Trane WSC060-120 User Manual

Packaged Heat Pumps
Precedent WSC060-120 50 Hz
February 2004
PKGP-PRC004-EN
Precedent™…The same Trane quality…with added flexibility.
Precedent is a flexible line of packaged units that cover a wide variety of applications.
ReliaTel™ microprocessor controls provide superior flexibility for the simplest to the most sophisticated applications. In addition to controls, Precedent offers many other outstanding features and option choices.
© 2003 American Standard Inc. All rights reserved. PKGP-PRC004-EN
With its sleek compact cabinet, rounded corners and beveled top, it may just be the most aesthetically pleasing packaged unit on the planet. And, of course, Precedent carries the Trane reputation for excellence, quality and reliability.
hard to stop a Trane
From simple applications, to the most complex, Precedent has the solution.
.
It’s
Contents
Introduction
Features and Benefits
Application Considerations
Selection Procedure
Model Number Description
General Data
Performance Data
Controls
Electrical Data
Jobsite Connections
Dimensional Data
Weights
2
4
9
10
12
13
14
34
35
38
39
46
PKGP-PRC004-EN
Mechanical Specifications
47
3
Unit Cabinet
The compact cabinet with rounded corners takes up less room and is less costly to ship. The beveled and ribbed top is not only aesthetically pleasing, it is designed to prevent water from pooling
Single Point Power
A single electrical connection powers the unit.

Features and Benefits

Easy-Adjust Idler Arm
With the Easy-Adjust Idler Arm, the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.
Patented Condenser Coil
Precedent boasts a patented 1+1+1 Hybrid coil, permanently gapped for easy cleaning.
Colored And Numbered Wiring
You save time and money tracing wires and diagnosing the unit.
Convertible Units
• The units ship in a downflow configuration. They can be easily converted to horizontal by simply moving two panels.
• Units come complete with horizontal duct flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and cost saver.
Compressors
Precedent™ contains the best compressor technology available to achieve the highest possible performance. Our compressor line includes Trane-built Climatuff
Easy Access Panels
Easy access panels reduce the number of possible water entry points. Remove two screws for access to the standardized internal components and wiring.
Low Ambient Cooling
All Precedent units have cooling capabilities down to -18°C (0°F) as standard.
4
reciprocating and scrolls.
Unit Base
For added water integrity, Precedent has a raised 29 mm 1( unit’s downflow supply and return to prevent water from blowing into the ductwork.
1
/8") lip around the
Sloped Drain Pans
Every Precedent unit has a non­corrossive, removable, double-sloped drain pan that’s easy to clean and reversible to allow installation of drain trap on either side of the unit.
Through the Base Condensate
Every unit includes provisions for through the base condensate drain connections. This allows the drain to be connected through the roof curb instead of a roof penetration.
Foil-Faced Insulation
All panels in the Evaporator section of the unit have cleanable foil-faced insulation. All edges are either captured or sealed to ensure no fibers get into the airstream.
PKGP-PRC004-EN
Features and Benefits
Standardized Components
• Components are placed in the same location on all Precedent Familiarize yourself with one Precedent and you are familiar with every Precedent.
Easy Access Low Voltage Terminal Board
Precedent’s Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire. This is another cost and time saving installation feature.
units.
Flexible Applications
• Only two roof curbs for the 5-10 ton Precedent line…simplifies curb selection.
• Airflow is outstanding. The Precedent can replace an older machine with old ductwork and, in many cases, improve comfort through better air distribution.
• Belt drive — standard or oversized supply fan motors meet a wide airflow range.
• Precedent offers ultimate flexibility. Options and components are not pre­packaged at the factory. Units are built to order in our standard “shortest in the industry” ship cycle time.
PKGP-PRC004-EN
Low Voltage Connections
The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire
Single-Side Service
Single-side service is standard on all Precedent units.
5
Features and Benefits
Micro Controls
Several years ago, Trane was the first to introduce microprocessor controls into the Light Commercial Market. That design, along with immeasurable experience, has provided the technology for Trane’s second-generation ReliaTel microprocessor controls.
ReliaTel Micro:
• Provides unit control for heating, cooling, and ventilating by utilizing input from sensors that measure outdoor and indoor temperature.
• Improves quality and reliability through the use of time-tested microprocessor controls and logic.
• Prevents the unit from short cycling, considerably improving compressor life.
• Ensures that the compressor will run for a specific amount of time, which allows oil to return for better lubrication, enhancing the reliability of the compressor.
• Reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.
• Eliminates the need for field-installed components with its built-in anti­short-cycle timer, time delay relay and minimum ‘’on’’ time controls. These controls are factory tested to assure proper operation.
• Requires no special tools to run the Precedent unit through its paces during testing. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps. The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.
• As long as the unit has power and the LED is lit, the Micro is operational. The light indicates that the Micro is functioning properly.
• Features expanded diagnostic capabilities when used with Trane’s Integrated Comfort
• As an energy benefit, softens electrical ‘’spikes’’ by staging on fans, compressors and heaters.
• The Intelligent Fallback or Adaptive Control is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature set points.
• Intelligent Anticipation is a standard feature of the Micro. Functioning constantly, the Micro and zone sensors work together in harmony to provide tight comfort control.
systems.
6
PKGP-PRC004-EN
Features and Benefits
Factory-installed Options
Hinged Access Doors
These doors permit easy access to the filter, fan/heat, and compressor/control sections. They reduce the potential roof damage from screws or sharp access door corners.
Economizer
Equipped with either dry bulb, reference or comparative enthalpy sensing, this feature provides free cooling as the outdoor temperature and/or humidity decreases. Economizers, correctly installed, offer valuable energy savings. Factory-installed economizers save time and ensure proper installation.
Phase Monitor
Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator.
Clogged Filter/Fan Fail Switches
These sensors allows a zone sensor service light or Integrated Comfort system to indicate a dirty filter or a fan that’s not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment.
Comm-3/4 Trane Communication Interface
Available factory or field-installed. This module, when applied with the Micro, easily interfaces with Trane’s Integrated Comfort
system.
