Tripp Lite PDU3EVSR6H50A User Manual

14.4kW 3-Phase Switched PDU - 6 C13 & 12 C19 Outlets (208V), Hubbell 50A CS8365C, 0U, Outlet Monitoring, TAA
MODEL NUMBER: PDU3EVSR6H50A
3-phase switched PDU distributes, monitors and manages power in a medium/large data center or network installation.
Features
3-Phase PDU Distributes, Monitors and Manages Network-Grade PowerRecommended for data
Highlights
6 C13 and 12 C19 208V outlets distribute AC power to connected equipment
Pre-installed WEBCARDLX with latest version of PADM20 for IP­based Auto Probe feature
Remote power monitoring and control reduces on-site visits and maintenance costs
6-ft. (1.83 m) cord with Hubbell 50A CS8365C (3P+E) 3-phase input connects to AC power source
Color touchscreen LCD provides current levels, environmental data and network info
Applications
Power mission-critical rack equipment in a data center, computer room or high-density network closet
Monitor power loads from various computers, switches, servers and other networking equipment
Maintain a computer network in a government, commercial or industrial facility
Manage multiple rack devices by rebooting or shutting down individual outlets as needed
Package Includes
PDU3EVSR6H50A 14.4kW 3­Phase Switched PDU
Built-in LX Platform interface
1 / 4
2-Year WarrantyThe PDU3EVSR6H50A is backed by a 2-year warranty, ensuring reliability and performance.
Specifications
OVERVIEW
UPC Code 037332206763 PDU Type Switched
INPUT
PDU Input Voltage 208V Recommended Electrical Service Three-phase 50A 208V service
Configuration cable
(18) Plug-lock insert sleeves
Rack-mounting hardware
Spare mounting buttons
PDUMVROTATEBRKT mounting bracket accessory
Owner’s manual
Maximum Input Amps 40 PDU Plug Type HUBBELL CS8365C 50A Input Phase 3-Phase Input Cord Details 6GA (SOOW) Input Cord Length (ft.) 6 Input Cord Length (m) 1.83
OUTPUT
Output Capacity Details 14.4kW (208V) total capacity; 20A max per breakered outlet bank; 16A max per C19 outlet; 12A max per C13 outlet Frequency Compatibility 50 / 60 Hz Output Receptacles (6) C13; (12) C19 Output Nominal Voltage 208V Overload Protection 6 20A circuit breakers, 1 per outlet bank Customized Load Management
Receptacles
USER INTERFACE, ALERTS & CONTROLS
Reported Load Segments Supports monitoring of current per input phase (L1, L2, L3), output current per load bank (Banks 1-6) and per output
Each outlet is individually controllable via remote interface
receptacle (1-18); Outlets are color-coded and labeled for phase and load bank identification; L1-L2 powers black outlets (Banks 1&4); L2-L3 powers dark-gray outlets (Banks 2&5); L3-L1 powers light-gray outlets (Banks 3&6)
2 / 4
Loading...
+ 2 hidden pages