Tripp Lite PDU3V602D354, PDU3V602D354A, PDU3V602D354B, PDU360AT6G60 Owner's Manual

1. Important Safety 2 Instructions
2. Installation 3
2.1 Mounting the ATS 3
2.2 Mounting the Power Strip 4
2.3 Connecting the Power Strip 4 to the ATS
2.4 Connecting the ATS 5
2.5 Networking the ATS 5
3. Features 6
4. Digital Display 8
5. Using the Digital Display 11
5.2 Navigating Config Menus 18 and Submenus
6. Configuration and Operation 20
6.1 Automatic Transfer Switch 20
7. Service 22
8. Warranty and Product 22 Registration
Español 24 Français 47
1
Owner’s Manual
PDU360AT6G60
(Series Number: AG-013D)
3-Phase 1U Monitored Rack PDU
with Automatic Transfer Switch (ATS)
PDU3V602D354, PDU3V602D354A,
PDU3V602D354B
(Series Number: AG-013E)
3-Phase Vertical Power Strip
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2016 Tripp Lite. All rights reserved.
PROTECT YOUR INVESTMENT!
Register your product for quicker service
and ultimate peace of mind.
You could also win an
ISOBAR6ULTRA surge protector—
a $100 value!
www.tripplite.com/warranty
16-01-031-933588.indb 1 3/22/2016 4:14:15 PM
2
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the installation, operation and storage of this product. Failure to heed these instructions and warnings may affect the product warranty.
• The Power Strip provides the convenience of multiple outlets, but DOES NOT provide surge or line noise protection for connected equipment.
• Use only with Tripp Lite PDU3V60XXXXX Series with overcurrent protection. Overcurrent protection per PDU consists of six double-pole 20A, 240V AC breakers (2 per phase).
• Do not exceed the following equipment ratings:
• For Outputs 1 and 2, the maximum full balanced load is 13.9A per bank when powered by a
3-phase ATS (Automatic Transfer Switch) with a rated input of 48A.
• The Automatic Transfer Switch and Power Strip are designed for indoor use only, in a controlled environment, away from excess moisture, temperature extremes, conductive contaminants, dust or direct sunlight.
• Keep indoor ambient temperature between 32°F and 113°F (0°C and 45°C).
• The Automatic Transfer Switch and Power Strip must be installed by a qualified technician only.
• Do not attempt to mount the Automatic Transfer Switch or Power Strip to an insecure or unstable surface.
• Install in accordance with National Electrical Code standards. Be sure to use the proper overcurrent protection for the installation, in accordance with the plug/equipment rating.
• Connect the Automatic Transfer Switch to an outlet that is in accordance with your local building codes and that is adequately protected against excess currents, short circuits and earth faults.
• The electrical outlets supplying power to the equipment should be installed near the equipment and easily accessible.
• Do not connect the Automatic Transfer Switch to an ungrounded outlet or to extension cords or adapters that eliminate the connection to ground.
• Be sure to provide a local disconnect device on any models that are permanently installed without a plug that is easily accessible.
• Never attempt to install electrical equipment during a thunderstorm.
• Individual equipment connected to the Power Strip should not draw more current than the individual outlet’s rating.
• The total load connected to the Power Strip must not exceed the maximum load rating for the Automatic Transfer Switch.
• Do not attempt to modify the Automatic Transfer Switch’s or Power Strip’s input plugs or power cables.
• Do not drill into or attempt to open any part of the Automatic Transfer Switch or Power Strip housing. There are no user-serviceable parts inside.
• Do not attempt to use the Automatic Transfer Switch or Power Strip if any part of it becomes damaged.
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
1. Important Safety Instructions
16-01-031-933588.indb 2 3/22/2016 4:14:15 PM
3
2.1 Mounting the Automatic Transfer Switch (ATS)
Mount your equipment in a 4-post rack or rack enclosure. The user must determine the fitness of hardware and procedures before mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or rack enclosure. The procedures described in this manual are for common rack and rack enclosure types and may not be appropriate for all applications.
