Trane UNT-SVX07A-EN User Manual

Installation, Operation, and Maintenance
UniTrane Fan-Coil & Force Flo Air Conditioners
200 to 1,200 cfm
Models FC & FF “ZO” and later design sequence
April 2005
UNT -SVX07A-EN
general information
About This Manual Literature Change History
Use this manual for UniT rane fan-coils and Force Flo cabinet heaters. This is the seventh revision of this manual. It provides specific installation, operation, and maintenance instructions for “ZO” and later design sequences for all models except low vertical, which are “SO” and later design sequences. For previous design sequence information, contact your local T rane representative.
Warnings and Cautions
Warnings and cautions appear at appropriate sections throughout this manual. Read these carefully.
WARNING
Indicates a potentially hazardous situation, which could result in death or serious injury if not avoided.
CAUTION
Indicates a potentially hazardous situation, which may result in minor or moderate injury if not avoided. Also, it may alert against unsafe practices.
WARNING
Hazardous V oltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other type conductors. Failure to use copper conductors may result in equipment damage.
Common HVAC Acronyms
For convenience, a number of acronyms and abbreviations are used throughout this manual. These acronyms are alphabetically listed and defined below.
BAS = Building automation systems cfm = Cubic-feet-per-minute ewt = entering water temperature F/A = Fresh air HV AC = Heating, ventilation and air conditioning I/O = Inputs/outputs IOM= Installation, operation, and maintenace manual LH = Left-hand O/A = Outside air R/A = Return air RH = Right-hand rpm = Revolutions-per-minute S/A = Supply air w.c. = W ater column ZSM = Zone sensor module
CAUTION
Indicates a situation that may result in equipment or property-damage­only accidents.
© 2005 American Standard Inc. UNT-SVX07A-EN
contents
Cross reference to related publications/information for UniT rane™ fan-coil & Force Flo™ equipment:
• Rover™ Installation, Operation and Programming Guide, EMTX-SVX01D-EN
• T racer
• T racer
• UniT rane™ Fan-Coil Catalog, UNT -PRC001-EN
• Force Flo
Installation ……………………………………………………………2
Operation ……………………………………………………………49
ZN510 Unit Controller , CNT -IOP-1
ZN520 Unit Controller, CNT-SVX04A-EN
Cabinet Heater Catalog, CAB-PRC001-EN
general information ……………………………………………2 dimensions & weights ……………………………………… 10 pre-installation considerations ………………………………28 mechanical requirements ……………………………………30 electrical requirements ………………………………………36 installation procedure ………………………………………41 pre-startup requirements ……………………………………46
general information …………………………………………49 sequence of operation ………………………………………50
Maintenance…………………………………………………………60
diagnostics ……………………………………………………60 troubleshooting ………………………………………………64 maintenance procedures ……………………………………67 typical wiring diagrams ………………………………………71
UNT-SVX07A-EN 3
general information
General
UniT rane fan-coil and Force Flo units are intended for single zone applications. These units have load capabilities of 200 to 1200 cfm. See Figure I-GI-1 for unit components. Fan-coil units are available as two-pipe, with or without electric heat (one hydronic circuit) or four-pipe (two hydronic circuits). Force-Flo units feature two-pipe hydronic, electric heat only, or steam only. Also, these units feature a variety of factory mounted piping packages.
Units with the three-speed fan switch only, are available with the switch mounted on the unit, or shipped sepa­rately, to be mounted in the occupied space. The unit mounted three-speed
Factory installed and tested controls
switch option, can be ordered with a low voltage(24 volts AC) transformer and three fan speed relays. The ship seperate three-speed switch option, only comes with a low voltage (24 volt AC) trans­former and three fan speed relays.
The T racer ZN010, ZN510, and ZN520 controllers are included inside the units control box assembly. These controllers utilize analog signals from a unit-mounted control device or from a control device mounted in the occupied space.
The controls interface option, includes a 24 volt AC transformer , and an interface terminal board. Controls provided by an external source, can be tied into the interface terminal board, utilizing female spade connectors.
Smaller unit footprint
Quiet operation
1
/4"
T wo, three or four-row coils
Model Number
Each UniT rane fan-coil and Force-Flo cabinet heater has a multiple character model number unique to that particular unit. T o determine a unit’s specific options, reference the model number on the unit nameplate on the fan scroll. The unit nameplate also identifies the serial number, sales order number, and installation and operating specifications.