The following options round-out the complete line of Precedent
— 0 - 50% Manual or Motorized
Outside Air
— Discharge Air Sensor
— Electric heaters (available as field-
installed accessories)
— Hail Protection Quality Coil
Guards
— Wide array of Zone Sensors
— Factory built Roof Curb
One of Our Finest Assets:
Trane Sales Representatives are a Support group that can assist you with: — Product — Application — Service — Training — Special Applications — Specifications — Computer Programs and much
more
Precedent has the features and benefits that make it first class in the light commercial rooftop market. Designed with input from field contractors and engineers, its airflow performance is outstanding.
Precedent…The same Trane quality…with added flexibility.
options:
PKGP-PRC004-EN
7
Features and Benefits
Va riTra c
When Trane’s changeover VAV System for light commercial applications is coupled with Precedent, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac.
Quality And Reliability Testing
• All Precedent rain tested at the factory to ensure water integrity.
• Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging.
• Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition.
• Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress.
VariTrac
designs were rigorously
• We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at 1,375 kPa (200 psig) and pressure tested to 3,100 kPa (450 psig).
• All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately.
• Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements.
We test designs at our factory not on our customers!
8
PKGP-PRC004-EN

Application Considerations

Application of this product should be within the cataloged airflow and cooling considerations.
Low Ambient Cooling
Precedent™ features, as standard, low ambient cooling down to -18°C (0°F). Contact your local Trane Representative for more assistance with low ambient cooling applications.
Barometric Relief
This product line offers an optional barometric relief damper for use in conjunction with economizer option. This option consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space.
NOTE: THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED.
PRESSURE DROP OF THE RETURN AIR SYSTEM SHOULD BE CONSIDERED TO CONTROL BUILDING PRESSURIZA­TION.
Condensate Trap
The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle.
Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to assure adequate service, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel.
Unit Pitch
These units have reversible sloped condensate drain pans. Units must be installed level, any unit slope must be toward side of unit where condensate drain is connected.
PKGP-PRC004-EN
9
Selection Procedure - SI Units
Cooling Capacity
Step 1
Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane calculation form or any other standard accepted method.
Step 2
Size the equipment using Table PD-1. Match the cooling loads at design conditions. Example: The following are the building cooling requirements:
A
Electrical Characteristics: 380–415/50/3
B
Summer Design Conditions: Entering Evaporator Coil: 27 DB/ 19 WB Outdoor Ambient: 35
C
Total Cooling Load: 17.0 kW
D
Sensible Cooling Load: 11.7 kW
E
Airflow: 3,400 m External Static Pressure: 130 Pa
F
Downflow Configuration
3
/hr
Table PD-1 shows that a WSC060AD has a gross cooling capacity of 18.1 kW and
14.7 kW sensible capacity at 35 degree C ambient and 3,400 m WB air entering the evaporator.
To find the net cooling capacities, fan motor heat must be subtracted. Determine the total unit static pressure:
External Static 130 Pa Standard Filter 1 in. 37 Pa Economizer 46 Pa Supplementary Electric Heat 21 Pa Total Static Pressure 234 Pa
Note: The Evaporator Fan Performance Table PD-9 has deducted the pressure drop for a 25 mm filter already in the downflow unit.
Therefore, the actual Total Static Pressure is 234 – 37 = 197 Pa. With 3,400 m3/hr and 197 Pa, Table PD-9 shows 0.75 kW.
Note below the table gives a formula to calculate Fan Motor Heat,
Fan Motor Heat (kW) =
1.144 x (Fan kW) + 0.132 = 1.144 x 0.75 + 0.132 = 1.0 kW
Net Total Cooling Capacity =
18.1 – 1.0 = 17.1 kW
Net Sensible Cooling Capacity =
14.7 – 1.0 = 13.7 kW
3
/hr with 27 DB/19
Heating Capacity
Step 1
Calculate the building heating load using the Trane calculation form or other standard accepted method.
Step 2
Size the equipment using Table PD-5 to match the heating loads at design conditions.
A
Total Heating Load: 16 kW
B
Outdoor Ambient (Winter) –9°C DB
C
Indoor Return Temperature: 21°C DB
D
Airflow: 3,400 m3/hr
Use the portion of Table PD-5 for the WSC060AD to determine capacity at winter design conditions. The mechanical heating portion of the heat pump will provide 8.3 kW.
Step 3
Because 8.3 kW is less than the building’s required heating capacity at winter design conditions, a supplementary heater must be selected.
16 kW – 8.3 kW = 7.7 kW
From Table PD-9, at 380 volts, the 10.9 kW Heater will be adequate to do the job.
From Table ED-5 select heater BAYHTRR418A (10.9 kW 380/50/3).
Air Delivery Selection
External static pressure drop through the air distribution system has been calculated to be 200 Pa. Enter Table PD-9 for a WSC060AD at 3400 m Pa static pressure. The standard motor will give the desired airflow.
Accessory Selection
Select accessories needed to accommodate the application.
10.9 kW 38.0 MBh
3
/h and 200
10
PKGP-PRC004-EN
Selection Procedure - IP Units
Cooling Capacity
Step 1
Calculate the building’s total and sensible cooling loads at design conditions. Use the Trane calculation form or any other standard accepted method.
Step 2
Size the equipment using Table PD-1a. Match the cooling loads at design conditions. Example: The following are the building cooling requirements:
A
Electrical Characteristics: 380–415/50/3
B
Summer Design Conditions: Entering Evaporator Coil: 80 DB/ 67 WB Outdoor Ambient: 95
C
Total Cooling Load: 53 MBh
D
Sensible Cooling Load: 33 MBh
E
Airflow: 2,000 cfm External Static Pressure: .52 in. w.g.
F
Downflow Configuration
Table PD-1a shows that a WSC060AD has a gross cooling capacity of 59.0 MBh and 45.7 MBh sensible capacity at 95 degree ambient and 2,000 cfm with 80 DB/67 WB air entering the evaporator.