Note: Each snap-in slide rail assembly consists of a sliding rack enclosure mounting bracket and an inner channel rail. For ease of installation, the inner channel rails come pre-attached to the ATS unit.
2. Installation
1
Align the rear bracket's tabs with the rack enclosure's square mounting holes 1A and push the metal hooks through the mounting holes 1B. Push the rear bracket toward the enclosure support post in order for the blue tabs to snap into the mount 1A. Align the front bracket's tabs with the rack enclosure's front square mounting holes and push the metal hooks through the mounting holes. Finally, push the front bracket toward the enclosure support post in order for the blue tabs to snap into the mount 1B.
2
Repeat step one for the second mounting bracket on the opposite side of the rack enclosure.
3
Once both mounting brackets are fixed onto the rack enclosure, secure the rear brackets using the included M5X10L screws.
4
Align the inner channel rails attached to the ATS with the mounting brackets. Then slide the unit into the rail assembly. Using a screwdriver, secure the ATS’s panel­mounted screws to the rack enclosure.
1A
1B
3
4
16-01-031-933588.indb 3 3/22/2016 4:14:16 PM
4
2.2 Mounting the Power Strip
Note: Power strips require a 4-inch installation width within the rack. Mounting buttons come pre-installed on the Power Strip for toolless mounting. A second set of button mounting holes on the Power Strip allow alternate positioning in the rack.
Position the Power Strip as desired within the rack enclosure, align the buttons with the rack mounting slots and slide the Power Strip downward into position.
Your model may differ slightly from image.
2. Installation
2.3 Connecting the Power Strip to the ATS
The power strip has two 8-conductor plugs. Each cord is labeled Output 1 and Output 2. The cord labeled Output 1 must be connected to the ATS Output 1 receptacle; the cord labeled Output 2 must be connected to the ATS Output 2 receptacle.
The power strip also has a 6-conductor circuit detection cable that requires connection from the power strip to the ATS unit.
Your model may differ slightly from image.
16-01-031-933588.indb 4 3/22/2016 4:14:17 PM
5
2. Installation
2.4 Connecting the ATS
2.4.1 Connect ATS Input Plugs
Note: The ATS comes equipped with two 3-Phase AC power inputs: Source A and Source B. Source A is the default preferred (primary) source. See 5.2 Navigating Config Menus and Submenus section for instructions on changing the preferred source. The connection instructions below assume Source A is the preferred source.
Connect the Source A input plug A to a preferred 3-Phase AC power source. Under normal operating conditions, the ATS will distribute AC power from the Source A input source. Connect the Source B input plug B to an alternative source of grounded AC power. Do not plug the Source B input into the same power source as the Source A input. The ATS will distribute AC power from the Source B input only if the Source A input becomes unavailable or unstable.
2.4.2 Connect Equipment
to Power Strip
Do not exceed the load rating of the power strip. The total electrical current used by each phase of the power strip will be displayed in amperes on the digital meter.
2.5 Networking the ATS
The ATS provides remote monitoring and more via Web browser, telnet and SNMP-based Network Management Systems.
Your ATS can receive its IP address assignment via DHCP server (dynamic) or static (manual) addressing methods. If you are uncertain which method to use, contact your network administrator for assistance before continuing the configuration process.
For more information about configuration and operation of the ATS via the PowerAlert® Web browser interface, refer to the SNMPWEBCARD User's Guide by going to www.tripplite.com/support/snmpwebcard.
Note: The MAC address (12-digit string in this format: 000667xxxxxx) is printed on a label and attached to the ATS enclosure. For static IP address assignment, use the DB9 configuration cable (73102) included with the ATS.
A
B
16-01-031-933588.indb 5 3/22/2016 4:14:17 PM
6
3. Features
ATS Automatic Transfer Switch (PDU360AT6G60)
Power Strip* (PDU3V602D354, PDU3V602D354A, PDU3V602D354B)
1
Power Strip Outlets: These single-phase IEC C13 and C19 outlets receive power from the
interlaced 3-phase power input connections of Source A or Source B of the ATS. These outlets are not controllable.