Following is a complete description of the fan-coil model number. Each digit in the model number has a corresponding code that identifies specific unit options.
Factory assembled, installed and tested piping package with IAQ drain pan to collect condensate
Removable, noncorrosive, positively-sloped drain pan that’s easy to clean
Easy to remove fan assembly
Cleanable closed-
16-gage steel construction
Easy filter access without front panel removal
Figure I-GI-1. UniTrane fan-coil unit components. Vertical cabinet model is shown.
4 UNT-SVX07A-EN
Damper allows up to 100% fresh air
cell insulation (non­fiberglass)
general
Installation
information
Model Number Description
FC B B 020 1 C P0 A 0 G 1 0 A A 2 M 000 0 0 1 0 0 0 A A 000 000 0 0 0 0 A 0 0 1 5 10 15 20 25 30 35 40 44
Digits 1, 2 — unit type
FC = fan-coil FF = force flo
Digit 3 — cabinet type
A = vertical concealed B = vertical cabinet C = horizontal concealed D = horizontal cabinet E = horizontal recessed F = vertical wall hung H = vertical recessed J = vertical cabinet slope top K = low vertical concealed L = low vertical cabinet M = inverted vertical cabinet N = inverted vertical recessed
Digit 4 — development sequence “B” Digits 5, 6, 7 — unit size
020 040 080 030 060 100
120
Digit 8 — unit voltage
1 = 115/60/1 4 = 230/60/1 2 = 208/60/1 9 = 220/50/1 3 = 277/60/1
Digit 9 — piping system/placement
A = no piping, RH, w/o aux drn pan B = no piping, LH, w/o aux drn pan C = no piping, RH, w/ aux drn pan D = no piping, LH, w/ aux drn pan E = no piping, RH, w/o aux drn pan,
extended end pocket
F = no piping, LH, w/o aux drn pan,
extended end pocket
G = no piping, RH, w/ aux drn pan,
extended end pocket
H = no piping, LH, w/ aux drn pan,
extended end pocket J = piping package, RH K = piping package, LH L = piping package, RH, extd end pkt M = piping package, LH, extd end pkt
Digits 10, 11 — design sequence Digit 12 — inlets
A = front toe space B = front bar grille C = front stamped louver D = bottom stamped louver E = bottom toe space F = back duct collar
G = back open return H = back stamped louver
Digit 13 — fresh air damper
0 = none A = manual, bottom opening B = manual, back opening C = manual, top opening D = auto, 2-position, bottom opening E = auto, 2-position, back opening F = auto, 2-position, top opening G = auto, economizer, bottom opening H = auto, economizer, back opening J = auto, economizer , top opening K = no damper , bottom opening L = no damper , back opening M= no damper, top opening
Digit 14 — outlets
A = front duct collar B = front bar grille C = front stamped louver D = front quad grille G = top quad grille H = top bar grille J = top duct collar
Digit 15 — color
0 = no paint (concealed units only) 1 = deluxe beige 4 = driftwood grey 2 = soft dove 5 = stone grey 3 = cameo white 6 = rose mauve
Digit 16 — tamperproof locks/leveling feet
0 = none A = locking panel B = keylock access door C = locking panel & keylock access door D = leveling feet F=
locking panel w/ leveling feet
G = keylock panel, keylock access door
w/ leveling feet
Digit 17 — motor
A = free discharge B = high static
Digit 18 — coil
A = 2 row cooling/heating B = 3 row cooling/heating C = 4 row cooling/heating D = 2 row cooling/1 row heating E = 2 row cooling/2 row heating F = 3 row cooling/1 row heating G = 2 row cooling only H = 3 row cooling only J = 4 row cooling only K = 2 row cooling/heating w/ elec heat
