Trane UCM-CLD, RLC-SVU02F-E4 Owner's Manual

UCM-CLD Chiller Control System
Owner Manual
RLC-SVU02F-E4
© 2009 Trane
RLC-SVU02F-E4
Foreword
These instructions are given as a guide to the operation of the controller(s) mounted on Trane RTAD/RTWB/RTRA chillers. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up.
Warnings and cautions
Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.
WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.
Safety recommendations
To avoid death, injury, equipment or property damage, the following recommendations should be observed during maintenance and service visits:
1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter "Installation". Always provide a pressure regulator.
2. Disconnect the main power supply before any servicing on the unit.
3. Service work on the refrigeration system and the electrical system
should be carried out only by qualified and experienced personnel.
Reception
On arrival, inspect the unit before signing the delivery note.
Reception in France only:
In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations ­Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery. Note: for deliveries in France, even concealed damage must be looked for at deli
very and immediately
treated as visible damage.
Reception in all countries except France:
In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team.
Warranty
Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.
Maintenance contract
It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.
Contents
3RLC-SVU02F-E4
General Information 2
Principles of operation of the UCM-CLD module 4
General Information 4 Operator’s Interface 5 Operational Features 9
Diagnostics 16
Diagnostics 16 Default Description 17
Controller for hydraulic module/ free cooling / heat recovery / RTWB heat pump applications 22
Hydraulic module control 23
Control logic 23 Module and outputs/inputs 24 Hydraulic module option 25 Data display menu 26 Configuration menu 27 Alarms messages - hydraulic module application 30 Mask and menu chart 31
Free cooling application 32
Heat recovery application 38
RTWB heat pump application 40
Principles of Operation of the Module UCM-CLD
RLC-SVU02F-E44
General Information
This UCM-CLD chiller control is composed of eight electronic modules, which each have their own 115V or 24V power supply and communicate with each other via a serial link. The names of the modules are linked to their functions.
Figure 1 : Operator’s interface
Compressor
Report
Refrigerant
Report
Chiller Report
Custom
Report
Select Report Group
Diagnostics
Service
Tests
Service
Settings
Operator Settings
Alarm
AutoEnterPrevious
StopCancelNext
Select Setting Group
ADAPTIVE CONTROL™
Module Functions
MCSP (Motor Compressor Start and Protection)
CPM (Chiller Protection and Management) Safety, protection, and control of the chiller EXV (Electronic Expansion Valves) Control of both electronic expansion valves CSR (Communication and Setpoint Reset) ,
Local CLD (Local Clear Language Display) Operator interface located in the front panel of the unit Remote CLD (Remote Clear Language Display)
TCI IV, COM 3 (Tracer Communication Interface 4, COM 3)
Safety, protection, and control of the helical-rotary compressor and its components
Control of the serial communication, unit external setpoints and ice-making mode (optional module)
Operator interface located up to 1500m from the unit, able to communicate with up to four units of the same type (optional module)
TCI IV, IPCB (Tracer Communication Interface 4, Inter Processor Communication Buffer)
Protection of the internal communication bus in the unit from external interferences (optional factory-mounted module, compulsory when using a Remote CLD)
Interface between the control of the unit and a Building Management System using Trane COMM 3 serial link
Principles of Operation of the Module UCM-CLD
5RLC-SVU02F-E4
Operator's Interface
Digital Display
The display of control regulation and operating parameters, diagnostics, and error messages is a 2-line, 40­character, liquid-crystal display. The display has a LED backlight to read in low-light conditions and to warm up the display under low ambient temperatures. When powering up the system, the display is not lit and the message [SELF-TEST IN PROGRESS] is displayed. The screen can display error codes, settings of various setpoints, specified temperature and pressure values, and the status of operating parameters and options.