2
Power Strip Input Power Cords: The 7-conductor plugs
contain an 8-position connector that attaches directly to the ATS.
3
ATS Source A and Source B Input: The cords are permanently
attached to the ATS and have IEC 309 60A Blue (3P + E) plugs.
4
Digital Display: Shows source status, measured values, display
modes and other information. See the Digital Display section for detailed explanations of the indicators and displays.
5
SNMP Reset Button: Press the reset button for 3 seconds to
reboot the ATS network card. Rebooting the network card will not erase network settings or interrupt AC power. The reset button is recessed. Use a paper clip or other suitable object to press it.
3
86 7
5
11 11 12
10
102
4
9 9
IEC 309 60A Blue (3P + E)
* PDU3V602D354B model shown. Appearance may vary by model.
1
16-01-031-933588.indb 6 3/22/2016 4:14:19 PM
7
3. Features
6
Network Interface: Use the RJ-45 jack to connect the ATS to the network
with a standard Ethernet patch cable. The Status LED
A
and Link LED
B
indicate operating conditions as shown in the table below. These ports are not compatible with PoE (Power Over Ethernet) applications.
Network Operating Conditions
A
Status LED Color
B
Link LED Color
Off Card Not Initialized Off No Network Connection Steady Green Card Initialized and Operational Flashing Amber 100 Mbps Network Connection Flashing Amber Error - Card Not Initialized Flashing Green 10 Mbps Network Connection
7
Configuration Port: Use this port to provide direct terminal connection to a computer with a
terminal emulation program. A serial cable is included with the ATS. If you need to order a replacement cable, contact Tripp Lite Customer Support at www.tripplite.com/support.
8
ENVIROSENSE Port: Use this port to connect a Tripp Lite ENVIROSENSE environmental
sensor to provide remote temperature/humidity monitoring and a dry contact interface to control and monitor alarm, security and telecom devices. Visit www.tripplite.com for ordering information.
Note: Do not connect a keyboard or mouse to this port.
9
Circuit Breakers: Each single phase output load (six output load banks) has its own double-
pole magnetic breaker. If the connected equipment load exceeds the maximum load rating for that phase, the circuit breaker will trip. Disconnect excess equipment before resetting the breaker(s).
10
Chassis Ground Screw: Use this to connect equipment that requires a chassis ground.
11
ATS Mating Receptacles: These receptacles only accept the 8-position connector on the
power strip input power cords.
Note: The receptacle labeled Output 1 on the ATS must be matched with Output 1 cord from the power
strip and the receptacle labeled Output 2 on the ATS must be match with Output 2 cord from the power strip.
12
Breaker Detect: The power strip’s six position cable connects to the ATS and allows the ATS
to sense the ON/OFF state of the power strip circuit breakers.
A B
16-01-031-933588.indb 7 3/22/2016 4:14:19 PM
8
4. Digital Display
1
Source Status LEDs: Lit LED patterns indicate which source is preferred, which sources(s) is (are) available for use, and which source is currently being used. See Source Status LED Indicators section for an explanation of the LED patterns.
2
Breaker Trip LED: Lit when a breaker has tripped.
3
3-Digit Display: Shows measured or calculated values such as Amperage, Kilowatts, Voltage,
Power Unbalance Percentage, Frequency, Power Factor and Temperature.
4
Enter Button: When a menu is selected using the Mode Button, the Enter Button scrolls
through the submenus within each category. Submenus are shown by the Indicator LEDs.
Note: Pushing the Enter and Mode button simultaneously for 2 seconds displays the IP address.
5
Indicator LEDs: Lit LED indicates which value is being displayed on the 3-digit screen.
Amps (A): The input current on the selected Source Input (A# or b#) or Output Load Circuit
(C#) is displayed in amps.
Wattage (kW): The Output Power for the selected Output Load Circuit (C#) or Total Output
Power (OP) is displayed in kW.