L = 3 row cooling/heating w/ elec heat M= 4 row cooling/heating w/ elec heat P = 2 row cooling/heating w/1 row heat Q = 2 row cooling/heating w/2 row heat R = 3 row cooling/heating w/1 row heat
Digit 19 — coil series
2 = 144 FPF
Digit 20 — coil air vent
A = automatic air vent M= manual air vent
Digits 21, 22, 23 — electric heat (208V derate)
000 = no electric heat 010 = 1.0 kW (0.75 kW) 015 = 1.5 kW (1.1 kW) 020 = 2.0 kW (1.5 kW) 025 = 2.5 kW (1.9 kW) 030 = 3.0 kW (2.3 kW) 040 = 4.0 kW (3.0 kW) 050 = 5.0 kW (3.8 kW) 060 = 6.0 kW (4.5 kW) 070 = 7.0 kW (5.3 kW) 08 0= 8.0 kW (6.0 kW) 100 = 10.0 kW
Digit 24 — reheat coil
0 = none B = hot water coil A = steam coil
Digit 25 — disconnect switch
0 = none D = disconnect switch
Digit 26 — filter
0= none 1= 1” throwaway filter 2= 1” throwaway pleated media filter 3= 1” throwaway, qty 2 4=
1” throwaway pltd media, qty 2 5= 1” throwaway, qty 3 6= 1” throwaway pltd media, qty 3 7= 1” throwaway, qty 4 8= 1” throwaway pltd media, qty 4
Digit 27 — main control valve
0 = none A = 2-way, 2-position, NO (30 psig) B = 3-way , 2-position, NO (28 psig) C = 2-way , 2-position, NC (30 psig) D = 3-way, 2-position, NC (20 psig) E = 2-way, 2-position, NO (50 psig) F = 3-way , 2-position, NO (28 psig) G = 2-way, 2-position, NC (50 psig) H = 3-way, 2-position, NC (28 psig)
UNT-SVX07A-EN 5
general
J = 2-way , modulating, 0.7 Cv (50 psig)* K = 3-way , modulating, 0.7 Cv (50 psig)* L = 2-way, modulating, 1.1 Cv (60 psig)* M= 3-way, modulating, 1.1 Cv (60 psig)* N = 2-way, modulating, 2.3 Cv (60 psig)* P = 3-way, modulating, 2.7 Cv (60 psig)* Q = 2-way, modulating, 3.3 Cv (60 psig)* R = 3-way, modulating, 3.8 Cv (60 psig)* X = field-supplied, NO Y = field-supplied, NC Z = field-supplied 3-wire modulating
Digit 28 — auxiliary control valve
0 = none A = 2-way, 2-position, NO (30 psig) B = 3-way, 2-position, NC (28 psig) C = 2-way, 2-position, NC (30 psig) D = 3-way, 2-position, NC (20 psig) E = 2-way, 2-position, NO (50 psig) F = 3-way, 2-position, NO (28 psig) G = 2-way, 2-position, NC (50 psig) H = 3-way, 2-position, NC (28 psig) J = 2-way, modulating, 0.6 Cv (60 psig) K = 3-way, modulating, 0.6 Cv (60 psig) L = 2-way, modulating, 1.1 Cv (60 psig) M= 3-way, modulating, 1.1 Cv (60 psig) N = 2-way, modulating, 2.3 Cv (60 psig) P = 3-way, modulating, 2.7 Cv (60 psig) Q = 2-way, modulating, 3.3 Cv (60 psig) R = 3-way, modulating, 3.8 Cv (60 psig) X = field-supplied, NO Y = field-supplied, NC Z = field-supplied 3-wire modulating
Digit 29 — piping packages
0 = none A = basic ball valve S & R B = basic ball valve S/man. crkt set C = basic ball valve S & R w/auto crkt set D = deluxe ball valve S & R E = deluxe ball valve S /man. crkt set R F = deluxe ball valve S & R w/auto crkt set
Digit 30 — control type
0 = none A = fan speed switch E = T racer ZN010 F = Tracer ZN510
Installation
G = T racer ZN520 H = CSTI
Digit 31 — control option
D = unit mtd fan mode, unit voltage, K = wall mtd fan mode V = unit mtd fan sp w/ setpnt X = unit mtd fan sp w/ wall mtd setpnt Y = unit mtd fan sp & wall mtd setpnt w/
comm.
Z = unit mtd fan sp, on/cancel, setpnt w/
comm. 1 = wall mtd on/cancel w/ comm. 2 = wall mtd fan speed, setpnt, on/cancel
w/ comm. 3 = unit mtd fan speed switch, low voltage 4 = wall mtd digital zone sensor , fan sp w/
setpnt, on/cancel, comm. 5 = wall mtd digital zone sensor, setpnt,
on/cancel, comm.