To find the net cooling capacities, fan motor heat must be subtracted. Determine the total unit static pressure:
External Static 0.52 in. Standard Filter 1 in. 0.15 in. Economizer 0.18 in. Supplementary Electric Heat 0.083 in. Total Static Pressure 0.933 in.
Note: The Evaporator Fan Performance Table PD-9a has deducted the pressure drop for a 1 in. filter already in the downflow unit.
Therefore, the actual Total Static Pressure is 0.933 – 0.15 = 0.78. With 2,000 cfm and 0.78 inches, Table PD-9a shows 1.00 bhp.
Note below the table gives a formula to calculate Fan Motor Heat,
Fan Motor Heat (MBh) =
2.915 x (Fan bhp) + 0.451 = 2.915 x 1.00 + 0.451 = 3.37 MBh
Net Total Cooling Capacity =
57 – 3.37 = 53.6 MBh
Net Sensible Cooling Capacity =
38 – 3.37 = 34.6 MBh
Heating Capacity
Step 1
Calculate the building heating load using the Trane calculation form or other standard accepted method.
Step 2
Size the equipment using Table PD-5a to match the heating loads at design conditions.
A
Total Heating Load: 50 MBh
B
Outdoor Ambient (Winter) 17 DB
C
Indoor Return Temperature: 70 DB
D
Airflow: 2,000 cfm
Use the portion of Table PD-5a for the WSC060AD to determine capacity at winter design conditions. The mechanical heating portion of the heat pump will provide 29.1 MBh.
Step 3
Because 29.1 MBh is less than the building’s required heating capacity at winter design conditions, a supplementary heater must be selected.
50 MBh – 29.1 MBh = 29.9 MBh
From Table PD-9a, at 380 volts, the 38.0 MBh Heater will be adequate to do the job.
10.9 kW 38.0 MBh
From Table ED-2 select heater BAYHTRR418A (38.0 MBh at 380 volts).
Air Delivery Selection
External static pressure drop through the air distribution system has been calculated to be 0.80 inches of water. Enter Table PD-9a for a WSC060AD at 2000 cfm and 0.80 static pressure. The standard motor will give the desired airflow.
Accessory Selection
Select accessories needed to accommodate the application.
PKGP-PRC004-EN
11

Model Number Description

W S C 060 A D R O A ** C 0 0 0 0 0 0 0 0 0 0 1 1 2 3 4,5,6 7 8 9 10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25
Digit 1 - Unit Function
W = Packaged Heat Pump
Digit 2 - Efficiency
S = Standard Efficiency
Digit 3 - Airflow
C = Convertible
Digits 4,5,6 - Nominal Gross Cooling Capacity (MBh)
kW Tons 060 = 17.6 5 072 = 21.1 6 090 = 26.4 7.5 120 = 35.1 10
Digit 7 - Major Design Sequence
A = First
Digit 8 - Unit Voltage
D = 380–415/50/3 T = 200/50/3
Digit 9 - Unit Controls
R = ReliaTel™ Microprocessor
Digit 10 - Electric Heater
0 = No Electric Heater
Digit 11 - Minor Design Sequence
A = First Sequence
Digits 12,13 - Service Sequence
** = Factory Assigned
Digit 14 - Fresh Air Selection
0 = No Fresh Air A = Manual Outside Air Damper 0-50% B = Motorized Outside Air Damper 0-50% C = Economizer, Dry Bulb 0-100% without
Barometric Relief
D = Economizer, Dry Bulb 0-100% with
Barometric Relief
E = Economizer, Reference Enthalpy
0-100% without Barometric Relief
F = Economizer, Reference Enthalpy
0-100% with Barometric Relief
G = Economizer, Comparative Enthalpy
0-100% without Barometric Relief
H = Economizer, Comparative Enthalpy
0-100% with Barometric Relief
Digit 15 - Supply Fan/Drive Type/Motor
0 = Standard Drive 1 = Oversized Motor
Digit 16 - Hinged Service Access/Filters
0 = Standard Panels/Standard Filters A = Hinged Access Panels/Standard Filters B = Standard Panels/50mm (2”) Pleated
Filters
C = Hinged Access Panels/50mm (2”)
Pleated Filters
Digit 17 - Condenser Coil Protection
0 = Standard Coil 1 = Standard Coil with Hail Guard 2 = Epoxy Coated Condenser Coil 3 = Epoxy Coated Condenser Coil
with Hail Guard
