IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
BAYLIFT002A
LIFTING LUG KIT
Single Package Heat Pump
13-14 SEER Convertible
2 - 5 Ton
WARNING:
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
NOTICE
Warnings and Cautions appear at appropriate locations throughout this manual.
Read these carefully.
All phases of this installation must comply with the NATIONAL,STATE & LOCAL CODES. In the absence of local codes, the
installation must conform with National Electric Code -- ANSI/
NFPA 70 or "LATEST REVISION."
Since The Trane Companyhas a policy of continuous product and product data
improvement, it reserves the right to change design and specification without notice.
result in minor or moderate injury. It may also
be used to alert against unsafe practices
and where property-damage-only accidents
could occur.
Indicates a potentially haz-
Indicates a potentially haz-
07/02
GENERAL INFORMATION
D
IMPORTANT: Read this entire manual before beginning installation procedures.
SAFETY NOTICE. THIS INFORMATION IS INTENDED FOR
USE BY INDIVIDUALS POSSESSING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING PRODUCT MAY RESULT IN PERSONAL INJURY
AND/OR PROPERTY DAMAGE. THE MANUFACTURER OR
SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION, NOR CAN IT ASSUME
LIABILITY IN CONNECTION WITH ITS USE.
WARNING:
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
IMPORTANT: RECONNECT ALL GROUNDING DEVICES.
ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING
ELECTICAL CURRENT ARE GROUNDED. IF GROUNDING
WIRES, SCREWS, STRAPS, CLIPS NUTS OR WASHERS
USED TO COMPLETE A PATH TO GROUND ARE REMOVED
FOR SERVICE. THEY MUST BE RETURNED TO THIER ORIGINAL POSITION AND PROPERLY FASTENED.
IMPORTANT: ALL POWER LEGS MAY NOT BE BROKEN BY
CONTACTORS. SEE WIRING DIAGRAM ON UNIT CONTROL
BOX COVER.
BEFORE STARTING THE COMPRESSOR, THE CRANKCASE
HEATER SHOULD BE ENERGIZED FOR EIGHT HOURS
Read this manual carefully before attempting to install, operate, or
perform maintenance on this unit. Installation and maintenance
should be performed by qualified service technicians only.
NOTE: "Warnings" and "Cautions" appear at appropriate
places in this manual. Your personal safety and the proper
operation of this air conditioning product require that you follow
them carefully. The manufacturer assumes no liability for
installations or servicing performed by unqualified personnel.
INSPECTION
1. Check for damage after the unit is unloaded. Report promptly,
to the carrier, any damage found to the unit. Do not drop the unit.
IMPORTANT: The use of "spreader bars" is required when
hoisting the unit ( to prevent damage to sides and top ).
2. Check the unit's nameplate to determine if the unit is correct for
the intended application. The power supply must be adequate
for both the unit and all accessories.
3. Check to be sure the refrigerant charge has been retained during
shipment. Access to 1/4" flare pressure taps may be gained by
removing the furnace compartment access panel.
1
TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS
(WCY024-060G Models)
ROOF INSULATION
ROOF DECK
FIELD SUPPLIED
RIGID INSULATION
ROOFING
FIELD SUPPLIED
CANT STRIP
FIELD SUPPLIE
SUPPORTS
AT EACH END
OF CURB
Page 2
SUPPLY AIR
DUCT
RETURN AIR
DUCT
ROOF MOUNTING
CURB
D
2
TYPICAL ROOFTOP INSTALLATION WITH BAYCURB030A
(WCY024-060G Models)
SEE NOTE 1
SEE NOTE 2
ROOF INSULATION
ROOF DECK
FIELD SUPPLIED
RIGID INSULATION
ROOFING
FIELD SUPPLIED
CANT STRIP
FIELD SUPPLIE
SUPPORTS
AT EACH END
OF CURB
NOTE 1: The WCY036-042G Models extend
out past this end of the curb only.
NOTE 2: Only the WCY048-060G Models
extend past both the end and the
side of the curb as illustrated
CONVERTING HORIZONTAL TO DOWNFLOW
3
SUPPLY AIR
DUCT
RETURN AIR
DUCT
ROOF MOUNTING
CURB
HORIZONTAL SUPPLY
AIR COVER
SHEET METAL
SCREWS
HORIZONTAL RETURN
AIR COVER
NOTE
SUPPLY OPENING
1. REMOVE THE SCREW NEAREST TO THE
OPENING AND PULL THE PANEL FIRMLY
TOWARD THE OUTSIDE OF THE UNIT TO
DISENGAGE THE BACK ATTACHMENT.
RETURN OPENING
2. REMOVE RIGHT HAND SCREW AND
MOVE PANEL TO THE RIGHT OR
REMOVE BOTH SCREWS.
* 18" WITH FRESH AIR ACCESSORY
* 30" WITH ECONOMIZER
D
SUPPLY AIR
C
HOLE IN ROOF
RETURN AIR
E
A
SERVICE
CLEARANCE
LINES
B
F
LOCATIONS AND RECOMMENDATIONS
These units are designed for outdoor installation. For proper installation, the following recommendations must be considered.
NOTE: Unit shipped for horizontal installation. Convert to
downflow per instruction.
The discharge air from the condenser fans must be unrestricted for
a minimum of 3 feet above the unit.
Roof Mounting Curb (field assembled BAYCURB030A and
BAYCURB033A, BAYCURB034A) or a field fabricated curb must be
in place before unit is hoisted to the roof.
Roof Mounting Curb (frame) must be installed on a flat, level
section of the roof (max. of 1/4" per foot pitch), providing a level
mounting surface for the unit. In addition, provide sufficient
height above the roof to prevent water from entering unit.
In locations where deep snows are encountered,RAlSE THE UNlT
A MINIMUM OF 12" OFF THE ROOF, DECK OR SLAB—the chance
of the coil being blocked with snow will be reduced. The water that
occurs during the defrost has a better chance of flowing from the
vicinity of the unit.
Roof Mounting Curb used with WCY—F models is approximately
14" high. This is normally sufficient height to prevent snow blockage
and additional clearance is not necessary.
Page 6
AVOID LOCATING THE UNIT WHERE SNOW TENDS TO DRIFT.
This will reduce the times when it is necessary for the customer to
remove the snow from around the unit. MAKE CERTAIN THE
CUSTOMER KNOWS THAT SNOW ACCUMULATIONS SHOULD
BE REMOVED FROM THE SIDES OF THE UNIT FOR BEST
EFFICIENCY.
A snow drift barrier may be installed around the unit to prevent a
build up of snow on the sides of the unit. The barrier should be of
sufficient distance from the unit to prevent restriction of airflow to
and from unit.
LOCATE THE UNIT SO THAT THE WATER VAPOR THAT DISCHARGES UPWARD DURING DEFROST DOES NOT CONDENSE
ON WINDOWS AND FOG THEM OR CAUSE ICICLES TO FORM
ON OVERHANGS.
1. Be sure the mounting curb spans structural members (trusses)
of the roof, thereby providing sufficient support for weight of the
unit, curb and duct(s) plus any accessories (factory or field
installed). See Figures 1, 2, 3, 4, 5, 6, 7, 8, 9,10,11 and 12.
NOTE: If any internal accessories are to be added to the unit it
should be done at the shop if at all practical.
2. Unit should be positioned so Roof-Run-Off water does not pour
directly on unit.