Digit 32 — IAQ options
0 = none 1 = dehumidification 4 = dehumidification w/sensor
Digit 33 — cntrl function #1
0 = w/o exhaust fan/damper or alarm
Digit 34 — cntrl function #2
0 = w/o occupant call or IAQ status
Digit 35 — control function #3
0 = none 1 = occ/unocc control 2 = condensate overflow detection 3 = occ/unocc & condensate overflow
Digit 36 — cntrl function #4
0 = none 1 = smoke input 2 = low temperature detection 3 = smoke input & low limit sensor
information
Digits 37, 38 — future cntrl functions Digit 39 —
0 = none
5
/8”standard vertical recessed panel
A = B = 2” projection panel C = 2.5” projection panel D = 3” projection panel E = 3.5” projection panel F = 4” projection panel G = 4.5” projection panel H = 5” projection panel J = 5.5”projection panel K = 6” projection panel L = 2”falseback M = 3” falseback N = 4” falseback P = 5” falseback Q = 6” falseback R = 7” falseback T = 8” falseback
Digit 40 — main autoflow gpm
A = 0.5 G = 3.0 N = 7.0 B = 0.75 H = 3.5 P = 8.0 C = 1.0 J = 4.0 Q = 9.0 D = 1.5 K = 4.5 R = 10.0 E = 2.0 L = 5.0 T = 11.0 F = 2.5 M= 6.0 U = 12.0
Digit 41 — auxiliary autoflow gpm
A = 0.5 F = 2.5 L = 5.0 B = 0.75 G= 3.0 M= 6.0 C = 1.0 H = 3.5 N = 7.0 D = 1.5 J = 4.0 P = 8.0 E = 2.0 K = 4.5
Digit 42 — subbase
0 = none A = 2” subbase D =5” subbase B = 3” subbase E =6” subbase C = 4” subbase F =7” subbase
Digit 43 — recessed flange
0 = none A = recessed flange
Digit 44 — wall boxes
0 = none A = anodized wall box
projection panel/falseback
6 UNT-SVX07A-EN
general
Installation
information
Table I-GI-1. Fan-coil component data
unit size 02 03 04 06 08 10 12
Coil Data
Face Area — Ft LxDxH — In. (cm)
2-Row 15x1.7x8 15x1.7x8 20x1.7x8 29.5x1.7x8 38x1.7x8 57x1.7x8 57x1.7x8 3-Row 15x2.6x8 15x2.6x8 20x2.6x8 29.5x2.6x8 38x2.6x8 57x2.6x8 57x2.6x8 4-Row 15x3.5x8 15x3.5x8 20x3.5x8 29.5x3.5x8 38x3.5x8 57x3.5x8 57x3.5x8
Volume — Gal. (Liters)
1-Row (Heat) .06 (.23) .06 (.23) .08 (.30) .11 (.42) .14 (.53) .21 (.79) .21 (.79) 2-Row .12 (.45) .12 (.45) .15 (.57) .22 (.83) .28 (1.06) .42 (1.59) .42 (1.59) 3-Row .18 (.68) .18 (.68) .23 (.87) .33 (1.25) .42 (1.59) .62 (2.35) .62 (2.35) 4-Row .24 (.91) .24 (.91) .30 (1.14) .44 (1.67) .56 (2.12) .83 (3.14) .83 (3.14)
Fins/Ft (cm)
2-Row 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 3-Row 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 4-Row 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7)
Reheat Coil Data (1-Row) Hot Water or Steam
Face Area — Ft LxDxH — In. (cm) 15x1.5x6 15x1.5x6 20x1.5x6 29.5x1.5x6 38x1.5x6 57x1.5x6 57x1.5x6 Volume — Gal. (Liters) .12 (.45) .12 (.45) .15 (.57) .22 (.83) .28 (1.06) .42 (1.59) .42 (1.59)
Fins/Ft (cm) 48 (1.6) 48 (1.6) 48 (1.6) 48 (1.6) 48 (1.6) 48 (1.6) 48 (1.6)
Fan/Motor Data
Fan Quantity 1 1 1 2 2 3 3 Size — Dia” x Width” (cm) 6.31x4 6.31x6.5 6.31x7.5 6.31x6.5 6.31x7.5 (1) 6.31x7.5 6.31x7.5
Size — Dia” x Width” (cm) (2) 6.31x6.5 Motor Quantity 1 1 1 1 1 2 2
Filter Data 1” (cm) TA and Pl. Media
Quantity 1 1 1 1 1 1 1 Size — In. (cm) 8
