Tripp-Lite SMART3000VS Specifications

Tripp-Lite SMART3000VS Specifications

SmartPro 120V 3kVA 2.25kW Line-Interactive UPS, Tower, Extended Run, Network Card Options, USB, DB9 Serial

MODEL NUMBER: SMART3000VS

Highlights

3kVA / 3000VA line interactive tower UPS system

120V nominal output during brownouts to 79V and overvoltages to 147V

Front panel status LEDs with load and battery capacity level display

USB, RS232, EPO and slot for Network Management Card options

NEMA L5-30P input; 7 NEMA 5-15R, 2 5-15/20R & 1 L5-30R outlets

This product is ENERGY STAR qualified for its ability to save customers money while helping to protect the environment

Description

Package Includes

Tripp Lite's SMART 3000VS intelligent, line interactive UPS with expandable runtime protects server, networking

SMART 3000VS UPS System,

and telecommunications equipment from blackouts, voltage fluctuations and transient surges. Small footprint,

PowerAlert Software and cabling,

tower UPS system occupies only 106 square inches of floorspace with a height of only 14.25 inches. Large

Instruction manual

capacity 3000 VA/2250 watt rated UPS system offers 4 minutes runtime at full load and 14 minutes at half load

during power failures. Runtime is expandable with optional external battery packs. Line interactive voltage regulation corrects brownouts as low as 79V and overvoltages as high as 147V to fully regulated 120V nominal output for smooth continuous operation of connected equipment. Includes a total of 10 outlets, 3 of which can be individually powered off and back on via software interface to selectively reboot remote equipment or shed less critical loads to extend battery runtime for more critical loads. Includes slot for Network Management Card options, such as Tripp Lite'sSNMPWEBCARD, plus 2 DB9 and 2 USB enhanced monitoring ports for unattended shutdown, remote control and monitoring of UPS system and power data. Ships in attractive gray color scheme. Compatible with Tripp Lite's PowerAlert and Watchdog service software.

Features

3000VA/2250 watt output capacity accommodates a variety of server, networking and telecom devices

High power density 3kVA UPS system occupies only 106 square inches of floorspace with a height of only 14.25 inches

Compatible with North American 120V/60 Hz power as found in the USA, Canada and Mexico

Offers 4 minutes runtime with a full load of 3000VA and 14 minutes with a half load of 1500VA

Runtime is expandable with BP48V24-2U(limit 1), BP48V60RT-3U(multi-pack compatible) and BP48V27-2US(multi-pack compatible) external battery packs

Intelligent battery management system extends battery life

Line interactive voltage regulation corrects severe brownouts and overvoltages from 79 to 147v back to normal 120v levels without using battery power

10 total outlets(7 NEMA5-15R; 2 NEMA5-15/20R; 1 L5-30R)

Includes NEMA L5-30P locking 30 amp input plug connection

Notification of system status via 5 LEDs and multi-function audible alarms

Included PowerAlert Software provides e-mail notification of power problems and the simultaneous automatic unattended shutdown of multiple servers

4 built-in communications ports(2-DB9, 2-USB) for remote monitoring and unattended shutdown

Slot for Network Management Card options, such as Tripp Lite's SNMPWEBCARD network interface

Supports Tripp Lite's WatchDog software application to restore unresponsive programs by automatically restarting them and rebooting completely locked computers by automatically switching UPS power off and back on again

Communication ports support on battery, low battery, power restored, AC line voltage, DC battery voltage, load percentage, battery charge current, battery capacity, internal UPS temperature and line frequency status messaging. Interface supports timed inverter shutoff after unattended shutdown, activate self-test and 10 second reboot of connected equipment

3 individual customized load management receptacles can be individually powered off and back on again via software interface to reboot remote equipment or perform "load shedding" of less critical loads to extend battery runtime for the most critical equipment

Built-in Emergency Power Off(EPO) interface supports emergency shutoff in large facilities

Hot-swappable/user replaceable batteries allow on-site battery replacement without powering off connected equipment

UPS battery set ships fully assembled and ready for use, no time consuming, connection of individual internal batteries by user is necessary

This product is ENERGY STAR qualified for its ability to save customers money while helping to protect the environment

Specifications

OUTPUT

Output Volt Amp Capacity (VA)

 

3000

 

 

 

Output kVA Capacity (kVA)

 

3

 

 

 

Output Watt Capacity (Watts)

 

2250

 

 

 

Output kW Capacity (kW)

 

2.2

 

 

 

Output Capacity Details

 

Output is reduced to 1600 watts maximum when used with external battery packs

 

 

 

Power Factor

 

0.8

 

 

 

Nominal Output Voltage(s)

 

110V; 115V; 120V

Supported

 

 

 

 

 

 

Nominal Voltage Details

 

120v nominal output in battery mode

 

 

 

Frequency Compatibility

 

60 Hz

 

 

 

Output Voltage Regulation (Line

 

-18% / +8%

Mode)

 

 

 

 

 

 

Output Voltage Regulation (Battery

 

+/- 5%

Mode)

 

 

 

 

 

 

Output Receptacles

 

(7) 5-15R; (2) 5-15/20R; (1) L5-30R

 

 

 

Load Management Receptacles

 

Three switchable two-outlet 5-15R load banks

 

 

 

Output Circuit Breakers

 

20A branch rated (x2) - breaker 1 protects 5-20R, breaker 2 protects 5-15R, L5-30R is unbreakered

 

 

 

Output AC Waveform (AC Mode)

 

Sine wave

 

 

 

Output AC Waveform (Battery Mode)

 

PWM sine wave

 

 

 

INPUT

 

 

 

 

 

 

 

 

Rated input current (Maximum Load)

 

24A

 

 

 

Loading...