Keyboard
A 16-key touchpad allows both navigation between menus and the modification of parameters and setpoints. The keys are divided into two groups:
Individual Menu Keys Control Keys
Chiller Report Menu + key Custom Report Menu
- key
Refrigerant Menu Previous key Compressor Menu Next key Operator Settings Menu Enter key Service Settings Menu* Cancel key Service Test Menu* Auto key Diagnostics Menu Stop key
* Levels 2 and 3 of the Service Settings Menu and the Service Test Menu are protected by a
password and are reserved for Trane Service Engineers.
Figure 2 : Control panel mounted on a model RTWA unit
Principles of Operation of the Module UCM-CLD
RLC-SVU02F-E46
Control Key Functions [+] key If the information displayed
is read-only, pressing this key will add it to the operator's menu. If the information can be modified, pressing this key will increase the value without exceeding the maximum possible value.
[-] key If the information displayed is read-only, pressing this key will remove it from the operator's menu. If the information can be modified, pressing this key will decrease the value without exceeding the minimum possible value.
[Previous] key Pressing this key allows the operator to scroll up to the previous information in the current menu. Each menu is looped, making it possible to scroll from the first item in the menu to the last item.
[Next] key Pressing this key allows the operator to scroll down to the next information in the current menu. Each menu is looped, making it possible to scroll from the last item in the menu to the first item.
[Enter] key Pressing this key allows the operator to validate a value after modification.
[Cancel] keyThis key should be pressed if a modified setting should not be saved.
[Auto key] Pressing this key allows the unit to be in Auto mode if it was previously placed in Stop mode with the [Stop] key. The unit cannot be forced into Auto mode if an external contact or the serial link has stopped it. When the unit is stopped by the remote interface (Remote CLD), the local mode order has priority.
[Stop] key Pressing this key allows the unit to be in Stop mode. In every case, and whatever the origin (except a local stop), the stop order and stop status have priority over a run order. The stop generated is a soft stop - the unit unloads before stopping.
Whether a [Stop] or [Auto] command will be accepted and stored is based on the following hierarchy:
1. Local Stop will always replace Local Auto, Remote Auto, and Remote Stop.
2. Local Auto will always replace Local Stop, Remote Auto, and Remote Stop.
3. Remote Stop will always replace Local Auto and Remote Auto. It will not replace Local Stop.
4. Remote Auto will always replace Local Auto and Remote Stop. It will not replace Local Stop.
Pressing the [Stop] key twice within five seconds will result in an Emergency Stop. The chiller will not unload.
Principles of Operation of the Module UCM-CLD
7RLC-SVU02F-E4
Parameters and setpoints within each menu
Menu Parameters/setpoints Range
Minimum/Maximum
Chiller Report Menu Active Chilled Water Setpoint
Evaporator Entering/ Leaving Chilled Water Temperature Condenser Entering / Leaving Chilled Water Temperature Active Ice-Storing Setpoint Active Hot Water Setpoint Entering/Leaving Hot Water Temperature Current Active Setpoint limits -17.8°/18.3°C Evaporator/Condenser Waterflow Ambient Air Temperature
Sources of setpoints (Tracer, local CLD, external) Custom Report Menu Custom-built by the operator (Can contain up to 20 settings) Refrigerant Report Menu Condenser/Evaporator Refrigerant Pressures
Refrigerant Temperature in Condenser
Refrigerant Temperature in Evaporator Compressor Report Menu Compressor Status
Time and Start Counters
Amps (% RLA)
Oil Temperature (GP compressor only) Operator Settings Menu Setpoint Source
External Chilled Water Setpoint
External Hot Water Setpoint
Chilled Water Pump Operation
Chilled Water Pump Off Delay 1 min/30 min
Ice Machine Control*
Panel Ice Termination Setpoint -6.6°/-0.5°C
Low Ambient Lockout
Low Ambient Lockout Setpoint -28.8°/15.5°C
Front Panel Current Limit Setpoint 40%/120%