1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)
Quantity 1 1 1 1 1 1 1 Size — In. (cm) 5 (14 x 49) (14 x 49) (14 x 61) (14 x 85) (14 x 107) (14 x 156) (14 x 156)
2
(cm2) 0.8 (743) 0.8 (743) 1.1 (1020) 1.6 (1490) 2.1 (1950) 3.2 (2970) 3.2 (2970)
(38x4x20) (38x4x20) (51x4x20) (75x4x20) (97x4x20) (145x4x20) (145x4x20) (38x7x20) (38x7x20) (51x7x20) (75x7x20) (97x7x20) (145x7x20) (145x7x20) (38x9x20) (38x9x20) (51x9x20) (75x9x20) (97x9x20) (145x9x20) (145x9x20)
2
(cm2) 0.6 0.6 0.8 1.2 1.6 2.4 2.4
(557) (557) (743) (1120) (1490) (2230) (2230) (38x4x15) (38x4x15) (51x4x15) (75x4x15) (97x4x15) (145x4x15) (145x4x15)
(16x10) (16x17) (16x19) (16x17) (16x19) (16x19) (16x19)
(16x6.5)
7
/8 x 191/8 87/8 x 191/8 87/8 x 241/8 87/8 x 335/8 87/8 x 421/8 87/8 x 611/8 87/8 x 611/8
(23x49) (23x49) (23x61) (23x85) (23x107) (23x155) (23x155)
1
/2 x 191/8 51/2 x 191/8 51/2 x 241/8 51/2 x 335/8 51/2 x 421/8 51/2 x 611/8 51/2 x 611/8
Table I-GI-2. Low vertical fan-coil component data
unit size 03 04 06
Coil Data
Face Area — Ft LxDxH — In. (cm)
2-Row 20x1.7x8 (51x4x20) 29.5x1.7x8 (75x4x20) 38x1.7x8 (97x4x20) 3-Row 20x2.6x8 (51x7x20) 29.5x2.6x8 (75x7x20) 38x2.6x8 (97x7x20)
Volume — Gal. (Liters)
1-Row (Heat) .08 (.30) .11 (.42) .14 (.53) 2-Row .15 (.57) .22 (.83) .28 (1.06) 3-Row .23 (.87) .33 (1.25) .42 (1.59)
Fins/Ft
2-Row 144 (4.7) 144 (4.7) 144 (4.7) 3-Row 144 (4.7) 144 (4.7) 144 (4.7)
Fan/Motor Data
Fan Quantity 1 1 1 Size — Dia”x Width” (cm) 5x23 (13x59) 5x32 (13x83) 5x41 (13x105) Motor Quantity 1 1 1
Filter Data
1” (2.5 cm) TA Quantity 1 1 1 Size — In. (cm) 8
UNT-SVX07A-EN 7
2
(cm2) 1.1 (1020) 1.6 (1490) 2.1 (1950)
7
/8x241/8 (23x61) 87/8x335/8 (23x85) 87/8 x 421/8 (23x107)
general
Available Models
model A vertical concealed
Installation
model B vertical cabinet
information
model C horizontal concealed
model D horizontal cabinet
model L low vertical concealed
model J slope-top cabinet
8 UNT-SVX07A-EN
model E horizontal recessed
model K low vertical cabinet
model M inverted vertical cabinet
(Force Flo only)
model F wall hung cabinet
model H
model N inverted vertical recessed
(Force Flo only)
vertical recessed
general
Factory-Installed Piping Packages
Installation
information
Note: This figure shows piping package components and basic arrangement. It is not an accurate pictorial of what factory-installed piping packages look like.
UNT-SVX07A-EN 9
dimensions
V ertical Concealed, Model A
Installation
& weights
Vertical Concealed Unit Dimensions & weights, in-lbs.
Unit Size 02-03 04 06 08 10-12 A 2’-8 11/16” 3’-1 11/16” 3’-11 3/16” 4’-7 11/16” 6’-2 11/16” B 1’-9 5/16” 2’-2 5/16” 2’-11 13/16” 3’-8 5/16” 5’-3 5/16” C 1’-10 13/16” 2’-3 13/16” 3’-1 5/16” 3’-9 13/16” 5’-4 13/16” D 1’-5 5/16” 1’-10 5/16” 2’-7 13/16” 3’-4 5/16” 4’-11 5/16” E 1’-7 5/16” 2’-0 5/16” 2’-9 13/16” 3’-6 5/16” 5’-1 5/16” operating weight 81 109 139 147 200 shipping weight 68 96 123 131 182
Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See fresh air opening dimensions on pages 23-24.
