Tripp Lite SMART1050SLT User Manual

Page 1
Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SMART1050SLT
Highlights
1050VA / 1.05kVA line-interactive tower UPS system for networks
Maintains sine-wave 120V nominal output over an input range of 95 to 145V
Simultaneous communications via SNMPWEBCARD slot, HID enabled USB
and DB9 serial ports
Free PowerAlert UPS monitoring software manages an unlimited number of
network UPS systems
Input: NEMA 5-15P (120V 15A) / Output: 8 NEMA 5-15R (120V)
2 year product warranty / $250,000 Ultimate Lifetime Insurance (USA, Puerto
Rico & Canada only)
Description
1050VA line-interactive tower UPS system for server, networking and telecommunications equipment. Upright tower form factor. Offers sine wave
100V, 110V or 120V nominal output in both AC and battery modes. Switches to battery-derived AC output during power failures and extreme voltage
variations. Line-interactive automatic voltage regulation (AVR) provides voltage boost during brownouts and voltage cut during overvoltages to
maintain regulated 100V, 110V or 120V nominal output over an input voltage range of 95-145V. Features NEMA 5-15P input plug and 8 NEMA
5-15R output receptacles. Network-grade AC surge and noise suppression. Network management interfaces support simultaneous communications
via USB port, DB9 serial port and SNMPWEBCARD slot. HID-compliant USB interface enables full integration with built-in power management and
auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility
power conditions via all 3 network interfaces. Includes PowerAlert monitoring software and complete cabling. Features 3-stage metered current
monitoring and battery charge status LEDs. Dataline surge suppression for dialup, DSL or network Ethernet connection. Utility power and voltage
regulation LEDs. Audible alarm. Self-test. Field replaceable, hot-swappable internal batteries and external battery packs. Attractive all-black color
scheme. Two-year warranty and $250,000 connected equipment insurance; extended warranty and service contracts available.
Applications
Ideal for protection of network fileservers, internetworking gear, switches, hubs, POS terminals, VOIP telephony and traditional PBX switching systems, back office computer systems, ATM machines, informational/Internet/commerce kiosks, remote unattended servers, web servers, database servers, security systems, card readers, security cameras and other sensitive electronic devices requiring clean, continuously regulated output power
Package Includes
SMART1050SLT UPS System PowerAlert Software CD USB and serial cabling Owner's manual with warranty information
Features
SmartPro line-interactive UPS system is ideal for voice, data, medical and industrial networking applications Line-interactive automatic voltage regulation (AVR) maintains selectable 100V, 110V or 120V nominal output during brownouts as low as 83V and overvoltages to 145V
Page 2
Enables continuous operation through blackouts, voltage fluctuations and surges Line-interactive AVR oprovides a 14% boost during brownouts and a 12% voltage cut during overvoltages Standard internal battery set offers 19 min. runtime at half load (325W) and 7 min. at full load (650W) Space-saving upright tower format Network interfaces support simultaneous communications via built-in USB port, DB9 serial port and SNMPWEBCARD slot HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, timed inverter sutoff, activate self-test and output power control NEMA 5-15P input plug; 8 x battery-supported NEMA 5-15R output receptacles Front panel LEDs offer current monitoring, voltage regulation and battery charge level information UPS ships fully assembled in full compliance with DOT regulations; no time-consuming connection of internal batteries by user required Single-line tel/DSL or network Ethernet line surge suppression 2-year warranty; $250,000 Ultimate Lifetime Insurance (USA & Canada only)
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V, 100V, 110V (selectable)
Frequency compatibility
50/60Hz
OUTPUT
Output VA 1050
Output watts 650
Output nominal voltage
100, 110, 120 or 127V AC
Output voltage regulation
LINE MODE: Sine wave line voltage 120V (-13%/+15%), BATTERY MODE: Sine wave output 120V (+/-5%)
Output frequency regulation
LINE MODE: Passes line frequency of +/-10% BATTERY MODE: Inverter output regulated to 60Hz (+/- 1Hz)
Outlet quantity / type 8 NEMA 5-15R
INPUT
Maximum input amps
6.1A (120V) / 6.6A (110V) / 7.2A (100V)
Input connection type
NEMA 5-15P
Input cord length 6 ft/1.8m
Recommended Electrical Service
15A 120V
BATTERY
Full load runtime 7 min.
Half load runtime 19 min.
