Tripp Lite SMART1500XL User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SMART1500XL
Highlights
1.5kVA / 1500VA line interactive tower UPS system
120V output, Corrects brownouts and overvoltages from 75V to 147V
Expandable runtime, Status LEDs with load level and battery capacity display
USB & RS232 ports, 1 switched load bank, Hot-swap batteries
NEMA 5-15P input, 6 NEMA 5-15R outlets
Description
Tripp Lite's SMART 1500XL intelligent, line interactive UPS system protects servers, networking accessories and telecommunications equipment from blackouts, voltage fluctuations and transient surges. Large internal batteries offer 20 minutes half load runtime and 7 minutes at full load during power failures. Runtime is expandable with the addition of BP36V15-2U (limit 1) or BP36V42-3U external battery packs. 1500VA/980 watt power handling capability supports a variety of networking, telecom and various other application types. Includes a total of 6 outlets, 1 of which can be individually powered on and off via software interface to selectively reboot remote equipment or to shed less significant loads to extend battery runtime for more critical equipment. Supports remote monitoring of UPS and site power conditions via built-in USB and DB9 monitoring ports. Includes PowerAlert UPS monitoring and unattended shutdown software with complete cabling. Notification of system status via 5 LEDs and multi-function audible alarms. Wall mountable with UPSWM wallmount bracket. Network-grade AC surge suppression protects equipment from damage and performance problems resulting from transient surges. Attractive, small-footprint tower housing uses less than 66 square inches of floor or desktop space.
Package Includes
SMART1500XL UPS System USB and DB9 monitoring cables PowerAlert unattended shutdown and UPS/Power monitoring software
Features
1500VA/980 watt power handling capability supports a variety of networking, telecom and various other application types Large internal batteries offer 20 minutes half load runtime and 7 minutes at full load during power failures Runtime is expandable with the addition of BP36V15-2U or BP36V42-3U external battery packs Automatic Voltage Regulation (AVR) circuits with two boost and one voltage reduction level maintains usable 120V nominal output over an input voltage range of 75-147V Includes a total of 6 NEMA5-15R outlets, 1 of which can be individually powered on and off via software interface to selectively reboot remote equipment or shed less significant loads to extend battery runtime for more critical equipment Includes 1 USB and 1 DB9 monitoring port for remote monitoring of UPS status and site power conditions PowerAlert UPS monitoring and unattended shutdown software with complete cabling included Notification of system status via 5 LEDs and multi-function audible alarms Wall mountable with UPSWM wallmount bracket Attractive small footprint black tower housing uses less than 66 square inches Built-in rear-exit cooling fan runs as needed to maintain optimal internal temperatures during extended run battery operation Hot-swappable/user replaceable batteries allow on-site battery replacement UPS battery set ships fully assembled and ready for installation, no time consuming connection of internal batteries by user is necessary Cold start capability enables UPS turn-on in battery mode during blackout conditions
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
1500
Output kVA capacity (kVA) 1.5
Output Watt Capacity (watts)
980
Output power factor 0.7
Nominal Output Voltage(s) Supported
120V
Frequency compatibility 60 Hz
Output voltage regulation (line mode)
-18%, +8%
Output voltage regulation (Battery mode)
+/- 5%
Built-in UPS output receptacles
6 5-15R outlet(s)
Built-in controllable switched load banks
One switchable single-outlet 5-15R load bank
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode)
PWM sine wave
INPUT
Rated input current (at maximum load)
12A
Nominal Input Voltage(s) Supported
120V AC
UPS input connection type 5-15P
Input circuit breaker 15A
UPS Input cord length (ft.) 6
UPS Input cord length (m) 1.8
Recommended Electrical Service
15A 120V
BATTERY
Full load runtime (minutes) 7 min. (980w)
Half load runtime (minutes) 20 min. (490w)
Expandable battery runtime Extended runtime supported via optional external battery packs
External battery pack compatibility
BP36V15-2U (limit 1); BP36V42-3U (multi-pack compatible)
DC system voltage (VDC) 36
Battery recharge rate (included batteries)
Less than 4 hours from 10% to 90%