Front Panel Hot Water Setpoint 25°/60°C
Front Panel Chilled Water Setpoint -17.8°/18.3°C
Design Delta Temperature Setpoint 2.2°/16.6°C
External Current Limit Setpoint
Differential to Start Setpoint 1.1°/16.6°C
Chilled Water Reset Type
Type Reset Ratio
Type Start Reset Setpoint
Type Max Reset Setpoint 0.0°/11.1°C
Principles of Operation of the Module UCM-CLD
RLC-SVU02F-E48
Service Settings Menu** LEVEL ONE-Information adjusted by customer
Unit Line Voltage Over/Undervoltage Protection Restart Inhibit Time 30/120 sec Balanced Compressor Starts and Hours Display Language and Units Programmable Relay Set-up 1/12 External Circuit Lockout
LEVEL TWO- Information adjusted by Service Engineer
Address of Serial Link 0/64 Display Lock Feature Leaving Water Temperature Setpoint Low Refrigerant Temperature Cutout Setpoint Low Water Temperature EXV Air Compressor Condenser Limit Setpoint 60/120% Phase Unbalance Protection Phase Reversal Protection Superheat Setpoint 2.2°/11.1°C EXV Control Response Circuit 1 2/200 EXV Control Response Circuit 2 2/200 Leaving Water Temperature Control Response Setpoint Fan Control Deadband bias Circuit 1 -50/50 Fan Control Deadband bias Circuit 2 -50/50
LEVEL THREE-Configuration/Protection Information
Compressor Model Number Prefix Number of Compressors Oil Loss Differential Setpoint Compressor A Ton Compressor B Ton Compressor C Ton Compressor D Ton Fan Control Variable Speed Fan Circuit 1 Variable Speed Fan Circuit 2 Number of Fans Circuit 1 Number of Fans Circuit 2 Reduced Inrush Starting Current Overload Compressor A Current Overload Compressor B Current Overload Compressor C Current Overload Compressor D Low Ambient Unit Half Air Flow Fan Low Ambient Unit Two-Speed Motor Night Noise Setback Number of EXV Circuit 1 Number of EXV Circuit 2 Refrigerant Type
Service Tests Menu Perform Expansion Valve Test
Perform Circuit locking or Pump-out Test Perform Compressor Test
Diagnostics Menu Current Diagnostics
History of Diagnostics Manual Reset of Diagnostics Erase History of Diagnostics
* Option ** This menu has three access levels. The control has a display lock feature that can be locked at request after level one.
Principles of Operation of the Module UCM-CLD
9RLC-SVU02F-E4
Operational features
Entering evaporator water temperature
When one or both compressors are running, the UCM continually monitors and compares the entering and leaving evaporator­water temperatures. If the temperature of the entering water drops more than 1°C below the leaving water temperature for more than 55°C- seconds, the UCM uses this to indicate a loss of water flow through the evaporator. This will shut down that circuit's compressor and will display MMR diagnostic.
Current Limit Setpoint (CLS)
The current limit setpoints for the system are entered through the Clear Language Display menus. The current limit Setpoint for each compressor is shown in Table 1.
Table 1 – Compressor current limit
Setpoint versus Chiller current limit Setpoint
System
CLS One Two 120% 120 120 100 % 120 100
80% 120 80
60% 120 60
40% 80 40
Based upon current levels received at the UCM, the compressor slide valve is modulated to prevent the actual chiller current from exceeding the CLS.
When a compressor is turned off, the CLS for the remaining running compressor shall be reset upward immediately. When a compressor is added, the CLS for the running compressor shall be ramped downward at a rate not less than 10% RLA per minute to the new Setpoint.
Numbers of compressor in
operation
Electronic expansion valve (EXV) test
This test can be performed only when the “Stop“ key has been pressed. It will confirm proper operation of the electronic expansion valve and the EXV module.
After the test has been initiated at the Clear Language Display, the UCM will:
1. Overdrive the EXV closed (25 seconds)
2. Overdrive the EXV open (25 seconds)
3. Overdrive the EXV closed (25 seconds)
4. Reset the display to disable and end the test
The EXV produces an audible clicking sound when it is driven against its end stops. Step 1 drives the EXV to its closed position, during which time service personnel can move from the CLD to the EXV.
