Trane WCY060G1, WCY048G1, WCY042G1, WCY024G1, WCY036G1 User Manual

...
INSTALLATION
WCY-IOM-1D 18-BB33D8-5
OPERATION MAINTENANCE
ALL phases of this installation must comply with
NATIONAL, STATE AND LOCAL CODES
WCY024G1 WCY030G1 WCY036G1 WCY042G1 WCY048G1 WCY060G1
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
BAYLIFT002A LIFTING LUG KIT
Single Package Heat Pump 13-14 SEER Convertible 2 - 5 Ton
WARNING:
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
NOTICE
Warnings and Cautions appear at appro­priate locations throughout this manual.
Read these carefully.
All phases of this installation must comply with the NATIONAL, STATE & LOCAL CODES. In the absence of local codes, the installation must conform with National Electric Code -- ANSI/
NFPA 70 or "LATEST REVISION."
Since The Trane Companyhas a policy of continuous product and product data improvement, it reserves the right to change design and specification without notice.
© 2002 American Standard Inc. All rights reserved
WARNING:
ardous situation which, if not avoided, could
result in death or serious injury.
CAUTION:
ardous situation which, if not avoided, may
result in minor or moderate injury. It may also be used to alert against unsafe practices
and where property-damage-only accidents could occur.
Indicates a potentially haz-
Indicates a potentially haz-
07/02
GENERAL INFORMATION
D
IMPORTANT: Read this entire manual before beginning instal­lation procedures.
SAFETY NOTICE. THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUATE BACK­GROUNDS OF ELECTRICAL AND MECHANICAL EXPERI­ENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDI­TIONING PRODUCT MAY RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRE­TATION OF THIS INFORMATION, NOR CAN IT ASSUME LIABILITY IN CONNECTION WITH ITS USE.
WARNING:
HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING
IMPORTANT: RECONNECT ALL GROUNDING DEVICES.
ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTICAL CURRENT ARE GROUNDED. IF GROUNDING WIRES, SCREWS, STRAPS, CLIPS NUTS OR WASHERS USED TO COMPLETE A PATH TO GROUND ARE REMOVED FOR SERVICE. THEY MUST BE RETURNED TO THIER ORIGI­NAL POSITION AND PROPERLY FASTENED.
IMPORTANT: ALL POWER LEGS MAY NOT BE BROKEN BY CONTACTORS. SEE WIRING DIAGRAM ON UNIT CONTROL BOX COVER. BEFORE STARTING THE COMPRESSOR, THE CRANKCASE HEATER SHOULD BE ENERGIZED FOR EIGHT HOURS
Read this manual carefully before attempting to install, operate, or perform maintenance on this unit. Installation and maintenance should be performed by qualified service technicians only.
NOTE: "Warnings" and "Cautions" appear at appropriate places in this manual. Your personal safety and the proper operation of this air conditioning product require that you follow them carefully. The manufacturer assumes no liability for installations or servicing performed by unqualified personnel.
INSPECTION
1. Check for damage after the unit is unloaded. Report promptly, to the carrier, any damage found to the unit. Do not drop the unit.
IMPORTANT: The use of "spreader bars" is required when hoisting the unit ( to prevent damage to sides and top ).
2. Check the unit's nameplate to determine if the unit is correct for the intended application. The power supply must be adequate for both the unit and all accessories.
3. Check to be sure the refrigerant charge has been retained during shipment. Access to 1/4" flare pressure taps may be gained by removing the furnace compartment access panel.
1
TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS
(WCY024-060G Models)
ROOF INSULATION
ROOF DECK
FIELD SUPPLIED
RIGID INSULATION
ROOFING
FIELD SUPPLIED
CANT STRIP
FIELD SUPPLIE
SUPPORTS
AT EACH END
OF CURB
Page 2
SUPPLY AIR
DUCT
RETURN AIR
DUCT
ROOF MOUNTING
CURB
D
2
TYPICAL ROOFTOP INSTALLATION WITH BAYCURB030A
(WCY024-060G Models)
SEE NOTE 1
SEE NOTE 2
ROOF INSULATION
ROOF DECK
FIELD SUPPLIED
RIGID INSULATION
ROOFING
FIELD SUPPLIED
CANT STRIP
FIELD SUPPLIE
SUPPORTS
AT EACH END
OF CURB
NOTE 1: The WCY036-042G Models extend
out past this end of the curb only.
