Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SU3000RTXL3U
SmartOnline Expandable 3U Rack / Tower UPS System - On-line, double-conversion, sine wave UPS with PDU
switching, current monitoring and fault tolerant auto-bypass
Highlights
3000VA / 2400W on-line, double-conversion, extended-run 3U rack / tower
UPS
Zero transfer time, on-line, double-conversion and economy-mode operation
supported
Maintains sine-wave 110/120V +/-2% output during overvoltages to 138 and
brownouts as low as 65V (50/60Hz auto-sensing)
Simultaneous use communications via HID compliant USB port, serial port,
SNMP/Web card slot and EPO interface
Fault tolerant auto-bypass mode, current monitoring and switched PDU control
via 2 switchable output load banks
Input: NEMA L5-30P (120V) / Output: 4 NEMA5-15R, 4 NEMA5-15/20R & 1
NEMA L5-30R
2 year product warranty / $250,000 Ultimate Lifetime Insurance (USA &
Canada only)
Estimated Retail Pricing: $1,400.00
Description
3000VA on-line, double-conversion UPS system for critical server, network and telecommunications equipment. 3U rackmount form factor with an
installed depth of 26 inches. Expandable battery runtime with optional BP72V15-2U and BP72V28RT-3U external battery packs. Full time sine wave
110 or 120V +. -2% output. Uninterruptible Power Supply (UPS) actively converts raw incoming AC power to DC, then re-converts output back to
completely regulated, filtered AC output. Operates continuously without using battery power during brownouts to 65V and overvoltages to 138V.
Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs. NEMA L5-30P input plug. NEMA 5-15, NEMA
5-15. 20R and NEMA L5-30R output receptacles. Network-grade AC surge and noise suppression. Zero transfer time between AC and battery
operation. Network management interfaces support simultaneous communications via USB port, DB9 serial port and SNMPWEBCARD slot.
Includes USB and DB9 serial ports. Built-in DB9 port offers both enhanced RS-232 enabled monitoring data, plus contact closure monitoring ability.
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Supports
simultaneous detailed monitoring of equipment load levels, self-test data and mains power conditions via all 3 network interfaces at once. Includes
PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. Integrated two bank PDU switching supports load
shedding and remote-reboot of connected equipment. 3 stage metered current monitoring and battery charge status LEDs. Dataline surge
suppression for dialup, DSL or network ethernet connection. Mains power and voltage regulation LEDs. Audible Alarm. Self-test. Fault-tolerant
auto-bypass mode. LED display panel easily rotates for better viewing in rackmount or tower configurations. 4 post rackmount accessories.
2-9USTAND tower kit and 2POSTRMKITWM two post rackmount hardware accessories available. Field replaceable, hot swappable internal
batteries and external battery packs. Attractive all-black UPS design. Two year warranty with $250,000 connected equipment insurance. Extended
warranty and service contracts available.
Applications
Ideal for protection of critical 120V equipment in server rooms, internetworking closets and telecommunications systems in rackmount or
tower applications. Common applications include corporate or departmental servers, workstations, hubs, routers, bridges, CAD/CAM