Voltage (V): The Source A or B Input Phase-to-Phase voltage (A# or b#) or Output Load
Circuit voltage (C#) is displayed in volts. Frequency (Hz): Source Input A or B frequency is displayed in Hz. Power Factor (PF): Output Load power factor is displayed as a decimal (from 0 to 1.00).
1 742
3 5 6
16-01-031-933588.indb 8 3/22/2016 4:14:19 PM
9
4. Digital Display
6
2-Digit Display: This display indicates which display mode is selected: Source Input Phase
(A# or b#), % Unbalanced (Ub), Output Circuits (C#), Total Output Power (OP), Temperature
(tC or tF), or Fault Code (FC). Source A Phases (A#): Displays measurements for Source A. They include phase current
(A), Voltage (V) and Frequency (Hz). Source B Phases (b#): Displays measurements for Source B. They include phase current
(A), Voltage (V) and Frequency (Hz). % Unbalanced (Ub): The display shows the unbalanced load percentage deviance from the
average measured value. The percentage for the phase with the highest deviance is displayed. Output Circuits (C#): Displays measurements for Output Circuits. They include Current (A),
Kilowatts (kW), Voltage (V) and Power Factor (PF). Total Output Power (OP): Displays total power on all output circuits. Temperature (t): The ATS unit’s internal temperature is displayed when this option is
selected. The temperature is displayed in Celsius by default, but can be switched to
Fahrenheit. Fault Code (FC): The Fault Code will only display if a breaker has tripped.
7
Mode Button: Scroll through the Display and Config menus using this button. Display menu
choice is shown on 2-digit display. Config menu choice is shown on 3-digit display.
16-01-031-933588.indb 9 3/22/2016 4:14:19 PM
10
4. Digital Display
Source Status LED Indicators
LED pattern Description
• Source A preferred
• Both sources of good quality and available
• Output is connected to Source A
• Source B preferred
• Both sources of good quality and available
• Output is connected to Source B
• Source A preferred
• Source A is of poor quality or unavailable
• Output is connected to Source B
• Source B preferred
• Source B is of poor quality or unavailable
• Output is connected to Source A
• Source A preferred
• Sources are of mixed levels of stability
• Output phases are powered by different sources
Note: “Available” LED will flash if phases of the source are of mixed levels of stability.
Lit LED
Unlit LED
Flashing LED
Note: This event is a rare occurrence.
16-01-031-933588.indb 10 3/22/2016 4:14:20 PM
11
5. Using the Digital Display
5.1 Navigating Display Menus and Submenus (Measurement)
Press the MODE button to go to the next Display menu. Press the Enter button to go to the next submenu (Amps, kW, Volts, Hz, PF). Press and hold MODE button for 2 seconds to switch to the first Config menu (refer to Navigating Config Menus and Submenus section). Press and hold both the MODE and Enter button for 2 seconds to show the IP address of the connected SNMP card. The scrolling pattern of the menus is outlined below.
Source A
Phase Current (L1)
Volts (L1-L2)
Hz (L1-L2)
Note: This is a 208V model; voltages displayed are phase-to-phase voltages (e.g., A1 in display indicates L1-L2 voltage).
