Tripp Lite SMART3000SLT User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SMART3000SLT
Highlights
3kVA / 3000VA line interactive tower UPS; Sine wave output
120V nominal output during brownouts to 83 and overvoltages to 145V
USB, RS232, EPO and optional SNMP/Web card are available for
simultaneous use
Front panel status LEDs with detailed load and battery capacity display
NEMA L5-30P input; 6 NEMA 5-15/20R & 1 L5-30R outlets
Description
3000VA line-interactive tower UPS system for server, networking and telecommunications equipment. Upright tower form factor. Offers sine wave 120V nominal output in both AC and battery modes. Switches to battery-derived AC output during power failures and extreme voltage variations. Line-interactive automatic voltage regulation (AVR) provides voltage boost/cut during brownouts/overvoltages to maintain regulated 120V nominal output over an input voltage range of 83-145V. Includes NEMA L5-30P input plug and 7 UPS-supported output receptacles (6 x 5-15/20R, 1 x L5-30R). Network-grade AC surge and noise suppression. Network management interfaces support simultaneous communications via USB port, DB9 serial port and SNMPWEBCARD slot. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility power conditions via all three network interfaces. Includes PowerAlert power management software and complete cabling. Three-stage metered current monitoring and battery charge status LEDs. Utility power and voltage regulation, and battery warning LEDs. Audible alarm. Self-test. Field-replaceable, hot-swappable internal batteries. Attractive all-black color scheme.
Package Includes
SMART3000SLT UPS System PowerAlert Software and cabling Owner's manual
Features
SmartPro line-interactive UPS system is ideal for voice, data, medical and industrial networking applications Line-interactive voltage regulation maintains selectable 120V nominal output during brownouts as low as 83V and overvoltages to 145V Enables continuous operation through blackouts, voltage fluctuations and surges Line-interactive automatic voltage regulation (AVR) provides 12% and 24% voltage boost during brownouts and a 12% voltage cut during overvoltages Standard internal battery set offers 9 min. runtime at half load (1125W) and 3.5 min. at full load (2250W) Space-saving upright tower format Network interfaces support simultaneous communications via built-in USB port, DB9 serial port and SNMPWEBCARD slot HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert power management software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, timed inverter shutoff, activate self-test and output power control NEMA L5-30P input plug/6 x NEMA 5-15/20R and 1 x NEMA L5-30R output receptacles Front panel LEDs provide current monitoring, voltage regulation, battery charge level and battery warning information UPS ships fully assembled in full compliance with DOT regulations; no time-consuming connection of internal batteries by user required
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
3000
Output kVA capacity (kVA) 3
Output Watt Capacity (watts)
2250
Output kW capacity 2.2
Output power factor 0.8
Nominal Output Voltage(s) Supported
120V
Frequency compatibility 60 Hz
Output voltage regulation (line mode)
-18% / +8%
Output voltage regulation (Battery mode)
+/- 5%
Built-in UPS output receptacles
6 5-15/20R outlet(s); 1 L5-30R outlet(s)
Output circuit breaker 20A branch rated (x2) - each breaker protects 3 5-15/20R outlets, L5-30R is unbreakered
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode)
Pure Sine wave
INPUT
Rated input current (at maximum load)
20A
Nominal Input Voltage(s) Supported
120V AC
UPS input connection type L5-30P
Input circuit breaker 30A
UPS Input cord length (ft.) 10
UPS Input cord length (m) 3
Recommended Electrical Service
30A 120V
BATTERY
Full load runtime (minutes)
3.5 min. (2250w)
Half load runtime (minutes)
9 min. (1125w)
DC system voltage (VDC) 48
Battery recharge rate (included batteries)
Less than 4.5 hours from 10% to 90%