10 UNT-SVX07A-EN
dimensions
V ertical Cabinet, Model B
Installation
& weights
Vertical Cabinet Unit Dimensions, in-lbs.
unit size 02-03 04 06 08 10-12
A 2’-9 5/16” 3’-2 5/16” 3’-11 3/16” 4’-8 5/16” 6’-3 5/16” B 1’-9 5/16” 2’-2 5/16” 2’-11 3/16” 3’-8 5/16” 5’-3 5/16” C7 D 1’-6” 2’-0” 2’-6” 3’-6” 5’-0” E 1’-7 5/16” 2’-0 5/16” 2’-9 13/16” 3’-6 5/16” 5’-1 5/16
F 3’-5 5/16” 3’-10 5/16” 4’-7 3/16” 5’-4 5/16” 6’-11 5/16” operating weight 97 125 155 16 4 218 shipping weight 84 112 139 148 20 0
Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
UNT-SVX07A-EN 11
5
/8”7 1/8”8 7/8”7 1/8”7 5/8
dimensions
Horizontal Concealed, Model C
Installation
& weights
Horizontal Concealed Unit Dimensions, in-lbs.
unit size 02-03 04 06 08 10-12
A 2’-8 11/16” 3’-1 11/16” 3’-11 3/16” 4’-7 11/16” 6’-2 11/16
B 1’-9 5/16” 2’-2 5/16” 2’-11 13/16” 3’-8 5/16” 5’-3 5/16
C 1’-10 13/16” 2’-3 13/16” 3’-1 5/16” 3’-9 13/16” 5’-4 13/16
D 1’-7 3/8” 2’-0 3/8” 2’-9 7/8” 3’-6 3/8” 5’-1 3/8
E 1’-6 1/8” 1’-11 1/8” 2’-8 5/8” 3’-5 1/8” 5’-0 1/8
F 1’-7 5/16” 2’-0 5/16” 2’-9 13/16” 3’-6 5/16” 5’-1 5/16” operating weight 81 109 139 147 20 0 shipping weight 68 96 123 13 1 18 2
Notes:
1. Coil connections are always on the drain pan side and opposite the control
box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
12 UNT-SVX07A-EN
dimensions
Horizontal Cabinet, Model D
Installation
& weights
Horizontal Cabinet Unit Dimensions, in-lbs.
unit size 02-03 04 06 08 10-12
A 2’-9 5/16 3’-2 5/16” 3’-11 3/16” 4’-8 5/16” 6’-3 5/16” B 1’-9 5/16 2’-2 5/16” 2’-11 13/16” 3’-8 5/16” 5’-3 5/16” C7 D 1’-6” 2’-0” 2’-6” 3’-6” 5’-0” E 1’-5 1/4 1’-10 1/4” 2’-7 3/4” 3’-4 1/4” 4’-11 1/4” F 3’-5 5/16” 3’-10 5/16” 4’-7 3/16” 5’-4 5/16” 6’-11 5/16” G8 H 1’ -4” 1’-10” 2’-4” 3’-4” 4’-10”
J 1’-7 3/4 1’-11 3/4” 2’-7 3/4” 3’-3 3/4” 4’-11 3/4” operating weight 97 125 155 164 218 shipping weight 84 112 139 148 20 0
Notes:
1. Coil connections are always on the drain pan side and opposite the control
box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
5
/8”7
5
/8”8
1
/8”8 7/8”7 1/8”7 5/8
1
/8”9 7/8”8 1/8”8 5/8
UNT-SVX07A-EN 13
dimensions
Horizontal Recessed, Model E
Installation
& weights
Horizontal Recessed Unit Dimensions, in-lbs.
unit size 02-03 04 06 08 10-12
A 2’-11 13/16” 3’-4 13/16” 4’-2 5/16” 4’-10 13/16” 6’-5 13/16” B 1’-9 5/16 2’-2 5/16” 2’-11 13/16” 3’-8 5/16” 5’-3 5/16” C 1’-10 13/16” 2’-3 13/16” 3’-1 5/16” 3’-9 13/16” 5’-4 13/16” D 1’-7 3/8 2’-0 3/8” 2’-9 7/8” 3’-6 3/8” 5’-1 3/8” E 1’-6 1/8 1’-11 1/8” 2’-8 5/8” 3’-5 1/8” 5’-0 1/8” F 2’-8 7/16 3’-1 7/16” 3’-10 15/16” 4’-7 7/16” 6’-2 7/16” G 2’-10 5/16 3’-3 5/16” 4’-0 13/16” 4’-9 5/16” 6’-4 5/16
H 1’-7 3/4 1’-11 3/4” 2’-7 3/4” 3’-3 3/4” 4’-11 3/4” operating weight 78 88 128 139 253 shipping weight 68 78 118 12 9 24 3
Notes:
1. Coil connections are always on the drain pan side and opposite the control
box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
14 UNT-SVX07A-EN
dimensions
V ertical Wall Hung Cabinet, Model F
Installation
& weights
Vertical wall hung cabinet unit dimensions & weights, in-lbs.
