SmartPro® 230V 1.5kVA 900W Line-Interactive UPS, 2U Rack/Tower, LCD, USB, DB9, 8 Outlets

MODEL NUMBER: SMX1500LCD

Highlights

Corrects underand overvoltages from 144V to 282V

8 C13 outlets

Interactive LCD monitoring screen

Monitoring of power conditions via POWERALERT12

12 min. runtime at half load; 4.5 min. at full load

Package Includes

SMX1500LCD SmartPro 230V 1.5kVA 900W Line-Interactive UPS

USB cable

RJ11 cable

Coaxial cable

(2) C13-to-C14 power cables

Tower/rack mounting hardware

Description

Owner’s manual

The SMX1500LCD SmartPro 230V 1.5kVA 900W Line-Interactive UPS provides battery backup and AC power protection against blackouts, brownouts, power surges and line noise that can damage electronics or destroy

data. Ideal for backing up home/office workstations, point-of-sale applications, VoIP systems and small business networks, the SMX1500LCD switches to battery mode in milliseconds to keep your connected equipment running long enough to save files and shut down safely with no data loss.

Featuring eight IEC-320-C13 outlets and a C14 inlet that accepts a user-supplied AC power cord, the SMX1500LCD has an internal battery that provides 12 minutes of support at half load and 4.5 minutes at full load. It can also power an entry-level PC up to 60 minutes or a single DVR/VCR component up to three hours. A front-panel LCD screen lets you monitor operating data, such as voltage, battery and overload statuses.

Automatic voltage regulation (AVR) maintains 230V nominal output over an input range of 144V to 282V without using battery power. EMI/RFI noise filtering improves your equipment’s performance and prevents damage. An 890-joule surge suppression rating protects your equipment from harmful power surges. With Tripp Lite’s free downloadable POWERALERT12 software, the SMX1500LCD enables safe unattended system shutdown and file saves in case of a prolonged power failure.

Features

Protects Mission-Critical Equipment

Provides fully regulated AC output for home/office workstations, point-of-sale applications, VoIP systems and small business networks

Audible alarm signals loss of utility power, low battery or overload

8 C13 outlets

C14 inlet accepts user-supplied AC power cord with country-specific plug

890-joule surge suppression rating

Reliable Battery Backup

Supports half load up to 12 min. and full load up to 4.5 min.

Powers entry-level PC up to 60 min. and a DVR/VCR component up to 3 hr.

Tripp-Lite SMX1500LCD Specifications

Cold-start capability enables turn-on in battery mode during blackouts

Internal batteries designed for hot-swap field replacement

96% line-power efficiency rating saves money in energy costs

Automatic Voltage Regulation (AVR)

Maintains 230V nominal output over input range of 144V–282V without using battery power

EMI/RFI Line Noise Filtering

Removes electromagnetic and radio frequency interference that can disrupt or damage equipment’s performance

Interactive LCD Screen

Front-panel LCD signals voltage, battery and overload statuses

Rotates for easy viewing in rack-mount or tower configurations

Communications Ports

USB and DB9 ports combine with free downloadable POWERALERT12 software to monitor operating conditions, monitor AC power, and enable safe unattended system shutdown and file saves in case of a prolonged power failure

Telephone/Ethernet/Satellite Protection Against Surges

RJ45 jacks protect phone/DSL/fax/modem/Ethernet network

2.2 GHz coaxial jacks protect CATV, satellite or broadcast antenna connections

Specifications

OUTPUT

Output Volt Amp Capacity (VA)

 

1500

 

 

 

Output kVA Capacity (kVA)

 

1.5

 

 

 

Output Watt Capacity (Watts)

 

900

 

 

 

Nominal Output Voltage(s)

 

220V; 230V; 240V

Supported

 

 

 

 

 

 

Nominal Voltage Details

 

230V nominal output in battery mode

 

 

 

Frequency Compatibility

 

50 / 60 Hz

 

 

 

Frequency Compatibility Details

 

Automatic frequency selection

 

 

 

Output Voltage Regulation (Line

 

-18%, +8%

Mode)

 

 

 

 

 

 

Output Voltage Regulation (Battery

 

+/- 5%

Mode)

 

 

 

 

 

 

Output Receptacles

 

(8) C13

 

 

 

Included Output Power Cables

 

Includes 2 C13 to C14 output power cables.

 

 

 

Hot-Swap PDU options

 

PDUBHV10 (2U / 8 C13 outlets)

 

 

 

Output AC Waveform (AC Mode)

 

Sine wave

 

 

 

 