The TRANSITION Networks RS485-CF-0x series serial-port fiber extension Media Converters extend distances between RS-485 or RS-482 nodes for up to two (2)
kilometers over multimode fiber or up to twenty (20) kilometers over singlemode fiber.
RS485-CF-0x series Media Converters allow RS-485 two-wire half-duplex operation, RS-485 four-wire full-duplex operation, and RS-422 four-wire operation, with switch-selectable termination and biasing resistors, at speeds from 1 Kb/s to 500 Kb/s.
RS-485/422 Serial-Port Fiber Extension
RS485-CF-01, RS485-CF-02
USER’S GUIDE
RS485-CF-01
Provides one (1) terminal block RS­485/RS-422 copper connector and one (1) set of RX (receive) and TX (transmit) ST 100BASE-FX connectors to multimode fiber @ 850 nM.
RS485-CF-01(SM)
Provides one (1) terminal block RS­485/RS-422 copper connector and one (1) set of RX (receive) and TX (transmit) ST 100BASE-FX connectors to singlemode fiber @ 1300 nM.
RS485-CF-01(SC)
Provides one (1) terminal block RS­485/RS-422 copper connector and one (1) set of RX (receive) and TX (transmit) SC 100BASE-FX connectors to multimode fiber @ 850 nM.
RS485-CF-02
Provides one (1) DB-9 RS-485/RS-422 copper connector and one (1) set of RX (receive) and TX (transmit) ST 100BASE-FX connectors to multimode
fiber @ 850 nM.
RS485-CF-02(SM)
Provides one (1) DB-9 RS-485/RS-422 copper connector and one (1) set of RX (receive) and TX (transmit) ST 100BASE-FX connectors to singlemode
fiber @ 1300 nM.
RS485-CF-02(SC)
Provides one (1) DB-9 RS-485/RS-422 copper connector and one (1) set of RX (receive) and TX (transmit) SC 100BASE-FX connectors to multimode
fiber @ 850 nM.
DB-9
Fiber
RS485/422 to Fiber
Media Converter
RS485-CF-0x in the Network . . . . . .2
Installation . . . . . . . . . . . . . . . . . . . .3
Operation . . . . . . . . . . . . . . . . . . . . .4
Fault Isolation and Correction . . . . .5
Cable Specifications . . . . . . . . . . . . .6
Technical Specifications . . . . . . . . . .7
Compliance Information . . . . . . . . . .8
RS485-CF-0X in the NETWORK
The RS485-CF-0x can be used to install a fiber network extension between RS-485 or RS-422 network nodes.
One slide switch on the RS485-CF-0x series Media Converter allows site selection of RS-485 2-wire (half-duplex) operation, RS-485 4-wire (full­duplex) operation, or RS-422 4-wire (full-duplex) operation (see page 3).
A second slide switch on the RS485-CF-0x series Media Converter allows echo prevention in two-wire mode or transmission only on "transmit/receive ­(B) RS-485 2wire, transmit - RS-422 and transmit/receive + (A) RS-485 2wire, transmit + RS-422" pair (see page 3).
A 4-position dip switch on the RS485-CF-0x series Media Converter allows site selection of 130 ohm terminator insertion on the "receive – RS485 4 wire, RS422 and receive + RS485 4 wire, RS422" pair or on the "transmit/receive - (B) RS485 2wire, transmit - RS422 and transmit/receive + (A) RS485 2wire, transmit + RS422" pair (see page 3.).
The dip switch also allows site selection of 1K ohm pull down on "transmit/receive - (B) RS485 2wire, transmit - RS422" or of 1K ohm pull up on "transmit/receive + (A) RS485 2wire, transmit + RS422” (see page 3).
RS485-CF-0x
2
RS-485/422 CABLE
RS-485/422 CABLE
INSTALLATION
Set Switches
Use small flatblade screwdriver or similar device to set recessed switches according to site installation.
1. Set the 2-wire /4-wire slide switch to the 4-wire setting to enable the "receive – RS485 4 wire, RS422 and receive + RS485 4 wire, RS422" pair for RS422 4 wire full duplex operation.
2. Set the RS-485/RS-422 slide switch to the RS-485 position to prevent echo in two-wire mode. Set the RS-485/RS-422 slide switch to the RS­422 to allow transmit only on "transmit/receive - (B) RS-485 2wire, transmit - RS-422 and transmit/receive + (A) RS-485 2wire, transmit + RS-422" pair.
3. Refer to drawing and to notes below for setting 4-position DIP switch.
* Position 1 ON inserts 130 ohm terminator on the "receive – RS485
4 wire, RS422 and receive + RS485 4 wire, RS422" pair.
** Position 2 ON inserts 130 ohm terminator on the "transmit/receive -
(B) RS485 2wire, transmit - RS422 and transmit/receive + (A) RS485 2wire, transmit + RS422" pair.
*** Position 3 ON enables 1K ohm pull
down
on "transmit/receive - (B)
RS485 2wire, transmit - RS422".
**** Position 4 ON enables 1K ohm pull
up
on "transmit/receive + (A)
RS485 2wire, transmit + RS422
Install Cable
COPPER /DB-9 CONNECTOR
NOTE: Shielded cables are required on the DB-9 for EMC compliance.
1. Locate or build TIA/EIA-574-DB-9 compliant cables configured as
shown on page 6, with a male DB-9 connector at one end of cable and with a straight-through cable.
2. Connect the male DB-9 connector at one end of cable to the
Media Converter female DB-9 connector.
3. Connect the other end of cable to the node device.
3
MDI
MDI-X
E-100BTX-FX-O4
9V DC Input
Config
Switches
1 2 3 4
RS-485
RS-422
DOWN=ON Inserts 130 resistor on "receive"*
DOWN=ON Inserts 130 resistor on "transmit"**
DOWN=ON Enables 1K "pull-down"***
DOWN=ON Enables 1K "pull-up"***
*
1
2
3
4
2-wire
4-wire
INSTALLATION -- Continued
COPPER /TERMINAL BLOCK CONNECTOR
1. Locate or build TIA/EIA-574-compliant terminal block cables configured as shown on page 6 and with straight-through cable.
2. Using a small flatblade screwdriver or a similar device, release each terminal block installation location as necessary. Refer to the diagram on page 6, connect the wires at one end of cable to the Media Converter terminal block connector.
3. Connect the other end of the cable to the node device.
FIBER
1. Locate or build TIA/EIA-574-compliant fiber cable with male two­stranded TX to RX connectors at both ends.
2. Connect the male TX and RX cable connectors at one end of the cable to the TX and RX female connectors, respectively, on the Media Converter.
3. Connect the male TX and RX cable connectors at the other end of the cable to the RX and TX connectors of the IEEE 802.3™ compliant fiber device.
Connect to Power
1. Install the power adapter cord at the back of the Media Converter.
2. Connect the power adapter plug to AC power.
3. Verify that the Media Converter is powered by observing the illuminated LED(s).
OPERATION
After installation, the Media Converter should function without operator intervention.
Status LEDs:
Use the status LEDs to monitor Media Converter operation in the network.
RXF Flashing LED indicates data reception on the fiber link.
RXC Flashing LED indicates data reception on the copper link.
P(o)W(e)R Steady LED indicates connection to external power.
RS485-CF-0x
4
RXF
RXF
RXC
RXC
PWR
PWR
T
X
R
X
TX
RX