unit size 02-03 04 06 08 10-12
A 2’-9 5/16” 3’-2 5/16” 3’-11 13/16” 4’-8 5/16” 6’-3 5/16” B 1’-9 5/16” 2’-2 5/16” 2’-11 13/16” 3’-8 5/16” 5’-3 5/16” C7 D 1’-6” 2’-0” 2’-6” 3’-6” 5’-0” E 1’-7 5/16” 2’-0 5/16” 2’-9 13/16” 3’-6 5/16” 5’-1 5/16
F 1’-7 3/4” 1’-11 3/4” 2’-7 3/4 3’-3 3/4” 4’-11 3/4” operating weight 97 125 155 164 218 shipping weight 84 1 12 139 148 20 0
Notes:
1. Coil connections are always on the side opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
UNT-SVX07A-EN 15
5
/8”7 1/8”8 7/8”7 1/8”7 5/8
dimensions
V ertical Recessed, Model H
Installation
& weights
Vertical Recessed Unit Dimensions, in-lbs.
unit size 02-03 04 06 08 10-12
A 2’-8 11/16” 3’-1 11/16” 3’-11 3/16” 4’-7 11/16” 6’-2 11/16” B 1’-9 5/16” 2’-2 5/16” 2’-11 13/16” 3’-8 5/16” 5’-3 5/16” C 1’-10 13/16” 2’-3 13/16” 3’-1 5/16” 3’-9 13/16” 5’-4 13/16” D 1’-5 5/16” 1’-10 5/16” 2’-7 13/16” 3’-4 5/16” 4’-11 5/16” E 3’-11” 4’-3” 5’-3” 5’-5 1/2” 7’-5 1/2” F 2’-6” 2’-6” 2’-6” 2’-9 1/2” 2’-9 1/2” G2 H 3’-6” 4’-0” 4’-9” 5’-3” 7’-3”
J 2’-2 1/2 2’-2 1/2 2’-2 1/2” 2’-3 1/2” 2’-3 1/2” operating weight 78 88 128 13 9 253 shipping weight 68 78 118 129 243
Notes:
1. Coil connections are always on the drain pan side and opposite the control
box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
5. Dimension 'G' refers to the required minimum distance between the finished
floor, and the bottom of the unit.
3
/8”2 3/8”2 3/8”4 1/8”4 1/8
16 UNT-SVX07A-EN
dimensions
V ertical Slope Top, Model J
Installation
& weights
Vertical Slope Top Unit Dimensions, in-lbs.
unit size 02-03 04 06 08 10-12
A 2’-9 5/16” 3’-2 5/16” 3’-11 13/16” 4’-8 5/16 6’-3 5/16” B 1’-9 5/16” 2’-2 5/16” 2’-11 13/16” 3’-8 5/16 5’-3 5/16” C7 D 1’-6” 2’-0” 2’-6” 3’-6” 5’-0”
E 1’-7 5/16” 2’-0 5/16” 2’-9 13/16 3’-6 5/16 5’-1 5/16
F 3’-5 5/16” 3’-10 5/16” 4’-7 13/16 5’-4 5/16 6’-11 5/16” operating weight 97 125 155 164 218 shipping weight 84 112 139 148 200
Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
UNT-SVX07A-EN 17
5
/8”7 1/8”8 7/8”7
1
/8”7
5
/8
dimensions
Low V ertical Concealed, Model K
Installation
& weights
Low Vertical Concealed Unit Dimensions, in-lbs.
unit size 03 04 06
A 3’-5 7/16 4’-2 15/16” 4’-11 7/16” B 2’-2 1/4 2’-11 3/4” 3’-8 1/4” C 2’-3 15/16” 3’-0 13/16” 3’-9 15/16” D 1’-10 5/16” 2’-7 13/16” 3’-4 5/16
E 2’-0 1/4 2’-9 3/4 3’-6 1/4” operating weight 109 139 147 shipping weight 96 123 131
Notes:
1. Coil connections are always on the drain pan side and opposite
the control box.