i.3.2
2.0.8
6.0
A i
A i
A i
16-01-031-933588.indb 11 3/22/2016 4:14:20 PM
12
5. Using the Digital Display
Volts (L2-L3)
Volts (L3-L1)
Hz (L2-L3)
Hz (L3-L1)
Source A
Phase Current (L2)
Source A
Phase Current (L3)
i.3.2
i.3.2
2.0.8
2.0.8
6.0
6.0
A2
A3
A2
A3
A2
A3
16-01-031-933588.indb 12 3/22/2016 4:14:21 PM
13
5. Using the Digital Display
Volts (L1-L2)
Volts (L2-L3)
Hz (L1-L2)
Hz (L2-L3)
Source B
Phase Current (L1)
Source B
Phase Current (L2)
i.3.2
i.3.2
2.0.8
2.0.8
6.0
6.0
16-01-031-933588.indb 13 3/22/2016 4:14:21 PM
14
5. Using the Digital Display
Volts (L3-L1)
Hz (L3-L1)
Kilowatts (L1-L2)
Source B
Phase Current (L3)
Unbalanced Load Detect
Phase Imbalance %
Output Load Circuit
Circuit Current (L1-L2)
i.3.2
2.0.8
6.0
i 0.0
i 3.2
2.7 5
C i
C i
16-01-031-933588.indb 14 3/22/2016 4:14:22 PM
15
5. Using the Digital Display
Voltage (L1-L2)
Voltage (L2-L3)
Power Factor (L1-L2)
Power Factor (L2-L3)
Circuit Current (L1-L2) (Page 14)
Output Load Circuit
Circuit Current (L2-L3)
Kilowatts (L2-L3)
2 0 8
2 0 8
i.0 0
i.0 0
C i
C 2
C i
C 2
i 3.2
2.7 5
C 2
C 2
16-01-031-933588.indb 15 3/22/2016 4:14:22 PM
16
5. Using the Digital Display
Voltage (L3-L1)
Power Factor (L3-L1)
Output Load Circuit
Circuit Current (L3-L1)
Total Output Power
Kilowatts
Temperature
tC = Celsius; tF = Fahrenheit
Kilowatts (L3-L1)
Source A Phase Current (L1) (Page 11)
Note: Total of six loads C1-C6
2 0 8
i.0 0
8.2 5
2 5
C 3
C 3
OP
i 3.2
2.7 5
C 3
C 3
16-01-031-933588.indb 16 3/22/2016 4:14:23 PM
17
5. Using the Digital Display
Fault Code Menu
The Fault Code Menu is only available when a breaker is tripped, causing the Breaker Trip LED to illuminate. The display will jump to the Fault Code menu and auto scroll through the tripped breakers (only tripped breakers will be shown in the scroll sequence). Manual scrolling option is still available, but Auto Scroll feature will remain active within the fault code menu while a fault exists. If Auto Scroll is disabled, the display will still jump to the Fault Menu but you must manually scroll through each tripped breaker individually. The number in the 3-digit display is defined as: br1 = Output Breaker L1-L2; br2 = Output Breaker L2-L3; br3 = Output Breaker L3-L1
Breaker 1 Tripped
IP Address Display
At any time, you can press and hold both Mode and Enter buttons for 2 seconds to show the IP address of the connected SNMP card. The 3 digit display will show “IP“. The 2 digit display to the right of it will show one IP address digit at a time until it shows the entire IP address. Decimal points and colons will be shown as hyphens. Note: This display supports IPv4 AND IPv6 addresses. The display will automatically transition back to whatever mode it came from after displaying the IP address.
Breaker 2 Tripped
Breaker 3 Tripped
Note: Total of six breakers br1-br6
F C
F C
F C
I P
I
16-01-031-933588.indb 17 3/22/2016 4:14:23 PM
18
5. Using the Digital Display
5.2 Navigating Config Menus and Submenus (Configuration)
While in any Display Menu, press and hold Mode button for 2 seconds to enter the first Config menu. Press Mode button to cycle to the next Config menu. Press and hold Mode button for 2 seconds to switch to Display menus.
Temperature Unit Options
Hold Enter button for 2 seconds to switch between options. The letter in the 2-digit display indicates the selected unit, C for Celsius and F for Fahrenheit.
Hold Enter button for 2 seconds to switch between Source A and Source B. The letter in the 2-digit display indicates the selected source.
Note: If both sources are available, the unit will transfer to the preferred source immediately once the setting is changed.
When enabled, the Auto Scroll function cycles through the output load circuit currents (C1, C2, C3) menus in 4-second intervals. “y” indicates the function is enabled; “n” indicates that it is disabled. Pressing any button interrupts the auto scroll function, allowing the user to navigate between menu options. If no button is pressed, there is a 10 second timeout and auto scroll will resume from the current menu.