Digit18 - Through the Base Provisions
0 = No Through the Base Provisions
Digit 19 - Disconnect/Circuit Breaker/Phase Monitor (3 phase only)
0 = No Disconnect or Circuit Breaker 3 = Phase Monitor Only (No Disconnect,
No Circuit Breaker)
Digit 20 - Convenience Outlet
0 = No Convenience Outlet
Digit 21 - Communications Options
0 = No Communications Interface 1 = Comm-3/4 Trane Communications
Interface
2 = Comm-5 LonTalk Communications
Interface
Digit 22 - Refrigeration System Option
0 = Standard Refrigeration System
Digit 23 - Refrigeration Controls
0 = No Refrigeration Control
Digit 24 - Smoke Detector
0 = No Smoke Detector
Digit 25 - Monitoring Controls
0 = No Monitoring Control 1 = Clogged Filter Switch 2 = Fan Failure Switch 3 = Discharge Air Sensing Tube 4 = Clogged Filter Switch and Fan Fail
Switch
5 = Clogged Filter Switch and Discharge
Air Sensing Tube
6 = Fan Fail Switch and Discharge Air
Sensing Tube
7 = Clogged Filter and Fan Fail Switches
and Discharge Air Sensing Tube
12
PKGP-PRC004-EN

General Data

Table GD-1 - General Data
Convertible Units Convertible Units Convertible Units Convertible Units
Cooling Performance
Gross Capacity - kW (MBh) 17.3 (59.0) 22.6 (77.0) 27.8 (95.0) 34.6 (118.0) COP (EER) Nominal Airflow - m3/h (cfm) 3400 (2000) 4080 (2400) 5100 (3000) 6800 (4000) Rated Airflow - m Net Capacity - kW (MBh) 16.7 (57.0) 21.4 (73.0) 26.4 (90.0) 33.1 (113.0) System Power - kW 6.13 6.46 8.26 11.19
Heating Performance
High Temperature Capacity - kW (MBh) 16.0 (54.5) 19.9 (68.0) 24.0 (82.0) 31.9 (109.0)
1
2
3
/h (cfm) 3400 (2000) 3570 (2100) 4460 (2625) 5950 (3500)
1
COP 3.40 3.45 3.54 3.36 System Power - kW 4.71 5.76 6.78 9.48
Compressor
Number - Type 1-Climatuff Scroll 1-Climatuff Scroll 1-Trane 3-D Scroll 2-Climatuff Scroll
Outdoor Sound Rating - dB
3
Outdoor Coil - Type Lanced Lanced Lanced Lanced
Tube Size - in. OD 0.3125 0.3125 0.3125 0.3125 Face Area - m Rows / FPI 3 / 17 2 / 17 3 / 17 3 / 17
2
(sq ft) 1.02 (10.96) 1.58 (17.00) 1.58 (17.00) 1.84 (19.83)
Refrigerant Control Expansion Valve Expansion Valve Expansion Valve Expansion Valve
Indoor Coil - Type Lanced Lanced Lanced Lanced
Tube Size OD - in. 0.3125 0.3125 0.3125 0.3125 Face Area - m Rows / FPI 3 / 16 3 / 16 4 / 16 4 / 16
2
(sq ft) 0.72 (7.71) 0.92 (9.89) 0.92 (9.89) 1.15 (12.36)
Refrigerant Control Short Orifice Short Orifice Short Orifice Short Orifice Drain Connection No. / Size - in. 1 / 0.75 NPT 1 / 0.75 NPT 1 / 0.75 NPT 1 / 0.75 NPT
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used / Diameter (in.) 1 / 22 1 / 26 1 / 26 1 / 26 Drive Type / No. Speeds Direct / 1 Direct / 1 Direct / 1 Direct / 1 CFM 2900 5100 5200 5800 No. Motors / kW (HP) 1 / 0.30 (0.40) 1 / .56 (0.75) 1 / .56 (0.75) 1 / .56 (0.75) Motor RPM 950 950 950 950
Belt Drive Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 1 1 1 Fan Diameter x Width - mm - in. 280 X 280 (11 x 11) 305 X 305 (12 x 12) 305 X 305 (12 x 12) (381 X 381) 15 x 15 Drvie Type / No. Speeds Belt / Variable Speed Belt / Variable Speed Belt / Variable Speed Belt / Variable Speed No. Motors 1 1 1 1 Standard Motor Power - kW (HP) 1.1 (1.5) 1.1 (1.5) 1.5 (2.0) 2.2 (3.0) Oversized Motor Power - kW (HP) - 1.5 (2.0) 2.2 (3.0) ­Motor RPM - Standard / Oversized 1450 / - 1450 / 1450 1450 / 2850 2850 / ­Motor Frame Size 56 56 56 56
Filters - Type Furnished Throwaway Throwaway Throwaway Throwaway
(No.) Size Reccommended - mm (2) 508 X 762 X 25 (4) 406 X 635 X 50 (4) 406 X 635 X 50 (4) 508 X 635 X 50 (No.) Size Reccommended - in. (2) 20 X 30 X 1 (4) 16 X 25 X 2 (4) 16 X 25 X 2 (4) 20 X 25 X 2
Refrigerant Charge - kg (lbs) of R-22
NOTES:
1. Cooling Performance is rated at 35.0 C (95 F) ambient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb. Heating Performance israted at 20.0 C (68 F) ambient, 8.3 C (47 F) entering dry bulb, 6.1 C (43 F) entering wet bulb. Gross capacity does not include the effect of fan motor heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to + 20 % of nominal airflow.
2. EER are rated at ARI conditions.
3. Outdoor Sound rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table “Sound Power Level”.
4. Refrigerant charge is an approcimate value. For a more precise value, see unit nameplate and service literature.
4
WSC060AD,T WSC072AD,T WSC090AD,T WSC120AD,T
2.72 (9.3) 3.31 (11.3) 3.20 (10.9) 3.28 (10.1)
80 85 85 79
3.6 (8.0) 4.3 (9.4) 5.7 (12.5) Circuit 1 - 3.5 (7.7) Circuit 2 - 3.5 (7.7)
PKGP-PRC004-EN
13

Performance Data

Table PD-1 — Gross Cooling Capacities (kW) WSC060AD,T (SI)
Enter. Ambient Temperature (C) Dry 30 35 40 45 Bulb Entering Wet Bulb Temperature (C)
3
/h Temp 16 19 22 16 19 22 16 19 22 16 19 22
m Airflow (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
3060 24 14.5 13.2 16.6 10.7 18.3 7.6 15.6 13.8 17.7 11.0 19.0 8.0 13.3 12.6 15.3 10.1 17.4 7.2 12.1 12.0 13.9 9.5 16.3 6.6
3400 24 14.9 14.1 16.9 11.3 18.5 7.8 16.1 14.7 18.0 11.5 19.2 8.2 13.7 13.5 15.6 10.4 17.6 7.4 12.5 12.5 14.2 10.1 16.5 6.9
3740 24 15.3 15.0 17.2 11.5 18.7 8.1 16.5 15.6 18.2 12.0 19.3 8.4 14.1 14.1 15.9 11.0 17.8 7.6 12.9 12.9 14.5 10.8 16.7 7.1
4080 24 15.6 15.6 17.4 12.1 18.8 8.3 16.8 16.4 18.4 12.4 19.5 8.6 14.5 14.5 16.1 11.5 17.9 7.9 13.4 13.4 14.7 10.8 16.9 7.3
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
27 15.3 15.3 16.7 13.4 18.4 10.4 16.3 16.3 17.8 13.9 19.1 10.8 14.3 14.3 15.4 12.8 17.5 10.0 13.3 13.3 14.1 12.2 16.3 9.5 30 16.7 16.7 17.0 16.3 18.5 13.2 17.6 17.6 18.0 16.8 19.3 13.4 15.7 15.7 15.8 15.8 17.5 12.8 14.7 14.7 14.7 14.7 16.4 12.3 33 17.9 17.9 17.9 17.9 18.7 15.9 18.6 18.6 18.6 18.6 19.5 16.0 17.0 17.0 17.0 17.0 17.7 15.6 16.0 16.0 16.0 16.0 16.6 15.2
27 16.0 16.0 17.0 14.2 18.6 10.9 17.0 17.0 18.1 14.7 19.3 11.5 15.0 15.0 15.8 13.6 17.7 10.5 13.9 13.9 14.5 13.0 16.6 10.0 30 17.4 17.4 17.4 17.4 18.8 13.8 18.2 18.2 18.4 17.8 19.5 13.9 16.4 16.4 16.4 16.4 17.8 13.6 15.4 15.4 15.4 15.4 16.7 13.2 33 18.5 18.5 18.5 18.5 19.0 16.7 19.1 19.1 19.1 19.1 19.8 16.7 17.6 17.6 17.6 17.6 18.1 16.6 16.7 16.7 16.7 16.7 17.0 16.3
27 16.6 16.6 17.4 15.0 18.8 11.2 17.5 17.5 18.3 15.4 19.6 11.3 15.6 15.6 16.2 14.5 17.9 11.0 14.4 14.4 14.8 13.9 16.8 10.5 30 17.9 17.9 17.9 17.9 19.0 14.4 18.6 18.6 18.7 18.7 19.7 14.4 17.0 17.0 17.0 17.0 18.0 14.2 15.9 15.9 15.9 15.9 16.9 13.9 33 18.9 18.9 18.9 18.9 19.3 17.5 19.5 19.5 19.5 19.5 20.0 17.4 18.1 18.1 18.1 18.1 18.4 17.5 17.2 17.2 17.2 17.2 17.3 17.2
27 17.1 17.1 17.6 15.8 18.9 11.6 18.0 18.0 18.5 16.0 19.7 11.8 16.1 16.1 16.5 15.3 18.1 11.4 14.9 14.9 15.1 14.7 17.0 11.0 30 18.3 18.3 18.3 18.3 19.2 14.9 19.0 19.0 19.0 19.0 19.9 14.8 17.4 17.4 17.4 17.4 18.2 14.9 16.4 16.4 16.4 16.4 17.1 14.6 33 19.2 19.2 19.2 19.2 19.5 18.2 19.8 19.8 19.8 19.8 20.2 17.9 18.5 18.5 18.5 18.5 18.6 18.2 17.6 17.6 17.6 17.6 17.6 17.6
Table PD-1a — Gross Cooling Capacities (MBH) WSC060AD,T (IP)
Enter. Ambient Temperature (F) Dry 85 95 105 115
CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 1800 75 54.0 46.5 61.5 35.8 65.9 24.0 49.6 44.2 57.7 34.7 63.5 22.6 45.0 41.9 52.8 32.5 60.3 21.1 40.3 39.5 47.6 30.2 56.2 19.4
2000 75 55.5 49.5 62.4 38.3 66.5 24.4 51.0 47.2 58.8 35.6 64.1 23.1 46.4 44.9 54.0 34.4 61.0 21.6 41.6 41.6 48.6 32.1 57.0 19.9
2200 75 56.8 52.4 63.1 39.9 66.9 24.8 52.3 50.1 59.6 37.2 64.5 23.5 47.3 47.3 54.9 35.1 61.5 22.0 43.1 43.1 49.5 34.0 57.6 20.4