DC system voltage 24VDC
Typical battery lifespan
4-6 years typical
Battery recharge rate Less than 6 hours to 90% after full load discharge
Replacement Battery Cartridge
RBC24-SLT
VOLTAGE REGULATION
Voltage regulation description
Automatic voltage regulation (AVR) circuits maintain clean, regulated computer-grade 120V, 110V or 100V nominal output, without using battery power, during brownouts to 83V and overvoltages to 145V
Page 3
Overvoltage correction
120V: input voltages between 127-145V are reduced by 12% / 110V: Inputs between 116-133V are reduced by 12% / 100V: Inputs between 106-121V are reduced by 12%
Brownout correction 120V: Input voltages between 95-108V are boosted by 14% / 110V: Inputs between 87-99V are boosted by 14% / 100V:
Inputs between 83-90V are boosted by 14%
LEDS ALARMS & SWITCHES
Front panel LEDs 10 front panel LEDs indicate line/battery power status, over/under voltage correction, battery charge level, load
percentage, overload and replace battery
Alarms Audible alarms indicate BATTERY MODE and OVERLOAD, UPS POWERED ON
Switches 2 front panel-mounted switches. POWER ON switch powers UPS on in AC or battery mode when pressed longer than 1
second. POWER ON switch also initiates self-test when pressed longer than 0.5 seconds with the UPS in line power mode. Also serves as an alarm s
SURGE / NOISE SUPPRESSION
AC surge suppression
690 joules
AC suppression response time
Instantaneous
Dataline suppression Includes 8-wire RJ45 jack; pins 1, 2, 3 and 6 provide 10baseT Ethernet line surge suppression with 7.5V clamping; pins
4 and 5 provide single-line tel/DSL line surge suppression starting at 260V
EMI / RFI AC noise suppression
Yes
PHYSICAL
Shipping weight (lbs) 39.6
Shipping weight (kg) 17.82
Shipping Dimensions (HWD/in)
14 x 9.75 x 18.5
Shipping Dimensions (HWD/cm)
35.6 x 24.8 x 47
Unit weight (lbs) 36
Unit weight (kg) 16.2
Unit Dimensions (HWD/in)
10.25 x 6.75 x 13.25
Unit Dimensions (HWD/cm)
26.04 x 17.15 x 33.7
Material of construction
Steel
Form factors supported
Tower
Cooling method Fan
Battery Access Supports battery access and hot-swap replacement without powering connected equipment off
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
Storage Temperature +5 to +122 degrees Fahrenheit/-15 to +50 degrees Celsius
Operating Temperature
+32 to +104 degrees Fahrenheit/0 to +40 degrees Celsius
Line mode BTU/hr. (Max.)
141 BTU/hr. (max. full load - line power mode)
Battery mode BTU/hr. (Max.)
452 BTU/hr. (max. full load - battery mode)
Audible Noise < 50 dBA @ 1m
Page 4
COMMUNICATIONS
Network monitoring port
Includes 2 built-in monitoring ports, 1 USB and 1 DB9. Each supports on battery, low battery, power restored, AC line voltage, DC battery voltage, load percentage, battery charge current, battery capacity, temperature and line frequency status messaging.
Software and cabling included
Includes PowerAlert UPS monitoring software for all common network and stand-alone operating systems. Ships with 2 cables, 1 USB and 1 DB9
SNMP compatibility SNMP adapter accessory # SNMPWEBCARD
WatchDog compatibility
Compatible with Tripp Lite's WatchDog Software to restore operation to locked equipment through soft reboot of application/OS or hard power off/on reboot of connected equipmentâideal for unattended kiosk applications
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode
4-6 milliseconds
Low voltage transfer to battery power
Switches to battery power as line voltage decreases to 95V (at 120V), 87V (at 110V) , or 83V (at 100V) or less. Resets back to line power mode as line voltage increases to 100V (at 120V), 92V (at 110V), or 87V (at 100V) or higher.
High voltage transfer to battery power
Switches to battery power as line voltage increases to 145V (at 120V), 133V ( at 110V), and 121V (at 100V) volts or higher. Resets back to line power mode as line voltage decreases to 141 (at 120V), 129 (at 110V), or 118V (at 100V) or less
SPECIAL FEATURES
Cold Start Inverter can be cold started to enable temporary AC output during a power failure by pressing and holding the POWER
ON button for longer than 1 second.
Appearance Attractive all-black color scheme
CERTIFICATIONS
Certifications Tested to UL1778 (USA), CSA C22.2 No. 107.3 (Canada), RoHS Compliant, Class B (Emissions), NOM (Mexico), FCC
Part 68 / Industry Canada (telecommunications)
WARRANTY
Product Warranty Period
2 years
Connected Equipment Coverage
$250,000 connected equipment insurance (USA / Canada only)
Optional Coverage 3-year and 5-year extended warranty coverage; next-day and on-site warranty coverage available for select
opportunities
Related Items
Audio Cables
CT120 Instant-Read- AC Outlet Circuit Tester Qty: [optional]
Extended Warranties
WEXT3-500-1500 3-Year Extended Warranty - For Smart Line-Interactive and Online Tower or Rack models,
1500VA or less
Qty: [optional]
WEXT5-500-1500 5-Year Extended Warranty - For Smart Line-Interactive and Online Tower or Rack models,
1500VA or less
Qty: [optional]
Power Distribution
PDU1215 Basic PDU / Power Distribution Unit - Safe, reliable power distribution for critical networking
equipment
Qty: [optional]
SNMP Accessories
ENVIROSENSE Monitors temperature, humidity and contact-closure inputs. (Requires SNMPWEBCARD or
switched PDU.)
Qty: [optional]
SNMPWEBCARD For remote monitoring and control via SNMP, Web or telnet. Qty: [optional]
Software
Page 5
WATCHDOGSW WatchDog Service Monitoring / Reboot Software Qty: [optional]
Surge Protectors
DTEL2 Network Surge Suppressor - Essential protection for data and communication lines Qty: [optional]
DNET1 Network Surge Suppressor - Essential protection for data and communication lines Qty: [optional]
DCATV Network Surge Suppressor - Essential protection for TV/VCR coaxial lines Qty: [optional]
USB Hubs/Accessories
U022-010 USB Cable - 10-ft. USB 2.0 AB Gold Device Cable Qty: [optional]
More information, including related products, owner's manuals, and additional technical specifications, can be found online at
www.tripplite.com/en/products/model.cfm?txtModelID=3253.
©2009 Tripp Lite. All Rights Reserved.