Tripp Lite SU10000RT3U User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SU10000RT3U
Highlights
10,000VA/10kVA on-line 6U rack/tower UPS with expandable runtime (3U
Power Module + 3U Battery Pack)
Zero transfer time, on-line, double-conversion and economy-mode operation
supported
Manual bypass switch and detachable PDU enable hot-swap UPS
replacement without powering off connected loads
200, 208, 230 or 240V selectable input/output voltage
2% output voltage regulation over an input voltage range of 156-276V
Enhanced serial communications ports, SNMP/Web Card Slot and EPO
interfaces
$250,000 Ultimate Lifetime Insurance (USA, Puerto Rico & Canada only)
Description
10,000VA (10kVA) on-line, double-conversion UPS system for critical server, network and telecommunications equipment. Installs in only 6 rack
spaces (3U power module and 3U battery pack); maximum installed rack depth of 32.5 in. Expandable battery runtime with optional external battery
packs. Full-time sine wave 200, 208, 220, 230, or 240V +/-2% output. Actively converts raw incoming AC power to DC, then re-converts output back
to completely regulated, filtered AC output. Operates continuously without consuming battery power during brownouts to 156V and overvoltages to
276V. Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs. Standard 3-wire 208V hardwire input
connection; NEMA L6-30R and L6-20R output receptacles. Detachable input-output PDU module with manual bypass switch enables hot-swap UPS
replacement without disrupting power to connected equipment. Network-grade AC surge and noise suppression. Zero transfer time between AC and
battery operation. Network management interfaces support communications via RS-232, contact-closure port and optional SNMPWEBCARD slot.
Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via network interfaces. Includes PowerAlert
monitoring software and complete cabling. Emergency Power Off (EPO) interface. Front panel LEDs provide at-a-glance confirmation of line power
status, battery power status, AC-to-DC conversion, DC-to-AC conversion, bypass mode and output power status. LED/LCD display panel rotates for
better viewing in rackmount or tower configurations. Detailed LCD panel with scroll buttons provides detailed diagnostic test information at startup
and during self tests, plus real-time data on input and output voltage, frequency (Hz), load percentage and battery charge level. Audible alarm.
Self-test. Fault-tolerant auto-bypass mode. 4-post rackmount accessories and 2-9USTAND tower kit included; 2POSTRMKITWM 2-post rackmount
hardware accessories available. Field-replaceable, hot-swappable power module and external battery packs. Attractive all-black color scheme.
2-year warranty; extended warranty and service contracts available. $250,000 connected equipment insurance
Applications
Ideal for protection of sensitive electronics in any application calling for upright tower or 19-in. rackmount UPS protection. Common applications include any mix of servers, workstations, hubs, routers, concentrators, IP telephony and traditional PBX switching systems
Package Includes
3U power module with detachable hot-swap PDU input/output panel and bypass switch 3U external battery pack
Two sets of 4-post rackmount rails (one for each of the 3U components) One set of tower stands for upright tower configuration PowerAlert Software, complete cabling, owner's manual with warranty information
Features
10,000VA (10kVA) on-line, double-conversion UPS system (high-voltage input/high-voltage output) Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without powering off connected equipment Installs in only 6 rack spaces (3U power module/3U battery pack) with a maximum installed depth of 32.5 in. Offers 4 min. runtime at full load (10,000VA/8000W) and 10 min. at half load (5000VA/4000W). Runtime is expandable with any number of optional external battery packs Full-time sine wave 200, 208, 220, 230, or 240V +/-2% output (user selectable) Actively converts raw incoming AC power to DC, then re-converts output to completely regulated, filtered AC output Operates continuously without using battery power during brownouts to 156V and overvoltages to 276V Standard 3-wire 208V hardwire input connection 4 x NEMA L6-20R and 2 x NEMA L6-30R output receptacles Detailed LCD panel with scroll buttons provides detailed diagnostic test information on startup and during self tests, plus real-time data on input and output voltage, frequency (Hz), load percentage, battery charge level and more Network-grade AC surge and noise suppression Zero transfer time between AC and battery operation Includes slot for internal SNMP/web card, plus DB9 enhanced serial monitoring port, and contact closure port for unattended shudown, remote control and monitoring of UPS system and power data Supports detailed monitoring of equipment load levels, self-test data and mains power conditions via network interfaces. Includes PowerAlert monitoring software and complete cabling Emergency Power Off (EPO) interface Front panel LEDs provide at-a-glance confirmation of line power status, battery power status, AC-to-DC & DC-to-AC conversion, bypass mode and output power status Fault-tolerant auto-bypass mode prevents loss of output during UPS fault conditions or excessive UPS loading 4-post rackmount and upright tower installation accessories included; 2POSTRMKITWM 2-post rackmount hardware accessories available Field-replaceable, hot-swappable power module and external battery packs Attractive all-black color scheme 2-year warranty; extended warranty and service contracts available $250,000 connected equipment insurance
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208V AC (200/208/220/230/240V)
Frequency compatibility
50/60 Hz
OUTPUT
Output VA 10000
Output watts 8000
Output nominal voltage
208V AC (200/208/220/230/240V)
Output voltage regulation
Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 3% total harmonic distortion when used with computer loads
Output frequency regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity / type 4 x NEMA L6-20R, 2 x NEMA L6-30R
INPUT
Maximum input amps 200V-46.7A / 208V- 44.9A / 220V- 42.4A / 230V-40.6A / 240V-38.9A
Input connection type Hardwire
BATTERY
Loading...