1000VA on-line, double-conversion UPS system for critical server, network and telecommunications
equipment. 2U rackmount form factor with an installed depth of only 13.5 inches. Extended runtime
available with optional BP24V15RT2U (limit 1), BP24V28-2U (limit 1), BP24V70-3U (multi-pack
compatible) or BP24V36-2US (multi-pack compatible) external battery packs. Full-time sine wave 120V
output with +/-2% voltage regulation. Online, double-conversion Uninterruptible Power Supply (UPS)
actively converts raw incoming AC power to DC, then re-converts output back to completely regulated,
filtered AC output. Operates continuously without using battery power during brownouts to 65V and
overvoltages to 150V. Highly efficient operation in optional economy mode saves BTU heat output and
energy costs. NEMA 5-15P input plug; NEMA 5-15R output receptacles. Network-grade AC surge and
noise suppression. Zero transfer time between AC and battery operation. Network management interfaces
support simultaneous communications via USB port, DB9 serial port and pre-installed WEBCARDLX
network management interface card.
The Java-free HTML5-based WEBCARDLX interface enables full remote access for site power and UPS
status monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or
SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network.
Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring
capabilities. Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet,
SSH, FTP, DHCP and NTP.
Front panel status LEDs with
detailed load and battery
metering
●
2 independently switchable
output load banks
●
NEMA 5-15P input; 5-15R
outlets
●
To enable the Auto Probe
feature, this product requires LX
firmware update 15.5.2 or later
to be installed
Package Includes
●
SU1000RTXL2Ua with preinstalled WEBCARDLX interface
●
USB, DB9 and EPO cabling
●
Mounting hardware for 4 post
rack enclosures
●
Instruction manual
Built-in DB9 port offers both enhanced RS-232 enabled monitoring data, plus contact closure monitoring
ability. HID-compliant USB interface enables integration with built-in power management and auto
shutdown features of Windows and Mac OS X.Supports simultaneous detailed monitoring of equipment
1 / 7
load levels, self-test data and utility power conditions via all 3 network interfaces. PowerAlert UPS
monitoring software is available via free download. Emergency Power Off (EPO) interface. Integrated twobank PDU switching supports load shedding and remote reboot of connected equipment. 3-stage metered
current monitoring and battery charge status LEDs. LED display panel easily rotates for viewing in
rackmount or tower configurations. Dataline surge suppression for dialup, DSL or network Ethernet
connection. Utility power and voltage regulation LEDs. Audible alarm. Self-test. Fault-tolerant auto-bypass
mode. 4-post rackmount accessories included; 2-9USTAND tower kit and 2POSTRMKITWM 2-post rack
& wallmount accessories available. Field-replaceable, hot-swappable internal batteries and external
battery packs. $250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only).
Features
●
SmartOnline high performance UPS system is ideal for critical voice, data, medical and industrial
network applications
●
True on-line, double-conversion UPS provides perfectly regulated sine wave output within 2% of 120V
under all usage conditions
●
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer
time
●
Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs
●
Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve
power problems not addressed by other UPS types
●
Corrects line voltage conditions as low as 65V and as high as 150V back to 120V (+/-2%) values
●
Standard internal battery set offers 14 minutes runtime at half load (400W) and 4.5 minutes at full load
(800W)
●
Extended runtime available with optional BP24V15RT2U (limit 1), BP24V28-2U (limit 1), BP24V70-3U
(multi-pack compatible) and BP24V36-2US (multi-pack compatible) external battery packs
●
Some external battery configurations require the use of Tripp Lite's External Battery Configuration
Software (see manual)
●
Intelligent battery management system extends battery life
●
Compact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth
of only 13.5 inches
●
Ships with all mounting accessories for 4 post rackmount installation
●
Optional 2POSTRMKITWM enables 2 post rackmount or wallmount installation
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
●
Network interfaces support simultaneous communications via built-in USB, DB9 serial / contact-closure
and pre-installed WEBCARDLX network management card
●
WEBCARDLX interface allows full remote access for power monitoring, configuration, control and email
notifications via secure web browser, SNMP, telnet or SSH
●
Optional E2 sensors enable site monitoring of temperature, humidity and contact-closure status
●
Reduce Service Calls with Auto Probe Autonomous Device Management. Auto Probe feature (Firmware
2 / 7
15.5.2 and greater) of the LX Platform Interface checks the connectivity status of any networked device
