Highlights
3000VA / 3kVA line interactive, extended-run tower UPS
Maintains 120V nominal output over an input range of 87 to 140V
Network communications supported via 3 DB9 ports (1 serial / 2 contact
closure)
Current monitoring and switched PDU control via 2 single-outlet load banks
Input: L5-30P (120V 30A) / Output: 4 NEMA 5-15/20R, 4 NEMA 5-15R (120V)
2 year product warranty / $250,000 Ultimate Lifetime Insurance (USA, Puerto
Rico & Canada only)
Description
Tripp Lite's SM3000NAFTA intelligent, line interactive large tower UPS system protects servers, networking accessories and telecommunications
equipment from blackouts, voltage fluctuations and transient surges. Large internal batteries offer 23 minutes half load runtime and 7 minutes fully
loaded. Runtime is expandable with optional BP24V28-2U (limit 1) and BP24V70-3U external battery packs. 3000VA/2400 watt power handling
capability supports a variety of networking, telecom and other sensitive electronic applications. Includes 8 protected outlets. Supports remote
monitoring of UPS and site power conditions via built-in RS-232 enabled monitoring port, plus standard UPS monitoring via 2 built in contact closure
ports. Includes PowerAlert UPS monitoring and unattended shutdown software with complete cabling. Built-in audible alarm and front panel LEDs
indicate line power, battery power, battery charge level, load level and voltage regulation status. Network grade AC surge suppression protects
equipment from damage and performance problems resulting from transient surges. Attractive large gray tower housing. Two year warranty with
$250,000 connected equipment insurance.
Applications
Ideal for the protection of communication equipment including: routers, hubs, switches, IP-PBX, Traditional PBX and Key/Hybrid Telephone Systems. Also ideal for the protection of data processing equipment such as fileservers, workstations and other sensitive devices requiring clean, continuously regulated output power. Extended runtimes are available using additional external battery packs BP24V28-2U (limit 1) and BP24V70-3U (multi-pack compatible).
Package Includes
SMART3000NET UPS System PowerAlert Software and three 6 foot network cables Warranty information Instruction manual
Features
SM3000NAFTA line interactive UPS offers battery derived AC output during power outages, voltage regulation during brownouts and overvoltages, plus network-grade AC surge suppression 3000VA/2400 watt power handling capability supports a variety of networking, telecom and other sensitive electronic devices Large internal batteries offer runtimes of 23 minutes at half load (1500VA/1200 watts) and 7 minutes at full load (3000VA/2400 watts) Runtime is further expandable with optional external BP24V28-2U (limit 1) and BP24V70-3U battery packs Automatic Voltage Regulation (AVR) circuits maintain 120V nominal output over an input voltage range of 87-140V
Includes 8 fully protected outlets (4 NEMA 5-15R & 4 NEMA 5-15/20R) with 2 single outlet load banks that can be individually powered off and back on again via software interface PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, email notification, event logging and running user defined script commands Offers simultaneous monitoring of up to 3 directly connected devices through included DB9 contact closure and RS-232 enabled interfaces, or the monitoring of any number of additional servers over IP with included PowerAlert monitoring software In addition to the contact closure monitoring of on battery, low battery and power restored messaging, built-in RS-232 interface supports messaging of UPS and line power status, including AC line voltage, DC battery voltage and remaining battery capacity Supports activate self-test and UPS output power control for delayed or immediate reboot of connected equipment Diagnostic LEDs (indicate 17 performance conditions) UL (USA), cUL (Canada), NOM (Mexico), FCC Class A (Emissions) $250,000 Ultimate Lifetime Insurance (USA & Canada Only)
Specifications
SYSTEM OVERVIEW
Voltage compatibility
120V AC
Frequency compatibility
60 Hz
OUTPUT
Output VA 3000
Output watts 2400
Output nominal voltage
120V AC
Output voltage regulation
LINE MODE: Sine wave line voltage 120V (-13% / +5%) BATTERY MODE: PWM sine wave output 120V +/-5%
Output frequency regulation
LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type
4 NEMA 5-15R and 4 NEMA 5-15/20R
Customized load management receptacles
2 individually controllable outlets support load shedding and remote reboot on demand of locked network devices. Controllable via PowerAlert software to switch off optional loads, like monitors, to increase available runtime for servers and other critical devices. "
Overload protection
Yes, via 35A input breaker and two 15A output load breakers
INPUT
Maximum input amps
22A
Input connection type
NEMA L5-30P
Input cord length 8 ft.
Recommended Electrical Service
30A 120V
BATTERY
Full load runtime 7 minutes (3000VA)
Half load runtime 23 minutes (1500VA)
Expandable battery runtime
Supports extended runtime with optional BP24V28-2U (limit 1) and BP24V70-3U (multi-pack compatible)
DC system voltage
24 V DC
Typical battery lifespan
3-6 years, depending on usage