Note: A tool may be needed to aid in hearing the clicking of the EXV, such as a screwdriver held between the EXV and the ear.
Current overload protection
The UCM continually monitors compressor current to provide unit protection in the event of an overcurrent or locked-rotor condition. Protection is based on the phase with the highest current and, if limits are exceeded, the UCM will shut down the compressor and will display an MMR diagnostic.
Leaving chilled-water temperature control
If the Auto key is pressed and a remote chilled-water Setpoint has been communicated, the UCM will control to that Setpoint. Otherwise, it will control to the front-panel Setpoint. Control is accomplished both by staging compressors and by modulating the slide valves on each compressor.
Upon start-up, if the leaving chilled­water temperature is dropping 0.8°C per minute or faster, the chiller will not load further.
Principles of Operation of the Module UCM-CLD
RLC-SVU02F-E410
Chilled-Water Reset (CWR)
As an option, the UCM will reset the chilled-water temperature setpoint, based on either the return water temperature or the outdoor air temperature. The CSR module is necessary to perform CWR.
The following are selectable: One of four reset types, from top to
bottom in order of reset: no CWR RETURN WATER TEMPERATURE
RESET ZONE TEMPERATURE RESET OUTDOOR AIR TEMPERATURE
RESET
Leaving-water temperature cutout
This temperature cutout provides protection against freezing caused by low leaving-water temperature. The setpoint is both factory-set and adjustable from the Service Setting Menu. Temperatures below the setpoint will cause the UCM to accelerate reduction of chiller capacity, even to the point of compressor shutdown. A non­latching diagnostic will be generated if the LWT is below the cutout for more than 16°C-seconds.
There must be a minimum of 2.7°C between the cutout temperature and both the front-panel and active­chilled-water setpoints. The Clear Language Display will not permit setting of either the front-panel or active-chilled-water temperatures less than 2.7°C above the cutout temperature. The second line will state:
Limited by Cutout Setpoint (+)
to change
If the leaving-water temperature cutout is set upward, the Clear Language Display will maintain the
2.7°C minimum and will automatically raise the settings on the front-panel and active-chilled­water setpoints, if necessary.
If the front-panel or active-chilled­water setpoints were adjusted, the display will show the following when the “enter“ key is pressed:
FRONT PANEL CHILLED WATER
SETPOINT HAS BEEN
INCREMENTED DUE TO CUTOUT
SETPOINT CHANGE
If the leaving-water temperature drops below the cutout setpoint while the compressors are de­energized, it will produce an IFW diagnostic. If the leaving-water temperature drops below the cutout setpoint while the compressors are energized for 16°C-seconds, the unit will shut down on an MAR diagnostic.
Principles of Operation of the Module UCM-CLD
11RLC-SVU02F-E4
Low refrigerant temperature cutout
Both circuits are protected from a saturated-evaporator refrigerant temperature that goes below this setting. The cutout Setpoint must be at a minimum of 8°C lower than the front panel or active chilled-water setpoints. See Table 2 for proper settings.
There must be a minimum of 8°C between the cutout temperature and active chilled-water setpoints. The Clear Language Display will not permit setting of the chilled-water temperature less than 8°C above this cutout temperature, and the display will flash the last valid temperature.
If the leaving-water temperature cutout is set upward, the Clear Language Display will maintain the 8°C minimum and will raise the settings of the chilled-water setpoints, if necessary.
If the chilled-water setpoints were adjusted, the display will show the following when the “Enter“ key is pressed:
FRONT PANEL CHILLED WATER
SETPOINT HAS BEEN
INCREMENTED DUE TO CUTOUT
SETPOINT CHANGE
If the saturated-evaporator refrigerant temperature for a circuit drops below this Setpoint for longer than 16°C-seconds, the circuit will be shut down and a CMR diagnostic will be displayed.