and automatically takes one or more user-configured actions if the device fails to respond; actions
include outlet reboot, set SNMP traps, SNMP OID sets, and even script execution when used in
conjunction with the Tripp Lite PowerAlert Network Shutdown Agent (PANSA)
●
HID-compliant USB interface enables integration with built-in power management and auto shutdown
features of Windows and Mac OS X
●
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from poweralert
●
Built-in Emergency Power Off (EPO) interface with cable
●
NEMA 5-15P input plug/NEMA 5-15R output receptacles
●
Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot
of individual devices (each load bank consists of one outlet)
●
Front panel LEDs offer current monitoring and battery charge level information
●
Single line TEL/DSL or network Ethernet line surge suppression
●
$250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only)
Output Volt Amp Capacity (VA)1000
Output kVA Capacity (kVA)1
Output Watt Capacity (Watts)800
3 / 7
Output Capacity DetailsOVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150%
load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and
frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE
bypass limits)
Power Factor0.8
Crest Factor3:1
Frequency Compatibility50 / 60 Hz
Frequency Compatibility DetailsOutput frequency matches input nominal on startup, defaults to 60 Hz on cold-start
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation
(Economy Line Mode)
Output Voltage Regulation (Battery
Mode)
+/- 2%
+/- 10%
+/- 2%
Load Management ReceptaclesTwo switchable single-outlet 5-15R load banks
Output AC Waveform (AC Mode)Pure Sine wave
Output AC Waveform (Battery
select-Tripp-Lite-SmartPro-UPS~RBC92-2U">RBC92-2U</a>
Battery AccessFront panel battery access door
Battery Replacement DescriptionHot-swappable, user replaceable batteries
Expandable RuntimeYes
VOLTAGE REGULATION
4 / 7
Voltage Regulation DescriptionOnline, double-conversion power conditioning
Overvoltage Correction2% output voltage regulation during overvoltages to 150
Undervoltage Correction2% output voltage regulation during undervoltages to 80
Severe Undervoltage Correction2% output voltage regulation during undervoltages to 65 (under 70% load only)
USER INTERFACE, ALERTS & CONTROLS
Switches2 switches control off/on power status and alarm-cancel/self-test operation. LX Platform Interface: Recessed reset
switch for interface reboot and factory reset
Alarm Cancel OperationPower-fail alarm can be silenced using alarm-cancel switch
Audible AlarmAudible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown
conditions
LED Indicators14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery
and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in
Wall-Mount-Racks~4POSTRAILKITWM">4POSTRAILKITWM</a> enables installation in 4-post short-depth
racks from 14.5 to 23.5 inches (368 to 597mm); <a class="productLink" href="//Heavy-
Duty-2-post-Front-Mounting-Ear-Kit~UPSHDEARKIT">UPSHDEARKIT</a> enables installation in 2 or 4-post
racks using front vertical rails only, without rear support
5 / 7
Primary Form FactorRackmount
Primary UPS Depth (mm)343
Primary UPS Height (mm)89
Primary UPS Width (mm)445
Rack Height2U
Shipping Dimensions (hwd / cm)23.11 x 50.55 x 59.18
Shipping Dimensions (hwd / in.)9.10 x 19.90 x 23.30
Shipping Weight (kg)18.14
Shipping Weight (lbs.)40.00
UPS Housing MaterialSteel
UPS Power Module Dimensions
(hwd, cm)
UPS Power Module Dimensions
(hwd, in.)
8.89 x 44.45 x 34.29
3.5 x 17.5 x 13.5
UPS Power Module Weight (kg)13.15
UPS Power Module Weight (lbs.)29
ENVIRONMENTAL
Operating Temperature Range+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)408
AC Economy Mode BTU / Hr. (Full
Card~WEBCARDLX">WEBCARDLX</a>
Network Monitoring Port DescriptionIncludes pre-installed WEBCARDLX Network Management Card; DB9 port supports RS232 and contact closure
communications; Economy-mode setting option is available using PowerAlert software and DB9 Serial cable
connection OR installed Network Management Card
PowerAlert SoftwareFor local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at
http://poweralert
Communications CableUSB and DB9 cabling included
WatchDog CompatibilitySupports Watchdog application, OS and hard-reboot restart options for remote applications
EPO PortRJ11 interface jack with 4-meter cable included. Supports normally open and normally closed EPO systems
6 / 7
Communications InterfaceContact closure; DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface;
LINE / BATTERY TRANSFER
Transfer TimeNo transfer time (0 ms.) in online, double-conversion mode
USB (HID enabled)
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS FeaturesAutomatic inverter bypass; Hot swappable batteries; Auto Probe Monitoring and Reboot (included); Zero transfer
Green Energy-Saving FeaturesHigh efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy
STANDARDS & COMPLIANCE
UPS CertificationsTested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category B (EMI)
WARRANTY
Product Warranty Period
(Worldwide)
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)