This Addendum sheet contains important instructions for proper
assembly and warnings that should be followed. Failure to heed
these instructions warnings may affect your safety.
Explanation of Symbols
Caution, Risk of Danger
Electrical Shock hazard
Protective Earth Ground
Recyclable, Contains Lead
Connector Cable
Assembly Instructions
The following accessories are included with your UPS system:
Connector (Qty. 1): Red Housing, ANEN Part Number: PA75B2-HL
Connector (Qty. 1): Black Housing, ANEN Part Number: PA75B0-HL
Terminals (Qty. 2): ANEN Part Number: PA5952-T
Use only the recommended crimping tool (user supplied): Buchanan Part
Number: C-24
2
Connector Cable
Assembly Instructions
Contact Tripp Lite at tripplite.com/support if you do not have the connectors
and terminals. If you need replacements, request the kit listed below:
UPS ModelKit NumberKit Includes
SMART1524ETBPA7524KIT(x2) 6 AWG DC Terminals
(x1) Red DC Connector Housing
(x1) Black DC Connector Housing
SMART1548ETBPA7548KIT(x2) 8 AWG DC Terminals
(x1) Red DC Connector Housing
(x1) Black DC Connector Housing
CAUTION: Assembly and installation should be performed by
qualified professional electrical service personnel only.
The user-supplied DC cables have a maximum recommended length of 2 m
(6.65 ft.). Use stranded copper conductors only.
Model SMART1524ET (24V UPS System): Use minimum 6 AWG wire,
rated to 105°C (221°F).
Model SMART1548ET (48V UPS System): Use minimum 8 AWG wire,
rated to 105°C (221°F).
Ground Wire (both models): Use minimum 12 AWG wire, rated to 105°C
(221°F).
Use a RED wire for the POSITIVE supply.
Use a BLACK wire for the NEGATIVE supply.
Use a GREEN wire for the GROUND wire.
Strip the wires using a
1
wire stripping tool.
Note: The recommended
length for the stripped
ends is ½ inch.
BLACK
RED
1
3
Connector Cable
Assembly Instructions
Insert the stripped wire ends into the terminals.
2
2
Crimp the terminal and wire with the recommended wire crimping tool.
3
Tug on the wire leads while holding the terminals to ensure the wire is
crimped securely.
3
4
Connector Cable
Assembly Instructions
Insert the RED crimped wire terminal into the RED DC connector
4
housing and the BLACK crimped wire terminal into the BLACK DC
connector housing. Then, join the connector housings together via the
slots on the housings. Be sure to observe the polarity.
BLACK
RED
4
Equipment Connection Warnings
CAUTION: Make sure UPS is powered down and disconnected
from AC mains power. The battery circuitry is not isolated
from AC mains. Turn off power to the UPS prior to battery
connection.
Do not connect or disconnect battery modules while the UPS is operating.
Never attempt to install electrical equipment during a thunderstorm.
Make sure your external battery matches your UPS Rating: 24V or 48V.
External Battery Warnings
Connect the GREEN ground wire between an external metal battery cabinet
and the ground lug on the front of the UPS.
Connect the RED and BLACK cables to the external battery. Be sure to
observe the polarity: RED to the positive terminal and BLACK to the negative
terminal of the external battery.
5
Connector Cable
Assembly Instructions
Once the cable assembly is attached to the external battery at the end
5
opposite the DC connector, it can be mated to the DC connector on the
UPS system’s front panel.
When connecting the cables to the external battery, you may observe
small sparks; this is normal.
RED
BLACK
5
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support
6
20-02-243 93-3C60_RevB