Tripp Lite SU2200XLNAFTA User Manual

SU2200XLNAFTA Estimated Runtime
Load in Watts
UPS Battery Pack 500W 600W 700W 800W 900W 1,000W 1,100W 1,200W 1,300W 1,400W 1,500W 1,600W SU2200XLNAFTA Internal Batteries 24 19 16 14 12 10.0 8.7 7.7 6.9 6.2 5.6 4.5
SU2200XLNAFTA 1 BP48V24-2U 97 79 66 56 48 42 38 34 30 28 25 23 SU2200XLNAFTA 1 BP48V60RT3U 197 161 136 117 101 89 79 71 65 59 54 50 SU2200XLNAFTA 2 BP48V60RT3U 396 328 279 242 211 187 167 151 137 126 116 107 SU2200XLNAFTA 3 BP48V60RT3U 596 497 425 370 325 289 259 235 214 197 181 168 SU2200XLNAFTA 4 BP48V60RT3U 794 666 572 499 440 392 353 320 293 269 249 231 SU2200XLNAFTA 5 BP48V60RT3U 991 833 717 628 554 495 447 406 372 343 317 295 SU2200XLNAFTA 6 BP48V60RT3U 1,185 999 862 756 669 598 540 492 451 416 386 360 SU2200XLNAFTA 7 BP48V60RT3U 1,376 1,163 1,005 883 782 701 634 578 531 490 455 424 SU2200XLNAFTA 8 BP48V60RT3U 1,565 1,325 1,147 1,009 895 803 727 664 610 564 524 489 SU2200XLNAFTA 9 BP48V60RT3U 1,751 1,485 1,287 1,135 1,007 904 820 749 689 637 592 553 SU2200XLNAFTA 10 BP48V60RT3U 1,934 1,643 1,426 1,259 1,118 1,005 912 834 768 711 661 617
All runtime values are in minutes.
Loading...