2. Coil connections are 5/8” O.D. sweat.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
18 UNT-SVX07A-EN
dimensions
Low V ertical Cabinet, Model L
Installation
& weights
Low Vertical Cabinet Unit Dimensions, in-lbs.
unit size 03 04 06
A 3’-10 15/16” 4’-8 7/16” 5’-4 15/16” B 2’-2 1/4” 2’-11 3/4” 3’-8 1/4” C 11 7/16 1’-1 5/16 11 7/16” D 2’-0” 2’-6” 3’-6”
E 2’-0 1/4 2’-9 3/4 3’-6 1/4” operating weight 125 155 164 shipping weight 112 139 148
Notes:
1. Coil connections are always on the drain pan side and
opposite the control box.
2. Coil connections are 5/8” O.D. sweat.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
UNT-SVX07A-EN 19
dimensions
Inverted V ertical Cabinet, Model M
Installation
& weights
Inverted vertical cabinet unit dimensions & weights, in-lbs.
unit size 02-03 04 06 08 10-12
A 2’-9 5/16 3’-2 5/16” 3’-11 13/16 4’-8 5/16” 6’-3 5/16” B 1’-9 5/16 2’-2 5/16” 2’-11 13/16 3’-8 5/16” 5’-3 5/16” C7 D 1’-6” 2’-0” 2’-6” 3’-6” 5’-0” E 1’-7” 2’-0” 2’-9 1/2 3’-6” 5’-1” F 1’-7 3/4 1’-11 3/4 2’-7 3/4 3’-3 3/4” 4’-11 3/4” G8
H 1’-4” 1’-10” 2’-4” 3’-4” 4’-10” operating weight 97 1 25 1 55 164 218 shipping weight 84 112 139 148 200
Notes:
1. Coil connections are always on the side opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
5
/8”7
5
/8”8
1
/8”8
1
/8”9
7
/8”7
7
/8”8
1
/8”7 5/8
1
/8”8 5/8
20 UNT-SVX07A-EN
dimensions
Inverted V ertical Recessed, Model N
Installation
Inverted vertical recessed unit dimensions & weights, in-lbs.
unit
size 02-03 04 06 08 10-12
operating weight 78 88 128 139 253 shipping weight 68 78 118 129 243
Notes:
1. Coil connections are always on the side opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See pages 21-22 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See pages 23-24 for fresh air opening dimensions.
& weights
A 2’-3 7/8 2’-8 7/8 3’-6 3/8 4’-2 7/8 5’-9 7/8” B 1’-9 5/16 2’-2 5/16” 2’-11 13/16” 3’-8 5/16” 5’-3 5/16” C 1’-10 13/16 2’-3 13/16 3’-1 5/16” 3’-9 13/16” 5’-4 13/16” D2 E 3’-11” 4’-3” 5’-3” 5’-5 1/2 7’-5 1/2” F 2’-6” 2’-6” 2’-6” 2’-9 1/2 2’-9 1/2
G 2’-2 1/2 2’-2 1/2 2’-2 1/2 2’-3 1/2 2’-3 1/2
H 3’-6” 4’-0” 4’-9” 5’-3” 7’-3”
3
/8”2
3
/8”2 3/8”4 1/8”4 1/8
Dimension 'D' refers to the required minimum distance between the finished floor, and the bottom of the unit.
UNT-SVX07A-EN 21
dimensions
Fan-Coil Coil Connections V ertical Units
Installation
& weights
Fan-Coil Coil Connections Horizontal Units
22 UNT-SVX07A-EN
dimensions
Force Flo Coil Connections,
V ertical Units
Installation
& weights
Force Flo Coil Connections,
Horizontal Units
HR - Hot Water Return HS - Hot Water Supply
Force Flo Coil Connections,
Inverted Units
UNT-SVX07A-EN 23
dimensions
Fresh Air Opening Locations Horizontal Units Models C, D, and E
Installation
& weights
Fresh Air Opening Dimensions, Horizontal Units
Unit Size 02-03 04 06 08 10-12
A 1’-6” 1’-11” 2’-8 1/2” 3’-5” 5’-0” B 1’-9 5/16” 2’-2 5/16” 2’-11 13/16” 3’-8 5/16” 5’-3 5/16
24 UNT-SVX07A-EN
Loading...
+ 56 hidden pages