●
Keep equipment operational
through power failures
●
Allow time to save data and
safely shut down components in
case of a prolonged blackout
Package Includes
●
SU3000RTXLCD2UN
SmartOnline Double-Conversion
UPS
●
WEBCARDLX network interface
card
●
USB cable
●
RS-232 cable
●
EPO cable
1 / 6
port connects the UPS to a contact closure switch to enable emergency inverter shutdown. Cables are
included.
WEBCARDLX Network Interface Offers 24/7 Remote Access for Monitoring and ControlThe
SU3000RTXLCD2UN includes the Java-free HTML5-based WEBCARDLX that enables full remote access
for site power and UPS status monitoring, configuration, control and email notifications via secure web
browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an
Ethernet network. Automated alerts help prevent accidental overloads, power loss and downtime.
WEBCARDLX allows you to use the Auto Probe feature, which can prevent costly service calls by
automatically rebooting non-responsive network devices.
Versatile Installation OptionsHardware is included for mounting the UPS system in 2U of space in an
EIA-standard 19-inch 4-post rack. Use the optional 2POSTRMKITWM (sold separately) for 2-post rack
mounting or the optional 2-9USTAND (sold separately) for mounting in an upright tower position. The 10foot power cord with NEMA L5-30P plug connects to any compatible AC outlet.
Specifications
OVERVIEW
UPC Code 037332253552
UPS Type On-Line
INPUT
Rated input current (Maximum Load) 24A
Nominal Input Voltage(s) Supported 100V AC; 110V AC; 115V AC; 120V AC; 127V AC
●
4-post rack-mounting hardware
●
Owner’s manual
Nominal Input Voltage Description 120V factory default
UPS Input Connection Type L5-30P
Input Circuit Breakers 40A
UPS Input Cord Length (ft.) 10
UPS Input Cord Length (m) 3.1
Recommended Electrical Service 30A 120V
Input Phase Single-Phase
OUTPUT
Output Volt Amp Capacity (VA) 3000
Output kVA Capacity (kVA) 3
Output Watt Capacity (Watts) 2700
Output kW Capacity (kW) 2.7
Output Capacity Details ON LINE MODE: Maximum output capacity is reduced to 2430W (115V), 2295W (110V) and 2160W (100V);
FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation
/ conversion mode (127/120V 1890 watts / 115V 1701 watts / 110V 1606 watts / 100V 1512 watts).
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150%
load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and
frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE
bypass limits)
Power Factor 0.9
2 / 6