installation requires 2-9USTAND accessory
Large internal batteries support a max load of 1500VA for 7 minutes and a half load of 750VA for 18 minutes
Expandable runtime with BP36V15-2U (limit 1) or with multiple BP36V42-3U rack/tower external battery packs
Maintains regulated 230V nominal output during brownouts and overvoltages from 151 to 282V
Includes 8 UPS supported outlets arranged in 3 individually controllable load banks (2 outlets per bank) that can be powered off and back
on again via software interface
IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles
PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, email notification,
event logging and running user-defined script commands.
Offers simultaneous monitoring by up to 2 directly-connected devices through included USB and DB9 interface ports, or the monitoring by
any number of additional servers over IP with included PowerAlert monitoring software.
Communications ports support messaging of UPS and line power status, including on-battery, low-battery, power restored, AC line voltage,
DC battery voltage and remaining battery capacity
Emergency Power Off (EPO) interface with cable
Supports timed inverter shutoff after unattended shutdown, activate self-test and UPS output power control for delayed or immediate reboot
of connected devices
Supports Tripp Lite's WatchDog software application to restore operation to locked equipment through soft reboot of application, OS or hard
power off/on reboot of connected equipment - ideal for unattended kiosk applications (requires optional WATCHDOGSW)
Built-in accessory slot supports SNMP with optional SNMPWEBCARD adapter
Emergency Power Off (EPO) interface with cable
Multi-function audible alarms and set of 5 front panel LEDs
Network-grade AC surge suppression
Attractive all-black color scheme
UPS battery set ships fully assembled, no time consuming connection of internal batteries by user is necessary
Specifications
OUTPUT
Output Volt Amp Capacity
(VA)
1500
Output kVA capacity (kVA) 1.5
Output Watt Capacity
(watts)
1000
Output kW capacity 1
Output power factor 0.7
Nominal Output Voltage(s)
Supported
230V
Nominal Voltage details 230v nominal inverter output voltage
Frequency compatibility 50 / 60 Hz
Output voltage regulation
(line mode)
-17%, +8%
Output voltage regulation
(Battery mode)
+/- 5%
Built-in UPS output
receptacles
8 C13 outlet(s)
Included output power
cables
Includes 2 C13 to C14 output power cables
Built-in controllable
switched load banks
Three switchable two-outlet C13 load banks
Output AC waveform (AC
mode)
Sine wave