Trane GSWD, WPWD, EXWA User Manual

Installation Owner Diagnostics
Water-to-Water
Water-Source Heat Pump Models WPWD, GSWD and EXWA
Models
WPWD
024-072 – 60 HZ
GSWD
024-072 – 60 HZ
“A” and later Design Sequence
EXWA
240 – 60 HZ
WSHP-SVX02A-EN
Notice
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
NOTICE:
WARNING -Indicates a potentially hazardous situation which, if
not avoided, could result in death or serious injury.
CAUTION -Indicates a potentially hazardous situation which, if
not
avoided, may result in minor or moderate injury. It
may also be used to alert against unsafe practices.
CAUTION -Indicates a situation that may result in equipment or
property-damage-only accidents.
Important!
Equipment is shipped FOB (Free on Board) at the manufacturer. Therefore, freight claims for damages against the carrier must be initiated by the receiver.
NOTICE:
Unit contains HCFC (R-22) Refrigerant Instructions! Section 608, Paragraph C of the 1990 Clean Air Act states:
Effective July 1, 1992, it shall be unlawful for any person, in course of maintaining, servicing, repairing, or disposing of an air conditioning system, to knowingly vent or release any CFC or HCFC refrigerant. Minimal releases (air purges or refrigerant hoses) associated with good faith attempts to recapture or recycle are exempt from the ban on venting.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
© 2002 American Standard Inc. WSHP-SVX02A-EN
Contents
Installation/Startup/Commissioning
Pre-installation Checklist General Information Dimensions/Weights Installation Instructions Electrical Requirements Pre-Startup Checklist
Startup/Commissioning
Sequence of Operation Operating Pressures Startup Checklist & Log
Maintenance
4 4
5 6 10 19 20
21 21 22 30
24 25
Warranty Information Troubleshooting Checklist Unit Wiring
WSHP-SVX02A-EN 3
26 28 29
Pre-installation Checklist
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.
Jobsite Inspection
Always perform the following checks before accepting a unit:
1. Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
2. Verify that the power supply complies with the unit nameplate specifica­tions.
3. Visually inspect the exterior of the unit, for signs of shipping damage. Do not
sign the bill of lading accepting the unit(s) until inspection has been com­pleted. Check for damage promptly after the unit(s) are unloaded. Once the bill of lading is signed at the jobsite, the unit(s) are now the property of the SOLD TO party and future freight claims MAY NOT be accepted by the freight company.
4. Verify that the refrigerant charge has been retained during shipment by use of gauges. Schrader taps are located external to the cabinet on the 2-ton through 6-ton equipment.
5. After assuring that charge has been retained, reinstall the schrader caps to
assure that refrigerant leakage does not occur.
WARNING
Microbial Growth!
Wet interior unit insulation can become an amplification site for microbial growth (mold), which may cause odors and damage to the equipment and building materials. If there is evidence of microbial growth (mold) on the interior insulation, the insulation should be removed and replaced prior to operating the system.
Jobsite Storage
This unit is intended for indoor use only. To protect the unit from damage due to the elements, and to prevent possible IAQ contaminant sources from growing, the unit should be stored indoors. If indoor storage is not possible, the following provisions for outdoor storage must be met:
1. Place the unit(s) on a dry surface or raise above the ground to assure ade­quate air circulation beneath the unit.
2. Cover the unit(s) with a water proof tarp to protect them from the elements.
3. Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growth (mold) which has been determined to be a cause of odors and serious health related indoor air quality problems.
4. Store units in the normal UP orientation to maintain oil in the compressor.
5. Do not stack more than three units in total height for the WPWD/GSWD 2-ton through 6-ton configurations, and no more than two units high for the EXWA 20-ton configuration.
4 WSHP-SVX02A-EN
General Information
Unit Nameplate
The unit nameplate is located at the front of the unit. It includes the unit model number, serial number, electri­cal characteristics, refrigerant charge, and other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the compressor shell.
Unit Description
Before shipment, each unit is leak test­ed, dehydrated, charged with refriger­ant and run tested for proper control operation.
Water-to-Refrigerant Coils
The brazed-plate water-to-refrigerant heat exchangers for the 2-ton through 6-ton equipment are constructed of stainless steel.
The water-to-refrigerant heat ex­changers for the 20-ton equipment are an inner copper tube or cupro-nickel
(option available on the source-side only) and steel tube (tube-within-a­tube) design.
Both heat exchanger types are leak tested to assure there is no cross leak­age between the water and refrigerant gas.
Water Connections
One inch brass swivel connections are provided for the 2-ton through 6-ton equipment. Each brass fitting has a one inch gasket for the connector. The gaskets are shipped in the electrical compartment to prevent loss at the job site.
Water connections for the 20-ton are located inside the unit at the units front (source-side) and back (load­side). The fitting consist of a 2-inch fe­male pipe threaded connection.
Controls
The control system offered to control the unit is a Basic 24 volt control for the 2-ton through 6-ton unit sizes, and a deluxe 24 volt micro processing board for the 20-ton unit.
