Tripp Lite SMART5000TEL3U User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SMART5000TEL3U
Highlights
5000VA line interactive 3U rack / tower UPS
Enhanced communication ports (2 USB / 2 DB9), free PowerAlert software
and cabling, slot for SNMP/Web card
Maintains 208V nominal output over an input range of 174-282 (also supports
400VA of 120V output)
5 output receptacles (L6-30, L6-20, 5-15)
$250,000 Ultimate Lifetime Insurance (USA, Puerto Rico & Canada only)
Description
Tripp Lite's SMART5000TEL3U intelligent, line interactive UPS protects server, networking and telecommunications equipment from blackouts,
voltage fluctuations and surges in a compact rackmount housing. Completely self-contained UPS system occupies only 3 rack spaces (3U) in a
standard 19 inch rack, making this model one of the smallest 5kVA UPS systems available. Included accessories support mounting 4 post rack
enclosures. Large capacity 5000 VA/3750 watt UPS system accepts raw 208/240V AC input, adjusting output to normal 208V levels. One pair of
120V outlets support up to 400VA monitors and other low voltage accessories. Includes slot for internal SNMP/web card, plus 2 DB9 and 2 USB
enhanced monitoring ports for unattended shutdown, remote control and monitoring of UPS system and power data. Five 5 outlets (two L6-20R,
one L6-30R and two 5-15R) allow the connection of high current 20 and 30 amp 208V connectors and up to two 120V devices (max 400VA at
120V).
Applications
Ideal for centralized UPS protection of critical 208 volt equipment in server rooms, internetworking closets and telecommunications systems in rackmount or tower applications. Common applications include any mix of servers, workstations, hubs, routers, concentrators, IP telephony and traditional PBX switching systems.
Package Includes
SMART5000TEL3U UPS System PowerAlert Software and cabling Mounting hardware Warranty information Instruction manual
Features
Large 5000VA/3750-watt output capacity accommodates solitary large loads or multiple low-power loads High power density 5kVA power module occupies only 3 rack spaces (3U) 16 minutes half-load runtime (with a continuous load 2500VA; much longer runtime available at smaller loads) Line-interactive voltage regulation corrects severe brownouts and overvoltages without using battery power High voltage output supports 208V server, internetworking and telecom applications Pair of 120V outlets supports up to 400VA for standard 120V monitors, voicemail and other low-power networking devices
Five total outlets (two L6-20R, one L6-30R and two 5-15R) Diagnostic LEDs provide visual indication of 17 separate performance conditions Included PowerAlert Software provides e-mail or pager notification of power problems and simultaneous automatic unattended shutdown of multiple servers 4 built-in communications ports (2 USB/2 DB9) for remote monitoring and unattended shutdown Slot for SNMP/web card (part#: SNMPWEBCARD) and environmental sensor (part#: ENVIROSENSE) for remote communications in large IP environments Emergency Power Off (EPO) interface for emergency shutoff in large facilities Hot-swappable/user-replaceable batteries allow on-site battery replacement through the front panel without powering off connected equipment or removing the UPS from the rack UPS ships fully assembled and ready for installation; no time-consuming user battery connections required $250,000 Ultimate Lifetime Insurance. No warranty cards required for coverage! 2-year manufacturer's product warranty
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208V AC
Frequency compatibility
60 Hz
OUTPUT
Output VA 5000
Output watts 3750
Output nominal voltage
208V AC
Output voltage regulation
LINE MODE: Sine wave output within 208V (-6% +20%) plus 120V nominal (600VA max @ 120V)
Output frequency regulation
LINE MODE: Passes line frequency of 60Hz +/-10%
Outlet quantity / type 1 NEMA L6-30R, 2 NEMA L6-20R and 2 NEMA 5-15R
Overload protection Resettable circuit breaker
INPUT
Maximum input amps 24A / 3970 watts @208V
Input connection type NEMA L6-30P
Input cord length 10 ft., 10 gauge
Recommended Electrical Service
30A 208V (or 50A 208V)
BATTERY
Full load runtime 8.5 min (5000VA)
Half load runtime 20 min (2500VA)
DC system voltage 48 VDC
Typical battery lifespan
3-6 years, depending on usage
Battery recharge rate 2-4 hours to 90%
Replacement Battery Cartridge
RBC94-3U (qty 3)
VOLTAGE REGULATION
Voltage regulation description
Automatic Voltage Regulation (AVR) circuits maintains clean, regulated computer-grade 208/120V nominal output, without using battery power, during brownouts to 167V and overvoltages to 260V
Overvoltage correction
Input voltages between 228V and 260V are reduced by 12%
Loading...