Preferred Source Selection
Auto Scroll Enable/Disable
C – F
P S S
C – F
P S S
F
A
C
2 Seconds
2 Seconds
2 Seconds
16-01-031-933588.indb 18 3/22/2016 4:14:24 PM
19
5. Using the Digital Display
LED Brightness
Hold the Enter button for 2 seconds to scroll through each brightness option. The number in the 2-digit display is defined as: 1=25%; 2=50%; 3=75%; 4=100%.
Note: The default brightness option is 4 (100%).
LED Test
Hold Enter button for 2 seconds to start an LED test. All LEDs will illuminate for 6 seconds.
Temperature Unit Options (Page 18)
4
i
2
3
2 Seconds
2 Seconds
2 Seconds
2 Seconds
8.8.8.
8 8
2 Seconds
16-01-031-933588.indb 19 3/22/2016 4:14:24 PM
20
6. Configuration and Operation
6.1 Automatic Transfer Switch
When the Source A and Source B inputs are both connected to power sources, the ATS operates as an Automatic Transfer Switch, providing redundant input power for high availability applications. The ATS will distribute power from the preferred input source under normal operating conditions and switch to the other input source under abnormal conditions. The default preferred source is Source A (Refer to the Navigating Config Menus and Submenus section for instructions on changing the preferred source). The ATS will switch to the preferred source whenever it is “Good” according to the ATS input voltage definitions (see section 6.1.2).
6.1.1 Preferred Configuration
The Automatic Transfer Switch function provides increased availability when the Source A and Source B inputs of the ATS are connected to separate power sources. For maximum availability, it is recommended when using UPS systems that the UPS systems are matching with pure sine wave output for the Source A and Source B input power sources. The automatic transfer switch function will be compromised if the Source A and Source B inputs are connected to the same utility power source.
Source B Power Source
Source B Input Cord
Equipment Loads
Source A
Input Cord
Source A
Power Source
Power Strip
Utility AUtility B
ATS
208V
~
/ L1 - L2
5A OUTPUT BREAKER
16-01-031-933588.indb 20 3/22/2016 4:14:25 PM
21
6. Configuration and Operation
6.1.2 Automatic Transfer Switch Source Selection
The ATS will power up and supply output if at least one of the inputs is greater than the minimum startup voltage. In normal operation, when both sources are of equal quality (“fair” or “good”), the unit will select the preferred source according to the preferred source selection setting (Refer to section 5.1 Navigating Config Menus and Submenus). If the currently selected source degrades to a quality less than the currently unselected source, the unit will transfer to the better quality source. If the currently unselected source improves in quality greater than the currently selected source, the unit will transfer to the better quality source.
Note: In the event of a voltage loss on one of the 3-phase input conductors, the loads connected to the failed phase conductor will transfer to the alternate source. The remaining load will follow and transfer to the alternate source within 1 second. If both sources have mixed levels of stability in their phases, the ATS will select the source of each phase on the basis of best available. If one of the sources has all 3 phases return to “good” quality, the unit will then transfer all phases to that source.
Input Voltage Ranges
Nominal Voltage
208V
Minimum Startup Voltage
163V
Good Voltage Range
172-241V
Fair Voltage Range
144-171V
Bad Voltage Range
0-143V
6.1.3 Quick Test
After installing the ATS/power strip and connecting equipment, you may test the Automatic Transfer Switch function by temporarily disabling the preferred AC input (default is Source A). The ATS will then switch from the preferred input to the alternate input. When the preferred input resumes supplying power, the ATS will switch back to the preferred input.
Note: The two inputs must be connected to separate sources of utility power. The automatic transfer switch function will be compromised if the two inputs are connected to the same power source. Do not perform a test with equipment that must remain in productive operation. Any test procedure must prepare for the contingency that the equipment may lose power. Do not test the ATS by detaching power cords which are connected to live power sources, as this eliminates the connection to ground and places your equipment at risk.
Preferred Source (A) Active
Alternate Source (B) Active
16-01-031-933588.indb 21 3/22/2016 4:14:25 PM
Loading...
+ 47 hidden pages