All power wiring to the equipment is made at the unit contactor for the 2-
ton through 6-ton equipment, and at the power block for the 20-ton equip­ment.
All low voltage wiring is made at the unit’s low voltage terminal board.
Wiring Connections
Troubleshooting and connection dia­grams for the equipment may be locat­ed in the back of this manual.
Basic 24V Controls
(for 2-ton through 6-ton units)
Safety devices for equipment contain­ing the basic 24V control option in­clude a low pressure switch and a freezestat to prevent compressor op­eration during low temperature activi­ty. The switch is set to activate at refrigerant pressures of 35 psig or 7 psig to fit most applications.
A high pressure switch prevents com­pressor operation during high or ex­cessive discharge pressures exceeding 395 psig.
The lockout relay communicates the low or high pressure situation to the compressor to prevent operation. The relay may be reset at the thermostat, or by cycling power to the unit.
General alarm may be accomplished through the lockout relay to drive light emitting diodes (LEDs) on a field sup­plied status indicating thermostat. Ter­minal 6 on the lockout relay is open for field use in malfunction indications. This feature will drive dry contacts only, and cannot be used to drive field installed control inputs.
Deluxe 24V Controls
(for 20-ton unit)
Units containing the Deluxe 24V con­trol design will incorporate a micro­processor-based control board. The Trane microprocessor board is factory wired to a terminal strip to provide all necessary terminals for field connec­tion. The deluxe board is equipped with a random start relay, anti-short cycle timer, brown out protection, compressor disable, unit safety con­trol, diagnostics and a generic relay
(which may be available for field use). See page 17 for diagnostic informa­tion. Desuperheater
(Option for 2-ton through 6-ton units)
For units containing the desuperheat­er option, the unit is shipped from the factory with a desuperheater water coil and pump mounted internal to the unit cabinetry. For domestic hot water hook-up instructions, see manual WSHPC-IN-4 or 72-9006-02.
The desuperheater pump fuse is locat­ed in the control box within a contain­er. The fuse is not factory installed to avoid possible pump damage at initial start-up. If the fuse in installed and the unit is started without water in the sys­tem, the pump will be damaged. See page 17 for fuse installation.
Schrader Connections
Connections for the low and high side of the refrigeration system are located conveniently on the unit’s right side for the 2-ton through 6-ton units, and behind the front, refrigeration access panel for the 20-ton unit.
WSHP-SVX02A-EN 5
Table 1: Unit weights
Size
024 163 153 036 183 173 042 203 193 048 214 204 060 244 234 072 277 267 240 1222 1156
Shipping
Weight
with pallet (lb)
w/o pallet (lb)
Shipping
Weight
Dimensions/Weights/ Clearance
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
Unit Location and Clearances
Locate the unit in an indoor area. The ambient temperature surrounding the unit must not be less than 45°F. Do not locate the unit in areas subject to freezing.
Attention should be given to service clearance and technician safety. The unit access panels may be easily re­moved. There must be enough space for service personnel to perform main­tenance or repair. Provide sufficient room to make water, and electrical connection(s). Local and national codes should be followed in providing electrical power connections. See Fig-
ure 1 for mechanical clearances.
Figure 1: Mechanical clearances
6 WSHP-SVX02A-EN
Dimensions
WPWD/GSWD 024-036
WSHP-SVX02A-EN 7
Dimensions
WPWD/GSWD 042-072
8 WSHP-SVX02A-EN
Dimensions
EXWA 240
WSHP-SVX02A-EN 9
Installation
General Installation Checks
The checklist below is a summary of the steps required to successfully in­stall a unit. This checklist is intended to acquaint the installing personnel with procedures required in the installation process. It does not replace the de­tailed instructions called out in the ap­plicable sections of this manual.
1 Remove packaging and inspect the
unit. Check the unit for shipping damage and material shortage; file a freight claim and notify appropri­ate sales representation.
Note: The units have been tied to the skid by (4) angle brackets. Re­move these brackets from the unit to slide unit from skid.
2 Verify the correct model, options
and voltage from the unit name­plate.
3 Verify the installation location of
the unit will provide the required clearance for proper operation.
4 Remove refrigeration access panel
and inspect the unit. Be certain the refrigerant tubing has clearance from adjacent parts.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Main Electrical
5 Verify the power supply complies
with the unit nameplate specifica­tions.
6 Inspect all control panel compo-
nents; tighten any loose connec­tions.
7 Connect properly sized and pro-
tected power supply wiring to a field-supplied/installed disconnect switch and to the main power ter­minal block (1TB1) in the unit con­trol box for the 20-ton equipment, or (1K1) for the 2-ton through 6­ton equipment.
8 Install proper grounding wires to
an earth ground.
Note: All field-installed wiring must comply with NEC and applicable local codes.
Low Voltage Wiring (AC & DC) Requirements
9 Connect properly sized control wir-
ing to the proper termination points between the field supplied thermostat and the terminal strip located in the equipment control box.
10 WSHP-SVX02A-EN
Loading...
+ 21 hidden pages