Table 2 – Leaving fluid temperature setpoints
°C °C °C % °C
5 1.5 -3.9 0 0 4 1 -4.4 10 -4 3 0 -5.4 13 -5 2-1 -6.416-7 1-2 -7.418-8 0-3 -8.420-9
-1 -4 -9.4 22 -10
-2 -5 -10.4 24 -11
-3 -6 -11.4 26 -13
-4 -7 -12.4 27 -13
-5 -8 -13.4 29 -15
-6 -9 -14.4 31 -16
-7 -10 -15.4 32 -17
-8 -11 -16.4 33 -18
-9 -12 -17.4 34 -19
-10 -13 -18.4 36 -20
-11 -14 -19.4 36 -20
-12 -15 -20.4 37 -21
Leaving
chilled-water
temperature
Leaving-water
temperature
cutout
Low refrigerant
temperature
cutout
Recommended
%EG
Solution
freeze
point
Principles of Operation of the Module UCM-CLD
RLC-SVU02F-E412
Balanced compressor starts and hours
This feature is enabled/disabled in balanced starts and hours (service setting menu). When enabled, the UCM will start the compressor with the fewest starts and stop the compressor with the greatest number of operating hours, as determined by the “compressor starts“ accumulator and the “compressor hours“ accumulator. This will tend to balance out hours and starts equally over both compressors.
Phase imbalance protection The Clear Language Display
monitors the current in each phase and calculates the percentage of imbalance as follows:
% imbalance = (Ix - I average)
I average I average = (I1 + I2 + I3) / 3 Ix = phase with greatest difference
from I average (without regard to sign).
If phase-unbalanced protection (service setting menu) is enabled and the average three-phase current is greater than 80% RLA, and the percent of imbalance is calculated to exceed 15%, the UCM will shut down the compressor and display a CMR diagnostic.
Reverse rotation protection
The Clear Language Display monitors incoming current during start-up and will shut down the compressor within one second if phase reversal is detected.
CCAAUUTTIIOONN
Phase relationship during installation of unit power must be carefully controlled to ensure compressor protection against reversed rotation.
Oil failure protection
The logic of the UCM uses a comparison of the entering oil temperature at the compressor, to the saturated-condenser temperature, to determine if there is an oil line restriction.
The differential between the entering-oil and the saturated­condenser temperatures is referred to as the “oil loss differential setpoint“ in the service settings menu.
If the entering oil temperature drops 2°C below the saturated-condenser temperature for more than 30 minutes, the circuit will shut down on a CMR diagnostic. The diagnostic will be presented as:
OIL SYSTEM FAULT - CKT X
DIP switch settings Compressor overload DIP switches.
IPC address
The IPC address sets the address for Inter-Processor Communications of the Clear Language Display modules. The following are the IPC DIP switch settings for the modules.
Module
IPC DIP A20-1 A20-2 A52 A9
Switch SW1 SW2 SW1 SW2 SW1 SW1
1 OFF Based OFF Based OFF OFF 2 OFF On OFF On OFF OFF 3 Motor Motor 4 RLA RLA 5
Principles of Operation of the Module UCM-CLD
13RLC-SVU02F-E4
2-10 V (dc)/4-20 mA input for External Chilled-Water Setpoint (CWS) or Current limit Setpoint (CLS)
When either external CWS or external CLS is used on the optional module A9, DIP switch SW1 positions 1 and/or 2 must be set to accommodate the type of of signal source the customer has chosen, either 2-10 V (dc) or 4-20 mA. Position SW1-1 sets 2-10 V (dc)/4­20 mA for external CLS. The “OFF“ setting configures the external input for 2-10 V (dc)/4-20 mA for external CLS. The “OFF“ setting configures the external input for 2-10V (dc), the “ON“ setting configures the external input for 4-20 mA.
Leaving Condenser-Water Temperature control option ­Model RTWB
If the machine is delivered with the LCWT control option (digit 49 position 3), the DIP switch on the module A9 must be set at position “ON.“ This option controls the condenser (CDS) leaving-water temperature (LCWT) based on a Hot Water Temperature setpoint (HWSP).