2400 75 57.9 55.2 63.6 41.2 67.2 25.2 53.5 52.9 60.3 38.8 64.9 23.9 48.9 48.9 55.7 38.1 61.9 22.4 44.5 44.5 50.3 34.3 58.1 20.8
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Bulb Entering Wet Bulb Temperature (F)
80 55.3 55.3 61.7 44.9 66.5 33.3 51.8 51.8 57.9 43.1 64.0 31.9 48.0 48.0 53.1 40.9 60.6 30.2 44.0 44.0 47.9 38.5 56.4 28.4 85 59.5 59.5 62.2 53.8 67.1 42.4 56.1 56.1 58.5 52.3 64.3 40.4 52.3 52.3 54.0 50.2 60.9 39.3 48.4 48.4 49.1 47.9 56.6 37.4 90 62.9 62.9 63.3 62.7 67.6 49.1 60.1 60.1 60.1 60.1 64.8 48.8 56.6 56.6 56.6 56.6 61.2 47.9 52.8 52.8 52.8 52.8 57.0 46.4
80 57.7 57.7 62.6 47.1 67.2 34.4 54.1 54.1 59.0 45.7 64.6 33.2 50.1 50.1 54.4 43.5 61.3 31.6 46.0 46.0 49.1 41.2 57.2 29.8 85 61.6 61.6 63.4 56.8 68.0 42.9 58.5 58.5 59.9 55.8 65.0 42.0 54.7 54.7 55.5 53.9 61.6 41.1 50.6 50.6 50.6 50.6 57.4 39.7 90 64.8 64.8 64.8 64.8 68.3 50.9 62.1 62.1 62.1 62.1 65.6 51.1 58.9 58.9 58.9 58.9 62.2 50.6 55.1 55.1 55.1 55.1 58.0 49.4
80 59.7 59.7 63.4 49.2 67.7 35.1 56.1 56.1 59.9 48.1 64.9 35.4 52.1 52.1 55.4 46.1 61.9 32.9 47.8 47.8 50.2 43.8 57.9 31.1 85 63.2 63.2 64.3 59.5 68.5 44.1 60.3 60.3 61.0 58.9 65.6 45.3 56.7 56.7 56.7 56.7 62.3 42.9 52.7 52.7 52.6 52.6 58.1 41.7 90 66.2 66.2 66.1 66.1 69.3 53.4 63.7 63.7 63.6 63.6 66.3 53.1 60.6 60.6 60.6 60.6 63.0 53.0 57.0 57.0 57.0 57.0 58.9 52.2
80 61.2 61.2 64.1 51.1 68.1 35.7 57.8 57.8 60.7 50.3 65.9 34.3 53.8 53.8 56.3 48.6 62.3 33.8 49.4 49.4 51.2 46.3 58.4 32.4 85 64.5 64.5 65.1 61.9 69.0 45.2 61.7 61.7 62.0 61.8 66.1 44.8 58.3 58.3 58.3 58.3 62.8 44.5 54.3 54.3 54.3 54.3 58.8 43.7 90 67.2 67.2 67.2 67.2 69.8 54.9 64.9 64.9 64.9 64.9 66.9 55.0 61.9 61.9 61.9 61.9 63.7 55.2 58.5 58.5 58.5 58.5 59.7 54.8
14
PKGP-PRC004-EN
Performance Data
Table PD-2 — Gross Cooling Capacities (kW) WSC072AD,T (SI)
Enter. Ambient Temperature (C) Dry 30 35 40 45 Bulb Entering Wet Bulb Temperature (C)
3
/h Temp 16 19 22 16 19 22 16 19 22 16 19 22
m Airflow (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
3670 24 20.3 18.1 22.7 14.4 23.9 10.2 19.0 17.4 21.7 14.0 23.6 9.9 17.6 16.7 20.2 13.4 22.9 9.6 16.1 16.0 18.6 12.7 21.7 9.2
4080 24 20.9 19.3 23.0 15.1 24.1 10.4 19.5 18.6 22.2 14.6 23.8 10.2 18.1 17.9 20.7 14.0 23.1 9.8 16.7 16.7 19.0 13.5 22.1 9.5
4490 24 21.4 20.4 23.2 15.6 24.2 10.7 20.1 19.8 22.5 15.3 23.9 10.4 18.7 18.7 21.1 14.7 23.3 10.1 17.3 17.3 19.3 14.3 22.3 9.7
4900 24 21.9 21.6 23.4 16.1 24.3 10.8 20.5 20.5 22.7 15.9 24.0 10.6 19.3 19.3 21.4 15.4 23.4 10.4 17.9 17.9 19.7 15.1 22.5 10.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
27 21.2 21.2 22.8 17.9 24.2 13.6 20.1 20.1 21.8 17.6 23.7 13.6 19.0 19.0 20.4 17.0 22.9 13.3 17.7 17.7 18.8 16.3 21.7 12.9 30 22.6 22.6 23.1 21.5 24.4 16.7 21.9 21.9 22.2 21.5 23.8 16.8 20.8 20.8 20.9 20.9 23.0 16.8 19.5 19.5 19.5 19.5 21.8 16.5 33 23.7 23.7 23.7 23.7 24.6 19.9 23.2 23.2 23.2 23.2 24.1 20.2 22.4 22.4 22.4 22.4 23.2 20.4 21.3 21.3 21.3 21.3 22.1 20.3
27 22.1 22.1 23.1 18.8 24.3 13.8 21.0 21.0 22.3 18.7 23.9 13.9 19.8 19.8 20.9 18.2 23.2 13.9 18.6 18.6 19.3 17.5 22.1 13.5 30 23.3 23.3 23.5 22.5 24.6 17.1 22.7 22.7 22.6 22.6 24.1 17.5 21.7 21.7 21.7 21.7 23.3 17.7 20.5 20.5 20.5 20.5 22.2 17.6 33 24.2 24.2 24.2 24.2 24.8 20.5 23.8 23.8 23.8 23.8 24.4 21.0 23.1 23.1 23.1 23.1 23.6 21.5 22.2 22.2 22.2 22.2 22.5 21.5
27 22.6 22.6 23.4 19.5 24.5 14.2 21.8 21.8 22.6 19.7 24.2 14.4 20.6 20.6 21.3 19.3 23.4 14.3 19.3 19.3 19.8 18.6 22.4 14.2 30 23.7 23.7 23.8 23.4 24.8 17.7 23.2 23.2 23.2 23.2 24.3 18.1 22.4 22.4 22.4 22.4 23.6 18.5 21.2 21.2 21.2 21.2 22.5 18.5 33 24.5 24.5 24.5 24.5 25.1 21.2 24.2 24.2 24.2 24.2 24.6 21.8 23.6 23.6 23.6 23.6 23.9 22.4 22.8 22.8 22.8 22.8 23.0 22.7