NOTE 2: Only the WCY048-060G Models
extend past both the end and the side of the curb as illustrated
CONVERTING HORIZONTAL TO DOWNFLOW
3
SUPPLY AIR
DUCT
RETURN AIR
DUCT
ROOF MOUNTING
CURB
HORIZONTAL SUPPLY
AIR COVER
SHEET METAL
SCREWS
HORIZONTAL RETURN
AIR COVER
NOTE SUPPLY OPENING
1. REMOVE THE SCREW NEAREST TO THE OPENING AND PULL THE PANEL FIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT.
RETURN OPENING
2. REMOVE RIGHT HAND SCREW AND MOVE PANEL TO THE RIGHT OR REMOVE BOTH SCREWS.
3. REMOVE EXTERIOR GASKET MATERIAL.
Page 3
DIMENSIONAL DATA
4
WCY024-060G OUTLINE - BACK
MODEL
WCY024G 79 74 74 104 331 WCY030G 82 64 86 110 342 21 24-3/8 WCY036G 110 82 88 118 398 WCY042G 110 82 88 118 398 19-1/4 27-1/2 WCY048G 149 104 117 134 504 WCY060G 126 98 121 157 502 20 28
CORNER WEIGHT(LBS)
W1 W2 W3 W4
UNIT
WEIGHT
ABCDEFG H JKLMNP
56-1/2 36 29-3/16 18-9/16 11-1/16 6-9/16 6-13/16 17
64 36 29-1/ 16 18-9/16 11-1/16 6-9/16 11-1/8 17
65-1/8 45 33-1/8 21-1/16 15-1/16 4-15/16 9-1/8 21-15/16
21 25-3/8
19-1/4 27-1/2
24-1/4 28-1/2
Page 4
17-1/2 10 3 4-7/16
17-1/2 10 3 8-3 /4
20 14 3-1/2 8-5/16
DIMENSIONAL DATA
6
6
E
L
5
WCY024-060G OUTLINE - FRONT
RECOMMENDED SERVICE CLEARANC
BACK * 6.0"
LEFT SIDE 30.0"
RIGHT SIDE 24.0"
FRONT SIDE 30.0"
* 18" WITH FRESH AIR ACCESSORY * 30" WITH EC ONOMI ZE R
MODEL A B C D
WCY024G WCY030G
WCO36G
WCY042G WCY048G
WCY060G
56-1/2 36 29-3/16 12-15/1
64 36 29-3/16 14-1/2
65-1/8 45 33-3/8 14-13/1
CLEARANCE TO
COMBUSTIBLE MATERIA
BOTTOM 0.0"
BACK 1.0"
LEFT SIDE 6.0" RIGHT SIDE 6.0" FRONT SIDE 12.0"
TOP 36.0"
From Dwg. 21D664
Page 5
6
" " "
REQUIRED CLEARANCE FOR UNIT INSTALLATION
AND ROOF PENETRATION HOLE SIZE REQUIRED
SERVICE
CLEARANCE
LINES
SIDE RAIL
WOOD NAILER
SERVICE CLEARANCE & PENETRATION DIMENSIONS
MODEL NO. A B C D E F
WCY024-030G 30" 30" *12" 24" 36" 25 WCY036-042G 30" 30" *12" 30" 44" 25 WCY048-060G 42" 30" *12" 36" 50" 25
* 18" WITH FRESH AIR ACCESSORY * 30" WITH ECONOMIZER
D
SUPPLY AIR
C
HOLE IN ROOF
RETURN AIR
E
A
SERVICE
CLEARANCE
LINES
B
F
LOCATIONS AND RECOMMENDATIONS
These units are designed for outdoor installation. For proper instal­lation, the following recommendations must be considered.
NOTE: Unit shipped for horizontal installation. Convert to downflow per instruction.
The discharge air from the condenser fans must be unrestricted for a minimum of 3 feet above the unit.
Roof Mounting Curb (field assembled BAYCURB030A and BAYCURB033A, BAYCURB034A) or a field fabricated curb must be in place before unit is hoisted to the roof.
Roof Mounting Curb (frame) must be installed on a flat, level section of the roof (max. of 1/4" per foot pitch), providing a level mounting surface for the unit. In addition, provide sufficient height above the roof to prevent water from entering unit.
In locations where deep snows are encountered,RAlSE THE UNlT A MINIMUM OF 12" OFF THE ROOF, DECK OR SLAB—the chance of the coil being blocked with snow will be reduced. The water that occurs during the defrost has a better chance of flowing from the vicinity of the unit.
Roof Mounting Curb used with WCY—F models is approximately 14" high. This is normally sufficient height to prevent snow blockage and additional clearance is not necessary.
Page 6
AVOID LOCATING THE UNIT WHERE SNOW TENDS TO DRIFT. This will reduce the times when it is necessary for the customer to remove the snow from around the unit. MAKE CERTAIN THE CUSTOMER KNOWS THAT SNOW ACCUMULATIONS SHOULD BE REMOVED FROM THE SIDES OF THE UNIT FOR BEST EFFICIENCY.
A snow drift barrier may be installed around the unit to prevent a build up of snow on the sides of the unit. The barrier should be of sufficient distance from the unit to prevent restriction of airflow to and from unit.
LOCATE THE UNIT SO THAT THE WATER VAPOR THAT DIS­CHARGES UPWARD DURING DEFROST DOES NOT CONDENSE ON WINDOWS AND FOG THEM OR CAUSE ICICLES TO FORM ON OVERHANGS.
1. Be sure the mounting curb spans structural members (trusses) of the roof, thereby providing sufficient support for weight of the unit, curb and duct(s) plus any accessories (factory or field installed). See Figures 1, 2, 3, 4, 5, 6, 7, 8, 9,10,11 and 12.
NOTE: If any internal accessories are to be added to the unit it should be done at the shop if at all practical.
2. Unit should be positioned so Roof-Run-Off water does not pour directly on unit.