Mechanical control settings
The settings for the High Pressure switch are shown below:
Pressure Switch Approval Close Open B51 PED 19-20 bar 22-23 bar High Pressure Czech republic
Poland B23 PED 1.5 bar 0.5 bar Low Pressure Czech republic
Poland
-4°C<LWTE<+15°C B23 PED 1.2 bar 0.2 bar Low Pressure Czech republic
Poland
-12°C<LWTE<-4°C
Figure 3 - Water Temperature Sensor Installation - Model RTWB
Compression
Fitting
Clamping Nut
Fitting Body
1/2" NPT x 1-1/2" Large Coupling
Limitations
In the heating mode, the chiller is not able to provide chilled water for a process. The leaving chilled-water temperature is not controlled. The UCM will only take care of safeties (water flow and freezing).
The option will provide contact to start/stop the evaporator and the condenser pumps. Any other devices such as valves (2 ways/3 ways), heat exchangers, variable-volume pumps, or other equipment will have to be controlled by another system.
Condenser Water Temperature Sensors - RTAD Total and Partial Heat Recovery
UCM-CLD will not display leaving and entering water temperature above 70.1°C, whereas on Total Heat Recovery units, the temperature on the additional controller could be higher. These conditions would appear in cooling mode only. This is not harmful to the operation of the chiller.
Principles of Operation of the Module UCM-CLD
RLC-SVU02F-E414
Hot-Water Mode Control Module - Option Model RTWB
Scope of Supply
The following parts will be installed in the control panel of the unit:
• One Additional Board A70 with display
• One CDS LWT sensor + immersion well to be installed by the customer
The sensor will be connected to terminals B3 and GND on terminal block J2 of the A70 module.
Sequence of Operation
• Cooling Mode
The unit will operate as a standard chiller (i.e., the chiller controls the leaving chilled-water temperature). The condenser pump will be driven by the UCM relay. The chiller uses the cooling setpoint defined in the A70 Module.
• Heating Mode
In the heating mode, the chiller will control the condenser leaving-water temperature. The temperature sensor connected to the A70 Module should be located in the condenser leaving­water connection downstream from the condenser. The control is done by loading or unloading the chiller. To load or unload the chiller, a chilled­water setpoint reset is applied (i.e., setpoint decrease = load; setpoint increase = unload). The condenser pump is always in operation. The evaporator pump is still controlled by the UCM and is always in operation. The chiller uses the heating setpoint defined in the A70 Module.
The chiller will be stopped if the condenser leaving-water temperature is greater than the setpoint + the “differential to stop”. The chiller will start if the condenser leaving-water temperature is lower than the setpoint - the “differential to start”.
• Sensor Failure In the heating mode, and if the CDS
leaving-water temperature sensor fails, the chiller is stopped and the alarm relay of the A70 Module is energized. The chiller can operate in the cooling mode if the CDS leaving-water temperature sensor has failed.
A70 Module and UCM interaction Chilled-Water setpoint: The A70
Module drives the chilled-water setpoint using a linear signal from an Analog Output of the A70 Module to the external chilled-water setpoint input of the UCM.
Chiller Enable/Disable: The A70 Module drives the chiller (on or off) using a dry contact from the A70 Module to the external start/stop input of the UCM.
CDS pump relay: The A70 Module drives the condenser pump relay.
In heating mode, the chiller controls the condenser leaving-water temperature. The A70 Heat Pump Module sends an external chilled­water setpoint to the UCM. This analog signal (factory set at 4­20mA) is constantly reset to match the heating load.
• Setpoint decreases Æ load the chiller
• Setpoint increases Æ unload the chiller
Note that the UCM still operates as a chilled-water controller.
On the UCM-CLD, the parameter “External Chilled Water setpoint” has to be enabled.
Loading...
+ 30 hidden pages