27 23.1 23.1 23.6 20.2 24.6 14.4 22.4 22.4 22.9 20.6 24.2 14.6 21.3 21.3 21.8 20.4 23.6 14.8 20.0 20.0 20.2 19.7 22.5 14.7 30 24.0 24.0 24.0 24.0 24.9 18.1 23.6 23.6 23.6 23.6 24.4 18.6 22.9 22.9 22.9 22.9 23.8 19.1 22.0 22.0 22.0 22.0 22.8 19.4 33 24.8 24.8 24.8 24.8 25.2 21.7 24.5 24.5 24.5 24.5 24.8 22.4 24.0 24.0 24.0 24.0 24.2 23.2 23.3 23.3 23.3 23.3 23.3 23.3
Table PD-2a — Gross Cooling Capacities (MBH) WSC072AD,T (IP)
Enter. Ambient Temperature (F) Dry 85 95 105 115
CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 2160 75 70.1 61.0 78.5 46.7 82.3 30.5 65.0 58.4 75.5 45.1 81.3 29.5 59.6 55.8 70.0 43.2 79.0 28.3 53.9 53.1 63.6 40.5 75.2 26.9
2400 75 72.0 64.9 79.4 48.9 82.8 31.0 66.8 62.4 76.7 47.2 81.8 30.0 61.4 59.8 71.5 45.0 79.7 28.8 55.7 55.7 65.0 43.0 76.2 27.5
2640 75 73.5 68.6 79.9 49.2 83.2 31.4 68.6 66.3 77.6 49.1 82.2 30.5 62.9 62.9 72.7 47.9 80.2 29.3 57.9 57.9 66.2 45.3 76.8 27.9
2880 75 75.0 72.4 80.5 50.4 83.5 31.9 70.2 70.2 78.2 51.7 82.5 31.0 65.0 65.0 73.7 50.2 80.6 29.8 59.8 59.8 67.2 47.7 77.4 28.4
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Bulb Entering Wet Bulb Temperature (F)
80 72.0 72.0 78.8 57.5 83.2 41.7 68.0 68.0 75.7 56.9 81.8 41.4 63.6 63.6 70.3 54.6 79.4 40.1 58.9 58.9 64.0 51.9 75.3 38.7 85 76.7 76.7 79.5 68.6 84.1 51.1 73.5 73.5 76.4 68.7 82.4 51.6 69.3 69.3 71.4 66.6 79.6 51.3 64.6 64.6 65.5 64.0 75.4 50.3 90 80.2 80.2 80.6 79.2 84.9 60.6 78.1 78.1 78.1 78.1 82.9 61.4 74.8 74.8 74.8 74.8 80.1 62.2 70.3 70.3 70.3 70.3 75.8 61.9
80 75.0 75.0 79.8 59.9 83.7 42.4 71.1 71.1 77.0 60.1 82.6 42.5 66.5 66.5 71.9 58.1 80.1 41.8 61.6 61.6 65.6 55.4 76.3 40.4 85 78.9 78.9 80.6 71.7 84.6 52.2 76.5 76.5 77.9 72.6 83.4 53.4 72.4 72.4 73.3 71.4 80.5 53.5 67.6 67.6 67.6 67.6 76.5 53.2 90 81.9 81.9 81.8 81.8 85.5 62.3 80.2 80.2 80.2 80.2 84.2 64.5 77.5 77.5 77.4 77.4 81.2 65.2 73.5 73.5 73.5 73.5 77.1 65.5
80 77.0 77.0 80.6 62.0 84.1 43.0 73.6 73.6 78.0 62.8 83.1 43.3 69.1 69.1 73.3 61.4 80.7 43.6 64.0 64.0 67.1 58.9 77.1 42.0 85 80.4 80.4 81.5 74.3 85.1 53.3 78.4 78.4 79.2 76.2 84.0 54.9 75.2 75.2 75.1 75.1 81.2 55.4 70.3 70.3 70.3 70.3 77.3 55.6 90 83.0 83.0 83.0 83.0 86.0 63.8 81.8 81.8 81.8 81.8 84.9 66.5 79.4 79.4 79.4 79.4 82.0 67.8 76.0 76.0 76.0 76.0 78.2 68.9
80 78.5 78.5 81.2 63.8 84.5 43.5 75.9 75.9 78.9 65.4 83.5 44.1 71.4 71.4 74.6 64.9 81.2 44.2 66.2 66.2 68.4 62.3 77.7 43.6 85 81.5 81.5 82.2 76.7 85.4 54.3 79.9 79.9 80.3 79.3 84.4 56.2 77.1 77.1 77.1 77.1 81.8 57.2 72.5 72.5 72.5 72.5 78.1 57.9 90 83.9 83.9 83.9 83.9 86.4 65.2 82.9 82.9 82.9 82.9 85.4 68.3 80.8 80.8 80.8 80.8 82.7 70.2 77.6 77.6 77.6 77.6 79.1 71.9
PKGP-PRC004-EN
15
Performance Data
Table PD-3 — Gross Cooling Capacities (kW) WSC090AD,T (SI)
Enter. Ambient Temperature (C) Dry 30 35 40 45 Bulb Entering Wet Bulb Temperature (C)
3
/h Temp 16 19 22 16 19 22 16 19 22 16 19 22
m Airflow (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 4590 24 25.5 22.7 28.1 18.0 29.5 12.6 23.7 21.8 26.9 17.4 29.0 12.3 21.9 21.0 25.1 16.6 28.1 11.9 20.5 16.8 20.7 12.4 20.8 9.3
5100 24 26.1 24.1 28.4 18.7 29.7 12.9 24.4 23.3 27.4 18.2 29.2 12.6 22.6 22.5 25.6 17.5 28.4 12.2 20.4 16.9 20.7 12.5 20.8 9.3
5610 24 26.7 25.6 28.7 19.0 29.8 13.3 25.0 24.8 27.7 19.0 29.4 12.9 23.2 23.2 26.0 18.3 28.6 12.6 20.6 17.3 20.8 12.6 20.9 9.3
6120 24 27.2 26.8 28.9 19.6 29.9 13.4 25.6 25.6 28.0 20.3 29.5 13.3 23.9 23.9 26.3 19.7 28.8 12.9 22.3 22.3 24.3 19.0 27.6 12.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
27 26.5 26.5 28.2 22.3 29.8 16.8 25.2 25.2 27.1 22.1 29.2 17.0 23.7 23.7 25.3 21.3 28.2 16.5 20.8 19.8 21.0 14.8 21.1 11.4 30 28.1 28.1 28.6 26.6 30.1 20.7 27.2 27.2 27.5 26.8 29.4 21.0 25.9 25.9 25.9 25.9 28.3 21.0 21.2 21.2 21.4 17.4 21.5 13.4 33 29.3 29.3 29.3 29.3 30.5 24.7 28.7 28.7 28.7 28.7 29.6 25.0 27.8 27.8 27.8 27.8 28.6 25.3 21.6 21.6 21.7 19.9 21.9 15.6
27 27.4 27.4 28.6 23.2 30.0 17.2 26.2 26.2 27.6 23.3 29.5 17.4 24.7 24.7 25.9 22.7 28.5 17.3 20.8 20.0 21.1 15.0 21.2 11.4 30 28.8 28.8 29.0 27.9 30.4 21.3 28.1 28.1 28.0 28.0 29.8 21.9 27.0 27.0 27.0 27.0 28.7 22.0 21.2 21.2 21.4 17.7 21.6 13.6 33 29.9 29.9 29.9 29.9 30.7 25.4 29.4 29.4 29.4 29.4 30.1 26.3 28.6 28.6 28.6 28.6 29.1 26.6 21.6 21.6 21.8 20.2 22.0 15.8
27 28.1 28.1 28.9 24.1 30.2 17.5 27.1 27.1 28.0 24.4 29.7 17.8 25.6 25.6 26.4 24.0 28.7 17.8 20.9 20.4 21.1 15.2 21.2 11.5 30 29.3 29.3 29.4 28.9 30.6 21.8 28.7 28.7 28.7 28.7 30.0 22.6 27.7 27.7 27.7 27.7 29.0 22.9 21.4 21.4 21.5 18.0 21.6 13.7 33 30.2 30.2 30.2 30.2 30.9 26.1 29.8 29.8 29.8 29.8 30.4 27.2 29.1 29.1 29.1 29.1 29.4 27.7 21.8 21.8 21.9 20.5 22.0 15.9
27 28.5 28.5 29.2 24.9 30.3 17.8 27.7 27.7 28.3 25.4 29.9 18.2 26.4 26.4 27.0 25.4 29.0 18.4 24.8 24.8 25.1 24.6 27.7 18.3 30 29.6 29.6 29.6 29.6 30.7 22.3 29.1 29.1 29.1 29.1 30.2 23.2 28.3 28.3 28.3 28.3 29.3 23.7 27.1 27.1 27.1 27.1 28.0 24.0 33 30.5 30.5 30.5 30.5 31.1 26.8 30.2 30.2 30.2 30.2 30.7 28.0 29.6 29.6 29.6 29.6 29.7 28.7 28.7 28.7 28.7 28.7 28.7 28.7
Table PD-3a — Gross Cooling Capacities (MBH) WSC090AD,T (IP)
Enter. Ambient Temperature (F) Dry 85 95 105 115
CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73 Airflow (F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 2700 75 87.8 76.5 97.1 58.3 101.4 37.7 81.1 73.3 93.3 56.2 99.9 36.5 74.3 70.1 86.7 54.3 97.1 35.0 70.3 57.6 71.2 40.6 71.5 28.7
3000 75 89.9 81.2 97.8 59.7 102.0 38.3 83.4 78.2 94.6 58.6 100.6 37.1 76.5 75.0 88.3 57.2 97.8 35.6 70.5 58.6 71.4 41.0 71.7 29.3
3300 75 91.9 85.9 98.6 61.8 102.4 39.0 85.5 83.0 95.6 62.2 101.0 37.7 78.3 78.3 89.7 58.7 98.5 36.3 70.8 59.6 71.6 41.4 71.9 29.1
3600 75 93.4 89.8 99.2 63.4 102.8 39.5 86.9 86.9 96.5 64.9 101.5 38.4 80.8 80.8 91.1 61.4 99.0 36.9 71.0 60.5 71.7 41.8 72.0 29.1
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Bulb Entering Wet Bulb Temperature (F)
80 90.1 90.1 97.5 71.3 102.5 52.9 85.0 85.0 93.6 70.9 100.7 51.5 79.4 79.4 87.1 68.3 97.6 49.8 71.3 67.7 72.3 48.5 72.7 35.8 85 95.4 95.4 98.3 84.9 103.6 63.1 91.7 91.7 94.5 85.4 101.8 64.2 86.4 86.4 88.5 83.4 97.9 63.8 72.6 72.6 73.4 56.8 73.9 42.3 90 99.3 99.3 99.8 97.9 104.7 74.9 96.7 96.7 96.7 96.7 102.5 76.8 93.0 93.0 93.0 93.0 98.6 77.4 74.0 74.0 74.5 65.1 75.1 48.9
80 93.4 93.4 98.6 74.0 103.1 52.4 88.6 88.6 95.0 74.5 101.6 52.6 82.9 82.9 88.9 72.5 98.5 51.9 71.6 68.9 72.5 49.1 72.9 36.0 85 97.8 97.8 99.7 88.5 104.3 64.5 94.7 94.7 96.3 90.1 102.7 66.1 89.9 89.9 91.1 89.4 99.1 66.5 73.0 73.0 73.7 57.7 74.2 42.7 90 101.2 101.2 101.2 101.1 105.5 76.9 99.1 99.1 99.1 99.1 103.7 79.9 95.8 95.8 95.8 95.7 99.8 80.9 74.4 74.4 74.8 66.1 75.4 49.5
80 95.5 95.5 99.5 76.4 103.6 53.1 91.6 91.6 96.2 77.9 102.2 53.6 86.0 86.0 90.7 76.8 99.2 54.2 71.9 69.9 72.7 49.7 73.1 36.2 85 99.4 99.4 100.7 91.5 104.9 65.7 96.9 96.9 97.8 94.3 103.3 67.8 93.1 93.1 93.0 93.0 100.0 69.1 73.3 73.3 73.9 58.5 74.3 43.0 90 102.5 102.5 102.5 102.5 106.1 78.7 100.9 100.9 100.9 100.9 104.5 82.3 97.9 97.9 97.9 97.9 100.8 84.1 74.7 74.7 75.0 67.1 75.6 50.0
80 97.1 97.1 100.2 78.6 104.1 53.7 93.9 93.9 97.2 80.9 102.7 54.4 88.5 88.5 92.2 80.8 99.9 54.9 72.1 70.9 72.9 50.2 73.2 36.4 85 100.7 100.7 101.5 94.2 105.3 66.9 98.6 98.6 99.0 97.9 103.9 69.4 95.0 95.0 95.0 95.0 100.9 71.6 73.5 73.5 74.0 59.3 74.5 43.3 90 103.5 103.5 103.5 103.5 106.6 80.4 102.1 102.1 102.1 102.1 105.1 84.5 99.6 99.6 99.6 99.6 102.1 87.8 74.9 74.9 75.2 68.0 75.8 50.5
16
PKGP-PRC004-EN
Loading...
+ 36 hidden pages